Short-Circuit Analysis IEC Standard ©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC CORTO CIRCUITO Estándar de ANSI/IEEE & IEC. Análisis de fallas transitorias (IEC 61363). Efecto de Arco (NFPA 70E 2000) Características principales: Efecto de Arco (NFPA 70E-2000) Integrado con coordinación de dispositivos de protección. Evaluación automática de dispositivos. ©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 2 HUBUNG SINGKAT STANDARD IEC

04 iec Short-Circuit Analysis.pdf

Embed Size (px)

Citation preview

  • Short-Circuit AnalysisIEC Standard

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

    CORTO CIRCUITO

    Estndar de ANSI/IEEE & IEC. Anlisis de fallas transitorias (IEC 61363). Efecto de Arco (NFPA 70E 2000)

    Caractersticas principales:

    Efecto de Arco (NFPA 70E-2000) Integrado con coordinacin de dispositivos de proteccin. Evaluacin automtica de dispositivos.

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 2

    HUBUNG SINGKAT STANDARD IEC

  • Purpose of Short-Circuit Studies

    A Short-Circuit Study can be used to determine any or all of the following:

    Verify protective device close and latch capability

    Verify protective device interrupting capability

    Protect equipment from large mechanical forces (maximum fault kA)

    I2t protection for equipment (thermal stress)

    Selecting ratings or settings for relay coordination

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 3

    Types of Short-Circuit Faults

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 4

    HUBUNG SINGKAT STANDARD IEC

  • Types of SC FaultsThree-Phase Ungrounded FaultThree-Phase Grounded FaultPhase to Phase Ungrounded FaultPhase to Phase Grounded FaultPhase to Ground Fault

    Types of Short-Circuit Faults

    Fault CurrentIL-G can range in utility systems from a few percent to possibly 115 % ( if Xo < X1 ) of I3-phase (85% of all faults).In industrial systems the situation IL-G > I3-phase is rare. Typically IL-G .87 * I3-phase In an industrial system, the three-phase fault condition is frequently the only one considered, since this type of fault generally results in Maximum current.

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 5

    Short-Circuit Phenomenon

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 6

    )tSin(Vmv(t) +=i(t)v(t)

    HUBUNG SINGKAT STANDARD IEC

  • i(t)v(t)

    (1) ) t Sin(Vmdtdi L Riv(t) +=+=

    expression following theyields 1equation Solving

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 7

    Offset) (DC

    TransientState Steady

    t) - sin(

    ZVm ) - tsin(

    ZVmi(t)

    LR-e

    ++=

    AC Current (Symmetrical) with No AC Decay

    DC Current

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 8

    HUBUNG SINGKAT STANDARD IEC

  • AC Fault Current Including the DC Offset (No AC Decay)

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 9

    Machine Reactance ( = L I )

    AC Decay Current

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 10

    HUBUNG SINGKAT STANDARD IEC

  • Fault Current Including AC & DC Decay

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 11

    IEC Short-Circuit Calculation (IEC 909)

    Initial Symmetrical Short-Circuit Current (I"k)

    Peak Short-Circuit Current (ip)

    Symmetrical Short-Circuit Breaking Current (Ib)

    Steady-State Short-Circuit Current (Ik)

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 12

    HUBUNG SINGKAT STANDARD IEC

  • IEC Short-Circuit Calculation Method

    Ik = Equivalent V @ fault location divided by equivalent Z

    Equivalent V is based bus nominal kV and c factor

    XFMR and machine Z adjusted based on cmax, component Z & operating conditions

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 13

    Transformer Z Adjustment

    KT -- Network XFMR

    KS,KSO Unit XFMR for faults on system side

    KT,S,KT,SO Unit XFMR for faults in auxiliary system, not between Gen & XFMR

    K=1 Unit XFMR for faults between Gen & XFMR

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 14

    HUBUNG SINGKAT STANDARD IEC

  • Syn Machine Z Adjustment

    KG Synchronous machine w/o unit XFMR

    KS,KSO With unit XFMR for faults on system side

    KG,S,KG,SO With unit XFMR for faults in auxiliary system, including points between Gen & XFMR

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 15

    Types of Short-Circuits

    Near-To-Generator Short-Circuit

    This is a short-circuit condition to which at least one synchronous machine contributes aThis is a short circuit condition to which at least one synchronous machine contributes a prospective initial short-circuit current which is more than twice the generators rated current, or a short-circuit condition to which synchronous and asynchronous motors contribute more than 5% of the initial symmetrical short-circuit current ( I"k) without motors.

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 16

    HUBUNG SINGKAT STANDARD IEC

  • Near-To-Generator Short-Circuit

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 17

    Types of Short-Circuits

    Far-From-Generator Short-Circuit

    This is a short circuit condition during which the magnitude of the symmetrical ac component of This is a short-circuit condition during which the magnitude of the symmetrical ac component of available short-circuit current remains essentially constant.

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 18

    HUBUNG SINGKAT STANDARD IEC

  • Far-From-Generator Short-Circuit

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 19

    Factors Used in If Calc

    calc ip based on Ik

    calc ib for near-to-gen & not meshed network

    q calc induction machine i for near to gen & not meshed network q calc induction machine ib for near-to-gen & not meshed network

    Equation (75) of Std 60909-0, adjusting Ik for near-to-gen & meshed network

    min & max calc ik

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 20

    HUBUNG SINGKAT STANDARD IEC

  • IEC Short-Circuit Study Case

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 21

    Types of Short-Circuits

    When these options are selected

    Maximum voltage factor is used

    Minimum impedance is used (all negative tolerances are applied and minimum resistance temperature is considered)

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 22

    HUBUNG SINGKAT STANDARD IEC

  • Types of Short-Circuits

    When this option is selected

    Minimum voltage factor is used

    Maximum impedance is used (all positive tolerances are applied and maximum resistance temperature is considered)

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 23

    Voltage Factor (c)

    Ratio between equivalent voltage & nominal voltage

    Required to account for:

    Variations due to time & place

    Transformer taps

    Static loads & capacitances

    Generator & motor subtransient behavior

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 24

    HUBUNG SINGKAT STANDARD IEC

  • Calculation Method

    Breaking kA is more conservative if the option No Motor Decay is selected

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 25

    IEC SC 909 Calculation

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 26

    HUBUNG SINGKAT STANDARD IEC

  • Device Duty Comparison

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 27

    Mesh & Non-Mesh If

    ETAP automatically determines mesh & non-meshed contributions according to individual contributions

    IEC Short Circuit Mesh Determination Method 0, 1, or 2 (default), , ( )

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 28

    HUBUNG SINGKAT STANDARD IEC

  • LL--G FaultsG Faults

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 29

    Symmetrical Components

    L-G Faults

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 30

    HUBUNG SINGKAT STANDARD IEC

  • Sequence Networks

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 31

    L-G Fault Sequence Network Connections

    ZZZV3I

    I3I

    021

    efaultPrf

    af 0

    ++

    =

    =

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 32

    0=gZif

    HUBUNG SINGKAT STANDARD IEC

  • L-L Fault Sequence Network Connections

    21

    efaultPrf

    aa

    ZZV3I

    II12

    +

    =

    =

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 33

    21

    L-L-G Fault Sequence Network Connections

    ZZZZZ

    VI

    I0III

    20

    201

    efaultPrf

    aaaa 012

    ++

    =

    ==++

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 34

    0=g Zif

    HUBUNG SINGKAT STANDARD IEC

  • Transformer Zero Sequence Connections

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 35

    becan faultsG -Lcase.severemost theisfault phase-3aGenerally

    Solid Grounded Devices and L-G Faults

    orGeneratorsifcasethebemayThis

    I: then trueare conditions thisIf

    & : ifgreater

    1f3

    1021

    1.4

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 37

    Complete reports that include individual branch contributions for:

    L-G Faults

    L-L-G Faults

    L-L Faults

    Unbalanced Faults Display & Reports

    One line diagram displa ed res lts that incl de

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 38

    One-line diagram displayed results that include:

    L-G/L-L-G/L-L fault current contributions

    Sequence voltage and currents

    Phase Voltages

    HUBUNG SINGKAT STANDARD IEC

  • Total Fault Current Waveform

    Transient Fault Current Calculation (IEC 61363)

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 39

    Percent DC Current Waveform

    Transient Fault Current Calculation (IEC 61363)

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 40

    HUBUNG SINGKAT STANDARD IEC

  • AC Component of Fault Current Waveform

    Transient Fault Current Calculation (IEC 61363)

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 41

    Top Envelope of Fault Current Waveform

    Transient Fault Current Calculation (IEC 61363)

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 42

    HUBUNG SINGKAT STANDARD IEC

  • Top Envelope of Fault Current Waveform

    Transient Fault Current Calculation (IEC 61363)

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 43

    IEC Transient Fault Current Calculation

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 44

    HUBUNG SINGKAT STANDARD IEC

  • Complete reports that include individual branch contributions for:

    L-G Faults

    L-L-G Faults

    L-L Faults

    Unbalanced Faults Display & Reports

    One-line diagram displayed results that include:

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 45

    g p y

    L-G/L-L-G/L-L fault current contributions

    Sequence voltage and currents

    Phase Voltages

    1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 46

    HUBUNG SINGKAT STANDARD IEC

  • 1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Slide 47

    HUBUNG SINGKAT STANDARD IEC