Describe the Configuration of C200 Hardware and I/O
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
2
April 19, 2023
Introduction
• In this lesson you will learn to configure C200 hardware and I/O using Control Builder
• At the conclusion of this lesson, you will be able to:
– Identify C200 hardware, slot numbers and addressing
– Configure and download hardware configurations for these components
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
3
April 19, 2023
Topics
• Hardware and Slot Numbers
• Configuring the FTEB, Controller, and CEE
• Configuring IOMs
• Loading the Controller, CEE, and IOMs
• Activating a CEE
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
4
April 19, 2023
C200 Chassis Hardware
• Below is an example C200 chassis configured with:
Control Processor (C200)
123
4
5678
5 6 7 8432
1
10-slot chassis
Power supply
ControlNet Interface (CNI)or FTE Bridge
IO Link Interface Module
Fieldbus Interface Module
Redundancy Module
CNI to Remote I/O
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
5
April 19, 2023
C200 I/O Slot Numbers
• To determine the slot location of C200 related hardware you must:
– Start counting at zero (do not count the power supply)
– Count from left to right
– Count both spaces if the module occupies two spaces
Power Supply 12
34
56
78
0
9
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
6
April 19, 2023
Topics
• Hardware and Slot Numbers
• Configuring the FTEB, Controller, and CEE
• Configuring IOMs
• Loading the Controller, CEE, and IOMs
• Activating a CEE
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
7
April 19, 2023
Fault Tolerant Ethernet Bridge (FTEB)
• Single-wide chassis module
• Connects to FTE cable A and B
• Supports chassis redundancy
• Can only be used for Supervisory Control Network connection
• ControlNet and downlink CNIs required for all I/O communications including peer-to-peer to AB devices
• Rotary switch for FTE Node Number (1 to 99)
– IP address of FTEB can be set to higher than 99 by configuring the Base IP address accordingly from System Preferences option
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
8
April 19, 2023
Fault Tolerant Ethernet Bridge (FTEB), contd.
• The FTEB can be used for FIM-only connections to the supervisory network
• In the Project and Monitoring tabs in Control Builder you will see the FTEB as the root for the CPM
• You will set up the FTEB using IP addresses
• An FTE community can only have 99 FTEBs so you are limited to 49 redundant pairs and 99 single FTEBs in one community
• The FTE connection to the FTEB is 10Mbps
– 10Mbps is only supported in FTE for connection from an FTEB to a switch and nowhere else
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
9
April 19, 2023
Configuring a FTEB
Must match the hardware switches found on top of the
FTEB card
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
10
April 19, 2023
Question 1: FTEB Node Numbering
No. '257' is not a valid FTEB node number. FTEB IP address can be set to higher then 99
by configuring the base IP address accordingly in System Preferences in Control Builder.
Click anywhere to continue.
No. '257' is not a valid FTEB node number. FTEB IP address can be set to higher then 99
by configuring the base IP address accordingly in System Preferences in Control Builder.
Click anywhere to continue.
No. '257' is not a valid FTEB node number. FTEB IP address can be set to higher then 99
by configuring the base IP address accordingly in System Preferences in Control Builder.
Click anywhere to continue.
No. '257' is not a valid FTEB node number. FTEB IP address can be set to higher then 99
by configuring the base IP address accordingly in System Preferences in Control Builder.
Click anywhere to continue.
No. '257' is not a valid FTEB node number. FTEB IP address can be set to higher then 99
by configuring the base IP address accordingly in System Preferences in Control Builder.
Click anywhere to continue.
No. '257' is not a valid FTEB node number. FTEB IP address can be set to higher then 99
by configuring the base IP address accordingly in System Preferences in Control Builder.
Click anywhere to continue.
No. '257' is not a valid FTEB node number. FTEB IP address can be set to higher then 99
by configuring the base IP address accordingly in System Preferences in Control Builder.
Click anywhere to continue.
