Upload
ethen-hancey
View
257
Download
12
Embed Size (px)
Citation preview
1
Industrial Instrumentation
Dr. –Ing. Naveed Ramzan
Level Sensors
Level is another common process variable that is measured in many industries. The method used will vary widely depending on the nature of the industry, the process, and the application.
Inventory: -- a constant supply or storage of materialControl: -- continuous, batch, blending, and mixing control-- stabilize flow to the next processAlarming: -- hi/lo limits, safety shut downData Logging: -- material quantities for inventory and billing
purposes and where regulatory requirements are necessary
Level Measurement
What is measured?What is measured?
The measured medium can be liquid, gas or solid and stored in vessels (open/closed tanks), silos, bins and hoppers.
Units of level can be expressed in:feet (meters)gallons (liters)pounds (kilograms)cubic volume (ft3, m3)
Hydrostatic Head Float Load Cells Magnetic Level
Gauge Capacitance
Transmitters Magnetostrictive Ultrasonic Microwave Laser Radar Guided Wave Radar Dip Stick Vibration
Methods ---- Direct or Indirect (inferential)
PEC – UET Lahore Dr. Shahid Naveed 11. April 2023 / Dr. –Ing Naveed Ramzan 5
Direct MethodsDirect Methods
Direct methods sense the surface or interface of the liquid and is not affected by changes in material density (Specific Gravity)
Examples: Dip Stick Resistance Tapes Sight Glass Floats Ultrasonic
Indirect Methods (Inferential)Indirect Methods (Inferential)
Indirect methods “infer” liquid level by measuring some other physical parameter such as pressure, weight, or temperature.
Changing materials means a corrective factor must be used or recalibrating the instrument.
Examples: Hydrostatic head methodsLoad CellsCapacitanceConductivity
When determining the type of level sensor that should be used for a given application, there are a series of questions that must be answered:
Open tank or closed tank? Can the level sensor be inserted into the tank or
should it be completely external? Contact or non-contact?
Continuous measurement or point measurement? Direct or Indirect measurement? What type of material is being measured? Liquid
or Solid? Clean or Slurry?
Selection Criteria
For all liquids you will need:
The system operating temperature with max. and min. excursions?
two wide range – expensive the sensor The system operating pressure?
Check that system ‘T’ and ‘P’ do not conflict with the materials of construction?
Selection Criteria
PEC – UET Lahore Dr. Shahid Naveed 11. April 2023 / Dr. –Ing Naveed Ramzan 9
For Solids:
Bulk density Be careful with very large silos as compaction
at the bottom can greatly change assume bulk densities
Flow characteristics?
Expected particle size distribution?
Is solid abrasive and/or corrosive and what is the moisture/solvent content?
Selection Criteria
PEC – UET Lahore Dr. Shahid Naveed 11. April 2023 / Dr. –Ing Naveed Ramzan 10
Simple and cheap Can be used with any wet
material and not affected by density.
Can not be used with pressurized tanks
Visual indication only (electronic versions are available)
RodGauge - similar to a dipstick found in a car, it has weighted line markings to indicate depth or volume
For Liquids
Dip Stick
Another simple direct method of measuring liquids.
Can be used in pressurized tanks (as long as the glass or plastic tube can handle the pressure)
Good for applications where non-contact measurement is needed (like beverages)
Sight Glass
For Liquids
Float rides the surface level to provide the measurement. Many different styles are available. Usually used for pump control, high/low level alarms and emergency shut-off
Liquid density does not affect measurement
Floats
For Liquids
Point Level Measurement Continuous Level Measurement
Advantages and disadvantages
Low CostConductive, non-coating liquids only
Insulating coatings can cause problems
Conductivity Level Measurement
For Liquids
The pressure of the fluid in the tank causes the tape to short-circuit, thus changing the total resistance of the measuring tape. An electronic circuit measures the resistance; it's directly related to the liquid level in the tank.
Resistance Tape
For Liquids
Bubblers allow the indicator to be located anywhere.
The air pressure in the tube varies with the head pressure of the height of the liquid.
Bottom of tube determines
reference point
P
Regulated purge system
(air or nitrogen)
Instrument input does not matter
Can’t be used in closed tanks or where purging a liquid is not allowed (soap). Very popular in the paper industry because the air purge keeps the tube from plugging.
Bubblers
PEC – UET Lahore Dr. Shahid Naveed 11. April 2023 / Dr. –Ing Naveed Ramzan 16
For Liquids
Advantages:
-- Easy installation
-- Continuous reading providing analogue or digital signal
-- No moving parts
-- Good accuracy and repeatability
Bottom of tube determines
reference point
P
Regulated purge system
(air or nitrogen)
Instrument input does not matter
Bubblers
For Liquids
Limitations:
-- Not suitable for pressurized tanks
-- Sediments may block tube or probe
-- Tanks must be freely vented
Bottom of tube determines
reference point
P
Regulated purge system
(air or nitrogen)
Instrument input does not matter
Bubblers
For Liquids
These methods infer level by measuring the hydrostatic head produced by the liquid column.
A pressure sensing element is installed at the bottom of the tank and pressure is converted to level.
Different liquid densities or closed tank applications must be accounted for.
Hydrostatic Head Level Sensors
General Theory for Head General Theory for Head MeasurementMeasurement
The Pressure exerted by the Height of the liquid is:
P = H x Density*
If the Density of the liquid is known then
H = Pressure Density*
Height (H)
Pressure PSI
Liquid Density (D)
*Note: For liquids other than water, use the density of water 0.0361 lb/in3 as a reference and multiply by the SG of the liquid.
Hydrostatic Head Level Sensors
ExampleExample
Height (H)
Tank 1 PSI
WaterDensity (D) Height
(H)
Tank 2 PSI
OilDensity (D)
A dip stick measurement of the level of these 2 tanks indicates 30 feet of liquid in both tanks. Calculate the pressure that each gauge will read if tank 1 contains water (S.G. = 1) and tank 2 contains oil (S.G. = 0.85)
P = ? psi P = ? psi
ExampleExample
Height (H)
Tank 1 PSI
WaterDensity (D) Height
(H)
Tank 2 PSI
OilDensity (D)
A dip stick measurement of the level of these 2 tanks indicates 30 feet of liquid in both tanks. Calculate the pressure that each gauge will read if tank 1 contains water (S.G. = 1) and tank 2
contains oil (S.G. = 0.85)
P = H x Density
= 30 ft x 0.0361 lbs/in3
= (30 x 12) x 0.0361
= 13 psi
P = ? psi
ExampleExample
Height (H)
Tank 1 PSI
WaterDensity (D) Height
(H)
Tank 2 PSI
OilDensity (D)
A dip stick measurement of the level of these 2 tanks indicates 30 feet of liquid in both tanks. Calculate the pressure that each gauge will read if tank 1 contains water (S.G. = 1) and tank 2
contains oil (S.G. = 0.85)
P = H x Density x SG
= 30 ft x 0.0361 lbs/in3 x 1
= (30 x 12) x 0.0361
= 13 psi
P = H x Density x SG
= 30 ft x 0.0361 lbs/in3 x 0.85
= (30 x 12) x 0.0361 x 0.85
= 11 psi
Practical Considerations when Practical Considerations when using head type instrumentsusing head type instruments
The reference point of the tank vs instrument input must be considered.
Height (H)
Pressure PSI
Liquid Density (D)
Height (H)Pressure
PSI
Liquid Density (D)
This may not be practical in some applications where the tank elevation is below grade or where a remote visual reading is required.
Hydrostatic Head Level Sensors (Cont‘d)
Tank ElevationsTank Elevations
Vertical rises and drops contribute to the overall height and therefore head pressure. Horizontal runs have no effect.
Height (H)
P
WaterDensity (D)
P
Hydrostatic Head Level Sensors (Cont‘d)
Closed Tank ApplicationsClosed Tank Applications
Open tanks are vented to atmosphere so the pressure at the bottom of the tank is only due to the head pressure of the liquid.
Closed tanks are not vented to atmosphere so the pressure at the bottom of the tank is due to the head pressure of the liquid + the vapour pressure above the
surface.
P Head = h x D
P (atmospheric)
P Head = (h x D) + P vapour
P vapour
Hydrostatic Head Level Sensors (Cont‘d)
Used where the sight glass level gauge can not be used.
Magneto-resistive types can provide an electrical output.
Liquid/liquid interface (such as water and oil) can be measured by changing the buoyancy of the magnetic float
Magnetic Level Sensor
Not the same as a float. The displacer is immersed in the tank and the
buoyant force of the liquid produces a torque which is proportional the amount of liquid level.
The output force can be
converted to provide a
proportional pneumatic or
electrical continuous
output of tank level.
Displacers
Displacer – side mounted unitDisplacer – side mounted unit
The displacer float size and diameter is selected according to the size of tank and the height of the level to be measured.
The output force can be converted to provide a proportional pneumatic or electrical continuous output of level.
Advantages and disadvantages:
Very little movement of displacer float
Affected by different liquid densities
Limited to smaller tanks sizes
Displacers
Non-Contact direct level sensor
Level is a function of the time it takes an ultrasonic pulse to hit the surface and return
Limitations include:• Surface foam absorbs signal, agitation create reflections
• High Pressure & High Temperatures affect the signal speed• Vapour and condensate create false echo’s
UltraSonic Level Measurement
Similar to ultrasonic but at a much higher frequency (6.3 GHz)
Various designs -- Frequency Modulated Continuous Wave-- Pulsed Wave-- Guided Wave
These sensors have better performance in applications where vapour, dust or uneven surfaces exist.
Radar Level Sensors (Microwave)
Tank level is determined by the weight of the quantity of material
Load Cells (strain gauge transducers) placed at the bottom of the tank measure the weight and then convert it to an electrical signal.
Load Cells
Capacitance Level Detection (RF Level Capacitance Level Detection (RF Level
Probes)Probes)
RF Capacitance level sensors are similar in operation to conductivity sensors and are typically used when non-
conductive liquids are measured.
The only variable is the dielectric of the tank material that varies in proportion to the level.
Conductive liquids like mineral water will short out the probe to the tank wall.
Good for solids
Can be used for non-Can be used for non-liquidsliquids RF capacitance
probes are used in a wide range of applications and are subjected to certain limitations such as: Electrode Coating Low sensitivity Temperature Different
materials Shielding & noise
Summary
• Level is measured by locating the boundary between two media, called
the interface• Level can be measured directly or
indirectly• Noninvasive devices are preferred
when the material is corrosive, hazardous, sterile, or at a high
temperature or pressure
Batch application using point level Batch application using point level measurementmeasurement
Detect if the level is at a predetermined point
Generally used to detect either a low-level condition or high-level condition
The output of a point level sensor is on-off, or 1 or 0 state digital signal
A batch process does NOT use a continuous level measurement device.
Creative Assignment! HAZOP?????
Discussion & Questions?