20
CHAPTER 5 FIRE SERVICE FEATURES SECTION 501 GENERAL 501.1 Scope. Fire service features for buildings, structures and premises shall comply with this chapter. 501.2 Permits. A permit shall be required as set forth in Sec- tions 105.6 and 105.7. 501.3 Construction documents. Construction documents for proposed fire apparatus access, location of fire lanes and con- struction documents and hydraulic calculations for fire hydrant systems shall be submitted to the fire department for review and approval prior to construction. 501.4 Timing of installation. When fire apparatus access roads or a water supply for fire protection is required to be in- stalled, such protection shall be installed and made serviceable prior to and during the time of construction except when ap- proved alternative methods of protection are provided. Tempo- rary street signs shall be installed at each street intersection when construction of new roadways allows passage by vehicles in accordance with Section 505.2. 501.5 Inspections. 501.5.1 Inspections for private water supply systems. Private water supply system installations and modifications shall be subject to field inspection and tests by the fire de- partment. 501.5.2 Inspection of fire apparatus access roads. Roads used for fire apparatus access shall be subject to field in- spection and may be subject to testing using fire apparatus. The owner is responsible for any repairs necessary due to the inadequate design of the access road. 501.5.3 Inspection of controlled access gates. Controlled access gates shall be subject to field inspection and may be tested using fire apparatus. SECTION 502 DEFINITIONS 502.1 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. ADDRESS DIRECTORIES. Graphic displays of dwelling unit or business suite locations that are weather resistant, inter- nally illuminated and permanently mounted adjacent to the fire apparatus access road. ALTERNATIVE SURFACE ACCESS ROADS. Roads for fire department use, that are required for fire department ac- cess, and that are constructed with approved materials, other than pavement. CONTROLLED ACCESS GATES. Automatic or manually operated gates or devices that are placed across a fire apparatus access road. FIRE APPARATUS ACCESS ROAD. A road that provides fire apparatus access to a facility, building or portion thereof. This is a general term inclusive of all other terms such as fire lane, private street, parking lot lane and access roadway. FIRE COMMAND CENTER. The principal attended or un- attended location where the status of the detection, alarm com- munications and control systems is displayed, and from which the system(s) can be manually controlled. FIRE DEPARTMENT MASTER KEY. A limited issue key of special or controlled design to be carried by fire department officials in command which will open key boxes on specified properties. FIRE FLOW. The flow rate of a water supply, measured at 20 psi residual pressure that is available for firefighting. FIRE LANE. A road or other passageway developed to allow the passage of fire apparatus. The driving surface may not be the same as for a public road. HYDAULICALLY MOST DEMANDING HYDRANT. The hydrant that results in the greatest flow and pressure re- quirement needed to supply the private fire distribution main(s). KEY BOX. A secure, tamperproof device with a lock operable by a fire department master key, and containing building entry keys and other keys that may be required for access in an emer- gency. PEDESTRIAN GATES. Pedestrian gates are gates used by pedestrians to provide access to or egress from buildings, yards, patios, courts, swimming pools and similar areas. PREEMPTION DEVICE. An approved electronic device at- tached to a controlled access gate that is used to open the gate when an electronic signal is received from an emergency vehicle. SPREAD NUMBERS. Numbers attached to a building that show the unit number of each dwelling unit on each floor of that residential building in a multibuilding residential complex. SECTION 503 FIRE APPARATUS ACCESS ROADS 503.1 Where required. Fire apparatus access roads shall be provided and maintained in accordance with this section. The Fire Department is the only authorized authority to designate fire lanes. 503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the City of Phoenix. The fire apparatus access road shall comply with the requirements of this section and shall extend to: 2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 51

05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

  • Upload
    docong

  • View
    214

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

CHAPTER 5

FIRE SERVICE FEATURES

SECTION 501GENERAL

501.1 Scope. Fire service features for buildings, structures andpremises shall comply with this chapter.

501.2 Permits. A permit shall be required as set forth in Sec-tions 105.6 and 105.7.

501.3 Construction documents. Construction documents forproposed fire apparatus access, location of fire lanes and con-struction documents and hydraulic calculations for fire hydrantsystems shall be submitted to the fire department for reviewand approval prior to construction.

501.4 Timing of installation. When fire apparatus accessroads or a water supply for fire protection is required to be in-stalled, such protection shall be installed and made serviceableprior to and during the time of construction except when ap-proved alternative methods of protection are provided. Tempo-rary street signs shall be installed at each street intersectionwhen construction of new roadways allows passage by vehiclesin accordance with Section 505.2.

501.5 Inspections.

501.5.1 Inspections for private water supply systems.Private water supply system installations and modificationsshall be subject to field inspection and tests by the fire de-partment.

501.5.2 Inspection of fire apparatus access roads. Roadsused for fire apparatus access shall be subject to field in-spection and may be subject to testing using fire apparatus.The owner is responsible for any repairs necessary due tothe inadequate design of the access road.

501.5.3 Inspection of controlled access gates. Controlledaccess gates shall be subject to field inspection and may betested using fire apparatus.

SECTION 502DEFINITIONS

502.1 Definitions. The following words and terms shall, for thepurposes of this chapter and as used elsewhere in this code,have the meanings shown herein.

ADDRESS DIRECTORIES. Graphic displays of dwellingunit or business suite locations that are weather resistant, inter-nally illuminated and permanently mounted adjacent to the fireapparatus access road.

ALTERNATIVE SURFACE ACCESS ROADS. Roads forfire department use, that are required for fire department ac-cess, and that are constructed with approved materials, otherthan pavement.

CONTROLLED ACCESS GATES. Automatic or manuallyoperated gates or devices that are placed across a fire apparatusaccess road.

FIRE APPARATUS ACCESS ROAD. A road that providesfire apparatus access to a facility, building or portion thereof.This is a general term inclusive of all other terms such as firelane, private street, parking lot lane and access roadway.

FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control systems is displayed, and from whichthe system(s) can be manually controlled.

FIRE DEPARTMENT MASTER KEY. A limited issue keyof special or controlled design to be carried by fire departmentofficials in command which will open key boxes on specifiedproperties.

FIRE FLOW. The flow rate of a water supply, measured at 20psi residual pressure that is available for firefighting.

FIRE LANE. A road or other passageway developed to allowthe passage of fire apparatus. The driving surface may not bethe same as for a public road.

HYDAULICALLY MOST DEMANDING HYDRANT.The hydrant that results in the greatest flow and pressure re-quirement needed to supply the private fire distributionmain(s).

KEY BOX. A secure, tamperproof device with a lock operableby a fire department master key, and containing building entrykeys and other keys that may be required for access in an emer-gency.

PEDESTRIAN GATES. Pedestrian gates are gates used bypedestrians to provide access to or egress from buildings,yards, patios, courts, swimming pools and similar areas.

PREEMPTION DEVICE. An approved electronic device at-tached to a controlled access gate that is used to open the gatewhen an electronic signal is received from an emergencyvehicle.

SPREAD NUMBERS. Numbers attached to a building thatshow the unit number of each dwelling unit on each floor ofthat residential building in a multibuilding residential complex.

SECTION 503FIRE APPARATUS ACCESS ROADS

503.1 Where required. Fire apparatus access roads shall beprovided and maintained in accordance with this section. TheFire Department is the only authorized authority to designatefire lanes.

503.1.1 Buildings and facilities. Approved fire apparatusaccess roads shall be provided for every facility, building orportion of a building hereafter constructed or moved into orwithin the City of Phoenix. The fire apparatus access roadshall comply with the requirements of this section and shallextend to:

2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 51

Page 2: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

1. 200 feet of all portions of the facility and all portions ofthe exterior walls of the first story of the building as mea-sured by an approved route around the exterior of thebuilding or facility in non-sprinklered buildings,

2. 300 feet of all portions of the facility and all portions ofthe exterior walls of the first story of the building as mea-sured by an approved route around the exterior of thebuilding or facility in sprinklered buildings,

Exception: An alternative means of fire protection isprovided.

503.1.2 Fences. When fences are installed that cause thedistances from an approved fire department access road toexceed the maximum distance allowed in Section 503, a pe-destrian gate shall be provided in the fence to maintain therequired fire department access. The gate shall be a mini-mum 4 feet in width and be equipped with a key box in ac-cordance with Section 506.

503.1.3 Additional access. The Fire Marshal is authorizedto require more than one fire apparatus access road based onthe potential for impairment of a single road by vehicle con-gestion, condition of terrain, climatic conditions or otherfactors that could limit access.

503.1.4 High-piled storage. Fire department vehicle ac-cess to buildings used for high-piled combustible storageshall comply with the applicable provisions of chapter 23.

503.2 Specifications. Fire apparatus access roads shall be in-stalled and arranged in accordance with Section 503.2.

Public streets and City approved access ways shall be in ac-cordance with City of Phoenix Streets and Traffic Departmentspecifications.

503.2.1 Dimensions. Fire apparatus access roads shall havean unobstructed width of not less than 20 feet (6096 mm),and an unobstructed vertical clearance of not less than 14feet.

Fire apparatus access roads established and approved perDevelopment Service Department site plan prior to the ef-fective date of this code, are not required to be widened ifmaintained and marked in accordance with this Chapter.

503.2.2 Authority. The Fire Marshal shall have the author-ity to require an increase in the minimum access widthswhere they are inadequate for fire or rescue operations.

503.2.3 Loading areas and passenger drop-off areas. Onprivate property, where fire apparatus access roads are uti-lized for loading or unloading or are utilized for passengerdrop off or pickup, an additional 8 feet of width shall beadded to the fire apparatus access road. This width is in ad-dition to the minimum 20 foot access road width.

503.2.4 Surface. Fire apparatus access roads shall be de-signed to and maintained to support a minimum imposedlive load of 66,000 pounds with a maximum axle load of28,000 pounds. Fire apparatus access roads shall be pro-vided and maintained with all-weather driving capabilitiessurface. When a surface other than paving is used for a fireapparatus access road, it shall comply with Section 503.6.6.

503.2.5 Turning radius. Fire apparatus access roads shallhave a minimum 45-foot center line radius (35 foot insideradius, 55 foot outside radius) on curves. See Figure 5-2.

503.2.6 Dead ends. Dead-end fire apparatus access roads inexcess of 200 feet (45 720 mm) in length shall be providedwith an approved area for turning around fire apparatus. SeeFigure 5-3.

503.2.7 Bridges and elevated surfaces. Where a bridge oran elevated surface is part of a fire apparatus access road, thebridge shall be constructed and maintained in accordancewith AASHTO Standard Specification for HighwayBridges. Bridges and elevated surfaces shall be designed tosupport a maximum live load of 66,000 pounds with a maxi-mum axle load of 28,000 pounds. Vehicle load limits shallbe posted at both entrances to bridges when required by theFire Marshal. Where elevated surfaces designed for emer-gency vehicle use are adjacent to surfaces which are not de-signed for such use, approved barriers, approved signs orboth shall be installed and maintained when required by theFire Marshal.

503.2.8 Grade. The grade of the fire apparatus access roadshall not exceed 15 percent (15 feet in 100 feet). Cross-slopeof an access road shall not exceed 3 percent.

503.2.9 Drainage. Water drainage shall be directed awayfrom or piped under the fire apparatus access roads. Pondingof water on an access road shall not exceed a depth of 6inches.

503.2.10 Stabilization. A stabilized edge meetingMaricopa Association of Governments standards or equiva-lent is required on fire apparatus access roads to provide sta-bilization.

503.3 Marking. Where required by the fire code official,painted curbs and approved signs or other approved notices orshall be provided and maintained for fire apparatus accessroads to identify such roads or prohibit the obstruction thereof.The marking of fire lanes shall be in accordance with Section503.3. Signs or notices shall be maintained in a clean and legi-ble condition at all times, and be replaced or repaired when nec-essary to provide adequate visibility.

503.3.1 Curbs. Fire apparatus access roads shall be identi-fied by curbs painted red on both the top and face along theentire length of the fire apparatus access road. Where nocurb exists or a rolled curb is installed, a 6-inch wide redstripe applied the full length of the fire apparatus access roadshall be installed.

503.3.2 Fire lane signs. Approved fire lane signs shall be inaccordance with Figures 5-4 and 5-5. The signs shall be in-stalled as follows:

1. Signs shall be attached to an approved stationary poleset in concrete a minimum of depth of 18 inches. SeeFigure 5-5

2. The bottom of each sign shall be 7 feet above grade.See Figure 5-5

3. The signs shall face oncoming traffic.

52 2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS

FIRE SERVICE FEATURES

Page 3: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

4. The signs shall be set back from the curb line or side-walk a minimum of 12 inches to a maximum of 18inches.

5. Signs shall be plainly visible at all times. Vegetationor other obstructions shall be located such that a mini-mum 3-foot clearance is maintained along the line ofsight.

6. Spacing of signs and marking of curbs shall be as fol-lows:

a. A sign shall be installed a maximum of 15 feetfrom the beginning and end of the fire lane.

b. When spacing between signs does not exceed75 feet, the curb on the sign side of the fire laneshall be painted red. See Figure 5-6, Detail 1.

c. When spacing between signs does not exceed100 feet, curb on the sign side of the fire laneshall be painted red and stenciled “FIRE LANENO PARKING” midway between signs. SeeFigure 5-6, Detail 2.

d. Spacing between signs shall not exceed 100feet.

e. Fire lanes up to 65 feet in length shall be identi-fied with 1 double faced sign and the curbpainted red and stenciled “FIRE LANE NOPARKING” 15 feet from each end of the road.See Figure 5-6, Detail 3.

f. Fire lane marking on bull-nose or islands shallhave one double faced sign located in the centerand the curb painted red. See Figure 5-6, Detail4.

503.3.3 Marking not required. Signs and red painted curbsare not required on either side of the fire apparatus accessroad when a fire apparatus access road is greater than 36 feetin width.

503.3.4 Signs required on both sides of a road. When afire apparatus access road is less than 28 feet in width firelane signs and red painted curbs are required on both sidesof the access road.

Fire apparatus access roads serving only R-3 Occupanciesare required to have signs and red painted curbs installed onboth sides of the road when 20 feet or less in width.

503.3.5 Signs required on one side of road. When a fireapparatus access road is 28 feet or greater and less than orequal to 36 feet in width, fire lane signs and red paintedcurbs are required to be installed on a minimum of one sideof the access road.

Fire apparatus access roads serving only R-3 Occupanciesrequire signs and red painted curbs on a minimum of one sideof the fire apparatus access road when it is greater than 20 feetand less than or equal to 28 feet in width.

503.3.6 Stenciling. The fire department is authorized to re-quire stenciling or other permanent markings to improve theidentification of fire apparatus access roads. When required,the stenciling shall state “FIRE LANE NO PARKING.” Let-tering in Figure 5-6 shall be white on a red painted curb and

shall be a minimum of 3 inches high with 1/2 inch brushstroke.

503.4 Obstruction of fire apparatus access roads. Fire appa-ratus access roads shall not be obstructed in any manner, in-cluding the parking of vehicles. The minimum widths andclearances established in Section 503.2.1 shall be maintainedat all times.

503.4.1 Required gates or barricades. The fire code offi-cial is authorized to require the installation and maintenanceof gates or other approved barricades across fire apparatusaccess roads, trails or other access-ways, not including pub-lic streets, alleys or highways.

503.4.2 Secured gates and barricades. When required,gates and barricades shall be secured in an approved man-ner. Roads, trails and other access-ways that have beenclosed and obstructed in the manner prescribed by Section503.5 shall not be trespassed on or used unless authorizedby the owner and the fire code official.

Exception: The restriction on use shall not apply to pub-lic officers acting within the scope of duty.

Locks, gates, doors, barricades, chains, enclosures,signs, tags or seals which have been installed by the firedepartment or by its order or under its control shall not beremoved, unlocked, destroyed or tampered with in anymanner.

Exception: When authorized by the fire code officialor performed by public officers acting within theirscope of duty.

503.4.3 Security gates. See Section 511.

503.4.4 Stopping or parking in fire apparatus accessroads. Motor vehicles, with or without power, includingtrailers, shall not be stopped or parked in any fire apparatusaccess road.

Any vehicle stopped or parked within an approved fireapparatus access road may be issued a “Notice of ParkingViolation” by any member of the Phoenix Fire Departmentor Phoenix Police Department, or any representative the firechief or police chief designates.

Any vehicle stopped or parked within the fire apparatusaccess road may be removed at the expense of the vehicleowner. Removal of a vehicle under such circumstances maybe authorized by the person in lawful possession of theproperty or by the chief. The person in lawful possession ofthe property shall keep designated fire apparatus accessroads free of vehicles and other obstructions.

See also Phoenix City Code Sections 36-133 and 36-134(4).

503.5 Maintenance of fire apparatus access roads. Fire ap-paratus access roads shall be maintained by the owner at alltimes. Faded, damaged or vandalized signs shall be replacedwith approved signs and posts.

503.6 Alternative surface fire apparatus access roads. Thissection applies when the alternative surface fire apparatus ac-cess road is not surfaced with traditional road building materi-als. Alternative surface fire apparatus access roads shall be in

FIRE SERVICE FEATURES

2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 53

Page 4: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

accordance with this section and Sections 503.2 through503.4.4.

503.6.1 Report. Alternative surface fire apparatus accessroads shall be designed by an engineer registered in theState of Arizona. The engineer shall prepare a sealed designreport for submittal to and approval by the fire department.Plans shall be sealed and submitted with the report. See Sec-tion 501.3.

503.6.2 Stabilization. Stabilization of the fire apparatus ac-cess road surface shall be addressed in the alternative sur-face fire apparatus access road report and may beaccomplished by curbing.

503.6.3 Compaction. Minimum 95 percent compaction ofsub-grade soil is required.

503.6.4 Curbs. A rolled curb shall be installed at the en-trances to fire apparatus access roads. See Chapter 45 forMaricopa Association of Government standards with Cityof Phoenix supplements.

503.6.5 Marking. The curb shall be painted red or red re-flectors shall be installed to define the width of alternativesurface fire apparatus access roads. The reflectors shall beimbedded into bordering curbing at intervals not exceeding15 feet. See Figure 5-8 for marking requirements.

503.6.6 Special inspections. An Arizona registered Profes-sional Engineer shall conduct a special inspection prior tofinal approvals being issued for the alternative surface fireapparatus access road. See Chapter 1.

503.6.6.1 Special inspection documentation. The spe-cial inspection documentation shall include, but not belimited to the following:

1. Sub-grade soil compaction report.

2. Base material quality, thickness and compaction.

3. Concrete depth and compressive strength, whenapplicable.

4. An evaluation of the installation in accordancewith design drawings and manufacturer specifica-tions.

5. Crown and drainage requirements.

6. Stabilization (if curbing is not used).

503.7 Fire apparatus access roads during construction. Firedepartment access during construction shall comply with thissection.

503.7.1 Required access. Fire apparatus access is requiredwithin 200 feet of all points on the exterior of the building.Fire apparatus access roads shall be provided prior to intro-ducing combustible materials on the construction site.

503.7.2 Width. Fire apparatus access roads shall be a mini-mum of 20 feet in width. Fire apparatus roads on construc-tion sites shall not be obstructed.

503.7.3 Surface. At a minimum, the surface of fire appara-tus roads shall be as follows:

1. Minimum 6 inches of native soil compacted to 95percent of standard proctor density (ASTM D698),and

2. Minimum 4 inches of aggregate base compacted to100 percent of standard proctor density (ASTMD698).

The surface of fire apparatus access roads may differfrom the above requirements if it is shown that the surfaceprovided is sufficient to support an imposed live load of66,000 pounds with a maximum axle load of 28,000pounds.

An engineer registered in the State of Arizona shall pre-pare and seal the soil compaction report. The report shall beavailable for review by the fire code official.

503.7.4 Stabilization. Curbs are not required for fire appa-ratus access roads for sites under construction.

503.7.5 Turning radius. Fire apparatus access roads shallhave a minimum 45-foot center line radius (35 foot insideradius, 55 foot outside radius) on curves. See Figure 5-2

503.7.6 Dead-ends. Dead-end fire apparatus access roadsin excess of 200 feet in length shall terminate in an approvedturnaround as shown in Figure 5-3.

503.7.7 Drainage. Water drainage shall be directed awaythe fire apparatus access road.

SECTION 504ACCESS TO BUILDING OPENINGS AND ROOFS

504.1 Required access. Exterior doors and openings requiredby this code or the International Building Code shall be main-tained readily accessible for emergency access by the fire de-partment. An approved access walkway leading from fireapparatus access roads to exterior openings shall be providedwhen required by the fire code official.

Key boxes, keys, and padlocks required for fire departmentaccess shall be in accordance with Section 506

504.2 Maintenance of exterior doors and openings. Exteriordoors and their function shall not be eliminated without priorapproval. Exterior doors that have been rendered nonfunctionaland that retain a functional door exterior appearance shall havea sign affixed to the exterior side of the door with the words“THIS DOOR BLOCKED.” The sign shall consist of lettershaving a principal stroke of not less than 0.75 inch (19.1 mm)wide and at least 6 inches (152 mm) high on a contrasting back-ground. Required fire department access doors shall not be ob-structed or eliminated. Exit and exit access doors shall complywith Chapter 10. Access doors for high-piled combustible stor-age shall comply with Section 2306.6.1.

504.3 Stairway access to roof. New buildings four or morestories in height, except those with a roof slope greater thanfour units vertical in 12 units horizontal (33.3 percent slope),shall be provided with a stairway to the roof. Stairway access tothe roof shall be in accordance with Section 1009.12. Suchstairway shall be marked at street and floor levels with a sign in-dicating that the stairway continues to the roof. Where roofs areused for roof gardens or for other purposes, stairways shall beprovided as required for such occupancy classification.

54 2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS

FIRE SERVICE FEATURES

Page 5: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

SECTION 505PREMISES IDENTIFICATION

505.1 General address numbers. Approved address numbersshall be provided for all new and existing buildings in such amanner as to be plainly visible and legible from the street orroad fronting the property.

505.2 Premises identification for residential occupancies.Shall be in accordance with Section 505.

505.2.1 Single-family homes. The address numbers for sin-gle-family homes shall be a minimum of 3 inches high, witha minimum 3/8 inch brush stroke on a contrasting back-ground.

505.2.2 Address marking of multi-family residentialoccupancies. The address, individual building, spread, anddwelling numbers at Group R occupancies shall be in accor-dance with this section.

505.2.2.1 Building or site address. The street addressnumbers for Group R occupancies shall be a minimum of12 inches high with a minimum of 2-inch wide brushstroke on contrasting color. For buildings less than 100feet long, a minimum of one address shall be provided.For buildings over 100 feet in length, the address is re-quired in a minimum of two places. Each building in acomplex shall display its own identification.

505.2.2.2 Building identification numbers. Eachbuilding shall display its specific alphabetical or numeri-cal designation which must be clearly visible from thefire apparatus access road. The building identificationnumbers shall be a minimum of 18 inches high with aminimum 3-inch brush stroke on contrasting color. Forbuildings less than 100 feet long, a minimum of onebuilding identification number per building shall be pro-vided. The building identification number is required tobe internally or externally illuminated.

505.2.2.3 Spread numbers. Spread numbers shall beprovided adjacent to the building identification numbersto indicate the apartment or unit numbers by floors in thebuilding. Spread numbers shall be a minimum of 7inches high with a 1-inch brush stroke on a contrastingbackground. The spread numbers are required to be in-ternally or externally illuminated.

505.2.2.4 Unit identification at entrances. When morethan one dwelling or unit is accessed from an entrance, aspread plate is required. See Figure 5-14 for spread platesign specifications.

505.2.2.5 Apartment or unit numbers. Individualapartment or unit numbers shall be a minimum 4-inchhigh with a minimum 3/8 inch brush stroke on a contrast-ing background.

505.2.2.6 Additional unit identification signs. Where abuilding is not visible from the fire apparatus accessroad, a directional sign indicating the location of the unitis required. See Figure 5-15 for sign specifications.

505.3 Premises identification for commercial buildings.Commercial building address numbers shall be a minimum of12 inches high with a minimum 2-inch brush stroke on con-

trasting background. The address shall be visible from all ac-cess directions. When buildings are more than 200 feet long orset back from the road more than 100 feet they shall be identi-fied with building address numbers that are a minimum of 24inches high with a 4-inch brush stroke of a contrasting color.

When buildings are greater than 500 feet in length, the num-ber and address shall be provided in a minimum of two loca-tions. When buildings have multiple access points, numbersand addresses shall be provided at each access point.

505.3.1 Multitenant commercial buildings. Individualtenant spaces in multitenant commercial buildings shallhave their address or suite number posted at the front en-trance and rear access doors. This number shall be a mini-mum of 6 inches high with a 1-inch brush stroke on acontrasting background.

505.3.2 Multiple buildings at a single address. Eachbuilding shall display its specific alphabetical or numericaldesignation that shall be clearly distinguishable from thefire apparatus access road. See Section 505.2.1 for mini-mum letter height and brush stroke requirements.

505.4 Address directories.

505.4.1 When required. An approved address directoryshall be provided at properties containing one of the follow-ing:

1. More than one principal building,

2. Buildings with unit identification numbers that arerandomly numbered or sequenced.

3. When, in the opinion of the fire code official, emer-gency response may be delayed due to the physicallayout of the complex.

505.4.2 Specifications. Address directories shall be con-structed and installed in accordance with this section.

505.4.3 Dimensions. The number of buildings in the com-plex shall determine the minimum dimensions of the direc-tory. Minimum directory dimensions shall be as follows:

1. Complexes containing 12 or fewer buildings require aminimum 3 feet by 3 feet (9 square feet) site directory.

2. Complexes containing 13 to 30 buildings require aminimum 4 feet by 4 feet (16 square feet) site direc-tory.

3. Complexes containing 31 or more buildings require aminimum 5 feet by 5 feet (25 square feet) site direc-tory. Stanchions or supports shall not be included inthe required size of the directory.

505.4.4 Framing. Framing materials shall not encroachupon the directory face by more than 1-1/2 inches.

505.4.5 Protection. The directory shall be protected againstvandalism and disfigurement by a clear polycarbonatecover, having a minimum thickness of 1/8 inch, sealed to pro-tect the directory from weather.

505.4.6 Illumination. Address directories shall be inter-nally illuminated utilizing white light.

505.4.7 Installation requirements. Support posts or stan-chions shall be set in concrete. Directories with dimensionsof 3 feet by 3 feet (9 square feet) shall be mounted with the

FIRE SERVICE FEATURES

2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 55

Page 6: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

bottom of the directory not less than 36 inches above grade.Directories with dimensions of 4 feet by 4 feet (16 squarefeet) and 5 feet by 5 feet (25 square feet) shall be mountedwith the bottom of the directory not less than 24 inchesabove grade.

505.4.8 Depictions. All depictions must be clear, easily un-derstood, and legible at a distance of 8 feet. The directoryshall depict structures, building numbers, units, apartmentor space numbers, tennis courts, swimming pools, elevators,driveways, streets, laundry rooms, fire hydrants, fire appa-ratus access roads and other features as determined by thefire department. The depictions shall comply with the fol-lowing:

1. Directories shall be a dark print on a contrasting lightbackground. Buildings shown on the directory shallnot be the same color as other features indicated onthe directory.

2. The name and address of the complex are requiredand shall not exceed 10 percent of the total size of thesite directory.

3. Swimming pools, canals, and waterway areas shall betranslucent blue.

4. Tennis courts shall be translucent green.

5. Fire hydrants shall be a 1/4 inch diameter black circlefilled in with a translucent yellow center. The abbrevi-ation ‘HYD” must be affixed by the location of the hy-drant on the directory.

6. The directory shall be properly oriented to the viewerwith a red dot, 1-inch in diameter, with the words“YOU ARE HERE” affixed at the appropriate loca-tion on the directory.

7. A north arrow shall be included in the upper rightquadrant of the directory. The arrow shall be a mini-mum of 3 inches in length and a minimum of 1-inchbrush stroke.

8. Interior fire apparatus access roads, where provided,shall be marked on the directory with red crosshatch-ing.

505.4.9 Setbacks. The directory shall be installed on the oc-cupancy’s property, at locations approved by the fire depart-ment. Placement of the address directory shall be as follows:

1. The directory shall be set back from the street or curb-ing at least 25 feet to allow emergency vehicles toclear the public right-of-way.

2. Shall not exceed a distance of 4 feet from the edge ofthe fire apparatus access road facing the direction ofoncoming traffic.

3. Shall not conflict with traffic visibility zones as pro-vided for by other ordinances.

4. Shall be immediately visible and free from obstruc-tions including architectural design and landscaping.

505.4.10 Prohibitions. Information such as advertising oradditional art work shall not be allowed on the address di-rectory.

505.4.11 Maintenance. All premises identification shall bemaintained clearly visible and free from obstructions, in-cluding landscaping.

505.5 Private street or road signs. Private streets and roadsshall be identified with approved signs. Signs shall be of an ap-proved size, weather resistant and be maintained until replacedby permanent signs.

SECTION 506KEY BOXES

506.1 Where required. Where access to or within a structureor an area is restricted because of secured openings or whereimmediate access is necessary for life-saving or fire-fightingpurposes, the fire code official is authorized to require a keybox to be installed in an approved location. The key box shallbe of an approved type and shall contain keys to gain necessaryaccess as required by the fire code official

When a building, other than a Group R-3 occupancy is moni-tored off-site for security, fire, or other service that notifies thefire department, a key box shall be installed in an accessiblelocation.

506.1.1 Height. The key box shall be mounted between 5 1/2

and 6 feet above grade.

506.1.2 Visibility. The key box shall be illuminated so as tobe immediately visible to fire personnel from the emergencyapparatus. Posts, fences, vehicles, growth, trash, storageand other materials shall not be placed or kept near keyboxes in a manner that would prevent the key boxes from be-ing immediately discernible.

506.1.3 Marking of keys for Fire Department access.Each key shall be color-coded to identify its function as fol-lows:

1. Green for access gates.

2. Yellow for elevators.

3. Red for the Fire Command Center.

4. Blue for keys related to water access (e.g., gates toswimming pools).

5. White for master keys.

Keys that are required to access secured areas for a func-tion not listed above, shall be provided with water-resistanttags. The tags shall be marked in a contrasting color with thekey’s function and room number. The terminology used tomark the tags shall provide immediate understanding as tothe key function.

506.2 Key box maintenance. The operator of the buildingshall immediately notify the fire code official and provide thenew key when a lock is changed or rekeyed. The key to suchlock shall be secured in the key box.

SECTION 507SHAFTWAYS AND PITFALLS

507.1 Trapdoors to be closed. Trapdoors and scuttle covers,other than those that are within a dwelling unit or automaticallyoperated, shall be kept closed at all times except when in use.

56 2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS

FIRE SERVICE FEATURES

Page 7: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

507.2 Shaftway markings. Vertical shafts shall be identifiedas required by this section.

507.2.1 Exterior access to shaftways. Outside openingsaccessible to the fire department and which open directly ona hoistway or shaftway communicating between two ormore floors in a building shall be plainly marked with theword “SHAFTWAY” in red letters at least 6 inches (152mm) high on a white background. Such warning signs shallbe placed so as to be readily discernible from the outside ofthe building.

507.2.2 Interior access to shaftways. Door or windowopenings to a hoistway or shaftway from the interior of thebuilding shall be plainly marked with the word“SHAFTWAY” in red letters at least 6 inches (152 mm) highon a white background. Such warning signs shall be placedso as to be readily discernible.

507.2.3 Exterior doors without landings. Exterior doorswithout landings shall be marked with the words “DAN-GER – NO EXIT.” The sign shall be installed on the interiorof the applicable door at a height of 6 feet above grade. Thesign plate shall be a minimum thickness of .080 aluminumconstruction. The sign face shall have a red reflective back-ground using 3M Scotchlite or equivalent. The sign faceshall consist of white screen printed letters having a princi-pal stroke of not less than 0.75 inch (19.1 mm) wide and atleast 6 inches (152 mm) high.

507.3 Pitfalls. The intentional design or alteration of buildingsto disable, injure, maim or kill intruders is prohibited. No per-son shall install and use firearms, sharp or pointed objects, ra-zor wire, explosives, flammable or combustible liquidcontainers, or dispensers containing highly toxic, toxic, irritantor other hazardous materials in a manner which may passivelyor actively disable, injure, maim or kill a fire fighter who forc-ibly enters a building for the purpose of controlling or extin-guishing a fire, rescuing trapped occupants or rendering otheremergency assistance.

SECTION 508FIRE PROTECTION WATER SUPPLIES

508.1 General. Water supplies for manual fire suppression andfire hydrants shall be in accordance with Sections 501 and 508.

508.1.1 Required water supply. An approved water supplycapable of supplying the required fire flow for fire protec-tion shall be provided to premises upon which facilities,buildings or portions of buildings are hereafter constructedor moved into or within the jurisdiction.

508.1.1.1 When a water supply for fire protection is notavailable from the City of Phoenix, or if the flow rate,pressure, or duration of the water supply available fromthe city does not meet the minimum requirements of thiscode, the owner shall be responsible for installing all ofthe infrastructure required to meet the fire flow, pressure,and duration requirements of this code.

508.1.2 Design information required. Plans, hydrauliccalculations, and specifications shall be submitted to the firecode official for review and approval prior to installation ofthe on-site water supply system. Underground fire main sys-

tems shall be installed in accordance with NFPA 24, PrivateFire Service Mains and Their Appurtenances. Water tankinstallations shall be in accordance with NFPA 22, WaterTanks for Private Fire Protection.

Exception: Public water distribution mains approved bythe City of Phoenix Water Services Department.

508.1.3 Hydraulic calculations. Calculations shall be sub-mitted to verify the private fire service main(s) will providethe minimum required fire flow, as determined by Section508.2, to the hydraulically most demanding on-site hy-drants with the water supply that is available to the system.

508.1.3.1 System flow requirement. The minimum re-quired fire flow rate shall be calculated using 1000 gpmincrements starting at the hydraulically most demandinghydrant. An additional 1000 gpm, or remainder of the re-quired fire flow, as determined by Section 508.2 shall beadded at each successive hydrant until the minimum re-quired fire flow has been accounted for.

508.1.3.2 System pressure requirement. A minimum20 psi residual pressure shall be maintained in thesystem.

All pressure losses in the system including frictionloss through pipe and fittings and changes in elevationshall be accounted for from the hydraulically most de-manding hydrant back to the location of the water flowtest that was used to determine the water supply availableto supply the new private hydrants and mains.

508.1.3.3 Method for determining friction loss. Fric-tion loss through pipe and fittings shall be determined us-ing the Hazen-Williams formula or other approvedhydraulic formula. The Hazen-Williams formula is asfollows:

P = 4.52 x Q1.85

C1.85 x D4.87

Where:

P = friction loss in psig per foot of pipe

Q = flow in gpm

C = Hazen-Williams co-effiecient of roughness,friction loss coefficient, pipe roughness coefficient,

D = actual internal diameter of the pipe in inches

508.1.3.4 Backflow prevention assembly. The pres-sure loss through any backflow prevention assem-bly installed on the system shall be included in thehydraulic calculations. The model and size of thebackflow prevention assembly shall be noted on theplans.

508.1.3.5 Water supply data. Water supply test infor-mation for public mains shall be obtained from the Cityof Phoenix Water Services Department within 90 days ofplan submittal. The Water Services Department hydrantflow test report form shall be submitted with the plans.

Water supply tests conducted on private fire servicemains shall be witnessed by the fire code official.

FIRE SERVICE FEATURES

2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 57

Page 8: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

508.1.3.5.1 Water flow test location. The location ofhydrants used to determine the available water supplyshall be shown on the plans. The plans shall providedetail on how the private fire service main is con-nected to the city main. The size and location of thecity main in the street and whether the main is dead-end or circulating shall be shown on the plans. If themain is a dead-end, the direction and distance to thenearest circulating main shall be noted on the plans.

The elevation of the static and residual pressure testgauge with relation to the on-site hydrants shall benoted on the plans.

508.1.3.5.2 Design safety factor. The water flow testresults shall be adjusted as noted in Sections508.1.3.5.3 and 508.1.3.5.4 to account for seasonaland daily fluctuations in the water supply system.

508.1.3.5.3 Static pressure over 90 psi. When thestatic pressure is over 90 pounds per square inch (psi)the maximum design static pressure will be 80 psi re-gardless of the actual test pressure. The slope of theoriginal design curve shall be used even though thedesign pressure is reduced to 80 psi.

508.1.3.5.4 Static pressure less than or equal to 90psi. When the recorded static pressure is less than orequal to 90 psi, the system design shall include a mini-mum 10 psi safety factor between the system flow andpressure demand and the available water supply.

508.2 Required water supply for fire protection. The mini-mum required fire flow for private fire service mains shall bedetermined as required in Appendix B.

508.2.1 Reduction in the required fire flow. A 50 percentreduction of the minimum required fire flow amount deter-mined by using Appendix B is allowed when the building isprotected throughout by an automatic fire sprinkler systemdesigned for the hazard and installed in accordance withNFPA 13, Standard for the Installation of Sprinkler Sys-tems. See B105.1

The flow required to supply the sprinkler system is not re-quired to be added to the fire flow.

508.2.2 Fire flow in public mains. The fire flow in publicwater mains shall be in accordance with the design stan-dards found in the City of Phoenix Water Services Depart-ment Design Standards Manual for Water Systems.

508.2.3 Storage of combustible materials or hazardousmaterials.

Additional fire flow as determined by engineering analy-sis shall be required to protect exterior storage of combusti-ble or hazardous materials when the fire flow required toprotect the exterior storage exceeds the fire flow required toprotect the building as determined by Appendix B.

508.2.4 Temporary water supply. A temporary water sup-ply for use during construction is allowed only by Appeal tothe Fire Marshal. When constructing one- and two-familyhouses, the installation of a temporary water supply shallonly be allowed for construction of the model homes. Con-struction shall occur, only on every other lot, or with a mini-

mum 30 foot spacing between structures. The followingdocumentation is required to be submitted with the appeal:

1. A report, stamped by a professional engineer, shall beprovided. This report shall include plans of the systemand hydraulic calculations. A minimum 1,500 gpm at25 psi for a minimum 2 hour duration shall be re-quired for systems in single-family home develop-ments. A minimum 2,500 gpm at 25 psi for aminimum 2 hour duration shall be required at all othertypes of occupancies. Spacing of hydrants shall be inaccordance with Section 508.4.4.

2. A permit shall be obtained from the Fire Departmentbefore installation of the temporary water supply iscommenced.

3. An inspection and test of the system shall be requiredprior to combustibles being brought on site.

508.3 Type of water supply. A water supply shall consist ofreservoirs, pressure tanks, elevated tanks, water mains or otherfixed systems capable of providing the required fire flow. Com-ponents of such installations are required to be listed or ap-proved for the intended use and installed in accordance with theappropriate nationally recognized standard.

508.3.1 Fire mains. Fire mains and appurtenances shall besized to accommodate the calculated fire flow but shall notbe less than 6 inches in diameter. Dead-end fire mains shallnot be less than 8 inches in diameter, unless calculation de-termine otherwise.

508.3.2 Water tanks. Water tanks for private fire protectionshall be installed in accordance with NFPA 22.

508.4 Fire hydrant systems. Fire hydrant systems shall com-ply with Sections 508.4. and 508.5.

508.4.1 General. Fire hydrant systems and fire hydrantsshall be in accordance with Section 508.4. The installationof fire mains and fire hydrants in the public right-of-wayshall also meet the Phoenix Water and Wastewater Depart-ment specifications.

508.4.2 Inspection, testing and maintenance. Fire hy-drant systems shall be subject to periodic tests as required byNFPA 25. Fire hydrant systems shall be maintained in an op-erative condition at all times and shall be repaired where de-fective. Additions, repairs, alterations and servicing shallcomply with approved standards. See Section 901.6.

508.4.3 Private fire service mains and water tanks. Pri-vate fire service mains and water tanks shall be periodicallyinspected, tested and maintained in accordance with NFPA25 at the following intervals:

1. Private fire hydrants (all types): Inspection annuallyand after each operation; flow test and maintenanceannually.

2. Fire service main piping: Inspection of exposed mainsand tanks, annually; flow test every 5 years.

3. Fire service main piping strainers: Inspection andmaintenance after each use.

508.4.4 Hydrant locations. Fire hydrants shall be placed inlocations approved by the Fire Department and as describedin Section 508.4.

58 2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS

FIRE SERVICE FEATURES

Page 9: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

508.4.4.1 Distance to building or facility. The distancefrom a hydrant to the most remote exterior point of thebuilding or facility shall not exceed that specified in thissection. The required distance shall first be measuredalong the path of the fire apparatus access road and thenalong the path that fire fighters would manually lay hose.Hydrants located across the road from the building or fa-cility may not be considered to comply with this require-ment if there is a median in the road.

508.4.4.2 Location at all buildings or facilities. At leastone fire hydrant shall be located within 350 feet of themost remote exterior point of the building or facility. Inall occupancies except sprinklered R-3’s a second firehydrant shall be located within 650 feet of the most re-mote exterior point of the building.

508.4.4.3 Group R-3 occupancies. For Group R-3buildings protected by a sprinkler system installed in ac-cordance with NFPA 13D, at least one fire hydrant shallbe located within 500 feet of the most remote exteriorpoint of the building.

508.4.4.4 Fire Hydrants shall be located on the right hand(passenger) side of the streets, intersection, drivewaysand fire lanes.

508.4.4.5 Existing public fire hydrants on major streets,collector streets, or any other street having four (4) ormore lanes of traffic, that are not divided by raised me-dian islands or light-rail tracks can be included in thecoverage analysis. If those streets classes are divided byraised median islands or light-rail tracks then the existinghydrant can only be included in the coverage analysis ifits location is on the same side of the meridian as the newdevelopment.

508.4.4.6 The first new fire hydrant shall be located at thestreet intersection or at the main entrance(s) into a subdi-vision, apartment complex, or commercial development.Additional hydrants shall be spaces per Section508.5.4.2

508.4.4.7 Parking areas. In open-air, on-grade parkingareas, at least one fire hydrant shall be located within 600feet of all areas.

508.4.4.8 Distance to fire department connection(FDC). At least one fire hydrant shall be located within200 feet of a fire department connection supplying build-ing fire protection systems. The distance between the hy-drant and FDC shall be measured along the path of thefire apparatus access road and as fire fighters would layhose. See also Section 912.

508.4.4.9 Hydrant spacing. Fire hydrants shall bespaced approximately 500 feet apart in single-family res-idential developments and shall be approximately 300feet apart in all other development types. The distancebetween hydrants shall be measured along the path of thefire apparatus access road.

508.5 Hydrant specifications.

508.5.1 City of Phoenix threads. Fire hydrants shall com-ply with City of Phoenix specifications and be providedwith Phoenix threads.

508.5.2 Height. Fire hydrants shall be installed so that thecenterline of the lowest outlet is not less than 18 inchesabove grade and the highest outlet does not exceed 30 inchesabove grade.

508.5.3 Color of hydrants. The color of hydrants shall befire hydrant yellow. Private fire hydrants shall have the bon-net painted reflective white. Hydrants not intended for firedepartment use shall have the bonnet painted black.

508.5.4 Tampering and obstructions. Vehicle parkingshall be prohibited within 15 feet in front of and in both di-rections parallel to the curb line in front of the fire hydrant.For hydrants that are set back from the curb, the 15 footclearance shall be measured from the curb line. Vehiclesparked in violation shall be issued a “Notice of Parking Vio-lation.” See Figure 5-11.

Posts, fences, vehicles, growth, trash, storage and othermaterials or objects shall not be placed or kept near fire hy-drants, fire department inlet connections or fire protectionsystem control valves in a manner that would prevent suchequipment or fire hydrants from being immediately discern-ible. The fire department shall not be deterred or hinderedfrom gaining immediate access to fire protection equipmentor fire hydrants.

508.5.5 Clear space around hydrants. A 3-foot (914 mm)clear space, measured from the center stem, shall be main-tained around the circumference of fire hydrants.

508.5.6 Physical protection. Where fire hydrants are sub-ject to impact by a motor vehicle, physical protection in-cluding, but not limited to guard posts or other approvedmeans shall comply with Section 312.

SECTION 509FIRE COMMAND CENTER

509.1 Features. Where required by other sections of this codeand in all buildings classified as high-rise buildings by the Inter-national Building Code, a fire command center for fire depart-ment operations shall be provided. The location andaccessibility of the fire command center shall be approved by thefire department. The fire command center shall be separatedfrom the remainder of the building by not less than a 1-hour fire-resistance-rated fire barrier. The room shall be a minimum of 96square feet (9 m2) with a minimum dimension of 8 feet (2438mm). A layout of the fire command center and all features re-quired by this section to be contained therein shall be submittedfor approval prior to installation. The fire command center shallcomply with NFPA 72 and shall contain the following features:

1. The emergency voice/alarm communication systemunit.

2. The fire department communications system.

3. Fire-detection and alarm system annunciator system.

4. Annunciator visually indicating the location of the ele-vators and whether they are operational.

FIRE SERVICE FEATURES

2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 59

Page 10: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

5. Status indicators and controls for air-handling systems.

6. The fire-fighter’s control panel required by Section909.16 for smoke control systems installed in the build-ing.

7. Controls for unlocking stairway doors simultaneously.

8. Sprinkler valve and water-flow detector display panels.

9. Emergency and standby power status indicators.

10. A telephone for fire department use with controlled ac-cess to the public telephone system.

11. Fire pump status indicators.

12. Schematic building plans indicating the typical floorplan and detailing the building core, means of egress,fire protection systems, fire-fighting equipment andfire department access.

13. Work table.

14. Generator supervision devices, manual start and trans-fer features.

15. Public address system, where specifically required byother sections of this code.

16. Key cabinet for fire fighter use.509.2 Identification. The fire command center shall be identi-fied by permanent easily visible sign noting “Fire Dept. Com-mand Center” located on the door to the fire command center.See Figure 509.2 for guidance.

509.3 Key box. A key box shall be permanently installed nearthe door to the fire command center. The key box shall be lo-cated 5 1/2feet to 6 feet above the floor level in a clearly visiblelocation.

SECTION 510IDENTIFICATION OF FIRE

PROTECTION EQUIPMENT510.1 Identification. Fire protection equipment shall be iden-tified in an approved manner. Rooms containing controls forair-conditioning systems, sprinkler risers and valves, or otherfire detection, suppression or control elements shall be identi-fied for the use of the fire department. Approved signs requiredto identify fire protection equipment and equipment location,shall be constructed of durable materials, permanently in-stalled and readily visible.

510.2 Exterior stairwells. When determined by the fire codeofficial where access is necessary for life-saving or fire-fightingpurposes, exterior stairwells providing access to fire protectionequipment shall be marked in accordance with this Chapter.

SECTION 511

CONTROLLED ACCESS GATES

511.1 General. The installation of controlled access gatesacross a fire apparatus access road shall be approved by the firecode official and meet the requirements of Section 511.

511.1.1 Permits. Permits shall be required to install or mod-ify controlled access gates.

511.1.2 Gate installation companies. When gates are in-stalled at any location that obstructs a fire apparatus accessroad, the installing company shall be licensed by the Ari-zona Registrar of Contractors as L-5 or C-5.

511.1.3 Egress. Fire apparatus access gates shall be de-signed and installed such that they do not obstruct the egressor departure of emergency vehicles.

511.1.4 Maintenance. All fire apparatus access gates shallbe maintained operable at all times and shall be inspected atleast annually. Copies of the annual inspection report shallbe maintained and be accessible for fire department review.

511.1.5 Inoperable gates. Controlled access gates that areinoperable and impede the entrance of fire apparatus shallbe chained open or removed at the owner’s expense.

511.1.6 Illegal gates. Controlled access gates that cross fireapparatus access roads that have been installed without apermit shall be chained open or removed at the owner’s orinstalling contractor’s expense until a permit and final ap-proval has been obtained from the fire department.

511.2 Fire apparatus access gates.

511.2.1 General. Access openings are required to be auto-matic where no turn-around is provided for fire apparatus.See Figure 5-3 for approved turnarounds.

511.2.2 Main entrance identification. Access openingsshall have signs that identify the location of the property’sprimary entrance, and signs shall be bolted on the street sideof the fire apparatus access gate. See Figure 5-16.

511.2.3 Marking and signage. Manual and automatic ac-cess openings are required to be marked in accordance withSection 511.3.5. Signage shall be provided in accordancewith Section 511.5.2.

511.3 Controlled access gate specifications. When controlledaccess gates are installed across a fire apparatus access road thespecifications in 511.2 shall apply.

511.3.1 Opening width. When the gate is fully opened, aminimum 20-foot clear width shall be provided for both theentrance and exit gates. Gates installed and approved priorto November 8, 2003, shall be maintained in accordancewith the original approval.

The fire code official shall require additional width open-ing when a 45-foot fire apparatus turning radius cannot bemet.

60 2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS

FIRE SERVICE FEATURES

Page 11: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

511.3.2 Electrically operated gates. Electrically operatedgates shall be installed in accordance with this section.

511.3.2.1 Standby power systems. Electrically operatedgates shall be provided with a standby power system.Standby power is permitted to be, but not limited to, bat-tery back-up or connection to an emergency generator.The activation of the system shall open gates and maintainthem in the open position until primary power is restoredto the system. Standby power systems are required tocomply with the National Electrical Code Article 701.

Exception: Controlled access gates installed at occu-pancies other than multifamily residential propertiesmay remain closed until the emergency gate switch isactivated, and shall then remain open while thestandby power system is operating the gate.

511.3.3 Opening time. Electrically operated controlled ac-cess gates shall open at a minimum rate of one foot persecond.

511.3.4 Key switch. Each electrically operated controlledaccess gate shall be equipped with an approved key switchon both sides of the gate. When separate entry and exit gatesare provided, the emergency key switch shall open the en-trance and exit gates.

511.3.5 Key switch identification. An approved sign read-ing “F.D. ACCESS” shall be installed within 12 inches ofthe emergency key switch. The key switch shall be illumi-nated so as to be visible from fire apparatus. See Figure 5-17for required sign plate specifications.

511.3.6 Height. The key switch shall be mounted between 51/2 feet and 6 feet above grade.

511.3.7 Obstruction and impairment. Posts, fences, vehi-cles, growth, trash, storage and other materials shall not bekept near key switches in a manner that would prevent thekey switches from being visible.

511.3.8 Bypass of systems. When activated, the emergencykey switch shall bypass all occupant and loop switch systems.

511.4 Preemption devices. Preemption devices are requiredon all new automatic fire access gates installed after January1, 2001, at residential properties. Gates installed without per-mits or proof of installation date, require preemption devices.Voluntary installations of preemption devices shall complywith the requirements of Section 511.2.7.

511.4.1 Locations. The devices shall be installed such thatthe gate will open for both ingress and egress of emergencyvehicles.

511.4.2 Minimum installation standards. The installationof preemption devices shall comply with the following:

1. Detectors shall be mounted 8 feet to 10 feet abovegrade.

2. Detectors shall be located a minimum of 18 inches be-hind the gate on the property side.

3. Detectors shall be mounted on a separate 4 inch by 4inch metal post and not on the guidepost. The metalpost shall be cemented a minimum of 18 inches belowgrade.

4. Detectors shall activate at a minimum of 150 feetfrom the gate.

5. Detectors shall point toward both the approach andthe exit path of the emergency vehicle.

6. The sight path of the detector shall be free of visualobstructions such as signs, covered parking, canopiesand vegetation.

7. Individual detectors shall be mounted together withthe power module in the dual detector-mounting box.Detectors shall be approved by the fire department. Alist of approved devices will be maintained by the firedepartment and available to the public.

511.5 Manual controlled access gates. Manual controlled ac-cess gates that cross fire apparatus access roads or other roadsthat, when determined by the fire code official, provide accessto areas where immediate access is necessary for life-saving orfire-fighting purposes shall comply with Section 511.3

511.5.1 Locking mechanism. All manual controlled accessgates that cross a fire apparatus access road shall use an ap-proved dual padlock mechanism. See Figures 5-18.1 and 5-18.2 for required locking mechanism specifications.

Gates installed and approved prior to November 8, 2003,shall be maintained in accordance with the original approval.

511.5.2 Signs. Approved signs shall be provided on themanual gates. The signs shall have a reflective backgroundand shall be bolted back-to-back onto each side of the gate.See Figures 5-4, 5-16, 5-17, 5-18.1 and 5-18.2.

511.5.3 Marking. Minimum 6-inch wide red, crosshatchedstriping shall be painted on the ground surface on both sidesof the manual access gate, including recessed areas as deter-mined by the fire department. A minimum of two applica-tions of paint is required. See Figure 5-18.1.

SECTION 512PEDESTRIAN GATES

512.1 General. Pedestrian gates installed as part of the meansof egress shall comply with the Phoenix Building Code andChapter 10 of this code.

512.2 Fire department access. Pedestrian gates installed aspart of the required fire department access shall comply withSection 511.

512.3 Swimming pools. All pedestrian gates in multi-familyand commercial occupancies that provide access to swimmingpools and are locked shall be provided with an approved keybox in accordance with Section 506. If a card reader system isinstalled a Fire Department Knox key switch must be installed.

FIRE SERVICE FEATURES

2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 61

Page 12: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

62 2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS

FIRE SERVICE FEATURES

FIGURE 5-2CENTERLINE TURNING RADIUS

Page 13: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

FIRE SERVICE FEATURES

2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 63

FIGURE 5-3

Page 14: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

64 2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS

FIRE SERVICE FEATURES

FIGURE 5-4APPROVED PHOENIX FIRE DEPARTMENT

FIRE ACCESS ROAD SIGNS(FIRE LANE SIGNS)

Page 15: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

FIRE SERVICE FEATURES

2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 65

FIGURE 5-5APPROVED FIRE LANE POSTS

Page 16: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

66 2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS

FIRE SERVICE FEATURES

FIGURE 5-6FIRE LANE STRIPING, STENCILING AND SIGN INSTALLATION

Page 17: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

FIRE SERVICE FEATURES

2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 67

FIGURE 5-7INTERIOR FIRE LANE DETAIL

Page 18: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

68 2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS

FIRE SERVICE FEATURES

FIGURE 5-8

Page 19: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

FIRE SERVICE FEATURES

2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 69

FIGURE 509.2

Page 20: 05 Phoenix Fire 2006 - iccsafe.org€¦ · FIRE COMMAND CENTER. The principal attended or un-attended location where the status of the detection, alarm com-munications and control

70 2003 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS