04763331

Embed Size (px)

Citation preview

  • 8/13/2019 04763331

    1/8

    Evaluation of Fault Protection Methods

    using ATP and MathCAD

    Louis V. Dusang, Jr., Brian K. Johnson, Senior Member, IEEE

    AbstractThis paper discusses combining the Alternative

    Transients Program (ATP) and MathCAD to teach protective

    relaying and to develop relay algorithms. A power system model

    is created in ATP with appropriate current and voltage

    measurements. The simulation output is converted to a

    COMTRADE format and imported into a detailed relay model

    implemented in MathCAD. The MathCAD model performs

    digital filtering calculations, symmetrical components

    calculations and models relay algorithms based on relay

    manufacturers published information. Focus here is on

    differential and ground fault protection for the common two bus,

    parallel line case. Emphasis is placed on fault detection and

    localization methods for ungrounded or high impedance

    grounded systems.

    Index TermsDigital simulation, power systems protection,

    ungrounded power systems

    I.INTRODUCTION

    With fast responding modern protective relaying schemes it

    is increasingly important to test them using transient

    waveforms rather than using steady-state solutions from fault

    programs [1]-[6]. One option is to use COMTRADE files

    captured from field data, but this is limited only to events that

    have actually occurred. Another option is to use transient

    simulation to generate a more comprehensive set of test cases

    and then play these waveforms to relays as COMTRADE files[1], [7].

    The same approach should also be used when training

    engineers and engineering students to set and test protective

    relays. Understanding the operation and performance of

    microprocessor based relays requires new engineering tools.

    The challenge educators face when preparing the next

    generation of protection engineers and relay designers is to

    teach both the analysis tools and the fundamental concepts of

    very complex relay systems and devices [8], [9]. This can

    also be used in developing new protection algorithms. One

    does not necessarily need to use commercial relays in an

    educational environment, and the development of new

    algorithms precludes use of commercial relays. One option is

    to implement a model of the relay algorithm directly in the

    transient simulation tool [2]-[10]. This has the advantage of

    allowing

    _____________________________

    Louis Dusang is with Northrop Grumman Shipbuilding, Pascagoula, MS

    39567 USA (phone: 228-935-2451; email: [email protected])

    B. K. Johnson is with the Dept. of Electrical and Computer Engineering atthe University of Idaho, Moscow, ID 83844 USA (phone: 208-885-6902;

    email: [email protected]).

    closed loop testing. However, developing a complete model,

    including anti-aliasing filters, cosine filters, and symmetrical

    components calculations can be challenging. Some transient

    simulation tools have built-in relay models that can help for

    this purpose, but are not comprehensive.

    In cases where closed loop testing of relays is not required

    another option to implement a relay model in a general

    purpose mathematical tool such as MATLAB or MathCAD

    [11], [12]. These programs are more suited to implementing

    complex digital filtering algorithms and relay algorithms.

    However, they have limited ability to close the loop and open

    simulated breakers in the transient simulation. Theseprograms are able to import data produced by other programs.

    This paper will utilize relay models implemented in

    MathCAD that import COMTRADE files generated from the

    output of an ATP [13] simulation using ATP Analyzer. The

    relay models implemented are based on protective algorithm

    information published by relay manufacturers. The

    approaches used in this paper have been used in several

    university level courses to allow distance education students

    to perform protective relaying labs that on campus students

    are able to conduct using hardware.

    COMTRADE (Common Format for Transient Data) is an

    IEEE standard (C37.111) developed for the power industry to

    allow easier exchange of event data between devices fromdifferent manufacturers both for post event analysis and for

    equipment testing.

    The ATP plotting function processes PL4 output files.

    Each COMTRADE file consists of three text files

    (assuming that you created the COMTRADE files in one of

    the standard text formats):

    1. DAT - contains the numerical data

    2. CFG - configuration information cross-referencing

    variables stored in DAT file

    3. HDR - information about how the file was

    created.

    We are interested in reading both the *.CFG and *.DAT

    files into MathCAD. The *.CFG file will be read into a

    MathCAD array called config and the *.DAT file into an

    array called data.

    ATP Analyzer was developed by BPA to make it easier for

    protection engineers to use ATP simulations (the development

    of ATPDraw was also supported by BPA for the same reason).

    When creating the file for use in MathCAD, the analog and

    digital signals need to be in the order you establish in your

    MathCAD file as you read the data into the file. Progressing

    through the conversion process there is text box showing the

    present sampling rate (in this case the ATP simulation time

    2008 IEEE Electrical Power & Energy Conference

    978-1-4244-2895-3/08/$25.00 2008 IEEE

  • 8/13/2019 04763331

    2/8

    step), replace this with 960 (this is 16 samples per 60 Hz

    cycle). This is a fairly common sampling rate for commercial

    protective relays and the MathCAD file is set up for this.

    Selecting Low Pass Filter removes the need to add the filter in

    MathCAD.

    The data in a COMTRADE file has both scaling and offset

    factors defined for them. This scales the measured data before

    its operation in the relay model. The MathCAD file can pull

    these numbers from the COMTRADE configuration file. Bynot changing the scaling and offset factors, the generated

    waveforms incur errors.

    II.GROUNDING METHODS TO LIMIT GROUND FAULT

    CURRENTS

    The main goals of system grounding are to give assistance

    in rapid detection and elimination of ground faults, minimize

    voltage and thermal stresses on equipment, provide personnel

    safety and reduce communication system interference [14]. In

    some cases, an exception is made for systems supplying

    critical processes or impacting personnel safety if the power

    system shuts down. In these cases an ungrounded or high

    resistance grounding scheme can be used. A phase-to-ground

    fault does not result in large fault currents and, if loads are

    connected phase-to-phase, can be tolerated until a clean

    shutdown or reconfiguration can be performed.

    Ground fault current magnitudes depend on the system

    grounding methods. Because a single phase to ground fault in

    ungrounded, high-impedance grounded and compensated

    systems does not affect the phase to phase voltages, it is

    possible to continue operating systems grounded in this

    fashion with a single line to ground fault present. However

    the system must have a phase-to-phase insulation level and all

    loads must be connected phase-to-phase.

    A. Ungrounded or Isolated Neutral System

    In an ungrounded system the neutral has no intentional

    connection to ground. However, because of the parasitic

    distributed phase-to-ground capacitance, the neutral of an

    ungrounded system may be considered to be grounded

    through a capacitor connected between neutral and ground as

    depicted in Fig. 1. The value of this capacitor will be equal to

    sum of the phase-to-ground capacitances.

    Fig. 1. Simplified Representation of an Ungrounded System

    In this system, the two major factors limiting ground fault

    current magnitude are the zero sequence line-to-ground

    capacitance and fault resistance. A line-to-ground fault shifts

    the system neutral voltage, but leaves the phase-to-phase

    voltages intact as shown in Fig. 2.

    Fig 2. Voltage phasor diagram for an ungrounded system

    (a) Unfaulted system, (b) Solid phase A to ground fault

    For a solid phase A to ground fault in an ideal lossless

    system, the faulted phase and ground potentials are equal, as

    shown in Fig 2. The phase-to-ground voltage of the two

    remaining unfaulted phases equals the phase-to-phase voltage

    (VBG = VBA, VCG = VCA) and the neutral-to-ground voltage

    equals the negative of the source phase to neutral voltage

    corresponding to the faulted phase (VNG= VAN). The phase-

    to-phase voltages are not impacted, only the line-to-ground

    and neutral-to-ground voltages. Thus continuity of service

    can be achieved in the presence of a single line-to-ground fault

    on this system if loads are connected phase-to-phase.

    One important characteristic to be considered for an

    ungrounded system is that this type of system is subject to

    excessive overvoltages. Ungrounded neutral ac systems are

    most commonly subject to overvoltages originating from

    resonant effect of series LC circuits by a transient change in

    voltage. Similarly, substantial overvoltages can be developed

    in ungrounded ac systems by sputtering or intermittent ground

    faults. In such faults the fault clears when the current througharc passes through a natural current zero. Since the ground

    current is capacitive, it is 90 degrees out of phase with the

    voltage. This results in trapped charge on the neutral to

    ground parasitic capacitance. At the next half cycle it can arc

    again, adding additional voltage to the capacitance at the next

    current zero. This will cause the neutral-to-ground, and thus

    the phase-to-ground, voltages to build up over time.

    Intermittent ground fault conditions on low voltage

    ungrounded neutral systems have quite often been observed to

    create overvoltages of five or six times normal. These

    overvoltages will deteriorate the insulation of the unfaulted

    phases and might lead to a second ground fault or a phase-to-

    phase fault. The second ground fault will involve large faultcurrents and will require instantaneous tripping of breakers.

    B. High Resistance Grounded System

    The high resistance grounded neutral system is one in

    which a large resistance has been inserted in the neutral

    connection to ground to limit the neutral current under ground

    fault conditions to a value not less than the system charging

    current. The grounding resistor may be connected in the

    neutral of a power or grounding transformer, generator or

    generator grounding bus, or across a broken delta connection

  • 8/13/2019 04763331

    3/8

    of distribution transformer secondary. Similar to the

    ungrounded system, ground faults on these systems shift the

    system neutral voltage without modifying the phase to phase

    voltages. Hence the system need not be disconnected at the

    occurrence of the first phase to ground fault.

    An advantage of the high resistance grounded system is

    that the potential line-to-ground overvoltage hazard associated

    with the ungrounded system is greatly reduced. This is

    because the distributed line-to-ground capacitance is bypassedby the neutral to ground high resistance connection so the

    neutral current is closer to being in phase with the voltage and

    providing a path to bleed off the trapped charge. The

    resistance also creates an overdamped response to transient

    variations.

    III.RELAY PROTECTION OVERVIEW

    A single digital relay may consist of many protection

    elements, see Table I.

    TABLE I

    ELEMENT LEGEND

    Elements Description

    27 Phase Undervoltage: A-, B-, or C-Phase

    59 Phase Overvoltage: A-, B-, or C-Phase

    81 Under- and Overfrequency

    25 Synchronism Check

    59N Zero-Sequence Overvoltage

    67P Directional Phase Overcurrent

    50P Nondirectional Phase Overcurrent

    32R Reverse Underpower

    32F Forward Overpower

    87 Phase Current Differential

    67N Directional Ground Overcurrent

    50N Nondirectional Ground Overcurrent

    The power element (32), undervoltage (27) and

    overvoltage (59) element, and underfrequency element (81)

    are all based on a time delay scheme with no fault location

    tripping selectivity (Table I). These elements are intended for

    generator protection. Reverse power protection uses a time

    delayed function to prevent a generator from acting as a motor

    on the system.

    The synchronism element (25) provides added protection

    by preventing the closing of any breaker and connecting twosystems that are out of phase. To allow breaker closing when

    power is only on one side of the breaker, a relay includes a

    dead-bus feature that bypasses the synchronism check

    element. Unlike with the previously described elements, a

    line-to-line voltage helps prevent a ground fault from affecting

    proper synchronism check element operation in an

    ungrounded system.

    A. Differential and Directional Protection

    The primary protection used for protection of very short

    transmission lines is line current differential (87). Line

    current differential protection is ideal because the current

    differential element zone of protection is the connection

    between the two relays associated with a line and a high speed

    communications link.

    Fig. 3 shows a typical line current differential scheme

    applied to a line.

    Relay 2

    87LA 87LB87LC

    87LG87L2

    Relay 1

    Ia, Ib, Ic87LC87LB 87LA

    87LG 87L2

    Fig. 3. Typical Line Current Differential Scheme

    Each relay exchanges time-synchronized Ia, Ib, and Ic

    current samples with the other. Current differential elements

    compare Ia, Ib, Ic, 3I2, and 3I0 (IG) currents from each line

    terminal. If a fault condition exists between the two relays,

    the line is isolated.Line current differential elements require an extensive

    communications channel between the two relays protecting

    the line since the sampled current waveforms need to be

    transferred. If the communications channel fails, the line

    current differential protection is disabled. The

    communications channel signal integrity checking is an

    automatic function within each relay.

    Directional overcurrent elements (67) determine if a fault

    exists on a line. The 67P element only detects multiphase

    faults, while the 67N element detects phase-ground faults.

    Both elements are necessary to detect all fault types because

    of the difference in pickup and sensitivity levels. The 67P

    elements operate from phase currents and the 67N elements

    operate from the current delivered by the core-flux summing

    current transformers or a CT in the neutral path. Depending

    on the power system, directional overcurrent elements are

    only enabled to trip when the current differential

    communications channel fails.

    B. Zero Sequence Detection

    The positive, negative and zero sequence networks are

    connected in series while evaluating single line-to-ground

    faults as shown to Fig. 4. The zero sequence impedance of an

    ungrounded and a high resistance grounded system has a very

    high magnitude compared to the positive and negative

    sequence impedance. Considering this high value one can

    ignore the positive and negative sequence impedance without

    significant loss of accuracy while evaluating single line-to-

    ground faults.

  • 8/13/2019 04763331

    4/8

    3ZF

    Relay R

    Z1S Z1R m Z1L (1-m) Z1L

    Relay S

    I1S I1R

    Relay R

    Z2S Z2R m Z2L (1-m) Z2L

    Relay S

    I2S I2R

    Relay R

    Z0R m Z0L (1-m) Z0L

    Relay S

    I0S I0R

    Z0S

    XC0S

    2

    XC0S

    2

    _

    +

    V2F

    Fig. 4. Connection of Sequence Networks for a Single Line-to-Ground fault

    A solid single phase A to ground fault in the forward

    direction can be represented the circuit in Fig. 1 by closing

    switch SF. The zero sequence representation for this forward

    ground fault is shown in Fig. 5a. The primary current I0 is

    flowing in at the CT polarity mark. A ground fault in the

    reverse direction can be implemented by closing switch SRof

    Fig. 1, with its zero sequence representation in Fig. 5b. The

    primary current I0is not flowing in at the CT polarity mark.

    Z0L

    XC0S XC0LV0 I0

    Relay

    (a) Forward fault direction

    (b) Reverse fault direction

    Fig. 5. Zero Sequence Representation

    IV.POWER SYSTEM OVERVIEW

    Providing a reliable system is an important objective for

    many commercial, industrial, and even residential

    environments. One way to increase reliability is utilizing anungrounded system or a high resistance grounded system.

    Since the majority of faults are single line-to-ground faults,

    especially on overhead systems. Ungrounded system can

    continue to supply the end user power under ground fault

    conditions; hence, for the purpose of this paper an ungrounded

    or high resistance ground power system is utilized.

    Fig. 6 is a common multi-source power system typically

    used to explain various components of a power system i.e.

    relay protection. With the below figure one can explain power

    system stability, distance protection, forward and reverse

    direction of current as seen by each relay, differential

    protection, etc. However, this paper will limit the protection

    discussion to current differential and directional ground fault

    protection.

    Fig. 6. Power System Configuration

    Differential protection is more or less the same regardless

    of power system design. However, ground fault protection

    including zero-sequence components depends on the

    grounding scheme used. In this case, directional schemes for

    ungrounded and high resistance grounded power systems are

    explained.

    V.ATPMODELING

    ATP is a useful tool for evaluating power systems.

    MathCAD is a helpful tool for analyzing relays. By combing

    the two software programs, relay functionality can be taught

    and better understood in universities in a practical sense.

    A power system is developed using ATP. ATP Analyzer

    produces a COMTRADE file from the ATP simulation output,

    which is input as a data file into MathCAD. Relay algorithms

    are developed in MathCAD. MathCAD takes data read from a

    COMTRADE file and postprocesses it. The COMTRADE

    configuration file format is such that the first row states how

    the file was created and the version of the standard, the second

    row gives the total number of inputs i.e. 18 - number of analog

    inputs (12) and number of digital inputs (6). Rows 3 - 21 areinput in an order of choice. Data is sampled 16 times per

    cycle or 960 hertz. Columns 0 and 1 of the COMTRADE file

    do not store data, so Column 2 is the first one of interest.

    This system is modeled as an ungrounded power system

    utilizing ideal sources and employs high resistance to ground,

    Fig. 7a. The system in Fig. 7b is similar to system in Fig. 7a.

    However, to better represent the power system being analyzed

    a transformer is added. The transformer adds source

    impedance to the system. In this case the transformer is

    modeled as a delta-delta. To improve numerical performance

    of the simulation it is necessary to add either a very small

    capacitance to ground (a few picofarads) or a very large

    resistance (tens of Mohms) to ground. These values should be

    chosen such that the current they carry does not impact the

    circuit, while at the same time providing a suitable ground

    reference.

    EMTP-like programs such as ATP use nodal admittance

    matrix methods that work best if circuits have a reference to

    ground. The floating voltage sources in Fig. 7a and Fig. 7b

    use an internal, ideal transformer to create a floating source.

    The transformer used has some potential to create numerical

    stability programs. To improve this, grounded sources are

    connected behind the transformer, which is connected

  • 8/13/2019 04763331

    5/8

  • 8/13/2019 04763331

    6/8

    grounded wye to ungrounded wye (it could also be delta

    connected on the side facing the power system of test. This

    creates an appropriate ungrounded source. The parasitic

    capacitances represented in cable models provide the ground

    path that fault current would flow through. Fig. 7c shows a

    system with a grounding transformer added to create a high

    resistance ground. This is a common way to create a high

    resistance to ground point in an ungrounded system.

    The orientation depicted in Fig. 8 reflects that shown inFig. 3. Note that I2 current flow can be in same direction as

    I1. In this case the direction change needs to be

    accommodated in the MathCAD file. This may seem

    intuitively obvious, but you remember you are creating and

    debugging two models.

    FAULT

    I1 I2

    Fig. 8. ATP Current Flow

    VI.MATHCADMODELING

    Fig. 9 depicts an oversimplified rendition of differential

    protection (analyzing each phase for a difference in current via

    OR logic) in which the line currents (87A, 87B and 87C) are

    calculated internal to the relay in a manner the manufacturer

    utilizes. For current differential protection if B-phase and C-

    phase have no differential current flow, but current flows

    through the differential relay in A-phase the differential relay

    will assert if the value exceeds the pickup setting.

    Fig. 9. Simplified Differential Fault Protection Logic

    Equation (1) represents Fig. 9 in MathCAD.

    Tr_s1v

    1 Is1_OPAv

    s1_1 Is1_RTAv

    >( ) Is1_OPAv Imin>( )if

    1 Is1_OPBv

    s1_1 Is1_RTBv

    >( ) Is1_OPBv Imin>( )if1 Is1_OPC

    v s1_1 Is1_RTC

    v>( ) Is1_OPCv Imin>( )if

    1 Tr_s1v 1

    0.01>if

    0 otherwise

    :=

    (1)

    Fig. 10 is a differential relay Operate / Restraint curve

    generated in MathCAD.

    0 2 4 60

    2

    4

    6

    6

    0

    s_ 1 I.axis( )

    60 I.axis

    (a) Percentage Characteristic (b) MathCAD version

    Fig. 10. Differential Relay Operate Curve

    Ground fault algorithms while more complicated are

    generated similar to the differential element. Ground fault

    consists of overcurrent and directional elements. Fig. 11 is a

    simple representation of ground fault sensing logic.

    Fig. 11. Simplified Ground Fault Logic

    Utilizing an SEL relay that incorporates a doubled-ended,zero-sequence impedance element that vectorially adds the

    two zero-sequence current measurements, using the

    communications link between two relays, to produce twice the

    total zero-sequence line current.

    To quantify this algorithm we construct Equation 2.

    2

    0

    *

    0000

    3

    )_13(3Re

    I

    AngZLIVZ T

    = (2)

    where:

    3V0 = Summation of phase voltages (VA+ VB+

    VC)

    3I0 = Summation of phase currents (IA+ IB+ IC)

    ZL0_Ang = Zero-sequence line-impedance angle

    Re = Real operator

    * = Complex conjugate

    Equation (3) represents Equation (2) in MathCAD. To

    avoid division by 0 add a 0.00001 constant to the

    denominator.

    Z0A_r1v

    Re VA0_r1v

    IA0_r1v

    1 ej Z1ANG

    ( )

    IA0_r1v( )

    2.00001+

    :=

    (3)

    Fig. 12 produces a forward/reverse fault impedance plane.

    If the resulting impedance calculation is below the forward

    threshold (and all of the supervisory conditionals are met), the

    fault is declared forward. Conversely, if the impedance is

    above the reverse threshold, the fault is declared reverse.

  • 8/13/2019 04763331

    7/8

    Zero-Sequence

    Impedance Plane X0

    R0

    Reverse Fault

    Forward Fault

    3V0

    3I0 (Forward Fault)

    3I0 (Reverse Fault)

    (a) Zero-Seq. Phasors (b) Impedance-Plane DirectionalElement Characteristics

    Fig. 12. Ground Directional Element Characteristics

    Similarly, Fig. 13 is a MathCAD produced forward/reverse

    fault impedance plane showing the relationship between 3V0

    and 3I0for forward and reverse faults. Positive Z0Tindicates a

    forward fault as indicated in Fig. 13a. Negative Z0Tindicates

    a reverse fault as indicated in Fig. 13b.

    0 5 10 15 20 25 303000

    2000

    1000

    0

    1000

    VA0_r1v

    IA0_r1 v

    Z0A_r1 v

    Z0A_r2 v

    v

    RS

    (a) In-line section

    0 5 10 15 20 25 30500

    0

    500

    1000

    1500

    2000

    VA0_r3v

    IA0_r3v

    Z0A_r3 v

    Z0A_r4 v

    v

    RS

    (b) Out-of-section

    Fig. 13. Ground Directional Decision

    As mentioned above relay manufacturers use their own

    algorithms for relay protection elements. As such, our relay

    model utilizes the 32 element in Equations (4)-(6), which

    represents the ground directional protection of an SEL relay,

    which utilizes the 32 element. The 50 element is essentially

    the level equation enabled. Equation (4) consists of zero-

    sequence algorithm resulting in Equation (6) equating to

    Fig. 11.

    F32G_r1v

    Z0A_r1v

    Z0Forward( ) IA0_r1v a0 IA1_r1v( ):= (4)

    Level1G_r1_puv

    1 IA0_r1v

    Level_1_50G_r1if

    1 Level1G_r1_puv 1

    0.01if

    0 otherwise

    :=

    (5)

    TR67G_r1v

    T32G_r1v

    TR50G_r1v

    := (6)

    VII.SIMULATION RESULTS

    After modeling the power system in ATP, the generated a

    COMTRADE file is incorporated into MathCAD to test the

    relay algorithm. Fig. 14 shows differential element correctly

    isolates fault by asserting both Relay 1 and Relay 2, only,

    isolating two- and three-phase fault conditions on the faulted

    line while leaving the unaffected line in tact. Additionally,

    even though a ground phase may have been involved in boththe two- and three-phase faults i.e. double line-to-ground fault

    the zero sequence algorithm remains low for all four relays

    such that its associated element, 67N, did not pick-up.

    0 10 20 300

    0.5

    1

    1.5

    2

    Tr_R1v

    Tr_R2v

    v

    RS

    0 10 20 300

    0.5

    1

    1.5

    2

    Tr_R3v

    Tr_R4v

    v

    RS

    (a) In-line section (b) Out-of section

    Differential Element

    0 10 20 300

    0.5

    1

    1.5

    2

    Ind_R1v

    Ind_R2v

    v

    RS

    0 10 20 300

    0.5

    1

    1.5

    2

    Ind_R3v

    Ind_R4v

    v

    RS

    (a) In-line section (b) Out-of sectionGround Directional Element

    Fig. 14. Differential Protection Results

    Likewise, Fig. 15 shows ground fault protection

    appropriately indicates a single line-to-ground on the faulted

    line. This is seen as a high signal on ground detection graph

    and no state change for the unaffected line or an assert signal

    by the differential protection graph.

  • 8/13/2019 04763331

    8/8

    0 10 20 300

    0.5

    1

    1.5

    2

    Tr_R1v

    Tr_R2v

    v

    RS

    0 10 20 300

    0.5

    1

    1.5

    2

    Tr_R3v

    Tr_R4v

    v

    RS

    (a) In-line section (b) Out-of sectionDifferential Element

    0 10 20 300

    0.5

    1

    1.5

    2

    Ind_R1v

    Ind_R2v

    v

    RS

    0 10 20 300

    0.5

    1

    1.5

    2

    Ind_R3v

    Ind_R4v

    v

    RS

    (a) In-line section (b) Out-of sectionGround Directional Element

    Fig. 15. Ground Directional Protection Results

    All three ATP models in Fig. 7 resulted in identical fault

    isolation responses for both differential and ground fault

    protection. The difference is a setting change in MathCAD.

    VIII.CONCLUSIONS

    Using two different software packages to develop models

    requires a thorough knowledge of relay principles. The

    current flow direction in ATP affects the MathCAD results.

    While this may be seem obvious, it is easy to include anegative sign in MathCAD for direction as well.

    A single line power system provides the concept of

    differential and ground fault protection from a practical. In

    doing so it teaches directional functionality. This becomes

    more evident with the parallel line power system in that fault

    isolation depends on relay settings. In other words, the

    assertion of both relays in the single line system, does not

    initially mean this occur for the parallel line system. Three

    relays may assert, but this only means that the settings are

    incorrect. The added benefit of the parallel is it use of explain

    blocking schemes.

    IX.REFERENCES[1] M. Kezunovic, T. Popovic, D. Sevcik and H. DoCarmo, Transient

    Testing of Protective Relays: Results Methodology and Tools,

    International Conference on Power Systems Transients (IPST 2003),

    New Orleans, Paper 5c-1, September 28November 2, 2003.

    [2] B. W. Garret, Digital Simulation of Power System Protection under

    Transient Conditions, Ph.D. thesis at the University of British

    Columbia, 1987.

    [3] R.E. Wilson and J.M. Nordstrom, EMTP Transient Modeling of a

    Distance Relay and a comparison with EMTP Laboratory Testing,

    IEEE Transactions on Power Delivery, Vol.8, No. 3, pp. 984992, July

    1993.

    [4] M.T. Glinkowski and J. Esztergalyos, Transient Modeling of

    Electromechanical Relays: Part I, Armature Type Overcurrent Relay,

    IEEE Transactions on Power Delivery, Vol. 11, No. 2, pp. 763770,

    April 1996.

    [5] M.T. Glinkowski and J. Esztergalyos, Transient Modeling of

    Electromechanical Relays: Part II, Plunger Type 50 Relays, IEEE

    Transactions on Power Delivery, Vol. 11, No. 2, pp. 771782,

    April 1996.

    [6] C. Henville, A. Hielbert, R. Folkers and R Wierckx, Dynamic

    Simulations Challenge Protection Performance, Proceedings of the

    Western Protective Relay Conference, October 2003, [Online].Available: http://www.selinc.com/techpprs/6156.pdf

    [7] P.G. McLaren, R. Kuffel, R. Wierckx, J. Giesbrecht and L Ardent, A

    Real Time Digital Simulator for Testing Relays, IEEE Transactions on

    Power Delivery, Volume 7, Number 1, pp. 207213, January 1992.

    [8] C. Kim, M. Lee, R.K. Aggarwal, Educational Use of EMTP MODELS

    for the Study of a Distance Relaying Algorithm for Protecting

    Transmission Lines, IEEE Transactions on Power Systems, Vol. 15,

    No. 1, pp. 915, February 2000.

    [9] R.W. Wall and B.K. Johnson, Using TACS Functions Within EMTP to

    Teach Protective Relaying Fundamentals, IEEE Transactions on Power

    Delivery, Vol. 12, No. 1, pp. 310, February 1997.

    [10] J.N. Peterson and R.W. Wall, Interactive Relay Controlled Power

    System Modeling, IEEE Transactions on Power Delivery, Vol. 6,

    No. 1, pp. 96102, January 1991.

    [11] MATLAB, The MathWorks, Inc., 3 Apple Hill Drive, Natick MA01760-2098 USA, http://www.mathworks.com/

    [12] MATHCAD, MathSoft Inc., 101 Main Street, Cambridge,

    Massachusetts, 02142 USA, http://www.mathsoft.com

    [13] H.W. Dommel, Digital computer solution of electromagnetic transients

    in single-and multi-phase networks, IEEE Transactions on Power

    Apparatus and Systems, Vol. PAS-88, No. 4, pp. 388399, April 1969.

    [14] J. Roberts, H.J. Altuve and D. Hou, "Review of ground fault protection

    methods for grounded, ungrounded and compensated distribution

    systems," presented at the 28th Annual Western Protective Relay Conf.,

    Spokane, Washington, October 23-25, 2001. [Online]. Available:

    http://www.selinc.com/techpprs/6123.pdf

    X.BIBLIOGRAPHY

    Louis Dusang received a Bachelor of Science in Electrical Engineeringdegree from Mississippi State University in 1988 and is pursuing his MSEE at

    the University of Idaho. He is a Registered Engineer in South Carolina. He

    has been an electrical engineer with Northrop Grumman Shipbuilding since

    November 2001. He is the lead project engineer for LDA Power Systems.

    Prior to joining NGSB, Mr. Dusang worked as both an electrical engineer and

    controls engineer for Jacobs.

    Brian K. Johnson (M92, SM2006) received the Ph.D. in Electrical

    Engineering from the University of Wisconsin-Madison in August 1992. He is

    currently an associate professor in the Department of Electrical Engineering at

    the University of Idaho. His interests include HVdc transmission, power

    system protection, and the application of power electronics to utility systems

    and realtime simulation of traffic systems.