No. '257' is not a valid FTEB node number. FTEB IP address can be set to higher then 99
by configuring the base IP address accordingly in System Preferences in Control Builder.
Click anywhere to continue.
Correct - Click anywhere to continueCorrect - Click anywhere to continueIncorrect - Click anywhere to continueIncorrect - Click anywhere to continueYou answered this correctly!You answered this correctly!
Your answer:Your answer:The correct answer is:The correct answer is:
You did not answer this question completelyYou did not answer this question completelyYou must answer the question before continuing
You must answer the question before continuing
Submit Clear
Which of the following is not a valid FTEB node number?
A) 110
B) 99
C) 257
D) 1
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
11
April 19, 2023
Configuring a Controller
Follow these steps to add a new control processor module (CPM) from the pull-down menus
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
12
April 19, 2023
Configuring a Controller – CPM Main Tab
• Data entry details will be provided in the lab exercise
MAC ID of CNI Card
connected to server
CNI slot #
Slot number of CPM
Check for the redundant controller and then enter its
name
ControlNet or Ethernet driver
Tag Name & Item Name
Driver Name
Alarm reporting by CEE
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
13
April 19, 2023
Configuring a Controller – CPM Main Tab, contd.
• Data entry details will be provided in the lab exercise Ethernet
NetworkDriver Name
Slot Number of CPM
Redundant Controller & Name
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
14
April 19, 2023
• History parameters and control level required to operate this CPM
Configuring a Controller – Server History Tab
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
15
April 19, 2023
Configuring a Controller – Group and Trend Assignment
Point, group, trend and associated displays (that reside on the
server) are defined on the Server Displays tab
Select OK to close and save the new
controller
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
16
April 19, 2023
Question 2: Supervisory MAC Address for a CPM
Incorrect. The Supervisory MAC address is the MAC address of the CNI card connected to the server.
Click anywhere to continue.
Incorrect. The Supervisory MAC address is the MAC address of the CNI card connected to the server.
Click anywhere to continue.
Incorrect. The Supervisory MAC address is the MAC address of the CNI card connected to the server.
Click anywhere to continue.
Incorrect. The Supervisory MAC address is the MAC address of the CNI card connected to the server.
Click anywhere to continue.
Incorrect. The Supervisory MAC address is the MAC address of the CNI card connected to the server.
Click anywhere to continue.
Incorrect. The Supervisory MAC address is the MAC address of the CNI card connected to the server.
Click anywhere to continue.
Correct! The Supervisory MAC address is the MAC address of the CNI card connected to the server.
Click anywhere to continue.
Correct! The Supervisory MAC address is the MAC address of the CNI card connected to the server.
Click anywhere to continue.
Correct - Click anywhere to continueCorrect - Click anywhere to continueIncorrect - Click anywhere to continueIncorrect - Click anywhere to continueYou answered this correctly!You answered this correctly!
Your answer:Your answer:The correct answer is:The correct answer is:
You did not answer this question completelyYou did not answer this question completelyYou must answer the question before continuing
You must answer the question before continuing
Submit Clear
While configuring a ControlNet connected control processor module (CPM) in Control Builder, which MAC address is entered as the Supervisory MAC address?
A) The device index of FTEB card
B) The MAC address of the PCIC card
C) The MAC address of CNI card connected to the I/O rack
D) The MAC address of CNI card connected to server
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
17
April 19, 2023
Configuring a CEE – CPM/CEE Tree View
Double-click to open the configuration form
Click the + sign to expand the CPM in the
Project tab
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
18
April 19, 2023
Configuring a CEE – Main Tab
Data entry details will be provided in the Lab exercise
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
19
April 19, 2023
Configuring C200 Hardware
• The Control Processor Module (CPM) and its Control Execution Environment (CEE) are configured but not yet downloaded
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
20
April 19, 2023
• Hardware and Slot Numbers
• Configuring the FTEB, Controller, and CEE
• Configuring IOMs
• Loading the Controller, CEE, and IOMs
• Activating a CEE
Topics
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
21
April 19, 2023
Configuring Input/Output Modules (IOMs)
Menu method
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
22
April 19, 2023
Configuring IOMs
Control Builder Automatically
Names the IOM
2
1
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
23
April 19, 2023
Configuring IOMs, contd.
