07/11/14 P.K.PATTANAIK 1
PRESENTATION ON 1.ELEMENTS OF SUB-STATION EQUIPMENTS
2.BASIC POWER SYSTEM CONCEPTS
byP.K.PATTANAIK
1. Kindly switch OFF/ Keep your Mobile phone in Vibration
mode .
2. Please interact with no CROSS TALK.
3. Kindly allow one to (speak/ ask queries) at a time.
4. Please maintain silence during presentation.
House Keeping ……
Thanks in ADVANCE for maintaining/ to maintain the HOUSE KEEPING RULES
1. Introduction
2. Acquaintance to Sub- Station Equipments
i. Working Principle
ii. Significance to Protection Scheme
iii.Name plate Study
iv.Updated technology in present Practice
3. Sub-Station Lay out/ Electrical Concepts
4. OPEN SESSION
5. Conclusion
Out Line ……
Thousands mile of journey starts from FIRST STEP
Skeleton Chart
Human being Protection system
DC +
DC -
SECONDARY
PROTECTION
ELECTRICAL PROTECTION SYSTEM
SUB STATION MAIN EQUIPMENTS
Equipments Functions
Lightning Arrester Discharges the lightning and switching surge Voltage to Earth
Wave trap Traps the high frequency signals to the system equipments
Isolator Air dis-connection of circuit for safety maintenance
Earth Switch Discharges voltage on Dead line
Circuit Breaker Auto disconnection of circuit for fault or abnormal condition
Current Transformer
Transforms current from High to Low for control and protection circuit
PotentialTransformer
Transforms voltage from High to Low for control and protection circuit
Lightning Arrester
Surge Arrestor / Lightning Arrestor
Modern surge arrestors :-
1. Metal Oxide Varistor (MOV)- ZnO2 Blocks with grain of 10μm dia.
2. Confirms IEC 60099-4 / IS 3070 with safety Vent and LCM ( Leakage Current Monitor)
3. Metal Oxide Varistor (MOV) is highly nonlinear in nature, which has sharply kinked voltage-current characteristics.
NAME PLATE STUDY ( LA)
Particulars Rating / Value
Make/Model
Sl No / Year
System Voltage 220 Kv
NDC 10 KAp
System BIL 1050KVp
MCOV 168 KV
LD Class 3
Approx. weight 135 KG
Frequency ( Hz) 50
Rated Voltage 198 KV
1. MCOV :- Maximum Continuous
Operating Voltage
2. BIL :- Basic Insulation Level
3. NDC:- Nominal Discharge Current
4. LD Class :- Line Discharge Class
5. Rated Voltage:- (system voltage x
√ 2)
√ 3
WAVE TRAP Particulars Value
Continuous Current Rating at 50 0 C ambient
1250 Amp
Max. Symmetrical Short Circuit Current For 1 Sec
31.5 KA
Rated Inductance 0.5 H
Blocking Range 150-500 KHz
Mounting Suspension
Basic Insulation Level 32.37 KVp
Standard Nominal Discharge Current for 8/20 micro Sec. Wave impulse
10 KA
Rated Voltage of Arrestor 6 KV
Tuning Broad Band
Visual Corona Extinction Voltage
156 KV
No of Turns in Main coil 28 (2 in Parallel
WAVE TRAP Working Function
ISOLATORS
Particulars Rating / Value
Particulars Rating / Value
Make Type
Voltage (KV) 245 Current ( Amp) 2000
STC (KA-Sec-KAp)
40-3-100 Impulse ( KVp) 1050
PF Voltage ( KV )
460 Frequency ( Hz) 50
DC Voltage (V) 220 AC Voltage ( V) 415
Operating Device MOM Year
Name Plate Study
Isolators/ Dis-connector
Modern Isolators :- 1. Single Break motorized type – Proper Gripping due to dragging each
other.2. One contact – provides 100% confirmed status. 3. Interlock scheme from Numerical Micro-processor Relay. 4. Operates on OFF load or EQUI-POTENTIAL Concept.
LOCKING OF ISOLATOR IN END POSITION
Switch Gear/ Circuit Breaker
UP TO 36 KV ( VCB ) 1. Quick Restoring of Dielectric
strength of Gap
2. Short gap needs lesser Control Mechanism
3. Low Weight
72 KV to 800 KV ( SF6 Filled Spring Mechanism)
4. SF6 (electronegative in nature with high quenching property and high dielectric strength
5. Spring- Spring mechanism takes less space and simple mechanism .
*CIGRE 1994:-Tech Report 83:-CIGRE analyzing worldwide Circuit Breaker advises the use of spring operating mechanism in order to ensure the highest reliability.
