    Outdoor Power Troubleshooting and Maintenance

    Troubleshooting and MaintenancePresentation

    ESBG - NTBU

  • 8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02

    2/14

    Outdoor Power Troubleshooting and Maintenance

    Contents

    Alarm information (Display &Event)

    ACH, ACL, AC Off Alarm

    DCL, DCH Alarm

    Load/Battery Breaker Trip Alarm

    Temperature/Humidity Alarm or Sensor Lose

    Rectifier Failure Alarm

    Controller(CCU/ NSCSU) Failure Cooling System Failure

    Q&A

  • 8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02

    3/14

    Outdoor Power Troubleshooting and Maintenance

    Display (Alarm)

    Home

    DCV

    DCISys Status(FL/EQU)

    Alarm Existing

    Sys Info Sys Setting Current Alarm

    All Alarm Function show on Display

    Show Real Information andAlarm Time in Event Log

  • 8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02

    4/14

    Outdoor Power Troubleshooting and Maintenance

    Rectifier

    I.D. Address

    Output Current

    Status

    Event Log

    Alarm Function Time

    Recover Time

    Current .setting

    DC Setting

    Alarm Setting

    Batt.Setting

    Other Setting

    Home

    DCV

    DCI

    Sys Status(FL/EQU)

    Alarm Existing

    Sys Info Sys Setting Current Alarm

    Battery

    Batt. String I.D.

    Batt.Status

    Batt. Current

    * DC/DC Data

    AC & Temp

    ACV VoltageAmbient Temp.

    Data &

    Version

    Date/TimeH/W version

    S/W version

    Display (Event Log)

  • 8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02

    5/14

    Outdoor Power Troubleshooting and Maintenance

    Add AC Socket

    RBS2216 AC Panel Configurations

    Changeover Switch

    Phase 1 (with Genset Socket & Changeover Switch):

    Implementation: from first batch

    Genset Socket

    Phase 2 (without Genset Socket & Changeover Switch):

    Implementation: TBD (Inventory Concern)

  • 8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02

    6/14

    Outdoor Power Troubleshooting and Maintenance

    ACH/ACL/ AC Off Alarm

    Check ACL/ACH alarm Setting. Verify the AC input voltage at the AC service

    panel by a multi-meter. To check whether commercial power problem or AC circuitbreaker tripped causes the AC Fail. The AC circuit breaker should be tripped until

    the AC utility is repaired and the AC input is within input specifications.

    Check AC detected CKT, please refer below:

    Each Phases is 180~ 240Vac

    CNB10

    CNB11

    50:1 Transformer

    220vac

    =4.4Vac

  • 8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02

    7/14

    Outdoor Power Troubleshooting and Maintenance

    DCH/DCL Alarm

    Check DCL/DCH alarm Setting. Verify the output bus-bar voltage. If the output

    voltage is not within tolerance+/- 0.1Vdc. However, swap the rectifier with a

    spare module, and return the faulty unit to Delta Products for repair. If the output

    of each rectifier is within tolerance, check the controllere parameters to ensure

    the correct FL/EQU settings.

  • 8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02

    8/14

    Outdoor Power Troubleshooting and Maintenance

    Load/Battery Breaker Trip Alarm

    If the circuit breaker continues to fail:

    Check trip load side still short or over rating.

    Check the DC Branch load (fed by the DC circuit breaker) to ensure the circuit

    breaker is the correct rating. If the branch load exceeds the circuit breaker rating,

    the circuit breaker must be changed to a higher rating.

    Swap with a spare circuit breaker with a higher rating.

  • 8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02

    9/14

    Outdoor Power Troubleshooting and Maintenance

    Temperature/Humidity Alarm or Sensor Lose

    This alarm is generated when the threshold temperature set in parameteralarm setting TA/Tb1 is exceeded and also controls the Temperature

    Compensation Voltage Control. The CSU senses the temperature via sensor

    TA/Tb1 and generates an Ambient Over Temperature Alarm setting TA/Tb1.

    TA& TB1 sensor

  • 8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02

    10/14

    Outdoor Power Troubleshooting and Maintenance

    Rectifier Failure Alarm

    When a rectifier fails, the alarm information is sent to the CSU and the rectifier is

    shut down. The rectifier should be swapped out with a spare unit and the faulty

    unit returned to Delta for repair.

    Warning! Do not open the rectifier module. There are no serviceable

    parts. Call Delta Customer Service for a RMA number for repair andreturn.

  • 8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02

    11/14

    Outdoor Power Troubleshooting and Maintenance

    Controller (CCU/NSCSU) Failure

    When a controller fails, all rectifiers still continued suopport system.Check inside

    LED still flash or not. Check display connector is perfect

    LED Flash is

    Normal

    LED Flash is

    Normal

  • 8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02

    12/14

    Outdoor Power Troubleshooting and Maintenance

    Cooling System Failure

    Pull

    Pull out spring from the hole

    from right bracketTurning spring

    Turning spring

    Step 1 Step 2 Step 3

    Air Filter Maintenance - 2

    The system is equipped with one piece of the filter on the door.

    To remove the filter, pull out the filter from slot and than, re-install the new

    one by push in to the slot.

  • 8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02

    13/14

    Outdoor Power Troubleshooting and Maintenance

    Cooling System Failure

    Loose the Thumbscrew Push the tray backward Pull out the Fan tray

    Replacing a Fan Tray

    The fan tray should replace when it is fail. First, un-plug the two connectors

    on the tray. Then, refer the figures below.

  • 8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02

    14/14

    Outdoor Power Troubleshooting and Maintenance

    Q & A