      TECHNICAL REPORT CSQ

    CSQ n° 9101.TESA

    Certificazione sistema di Qualità

    ISO9001

      POWER TRANSFORMER  pag. 1/15

    Page 1 of 15

    Ability to Withstand Dynamic Effects of Short Circuit

    Comparative Statement

    DATA: 28/03/10ISSUED BY APPROVED BY

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    2/15

      TECHNICAL REPORT CSQ

    CSQ n° 9101.TESA

    Certificazione sistema di Qualità

    ISO9001

      POWER TRANSFORMER  pag. 2/15

    2

    Ability to Withstand Dynamic Effects of Short Circuit Comparative Statement

    The IEC 60076-5 standard gives the comparison criteria to verify the applicability of a short-circuit withstand

    test performed on a transforer to a similar transformer. The technical feature to be taken into consideration are

     prescribed in the Annex B “Guidance for the identification of a similar transformer” and showed in Table 1

     below.

    Tesar has positively tested a Cast-Resin Transformer 2500 kVA at CESI Laboratory (test certificate n.

    A7030507 dtd 3rd

     Ddecember 2007):

    This test certificate is applicable to the transformers having characteristics according to the content of Table 1

    and Table 2

    Table 1

    Critical features as per IEC 60076.5 Tested Transformer 2500

    kVA

    Similar Transformers

    same type of operation: distribution type distribution type

    same conceptual design: cast resin, core type with

    concentric and circularwindings

    cast resin, core type with

    concentric and circular windings

    same arrangement of main windings and

    geometrical sequence

    HV : cast

    LV: pre-preg

    Geometrical sequence :

    HV outside , LV inside

    Same as the tested transformer

    same type of winding conductors Al Same as the tested transformer

    same type of main windings layer for LV and HV coils layer for LV and HV coils

    absorbed power for at short circuit between

    30% and 130% of that of the reference unit

    from 12.038,52 up to

    52166,93 p.u.

    ≤ 52.166,93 p.u.

    axial forces and relative winding stresses at

    short circuit not exceeding 110% of those in

    the reference unit

    as per design Transformers in Table 2 have

    forces and stresses within the

    limit required

    same manufacturing process HV : cast

    LV : pre-preg

    Same

    same clamping and supporting arrangement Correlated to the short

    circuit current

    Same arrangement , correlated to

    the short circuit current

    Table 2

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    3/15

      TECHNICAL REPORT CSQ

    CSQ n° 9101.TESA

    Certificazione sistema di Qualità

    ISO9001

      POWER TRANSFORMER  pag. 3/15

    3

    Tested transformer

    Rated Power [kVA] 2500

    Impedance [%] 6,23

    Absorbed power at S.C. [pu] 40.128,41

    Range 30% [pu] 12.038,52

    Range 130% [pu] 52.166,93

    Similar transformer

    Rated Power

    Rated

    Impeda

    nce

    Absorbed

     power at

    S.C.

    Impedance

    min

    Impedance

    max

    [kVA] [%] [pu] [pu] [pu]

    500 4 12.500,00 0,96 4,15

    630 4 15.750,00 1,21 5,23

    800 6 13.333,33 1,53 6,65

    1000 6 16.666,67 1,92 8,31

    1250 6 20.833,33 2,40 10,38

    1500 6 25.000,00 2,88 12,46

    1600 6 26.666,67 3,07 13,29

    2000 6 33.333,33 3,83 16,61

    2500 6 41.666,67 4,79 20,77

    2700 6 45.000,00 5.17 22,43

    3000 6 50.000,00 5,75 24,92

     

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    4/15

     

    4

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    5/15

     

    5

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    6/15

     

    6

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    7/15

     

    7

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    8/15

     

    8

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    9/15

     

    9

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    10/15

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    11/15

     

    11

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    12/15

     

    12

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    13/15

     

    13

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    14/15

     

    14

  • 8/17/2019 05-Short Circuit Dynamic Comparative Statement

    15/15