VCB
Circuit Breaker
420 kV SF6 GCBWith SP/Pneumatic Mechanism
Switch Gear/ Circuit Breaker
800 KV SF6 LIVE TANK
400 KV SF6 Gas Breaker
Switch Gear/ Circuit Breaker
CB with Composite Insulator CB with PIR and Graded Capacitor
Circuit Breaker Name Plate StudyParticulars Rating / Value Particulars Rating / Value
Make Rated Lightening impulse with Stand voltage
650 KVp
Type Rated short Circuit Breaking Current 31.5 KA
Rated Voltage 145 KV Rated Operating pressure 15.5 KG/cm2 - g
Rated Frequency 50 HZ First pole to Clear factor 1.5
Rated Normal Current
3150 A Rated Duration of short Circuit current 31.5 KA , 3 Sec
Rated Closing Voltage
220 V DC Rated Line Charging Breaking Current Rated SF6 Gas pressure
50 A
Rated Opening Voltage
220V DC Rated Voltage and frequency for Aux. Circuit
415 VAC , 50 HZ
GAS PRESSURE SF6
6.0 bar at 20 0
cRated operating Sequence 0-0.3S-CO-3Min-CO
Total weight with Gas
2000 KG Gas weight 9 KG
Sl. No. STD. IEC 56
Month / Year of Manufacturing
Circuit Breaker Name Plate StudyRated Lightning withstand voltage:- Peak value of standard voltage surge 1.2/50 μs that the insulation of a device can withstand. The meaning of this is “ in 1.2 micro second the voltage reaches its peak value and in 50 micro second it decays to the half of this value
1st pole to clear factor:- For 3 phase circuit breakers, arc extinction in 3 pole does not become simultaneous, for which the recovery voltage of the pole, first to extinguish the arc is of the order of 1.2 to 1.5 times the phase voltage and called First Pole to Clear Factor and defined as the ratio of the Voltage between the (healthy phase and faulty phase) to (Normal phase voltage)
Operating cycle :- The possible operational sequence of the breaker between the close and opening operation is called Operating cycle . This information is important for the choice of the breaker whether suitable for auto reclosing system or not. General operating cycle is as ( O-10s-CO-3min-CO for normal operation and O-0.3s-CO-3min-CO for auto re-close condition
Short-time Current Rating:- The circuit breaker must be capable of carrying short-circuit current for a short period while another circuit breaker (in series) is clearing the fault. The rated short-time current is the rms value (total current, both A.C and D.C components) of the current that the circuit breaker can carry safely for a specified short period
Transient Recovery Voltage (TRV) or Re-striking voltage:-For the AC circuit breaker , for the case of current interruption even after current becoming zero, certain voltage appears across the contacts, which is transient in nature and called TRV or Re-striking Voltage.
Instrument Transformer ( CT, PT)
Current Transformer Principle
I2
I1
Current sensor
Voltage Transformer Principle
Magnetic circuit (core)
U1 U2
Voltage sensor
Secondary Windings
Primary Windings
CVT Principle
OUT DOOR S/S CTs (Live Tank CT)
Live Tank CT Dead Tank CT U Shape
Voltage Transformer CVT
Capacitor elements
Capacitor column
Insulating oil
Insulator flange
Secondary terminal box
Inductance
MV Transformer
Oil expansion device
Damping circuit
Combined CT and PT unit
Optic Fiber CT
Current Transformer Principle
CT NAME PLATE STUDY Particulars Rating / Value Particulars Rating / Value
Make Type
Ref. Standard IS 2705-1992 HSV/NSV 245/ 220 KV
BIL 1050/460 KV S.T.Current 40/ 1 KA/Sec
Frequency 50 HZ Wt. Of Oil 350 KG
Making Capacity 100 KAp TOTAL WEIGHT 1200 KG
Sl. No/YEAR
P1
C1P2
C2
S1 S2 S3
RATIO 400-200-100/1-1-1-1-1
PRI/SEC CURRENT (A) 400/1 200/1 100/1
PRI. CONN. P1C1– P2C2 C1-C2 C1-C2
SEC. CONN.
CORE 1 1S1-1S3 1S1-1S3 1S1-1S2
CORE2 2S1-2S3 2S1-2S3 2S1-2S2
CORE3 3S1-3S3,S’ 3S1-3S3,S’ 3S1-3S2,S’
CORE4 4S1-4S3 4S1-4S3 4S1-4S2
CORE5 5S1-5S3 5S1-5S3 5S1-5S2
CORE 1 2 3 4 5
OUT PUT* - - 40 - -
ACC. CLASS* PS PS 0.5 PS PS
ISF/ALF* - - ≤ 5 - -
Vk (V) Min* 1200 1200 - 1200 1200
I exc@Vk *(mA) Max * 25 25 - 25 25
Rct at 75 0 C Max* 5 5 - 5 5
* AT 400/1 AND 200/1 RATIO ONLY
CT NAME PLATE STUDY
CVT NAME PLATE STYUDY Particulars Rating / Value Particulars Rating / Value
Make Sl. No.
Type Rated Voltage 220/√3 KV
Highest System Voltage 245 KV Rated Insulation Level 245/460/1050 KV
Total Creepage 6125 min. nom.mm Rated Frequency 50 HZ
Wt of Oil 140 KG Standard IEC : 60186/ IS : 3156
Total Weight 750 KG HV ( Pri) Capacitance 4840 pF
Int. V ( Sec ) Capacitance 48400 pF Equip. Cap ( Cn ) for PLCC
4400 + 10 % - 5 % pF
Nom. Intermediate Volt. 20/√3 KV Temp. category - 5 to 55 0 C
Total Thermal Burden 750 VA Class of Insulation A
1 ph solidly earth Connection Suitable for hot Line Washing
Month / Year of Manufacturing
Voltage Divider ratio 220/√3 KV/20/√3 KV
Voltage Factor 1.2 Continuous / 1.5 for 30 Sec
G.A Drg. No.
Rated Sec. Voltage Terminal Marking Rated burden VA Acc. Class
110/√3 V , 110/√3 V (1a-1n), (2a-2n) 150, 150 0.5, 0.5
110/√3 V 3a-3n 50 3P
CVT NAME PLATE STUDY
Polarity and connection.Star connection circuit IR = I , angle( 0 ) IY = I, angle (-120) IB = I, angle (120) IR+ IY+ IB= IN
CT Circuit Connection Principle
R
R
By
Application of Instrument Transformers
DC +
DC -
SECONDARY
PROTECTION
ELECTRICAL PROTECTION SYSTEM
600/1 A
2400 A 4800A
4 A 4A
0 A
FAULT OUTSIDE Differential ZONE
1200/1A
132Kv
66Kv
600/1A
2400 A 4800A
4A 4A
8A
1200/1A
132KV 66Kv
FAULT INSIDE DIFFERENTIAL ZONE
PROTECTION PHILOSOPHY ( WHY)
1. Safety to Equipments and working personnel
2. To minimize damage and interruption
3. To prevent the Electric Failure
4. Loss of revenue due to outage
5. Inconvenience to the consumers
6. High Down time for repair / replacement
If No…. Then What…
Circuit Breaker
TripCoil
CircuitBreakerMecha-
nism
DC-System
ProtectionEquipment
CT
VT
TE
Protection System
Fault Clearance System
The Fault Clearance System
1. What is Relay?A device which detect intolerable or unwanted
conditions within the assigned area.A watchman or watchdog for the
equipment/areaSilent sentinels to power system.
2. How relays are differentiated?Functional categoriesInput quantitiesOperating PrinciplesPerformance Characteristics.
3. What are functional types?Protective relay.Monitoring relay.Reclosing relay.Regulating relay.Synchronising relay.
4. What are various input type?Voltage, Current, Temperature, Flow, Vibration, Pressure.
PROTECTION DEVICES
PROTECTION DEVICE FOR GRID SUB STATION
Self-supervision
Setting groups
Programmable logic
Adaptive schemes
Multiple protection characteristics
Communication capability
Instrumentation features
FEATURES OF NUMERICAL RELAYS
ADDITIONAL FEATURES
State-of-the-art-technology Simple design Operational flexibility Low relay burden Reduction of panel size & wiring Reduced commissioning time Reduced testing time Fault disturbance recording & analysis Sequence of events recording
PROTECTION SYSTEM
132KV BUS
132 KV D/C TR. LINE
Generation Evacuation
220 KV BUS
11KV BUS
132/11KV T/F
LINKAGE TO GRID
220 KV LINEGenerator protection
Line protection
T/F Protection
Bus Bar Protn.
LBB
STATOR E /F
GEN. DIFF.
OVER ALL DIFF.
INTER TURN
Reverse Power
Field Failure
T/F INTERNAL PROT.: Buchholz ,Wdg. Temp. , Oil temp. & PRV trip/alarm
GENERATOR PROTECTION
TRASFORMER PROTECTION
Differential element
100MVA , 220/66 KV
Yy0
262.5A
00
875A
00
400/1 1200/1
REF HV
REF LV
400/1 1200/1
Differential zone
HV REF ZONE
LV REF ZONE
BACK UP O/C & E/F
Over fluxing
Buchholz, WT, OT, & PRV alarm / trip
BUS FAULT
BUS BAR PROTECTIONBUS-1
BUS-2
BUS BAR PROTECTIONZONE-1
BUS BAR PROTECTIONZONE-1
ZONE-2
X X
X XX
X
XX
X
X
XX
A B C D
LINE PROTECTION
Z1Z2Z3
Z1
Z2
Z3
Event Logger
Disturbance recorder
Fault Locator
Numerical relays
IED ( Intelligent Electronics Device)