Upload
rudy-soward
View
215
Download
0
Embed Size (px)
Citation preview
1
FREQUENCY CONTROL
-- Bhanu Bhushan --
(April, 2011)
2
What is frequency ?
How would you explain it to a layman ?
3
Number of times the voltage reverses
in half a second.
4
From where does it come ?
What governs the frequency ?
5
Speed at which the turbine - generators
are running at that time.
3000 rpm = 50 rps = 50.0 Hz
2940 rpm = 49 rps = 49.0 Hz
( for 2 - pole generators )
6
Is it same all over a system ?
7
Yes.
But, why ?
8
Because polarity of voltages produced
by all generators must be same at a
particular time, and must reverse together.
9
Is the frequency constant ?
10
No.
Why not ?
Why does frequency keep changing
all the time ?
(Transparencies)
11
12
13
14
15
• Because total consumer load keeps changing from time to time, and
• Because total generation is not changing in step with the change in total load.
• Situation is seriously aggravated when governors are not in normal operation.
• How is the frequency stabilized and controlled ?
16
What happens if the frequency differs from
the rated value of 50.0 Hz ?
What are the adverse effects of high and
low frequency ?
17
18
19
20
21
22
• Motors & driven equipment : over-loading / reduced output
• Transformers : --- / over-fluxing
• Capacitors : --- / effectiveness falls
• Reactors : effectiveness falls / ---
• Transmission lines : parameters change
• Steam turbines : resonance of LP blades
• Generating stations : --- / MW capability falls
• Power system : effect on voltage profile.
23
Permissible band of frequency ?
• Obligation to consumers
• Requirement of power plants
• Requirement of system operation
• Electric clocks.
24
• Indian Electricity Rules, 1956 : +/- 3%
• IEC for Steam turbines : + 1%, - 2%
• IEGC ?
• England :
25
The basic function of governor on a prime mover
• To vary the power input to match the power output, and thereby contain the speed change.
• Additionally, in case of grid-connected generating units, to enable stable parallel operation by equitable sharing of system load changes.
26
(G1+G2+G3) = (L1+L2+L3)
GI
L1
G2
L2x
REGION
y
G3
REGION
L3
x=L1-G1 y=L3-G3
27
• Suppose L1 increases to L1’. Frequency would decline to a new level at which (G1’+G2’+G3’) = (L1’+L2’+L3’)
• Then x’ = L1’ – G1’; y’ = L3’ – G3’• x’ may not be = x; y’ may not be = y• Such fluctuations keep happening all the time. • Let us assume that L2 & L3 remain unchanged
when frequency declines.• Then (G1’+G2’+G3’-G1-G2-G3) = L1’-L1.
28
• If all generating units are on FGMO with an equal droop, (G1’-G1)/G1 = (G2’-G2)/G2 =
(G3’-G3)/G3 = (L1’-L1)/(L1+L2+L3).• In Western countries, it is mandatory to
continuously regulate G1 such that x’ = x within 10-15 minutes, assuming x was = interchange schedule for the State to begin with.
• This is possible only if (G1’’-G1) = (L1’-L1).• This requires that every constituent has adequate
spinning reserves and AFC. (Self-sufficiency)• No concept of region-wide merit-order.
29
Steps in frequency control
• Change of total generation in the system to match the new total system load, through FGMO, without any time delay.
• Change the total generation in affected area to absorb the change in area load.
• Change the generation in affected area to restore merit-order. May be combined with the previous step.
• Additional sale / purchase for economy.
30
• Frequency and all tie-line flows automatically return to the previous level, without any corrective action in other control areas. The latter’s generation also returns to previous level, without any change in governor settings.
• Can this conventional scheme work after vertical unbundling of power utilities? How would a Discom keep to its import schedule?
31
In our case, x generally is above / below schedule.• Each State has notified entitlements in Central
generating stations • Suppose it is ‘a’ MW on a day• Then, (x – a) = over-drawal, for which the State
has to pay UI charges into the regional pool account. ‘x’ is metered in 15 minute wise energy.
• UI rate is determined for each 15-minute period according to average frequency during the period.
32
When frequency is low (because of a general deficit), UI rate would be high and the State should plan to curtail its over-drawal, by
-- Harnessing all generation within the State
-- Procuring additional power.
Load - shedding only when no additional power is available at a price that the State utilities can pay, and UI rate is not affordable or frequency has come down to a level which endangers the grid.