Operating ambient temperature
Minimum exposure temperature: -50°F (-46°C)
without damage to the unit
Maximum exposure temperature: 825°F (440°C)
without damage to the unit
AGENCY APPROVALS
Fenwal Part Number: 17343-124
II 3 G, EEx nC IIC
HAZARDOUS LOCATIONS
APPROVALS
DESCRIPTIONThe Fire & Overheat Detector monitors for fire and
overheat conditions. It can be used in areas of veryhigh temperatures.
The detector is made from welded stainless steel
and is completely sealed. It is non-repairable and
cannot be disassembled. The detector is set to a
specified alarm temperature at the factory and cannot
be re-adjusted.
Electrical connections are made through two terminal
posts with threads inside. Stainless steel screws are
used to attach wires to the two terminals. Mounting
is with 3/4-14 NPT threads
PART NUMBERS
and TEMPERATURE SETTINGS
Temperature setpoint tolerance: ±25°F (±14°C)
ENGINEERING DATA
Contact Rating17343-124 0.5 AMP at 28 VDC
SPST contacts, close on temperature rise
Construction:Hermetically sealed switch with glass to metal seals.
Model 17343-124
Fire and Overheat Detectors
Models 17343-124, Fire & Overheat Detectors Pagewww.fenwalcontrols.com 1-800-FENWAL-1
®
03.02.GE A
17343-124
Insulation Resistance
20 Megohm @ 500 VDC,
terminals to shell
Dielectric Strength500 VAC, 1 minute,
terminals to shell
Set PointTemperature Max AmbientTemperature
140°F (60°C) 100°F (38°C)
325°F (163°C) 300°F (149°C)
600°F (316°C) 500°F (260°C)
725°F (385°C) 625°F (329°C)
425°F (218°C)
GE PN Fenwal PN Setting Color
361A2285P110 17343-124 140°F (60°C) None
361A2285P111 17343-124 325°F (163°C) Red
361A2285P112 17343-124 600°F (316°C) Orange
361A2285P113 17343-124 725°F (385°C) Gray
361A2285P114 17343-124 425°F (218°C) Green
17343-124 Locations
UL ListedUIPV.E139663
Class I, Groups B, C & D per NFPA 72E
CSA Certified
Class 4868-01
Class I, Groups B, C & D
CSA Std C22.2 No. 24-93
CE/ATEX
Directive 94/9/EC
Group II, Category 3 (Gas)
protection level "nC"
Group II, Category 3 (Gas) protection level "nC"
Atex Certificate: ITS03ATEX41211
7/16/2019 03.02.gea
http://slidepdf.com/reader/full/0302gea-5634f8a4a5dfc 2/2
!
400 MAIN STREET, ASHLAND, MA 01721
TEL: (508) 881-2000 FAX: (508) 881-6729
www.fenwalcontrols.com
© 2004 Kidde-Fenwal Inc. Printed in U.S.A.
These instructions do not purport to cover all the details or variations in the equipmentdescribed, nor do they provide for every possible contingency to be met in connection withinstallation, operation and maintenance. All specifications are subject to change without notice.Should further information be desired or should particular problems arise which are not coveredsufficiently for the purchaser’s purposes, the matter should be referred to KIDDE-FENWAL,Inc., Ashland, Massachusetts.
P/N REV 9/17/04
Page 2 Models 17343-124, Fire & Overheat Detectors www.fenwalcontrols.com 1-800-FENWAL-1
®
OUTLINE DRAWING
INSTALLATION
NOTE : Local authorities having jurisdiction should
be consulted before installation.
The 17343-124 detector must be installed in a suitable
enclosure with appropriate group and category rating
for the application.
The 17343-124 detector must be mounted into an
enclosure that complies with the appropriate require-
ments for Category 3 applications. Enclosures must
have a 3/4 NPT opening to mount the detector.
Thread the unit into the 3/4 NPT opening at least
5 full turns and torque to 20 foot pounds (27 N m).
NOTE : See CAUTION regarding NPT threads
on outline drawing below.
For ATEX applications ensure that enclosures
are grounded to an ATEX approved mounting box.
Connect system wiring to the detector's terminals
per applicable electrical codes using 8-32 UNC 2A
stainless steel slotted hex head screws with integral
washer (provided).
NOTE : See
CAUTION regarding torque limit on outline drawing below.
CAUTION :Do not apply
more than 25 inch
pounds (2.82 N m)
of torque to the
terminals
HANDLING AND STORAGETake precautions to ensure that the shell and threads
are not subject to damage.
! CAUTION :Do not use any
anti-sieze, thread
locking compound
or lubricants on
the NPT threads
!
!