MAC address of the remote rack’s CNI card
Slot number of the CNI inthe processor rack through which this card will communicate
Module slot number
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
24
April 19, 2023
Assigning IOMs
213
Assigned to CEE
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
25
April 19, 2023
Question 3: Configuring an IOM
Incorrect. Before you can load IOMs, they must be assigned to the Control Execution Environment.
Click anywhere to continue.
Incorrect. Before you can load IOMs, they must be assigned to the Control Execution Environment.
Click anywhere to continue.
Correct! Before you can load IOMs, they must be assigned to the Control Execution Environment.
Click anywhere to continue.
Correct! Before you can load IOMs, they must be assigned to the Control Execution Environment.
Click anywhere to continue.
Incorrect. Before you can load IOMs, they must be assigned to the Control Execution Environment.
Click anywhere to continue.
Incorrect. Before you can load IOMs, they must be assigned to the Control Execution Environment.
Click anywhere to continue.
Incorrect. Before you can load IOMs, they must be assigned to the Control Execution Environment.
Click anywhere to continue.
Incorrect. Before you can load IOMs, they must be assigned to the Control Execution Environment.
Click anywhere to continue.
Correct - Click anywhere to continueCorrect - Click anywhere to continueIncorrect - Click anywhere to continueIncorrect - Click anywhere to continueYou answered this correctly!You answered this correctly!
Your answer:Your answer:The correct answer is:The correct answer is:
You did not answer this question completelyYou did not answer this question completelyYou must answer the question before continuing
You must answer the question before continuing
Submit Clear
Before loading an IOM, it must be:
A) Activated
B) Assigned
C) Renamed
D) Validated
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
26
April 19, 2023
• Hardware and Slot Numbers
• Configuring the FTEB, Controller, and CEE
• Configuring IOMs
• Loading the Controller, CEE, and IOMs
• Activating a CEE
Topics
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
27
April 19, 2023
Loading the Controller, CEE, and IOMs
Not yet loaded
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
28
April 19, 2023
Verify that the items to load are checked
Note: You can decide to have the modules go to the active state automatically by clicking this checkbox, with the Post Load State selected, to be “Active”
Loading the Controller, CEE, and IOMs, contd.
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
29
April 19, 2023
Topics
• Hardware and Slot Numbers
• Configuring the FTEB, Controller and CEE
• Configuring IOMs
• Loading the Controller, CEE and IOMs
• Activating a CEE
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
30
April 19, 2023
Activating a Control Strategy
Select Cold Start
Double-click CEE
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
31
April 19, 2023
Activating a Control Strategy, contd.
Click Yes
Blue: The object is not running (inactive)
Green: The object is running (active)
Red: Communication failure
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
32
April 19, 2023
Summary
• When configuring and loading C200 hardware and I/O in Control Builder, remember:
– To determine the IOM slot number of hardware in the C200 chassis, start counting at zero, but do not count the power supply, count from left to right and count both spaces, if the module occupies two spaces
– An FTEB node number can be set to higher than 99
– The Supervisory MAC address of the CPM is the MAC address of the CNI card connected to the server
– Before loading the Control Processor Module (CPM), its Control Execution Environment (CEE), and I/O modules (IOMs):
• Configure the CPM, its CEE and I/O modules (IOMs)
• Assign the IOMs to the CEE
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
33
April 19, 2023
Conclusion
Describe the Configuration of C200 Hardware and I/O
CompletionCompletionCertificateCertificate
Proceed to the next lesson in your course material
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
34
April 19, 2023
This page intentionally left blank
C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O
EXP20R300 - EPKS CEE C200/C300/ACE
35April 19, 2023
Describe the Import/Export Procedure in Control Builder
C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
36
April 19, 2023
Introduction
• In this lesson you will learn to import and export control strategy configurations from one server to another
• At the conclusion of this lesson, you will be able to:
– Describe how to export control strategy configurations from a Control Builder project
– Describe how to import control strategy configurations into a Control Builder project
C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
37
April 19, 2023
Control Builder - Export
• The Export function lets you export all or a portion of the ERDB viewed in the Project Tree to the Ixport folder or a user-defined location
• The exported portions or all of the ERDB are stored in the Ixport folder at directory location– C:\Program Files\Honeywell\
Experion PKS\Engineering Tools (by default)
C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
38
April 19, 2023
Ixport Directory
Control Builder(Server 1)
Control Builder(Server 2)
Control Strategy Configuration
Project Tree
Control Strategy Configuration
Project Tree
Export Data
Import Data
Control Builder – Import/Export
CM, SCM and hardware configurations can be moved between servers using the Import/Export function
C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
39
April 19, 2023
Control Builder – Export
• In Control Builder, select File > Export to call up the dialog box shown:
All items in Current project
Import\Export text files target location
All items in current project use selection buttons (or use <Ctl> + mouse select or <Shift> + mouse select to export specific CMs from the point window)
List of items to Export based on selections from window(Export.sl)
Select to start export
C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
40
April 19, 2023
Control Builder – Export, contd.
Exporting Data Dialog Box
C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
41
April 19, 2023
Control Builder – Import
• In Control Builder, select File > Import to call up the dialog box shown:
All items in Current Import/Export text Files location
Import\Export text Files target location
Import and Assign
Select to start Import
Use selection buttons (or use <Ctl> + mouse select or <Shift> + mouse select to import specific CMs from the Point window)
When enabled, Your own list of items to import (Filename.sl)
List of items to Import based on Selections from Window (Import.sl)
C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
42
April 19, 2023
Question 1: Importing and Exporting
Incorrect. CMs, SCMs and the hardware configuration can be copied and restored to
another server.
Click anywhere to continue.
Incorrect. CMs, SCMs and the hardware configuration can be copied and restored to
another server.
Click anywhere to continue.
Correct! CMs, SCMs and the hardware configuration can be copied and restored to
another server.
Click anywhere to continue.
Correct! CMs, SCMs and the hardware configuration can be copied and restored to
another server.
Click anywhere to continue.
Incorrect. CMs, SCMs and the hardware configuration can be copied and restored to
another server.
Click anywhere to continue.
Incorrect. CMs, SCMs and the hardware configuration can be copied and restored to
another server.
Click anywhere to continue.
Incorrect. CMs, SCMs and the hardware configuration can be copied and restored to
another server.
Click anywhere to continue.
Incorrect. CMs, SCMs and the hardware configuration can be copied and restored to
another server.
Click anywhere to continue.
Correct - Click anywhere to continueCorrect - Click anywhere to continueIncorrect - Click anywhere to continueIncorrect - Click anywhere to continueYou answered this correctly!You answered this correctly!
Your answer:Your answer:The correct answer is:The correct answer is:
You did not answer this question completelyYou did not answer this question completelyYou must answer the question before continuing
You must answer the question before continuing
Submit Clear
Which of the following statements best describes the import/export function?
A) Only the hardware configuration can be moved between servers
B) CMs, SCMs, and the hardware configuration can be copied and restored to another server
C) Only CMs can be moved between servers
D) None of the above
C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
43
April 19, 2023
Summary
• The Import/Export function in Control Builder:
– Allows you to copy CM, SCM, and hardware configurations from one server’s ERDB to another server’s ERDB
C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder
EXP20R300 - EPKS CEE C200/C300/ACE
Honeywell
44
April 19, 2023
Conclusion
Describe the Import/Export Procedure in Control Builder
CompletionCompletionCertificateCertificate
Proceed to the Configure C200 Hardware in a Simulation Control Environment (SCE) and Import the Remaining I/O Modules into the SCE
lab exercises
C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder