Outdoor Power Troubleshooting and Maintenance
Troubleshooting and MaintenancePresentation
ESBG - NTBU
8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02
2/14
Outdoor Power Troubleshooting and Maintenance
Contents
Alarm information (Display &Event)
ACH, ACL, AC Off Alarm
DCL, DCH Alarm
Load/Battery Breaker Trip Alarm
Temperature/Humidity Alarm or Sensor Lose
Rectifier Failure Alarm
Controller(CCU/ NSCSU) Failure Cooling System Failure
Q&A
8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02
3/14
Outdoor Power Troubleshooting and Maintenance
Display (Alarm)
Home
DCV
DCISys Status(FL/EQU)
Alarm Existing
Sys Info Sys Setting Current Alarm
All Alarm Function show on Display
Show Real Information andAlarm Time in Event Log
8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02
4/14
Outdoor Power Troubleshooting and Maintenance
Rectifier
I.D. Address
Output Current
Status
Event Log
Alarm Function Time
Recover Time
Current .setting
DC Setting
Alarm Setting
Batt.Setting
Other Setting
Home
DCV
DCI
Sys Status(FL/EQU)
Alarm Existing
Sys Info Sys Setting Current Alarm
Battery
Batt. String I.D.
Batt.Status
Batt. Current
* DC/DC Data
AC & Temp
ACV VoltageAmbient Temp.
Data &
Version
Date/TimeH/W version
S/W version
Display (Event Log)
8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02
5/14
Outdoor Power Troubleshooting and Maintenance
Add AC Socket
RBS2216 AC Panel Configurations
Changeover Switch
Phase 1 (with Genset Socket & Changeover Switch):
Implementation: from first batch
Genset Socket
Phase 2 (without Genset Socket & Changeover Switch):
Implementation: TBD (Inventory Concern)
8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02
6/14
Outdoor Power Troubleshooting and Maintenance
ACH/ACL/ AC Off Alarm
Check ACL/ACH alarm Setting. Verify the AC input voltage at the AC service
panel by a multi-meter. To check whether commercial power problem or AC circuitbreaker tripped causes the AC Fail. The AC circuit breaker should be tripped until
the AC utility is repaired and the AC input is within input specifications.
Check AC detected CKT, please refer below:
Each Phases is 180~ 240Vac
CNB10
CNB11
50:1 Transformer
220vac
=4.4Vac
8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02
7/14
Outdoor Power Troubleshooting and Maintenance
DCH/DCL Alarm
Check DCL/DCH alarm Setting. Verify the output bus-bar voltage. If the output
voltage is not within tolerance+/- 0.1Vdc. However, swap the rectifier with a
spare module, and return the faulty unit to Delta Products for repair. If the output
of each rectifier is within tolerance, check the controllere parameters to ensure
the correct FL/EQU settings.
8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02
8/14
Outdoor Power Troubleshooting and Maintenance
Load/Battery Breaker Trip Alarm
If the circuit breaker continues to fail:
Check trip load side still short or over rating.
Check the DC Branch load (fed by the DC circuit breaker) to ensure the circuit
breaker is the correct rating. If the branch load exceeds the circuit breaker rating,
the circuit breaker must be changed to a higher rating.
Swap with a spare circuit breaker with a higher rating.
8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02
9/14
Outdoor Power Troubleshooting and Maintenance
Temperature/Humidity Alarm or Sensor Lose
This alarm is generated when the threshold temperature set in parameteralarm setting TA/Tb1 is exceeded and also controls the Temperature
Compensation Voltage Control. The CSU senses the temperature via sensor
TA/Tb1 and generates an Ambient Over Temperature Alarm setting TA/Tb1.
TA& TB1 sensor
8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02
10/14
Outdoor Power Troubleshooting and Maintenance
Rectifier Failure Alarm
When a rectifier fails, the alarm information is sent to the CSU and the rectifier is
shut down. The rectifier should be swapped out with a spare unit and the faulty
unit returned to Delta for repair.
Warning! Do not open the rectifier module. There are no serviceable
parts. Call Delta Customer Service for a RMA number for repair andreturn.
8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02
11/14
Outdoor Power Troubleshooting and Maintenance
Controller (CCU/NSCSU) Failure
When a controller fails, all rectifiers still continued suopport system.Check inside
LED still flash or not. Check display connector is perfect
LED Flash is
Normal
LED Flash is
Normal
8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02
12/14
Outdoor Power Troubleshooting and Maintenance
Cooling System Failure
Pull
Pull out spring from the hole
from right bracketTurning spring
Turning spring
Step 1 Step 2 Step 3
Air Filter Maintenance - 2
The system is equipped with one piece of the filter on the door.
To remove the filter, pull out the filter from slot and than, re-install the new
one by push in to the slot.
8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02
13/14
Outdoor Power Troubleshooting and Maintenance
Cooling System Failure
Loose the Thumbscrew Push the tray backward Pull out the Fan tray
Replacing a Fan Tray
The fan tray should replace when it is fail. First, un-plug the two connectors
on the tray. Then, refer the figures below.
8/12/2019 06troubleshooting Maintenance 130529204302 Phpapp02
14/14
Outdoor Power Troubleshooting and Maintenance
Q & A