486
PCS-902 Line Distance Relay Instruction Manual NR Electric Co., Ltd.

03- PCS902 Line Distance Relay

  • Upload
    toing

  • View
    264

  • Download
    94

Embed Size (px)

DESCRIPTION

PCS902 Line Distance Relay

Citation preview

  • PCS-902

    Line Distance Relay

    Instruction Manual

    NR Electric Co., Ltd.

  • Preface

    PCS-902 Line Distance Relay i

    Date: 2013-12-18

    Preface

    Introduction

    This guide and the relevant operating or service manual documentation for the equipment provide

    full information on safe handling, commissioning and testing of this equipment.

    Documentation for equipment ordered from NR is dispatched separately from manufactured goods

    and may not be received at the same time. Therefore, this guide is provided to ensure that printed

    information normally present on equipment is fully understood by the recipient.

    Before carrying out any work on the equipment, the user should be familiar with the contents of

    this manual, and read relevant chapter carefully.

    This chapter describes the safety precautions recommended when using the equipment. Before

    installing and using the equipment, this chapter must be thoroughly read and understood.

    Health and Safety

    The information in this chapter of the equipment documentation is intended to ensure that

    equipment is properly installed and handled in order to maintain it in a safe condition.

    When electrical equipment is in operation, dangerous voltages will be present in certain parts of

    the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger

    personnel and equipment and cause personal injury or physical damage.

    Before working in the terminal strip area, the equipment must be isolated.

    Proper and safe operation of the equipment depends on appropriate shipping and handling,

    proper storage, installation and commissioning, and on careful operation, maintenance and

    servicing. For this reason, only qualified personnel may work on or operate the equipment.

    Qualified personnel are individuals who:

    Are familiar with the installation, commissioning, and operation of the equipment and of the

    system to which it is being connected;

    Are able to safely perform switching operations in accordance with accepted safety

    engineering practices and are authorized to energize and de-energize equipment and to

    isolate, ground, and label it;

    Are trained in the care and use of safety apparatus in accordance with safety engineering

    practices;

    Are trained in emergency procedures (first aid).

    Instructions and Warnings

    The following indicators and standard definitions are used:

  • Preface

    PCS-902 Line Distance Relay ii

    Date: 2013-12-18

    DANGER!

    It means that death, severe personal injury, or considerable equipment damage will occur if safety

    precautions are disregarded.

    WARNING!

    It means that death, severe personal, or considerable equipment damage could occur if safety

    precautions are disregarded.

    CAUTION!

    It means that light personal injury or equipment damage may occur if safety precautions are

    disregarded. This particularly applies to damage to the device and to resulting damage of the

    protected equipment.

    WARNING!

    The firmware may be upgraded to add new features or enhance/modify existing features, please

    make sure that the version of this manual is compatible with the product in your hand.

    WARNING!

    During operation of electrical equipment, certain parts of these devices are under high voltage.

    Severe personal injury or significant equipment damage could result from improper behavior.

    Only qualified personnel should work on this equipment or in the vicinity of this equipment. These

    personnel must be familiar with all warnings and service procedures described in this manual, as

    well as safety regulations.

    In particular, the general facility and safety regulations for work with high-voltage equipment must

    be observed. Noncompliance may result in death, injury, or significant equipment damage.

    DANGER!

    Never allow the current transformer (CT) secondary circuit connected to this equipment to be

    opened while the primary system is live. Opening the CT circuit will produce a dangerously high

    voltage.

    WARNING!

    Exposed terminals

    Do not touch the exposed terminals of this equipment while the power is on, as the high voltage

    generated is dangerous

  • Preface

    PCS-902 Line Distance Relay iii

    Date: 2013-12-18

    Residual voltage

    Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It

    takes a few seconds for the voltage to discharge.

    CAUTION!

    Earth

    The earthing terminal of the equipment must be securely earthed

    Operating environment

    The equipment must only be used within the range of ambient environment detailed in the

    specification and in an environment free of abnormal vibration.

    Ratings

    Before applying AC voltage and current or the DC power supply to the equipment, check that they

    conform to the equipment ratings.

    Printed circuit board

    Do not attach and remove printed circuit boards when DC power to the equipment is on, as this

    may cause the equipment to malfunction.

    External circuit

    When connecting the output contacts of the equipment to an external circuit, carefully check the

    supply voltage used in order to prevent the connected circuit from overheating.

    Connection cable

    Carefully handle the connection cable without applying excessive force.

    Copyright 2013 NR. All rights reserved.

    We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination

    to third parties is strictly forbidden except where expressly authorized.

    The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If

    nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.

    We reserve the rights to make technical improvements without notice.

    NR ELECTRIC CO., LTD.

    69 Suyuan Avenue. Jiangning, Nanjing 211102, China

    Tel: +86-25-87178185, Fax: +86-25-87178208

    Website: www.nrelect.com, www.nari-relays.com

    Version: R1.07

    http://www.nrelect.com/http://www.nari-relays.com/
  • Preface

    PCS-902 Line Distance Relay iv

    Date: 2013-12-18

    Documentation Structure

    The manual provides a functional and technical description of this relay and a comprehensive set

    of instructions for the relays use and application.

    All contents provided by this manual are summarized as below:

    1 Introduction

    Briefly introduce the application, functions and features about this relay.

    2 Technical Data

    Introduce the technical data about this relay, such as electrical specifications, mechanical

    specifications, ambient temperature and humidity range, communication port parameters, type

    tests, setting ranges and accuracy limits and the certifications that our products have passed.

    3 Operation Theory

    Introduce a comprehensive and detailed functional description of all protective elements.

    4 Supervision

    Introduce the automatic self-supervision function of this relay.

    5 Management

    Introduce the management function (measurement, recording and remote control) of this relay.

    6 Hardware

    Introduce the main function carried out by each plug-in module of this relay and providing the

    definition of pins of each plug-in module.

    7 Settings

    List settings including system settings, communication settings, label settings, logic links and etc.,

    and some notes about the setting application.

    8 Human Machine Interface

    Introduce the hardware of the human machine interface (HMI) module and a detailed guide for the

    user how to use this relay through HMI. It also lists all the information which can be view through

    HMI, such as settings, measurements, all kinds of reports etc.

    9 Configurable Function

    Introduce configurable function of the device and all configurable signals are listed.

    10 Communication

    Introduce the communication port and protocol which this relay can support, IEC60970-5-103,

    IEC61850 and DNP3.0 protocols are introduced in details.

    11 Installation

  • Preface

    PCS-902 Line Distance Relay v

    Date: 2013-12-18

    Introduce the recommendations on unpacking, handling, inspection and storage of this relay. A

    guide to the mechanical and electrical installation of this relay is also provided, incorporating

    earthing recommendations. A typical wiring connection to this relay is indicated.

    12 Commissioning

    Introduce how to commission this relay, comprising checks on the calibration and functionality of

    this relay.

    13 Maintenance

    A general maintenance policy for this relay is outlined.

    14 Decommissioning and Disposal

    A general decommissioning and disposal policy for this relay is outlined.

    15 Manual Version History

    List the instruction manual version and the modification history records.

    Typographic and Graphical Conventions

    Deviations may be permitted in drawings and tables when the type of designator can be obviously

    derived from the illustration.

    The following symbols are used in drawings:

    &

    AND gate

    1

    OR gate

    Comparator

    BI Binary signal via opto-coupler

    SET I>Input signal from comparator with setting

    EN Input signal of logic setting for function enabling

  • Preface

    PCS-902 Line Distance Relay vi

    Date: 2013-12-18

    SIG Input of binary signal except those signals via opto-coupler

    XXXOutput signal

    t

    t

    Timer

    Timer (optional definite-time or inverse-time characteristic)

    10ms 0ms

    Timer [delay pickup (10ms), delay dropoff (0ms), non-settable]

    [XXX] 0ms

    Timer (delay pickup, settable)

    0ms [XXX]

    Timer (delay dropoff, settable)

    [XXX] [XXX]

    Timer (delay pickup, delay dropoff, settable)

    IDMT

    Timer (inverse-time characteristic)

    ---xxx is the symbol

    Symbol Corresponding Relationship

    Basic Example

    A, B, C L1, L2, L3 Ia, Ib, Ic, I0 IL1, IL2, IL3, IN

    AN, BN, CN L1N, L2N, L3N Ua, Ub, Uc VL1, VL2, VL3

    ABC L123 Uab, Ubc, Uca VL12, VL23, VL31

    U (voltage) V U0, U1, U2 VN, V1, V2

  • 1 Introduction

    PCS-902 Line Distance Relay 1-a

    Date: 2013-09-05

    1 Introduction

    Table of Contents

    1 Introduction ...................................................................................... 1-a

    1.1 Application ....................................................................................................... 1-1

    1.2 Function ........................................................................................................... 1-3

    1.3 Features ........................................................................................................... 1-6

    List of Figures

    Figure 1.1-1 Typical application of PCS-902 ............................................................................ 1-1

    Figure 1.1-2 Functional diagram of PCS-902 ........................................................................... 1-2

  • 1 Introduction

    PCS-902 Line Distance Relay 1-b Date: 2013-09-05

  • 1 Introduction

    PCS-902 Line Distance Relay 1-1

    Date: 2013-09-05

    1.1 Application

    PCS-902 is a digital line distance protection with the main and back-up protection functions, which

    is designed for overhead line or cables and hybrid transmission lines of various voltage levels.

    Optical fibre channel or PLC channel

    Communication channel via direct dedicated fibre, MUX or PLC

    52

    PCS-902PCS-902

    52

    Figure 1.1-1 Typical application of PCS-902

    Main protection of PCS-902 comprises of pilot distance protection (PUTT, POTT, blocking and

    unblocking) and pilot directional earth-fault protection (selectable for independent communication

    channel or sharing channel with POTT), which can clear any internal fault instantaneously for the

    whole line with the aid of protection signal. DPFC distance protection can perform extremely high

    speed operation for close-up faults. There is direct transfer trip (DTT) feature incorporated in the

    relay.

    PCS-902 also includes distance protection (3 forward zones and 1 reverse zone distance

    protection with selectable mho or quadrilateral characteristic), 4 stages directional earth fault

    protection, 4 stages directional phase overcurrent protection, 2 stages voltage protection

    (under/over voltage protection), 4 stages frequency protection (under/over frequency protection),

    broken conductor protection, pole discrepancy protection, breaker failure protection, thermal

    overload protection, and dead zone protection etc. Morever, a backup overcurrent and earth fault

    protection will be automatically enabled when VT circuit fails. In addition, stub overcurrent

    protection is provided for one and a half breakers arrangement when transmission line is put into

    maintenance.

    PCS-902 has selectable mode of single-phase tripping or three-phase tripping and configurable

    auto-reclosing mode for 1-pole, 3-poles and 1/3-pole operation.

    PCS-902 with appropriate selection of integrated protection functions can be applied for various

    voltage levels and primary equipment such as cables, overhead lines, interconnectors and

    transformer feeder, etc. It also supports configurable binary inputs, binary outputs, LEDs and IEC

    61850 protocol.

  • 1 Introduction

    PCS-902 Line Distance Relay 1-2 Date: 2013-09-05

    BUS

    LINE

    25

    FR

    FL

    52

    85 21

    Data Transmitt/Receive

    27

    59

    50BF67P21D 67G

    50STB (Only for one and a half breakers arrangement)

    50G

    51G

    50P

    51P

    79SOTF

    49 46BC

    81

    50GVT 50PVT 62PD

    50DZ

    Figure 1.1-2 Functional diagram of PCS-902

    No. Function ANSI

    1 Pilot protection 85

    2 DPFC distance protection 21D

    3 Distance protection 21

    4 Earth fault protection 67G

    5 Definite-time earth-fault protection 50G

    6 Inverse-time earth-fault protection 51G

    8 Phase overcurrent protection 67P

    9 Definite-time phase overcurrent protection 50P

    10 Inverse-time phase overcurrent protection 51P

    11 Overvoltage protection 59

    12 Undervoltage protection 27

    13 Frequency protection 81

    14 Broken conductor protection 46BC

    15 Breaker failure protection 50BF

    16 Thermal overload protection 49

    17 Stub overcurrent protection 50STB

    18 Dead zone protection 50DZ

    19 Pole discrepancy protection 62PD

    20 Switch onto fault SOTF

    21 Phase overcurrent protection when VT circuit failure 50PVT

    22 Earth fault protection when VT circuit failure 50GVT

    23 Synchronism check 25

    24 Automatic reclosure 79

    25 Fault recorder FR

  • 1 Introduction

    PCS-902 Line Distance Relay 1-3

    Date: 2013-09-05

    26 Fault location FL

    1.2 Function

    1. Protection Function

    Distance protection

    Three zones forward phase-to-ground distance elements (mho or quadrilateral

    characteristic)

    One pilot zone phase-to-ground distance element (mho or quadrilateral characteristic)

    with weakinfeed distance element

    One zone reverse phase-to-ground distance element (mho or quadrilateral characteristic)

    Three zones forward phase-to-phase distance elements (mho or quadrilateral

    characteristic)

    One pilot zone phase-to-phase distance element (mho or quadrilateral characteristic)

    with weakinfeed distance element

    One zone reverse phase-to-phase distance element (mho or quadrilateral characteristic)

    Load encroachment for mho and quadrilateral characteristic distance element

    Power swing blocking releasing, selectable for each of above mentioned zones

    Deviation of Power Frequency Component (DPFC) distance protection

    Current protection

    Four stages phase overcurrent protection, selectable time characteristic (definite-time or

    inverse-time) and directionality (forward direction, reverse direction or non-directional)

    Four stages directional earth fault protection, selectable time characteristic (definite-time

    or inverse-time) and directionality (forward direction, reverse direction or non-directional)

    Breaker failure protection

    Optional instantaneously re-tripping

    One stage with two delay timers

    Thermal overload protection

    Stub overcurrent protection

    Dead zone protection

    Pole discrepancy protection

    Broken conductor protection

    Switch onto fault (SOTF)

  • 1 Introduction

    PCS-902 Line Distance Relay 1-4 Date: 2013-09-05

    Via distance measurement elements

    Via dedicated earth fault element

    Backup protection when VT circuit failure

    Phase overcurrent protection when VT circuit failure

    Earth fault protection when VT circuit failure

    Voltage protection

    Two stages overvoltage protection

    Two stages undervoltage protection

    Frequency protection

    Four stages overfrequency protection

    Four stages underfrequency protection

    f/dt block criterion for underfrequency protection

    Control function

    Synchro-checking

    Automatic reclosure (single shot or multi-shot (max. 4) for 1-pole AR and 3-pole AR)

    Pilot scheme logic

    Phase-segregated communication logic of distance protection

    Weak infeed logic of pilot distance protection

    Weak infeed logic of pilot directional earth fault protection

    Communication scheme of optical pilot channel (Optional)

    Direct optical link

    Connection to a communication network, support G.703 and C37.94 protocol

    Dual-channels redundancy

    2. Measurement and control function

    Remote control (open and closing)

    Synchronism check for remote and manual closing (only for one circuit breaker)

    Energy metering (active and reactive energy are calculated in import respectively export

    direction)

    3. Logic

    User programmable logic

  • 1 Introduction

    PCS-902 Line Distance Relay 1-5

    Date: 2013-09-05

    4. Additional function

    Fault location

    Fault phase selection

    Parallel line compensation for fault location

    VT circuit supervision

    CT circuit supervision

    Self diagnostic

    DC power supply supervision

    Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision

    events, 256 control logs and 1024 device logs.

    Disturbance recorder including 32 disturbance records with waveforms (The file format of

    disturbance recorder is compatible with international COMTRADE file.)

    Four kinds of clock synchronization methods

    Conventional

    PPS (RS-485): Pulse per second (PPS) via RS-485 differential level

    IRIG-B (RS-485): IRIG-B via RS-485 differential level

    PPM (DIN): Pulse per minute (PPM) via the optical coupler

    PPS (DIN): Pulse per second (PPS) via the optical coupler

    SAS

    SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network

    SNTP (BC): Broadcast SNTP mode via Ethernet network

    Message (IEC103): Clock messages through IEC103 protocol

    Advanced

    IEEE1588: Clock message via IEEE1588

    IRIG-B (Fiber): IRIG-B via optical-fibre interface

    PPS (Fiber) PPS: Pulse per second (PPS) via optical-fibre interface

    NoTimeSync

    5. Monitoring

    Number of circuit breaker operation (single-phase tripping, three-phase tripping and

    reclosing)

    Channel status

  • 1 Introduction

    PCS-902 Line Distance Relay 1-6 Date: 2013-09-05

    Frequency

    6. Communication

    Optional 2 RS-485 communication rear ports conform to IEC 60870-5-103 protocol

    1 RS-485 communication rear ports for clock synchronization

    Optional 2 or 4 Ethernet ports (depend on the chosen type of MON plug-in module) conform

    to IEC 61850 protocol, DNP3.0 protocol or IEC 60870-5-103 protocol over TCP/IP

    Optional 2 Ethernet ports via optic fiber (ST interface) conform to IEC 61850 protocol, DNP3.0

    protocol or IEC 60870-5-103 protocol over TCP/IP

    GOOSE and SV communication function (optional NET-DSP plug-in module)

    7. User Interface

    Friendly HMI interface with LCD and 9-button keypad on the front panel.

    1 front multiplex RJ45 port for testing and setting

    1 RS-232 or RS-485 rear ports for printer

    Language switchoverEnglish+ selected language

    Auxiliary softwarePCS-Explorer

    1.3 Features

    The intelligent device integrated with protection, control and monitor provides powerful

    protection function, flexible protection configuration, user programmable logic and

    configurable binary input and binary output, which can meet with various application

    requirements.

    High-performance hardware platform and modularized design, MCU (management control

    unit)DSP (digital signal processor). MCU manages general fault detector element and DSP

    manages protection and metering. Their data acquisition system is completely independent in

    electronic circuit. DC power supply of output relay is controlled by the operation of fault

    detector element operates, this prevents maloperation due to error from ADC or damage of

    any apparatus.

    Fast fault clearance for faults within the protected line, the operating time is less than 10 ms

    for close-up faults, less than 15ms for faults in the middle portion of protected line and less

    than 25ms for remote end faults.

    The unique DPFC distance element integrated in the protective device provides extremely

    high speed operation and insensitive to power swing.

    Self-adaptive floating threshold which only reflects deviation of power frequency component

    improves the protection sensitivity and stability under the condition of load fluctuation and

    system disturbance.

  • 1 Introduction

    PCS-902 Line Distance Relay 1-7

    Date: 2013-09-05

    Advanced and reliable power swing blocking releasing feature which ensure distance

    protection operate correctly for internal fault during power swing and prevent distance

    protection from maloperation during power swing

    Flexible automatic reclosure supports various initiation modes and check modes

    Multiple setting groups with password protection and setting value saved permanently before

    modification

    Powerful PC tool software can fulfill protection function configuration, modify setting and

    waveform analysis.

  • 1 Introduction

    PCS-902 Line Distance Relay 1-8 Date: 2013-09-05

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-a

    Date: 2013-09-05

    2 Technical Data

    Table of Contents

    2 Technical Data .................................................................................. 2-a

    2.1 Electrical Specifications ................................................................................. 2-1

    2.1.1 AC Current Input ................................................................................................................ 2-1

    2.1.2 AC Voltage Input ................................................................................................................ 2-1

    2.1.3 Power Supply ..................................................................................................................... 2-1

    2.1.4 Binary Input ........................................................................................................................ 2-1

    2.1.5 Binary Output ..................................................................................................................... 2-2

    2.2 Mechanical Specifications ............................................................................. 2-3

    2.3 Ambient Temperature and Humidity Range .................................................. 2-3

    2.4 Communication Port ....................................................................................... 2-3

    2.4.1 EIA-485 Port ...................................................................................................................... 2-3

    2.4.2 Ethernet Port ...................................................................................................................... 2-3

    2.4.3 Optical Fibre Port ............................................................................................................... 2-4

    2.4.4 Print Port ............................................................................................................................ 2-5

    2.4.5 Clock Synchronization Port ................................................................................................ 2-5

    2.5 Type Tests ........................................................................................................ 2-5

    2.5.1 Environmental Tests ........................................................................................................... 2-5

    2.5.2 Mechanical Tests................................................................................................................ 2-5

    2.5.3 Electrical Tests ................................................................................................................... 2-5

    2.5.4 Electromagnetic Compatibility ............................................................................................ 2-5

    2.6 Certifications ................................................................................................... 2-6

    2.7 Terminals ......................................................................................................... 2-7

    2.8 Measurement Scope and Accuracy ............................................................... 2-7

    2.9 Management Function .................................................................................... 2-7

    2.9.1 Control Performance .......................................................................................................... 2-7

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-b

    Date: 2013-09-05

    2.9.2 Clock Performance ............................................................................................................ 2-7

    2.9.3 Fault and Disturbance Recording ....................................................................................... 2-8

    2.9.4 Binary Input Signal ............................................................................................................. 2-8

    2.10 Protective Functions ..................................................................................... 2-8

    2.10.1 Fault Detector .................................................................................................................. 2-8

    2.10.2 Distance Protection .......................................................................................................... 2-8

    2.10.3 Phase Overcurrent Protection .......................................................................................... 2-8

    2.10.4 Earth Fault Protection ...................................................................................................... 2-8

    2.10.5 Overvoltage Protection..................................................................................................... 2-9

    2.10.6 Undervoltage Protection ................................................................................................... 2-9

    2.10.7 Overfrequency Protection ................................................................................................ 2-9

    2.10.8 Underfrequency Protection .............................................................................................. 2-9

    2.10.9 Breaker Failure Protection ............................................................................................... 2-9

    2.10.10 Thermal Overload Protection ....................................................................................... 2-10

    2.10.11 Stub Overcurrent Protection ......................................................................................... 2-10

    2.10.12 Dead Zone Protection .................................................................................................. 2-10

    2.10.13 Pole Discrepancy Protection ........................................................................................ 2-10

    2.10.14 Broken Conductor Protection ....................................................................................... 2-10

    2.10.15 Auto-reclosing .............................................................................................................. 2-11

    2.10.16 Transient Overreach .................................................................................................... 2-11

    2.10.17 Fault Locator ................................................................................................................ 2-11

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-1

    Date: 2013-09-05

    2.1 Electrical Specifications

    2.1.1 AC Current Input

    Phase rotation ABC

    Nominal frequency (fn) 50Hz, 60Hz

    Rated current (In) 1A 5A

    Linear to 0.05In~40In (It should measure current without beyond full scale

    against 20 times of related current and value of DC offset by 100%.)

    Thermal withstand

    -continuously

    -for 10s

    -for 1s

    -for half a cycle

    4In

    30In

    100In

    250In

    Burden < 0.15VA/phase @In < 0.25VA/phase @In

    Number Up to 7 current input according to various applications

    2.1.2 AC Voltage Input

    Phase rotation ABC

    Nominal frequency (fn) 50Hz, 60Hz

    Rated voltage (Un) 100V~130V

    Linear to 1V~170V

    Thermal withstand

    -continuously

    -10s

    -1s

    200V

    260V

    300V

    Burden at rated < 0.20VA/phase @Un

    Number Up to 6 voltage input according to various applications

    2.1.3 Power Supply

    Standard IEC 60255-11:2008

    Rated voltage 110Vdc/125Vdc/220Vdc/250Vdc

    Permissible voltage range 88~300Vdc

    Permissible AC ripple voltage 15% of the nominal auxiliary voltage

    Burden

    Quiescent condition

    Operating condition

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-2

    Date: 2013-09-05

    Maximum permissible voltage 100Vdc

    Withstand voltage 2000Vac, 2800Vdc (continuously )

    Response time for logic input 1ms

    Number Up to 36 binary input according to various hardware configurations

    Rated voltage 110Vdc 125Vdc 220Vdc 250Vdc

    Rated current drain 1.1mA 1.25mA 2.2mA 2.5mA

    Pickup voltage 77-132Vdc 87.5-150Vdc 154-264Vdc 175-300Vdc

    Dropoff voltage

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-3

    Date: 2013-09-05

    Dropoff time

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-4

    Date: 2013-09-05

    Transmission rate 100Mbits/s

    Transmission standard 100Base-TX 100Base-FX

    Transmission distance

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-5

    Date: 2013-09-05

    Minimum receiving power Min. -25.0dBm

    Margin Min +3.0dB

    2.4.4 Print Port

    Type RS-232

    Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s

    Printer type EPSON 300K printer

    Safety level Isolation to ELV level

    2.4.5 Clock Synchronization Port

    Type RS-485

    Transmission distance 100M@500VDC

    2.5.4 Electromagnetic Compatibility

    1MHz burst disturbance test

    IEC 60255-22-1:2007

    Common mode: class 2.5kV

    Differential mode: class 1.0kV

    Electrostatic discharge test

    IEC60255-22-2:2008 class

    For contact discharge: 8kV

    For air discharge: 15kV

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-6

    Date: 2013-09-05

    Radio frequency interference tests

    IEC 60255-22-3:2007 class

    Frequency sweep

    Radiated amplitude-modulated

    10V/m (rms), f=80~1000MHz

    Spot frequency

    Radiated amplitude-modulated

    10V/m (rms), f=80MHz/160MHz/450MHz/900MHz

    Radiated pulse-modulated

    10V/m (rms), f=900MHz

    Fast transient disturbance tests

    IEC 60255-22-4:2008

    Power supply, I/O, Earth: class , 4kV, 2.5kHz, 5/50ns

    Communication terminals: class , 2kV, 5kHz, 5/50ns

    Surge immunity test

    IEC 60255-22-5:2008

    Power supply, AC input, I/O port: class , 1.2/50us

    Common mode: 4kV

    Differential mode: 2kV

    Conducted RF Electromagnetic

    Disturbance

    IEC 60255-22-6:2001

    Power supply, AC, I/O, Comm. Terminal: Class , 10Vrms, 150

    kHz~80MHz

    Power Frequency Magnetic Field

    Immunity

    IEC 61000-4-8:2001

    class , 100A/m for 1min, 1000A/m for 3s

    Pulse Magnetic Field Immunity IEC 61000-4-9:2001

    class , 6.4/16s, 1000A/m for 3s

    Damped oscillatory magnetic field

    immunity

    IEC 61000-4-10:2001

    class , 100kHz & 1MHz100A/m

    Auxiliary power supply performance

    - Voltage dips

    -Voltage short interruptions

    IEC60255-11: 2008

    Up to 200ms for dips to 40% of rated voltage without reset

    100ms for interruption without rebooting

    2.6 Certifications

    ISO9001:2008

    ISO14001:2004

    OHSAS18001:2007

    ISO10012:2003

    CMMI L4

    EMC: 2004/108/EC, EN50263:1999

    Products safety(PS): 2006/95/EC, EN61010-1:2001

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-7

    Date: 2013-09-05

    2.7 Terminals

    Connection Type Wire Size

    AC current

    Crimp terminals, 1.5mm2~4.0mm

    2 lead

    If using 4.0mm2 lead, only dedicated terminal cable lug provided by NR

    can be adopted.

    AC voltage Crimp terminals, 1.0mm2~2.5mm

    2 lead

    Power supply Crimp terminals, 1.0mm2~2.5mm

    2 lead

    Contact I/O Crimp terminals, 1.0mm2~2.5mm

    2 lead

    Grounding (Earthing) Connection BVR type, 2.5mm~6.0mm2

    lead

    2.8 Measurement Scope and Accuracy

    Item Range Accuracy

    Phase range 0 ~ 360 3

    Frequency fn3 Hz 0.02Hz

    Currents from protection measurement current transformers

    Current 0.05~5.00In 2.0% of rating (0.05~1.00In)

    2.0% of applied quantities (1.00~5.00In)

    Voltage 0.05~1.50Un 1.0% of rating (0.05~1.00Un)

    1.0% of applied quantities (1.00~1.50Un)

    Active power (W) 0.05~1.50Un

    0.05~5.00In

    3.0% of rating (0.05~1.00In, 0.05~1.00Un)

    3.0% of applied quantities (1.00~5.00In, 1.00~1.50Un)

    Reactive power (VAr) 0.05~1.50Un

    0.05~5.00In

    3.0% of rating (0.05~1.00In, 0.05~1.00Un)

    3.0% of applied quantities (1.00~5.00In, 1.00~1.50Un)

    Apparent power (VA) 0.05~1.50Un

    0.05~5.00In

    3.0% of rating (0.05~1.00In, 0.05~1.00Un)

    3.0% of applied quantities (1.00~5.00In, 1.00~1.50Un)

    Energy (Wh) 0.05~1.50Un

    0.05~5.00In

    3.0% of rating (0.05~1.00In, 0.05~1.00Un)

    3.0% of applied quantities (1.00~5.00In, 1.00~1.50Un)

    Energy (VAh) 0.05~1.50Un

    0.05~5.00In

    3.0% of rating (0.05~1.00In, 0.05~1.00Un)

    3.0% of applied quantities (1.00~5.00In, 1.00~1.50Un)

    2.9 Management Function

    2.9.1 Control Performance

    Control mode Local or remote

    Accuracy of local control 1s

    Accuracy of remote control 3s

    2.9.2 Clock Performance

    Real time clock accuracy 3s/day

    Accuracy of GPS synchronization 1ms

    External time synchronization IRIG-B (200-98), PPS, IEEE1588 or SNTP protocol

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-8

    Date: 2013-09-05

    2.9.3 Fault and Disturbance Recording

    Maximum duration 10000 sampled points (24 sampled points per cycle)

    Recording position 10 cycles before pickup of trigger element

    2.9.4 Binary Input Signal

    Resolution of binary input signal 1ms

    Binary input mode Potential-free contact

    Resolution of SOE 2ms

    2.10 Protective Functions

    2.10.1 Fault Detector

    2.10.1.1 DPFC Current Element

    Setting range 0.050In~30.000In (A)

    Accuracy 2.5% of setting or 0.02In whichever is greater

    2.10.1.2 Residual Current Element

    Setting range 0.050In~30.000In (A)

    Accuracy 2.5% of setting or 0.02In whichever is greater

    2.10.1.3 Overvoltage Element

    Setting range Un~2Unn (V)

    Accuracy 2.5% of setting or 0.01Un, whichever is greater

    2.10.2 Distance Protection

    Setting range (0.000~4Unn)/In (ohm)

    Accuracy 2.5% of setting or 0.1/In whichever is greater

    Resetting ratio 105%

    Time delay 0.000~10.000 (s)

    Accuracy 1%Setting+30ms

    2.10.3 Phase Overcurrent Protection

    Setting range 0.050In~30.000In (A)

    Accuracy 2.5% of setting or 0.02In whichever is greater

    Resetting ratio 95%

    Time delay 0.000~20.000 (s)

    Accuracy (definite-time characteristic) 1% of Setting+30ms (at 2 times current setting)

    Accuracy (inverse-time characteristic) 2.5% operating time or 30ms, whichever is greater

    (for current between 1.2 and 20 multiples of pickup)

    2.10.4 Earth Fault Protection

    Setting range 0.050In~30.000In (A)

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-9

    Date: 2013-09-05

    Accuracy 2.5% of setting or 0.02In whichever is greater

    Resetting ratio 95%

    Time delay 0.000~20.000 (s)

    Accuracy (definite-time characteristic) 1% of Setting+30ms (at 2 times current setting)

    Accuracy (inverse-time characteristic) 2.5% operating time or 30ms, whichever is greater

    (for current between 1.2 and 20 multiples of pickup)

    2.10.5 Overvoltage Protection

    Setting range Un~2Unn (V)

    Accuracy 2.5% of setting or 0.01Un, whichever is greater

    Resetting ratio 95%

    Time delay 0.000~30.000 (s)

    Accuracy (definite-time characteristic) 1% of Setting+30ms (at 1.2 times voltage setting)

    Accuracy (inverse-time characteristic) 2.5% operating time or 30ms, whichever is greater

    (for voltage between 1.2 and 2 multiples of pickup)

    2.10.6 Undervoltage Protection

    Setting range 0~Unn (V)

    Accuracy 2.5% of setting or 0.01Un, whichever is greater

    Resetting ratio 105%

    Time delay 0.000~30.000 (s)

    Accuracy (definite-time characteristic) 1%Setting+30ms (at 1.2 times voltage setting)

    Accuracy (inverse-time characteristic) 2.5% operating time or 30ms, whichever is greater

    (for voltage between 0.5 and 0.8 multiples of pickup)

    2.10.7 Overfrequency Protection

    Setting range 50.00~65.00 (Hz)

    Accuracy 0.02Hz

    Resetting ratio 95%

    Time delay 0.000~100.000 (s)

    Accuracy 1%Setting+30ms (at 1.2 times frequency setting)

    2.10.8 Underfrequency Protection

    Setting range 45.00~ 60.00 (Hz)

    Accuracy 0.02Hz

    Resetting ratio 105%

    Time delay 0.000s ~ 100.000 (s)

    Accuracy 1%Setting+30ms (at 0.8 times frequency setting)

    df/dt blocking setting range 0.200~20.000 (Hz/s)

    Accuracy 0.02Hz/s

    2.10.9 Breaker Failure Protection

    Pick-up time

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-10

    Date: 2013-09-05

    Drop-off time

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-11

    Date: 2013-09-05

    Resetting ratio 95%

    Time delay 0.000~600.000 (s)

    Accuracy 1% of Setting+30ms

    2.10.15 Auto-reclosing

    Phase difference setting range 0~89 (Deg)

    Accuracy 2.0Deg

    Voltage difference setting range 0.02Un~0.8Un (V)

    Accuracy Max(0.01Un, 2.5%)

    Frequency difference setting range 0.02~1 (Hz)

    Accuracy 0.01Hz

    Operating time of synchronism check 1%Setting+20ms

    Operating time of energizing check 1%Setting+20ms

    Operating time of auto-reclosing 1%Setting+20ms

    2.10.16 Transient Overreach

    Tolerance for all high-speed protection 2%

    2.10.17 Fault Locator

    Accuracy for multi-phase faults with single end feed < 2.5%

    Tolerance will be higher in case of single-phase fault with high ground resistance.

  • 2 Technical Data

    PCS-902 Line Distance Relay 2-12

    Date: 2013-09-05

  • 3 Operation Theory

    PCS-902 Line Distance Relay 3-a

    Date: 2013-12-25

    3 Operation Theory

    Table of Contents

    3 Operation Theory ............................................................................. 3-a

    3.1 System Parameters ......................................................................................... 3-1

    3.1.1 General Application ............................................................................................................ 3-1

    3.1.2 Function Description .......................................................................................................... 3-1

    3.1.3 Settings .............................................................................................................................. 3-1

    3.2 Line Parameters .............................................................................................. 3-1

    3.2.1 General Application ............................................................................................................ 3-1

    3.2.2 Function Description .......................................................................................................... 3-2

    3.2.3 Settings .............................................................................................................................. 3-2

    3.3 Circuit Breaker Position Supervision ............................................................ 3-2

    3.3.1 General Application ............................................................................................................ 3-2

    3.3.2 Function Description .......................................................................................................... 3-2

    3.3.3 Function Block Diagram ..................................................................................................... 3-3

    3.3.4 I/O Signals ......................................................................................................................... 3-4

    3.3.5 Logic .................................................................................................................................. 3-4

    3.3.6 Settings .............................................................................................................................. 3-5

    3.4 Fault Detector (FD) .......................................................................................... 3-5

    3.4.1 Application.......................................................................................................................... 3-5

    3.4.2 Fault Detector in Fault Detector DSP ................................................................................. 3-5

    3.4.3 Protection Fault Detector in Protection Calculation DSP ................................................... 3-8

    3.4.4 Function Block Diagram ..................................................................................................... 3-9

    3.4.5 I/O Signals ......................................................................................................................... 3-9

    3.4.6 Logic .................................................................................................................................. 3-9

    3.4.7 Settings ............................................................................................................................ 3-10

    3.5 Auxiliary Element .......................................................................................... 3-10

  • 3 Operation Theory

    PCS-902 Line Distance Relay 3-b

    Date: 2013-12-25

    3.5.1 General Application .......................................................................................................... 3-10

    3.5.2 Function Description ........................................................................................................ 3-10

    3.5.3 Function Block Diagram ................................................................................................... 3-13

    3.5.4 I/O Signals ....................................................................................................................... 3-14

    3.5.5 Logic ................................................................................................................................ 3-16

    3.5.6 Settings ............................................................................................................................ 3-19

    3.6 Distance Protection ...................................................................................... 3-21

    3.6.1 General Application .......................................................................................................... 3-21

    3.6.2 Function Description ........................................................................................................ 3-21

    3.6.3 DPFC Distance Protection ............................................................................................... 3-29

    3.6.4 Load Encroachment ......................................................................................................... 3-33

    3.6.5 Mho Distance Protection .................................................................................................. 3-35

    3.6.6 Quadrilateral Distance Protection .................................................................................... 3-50

    3.6.7 Pilot Distance Zone .......................................................................................................... 3-60

    3.6.8 Power Swing Detection .................................................................................................... 3-63

    3.6.9 Power Swing Blocking Releasing ..................................................................................... 3-64

    3.6.10 Distance SOTF Protection ............................................................................................. 3-70

    3.7 Optical Pilot Channel (Option) ..................................................................... 3-75

    3.7.1 General Application .......................................................................................................... 3-75

    3.7.2 Function Description ........................................................................................................ 3-75

    3.7.3 Function Block Diagram ................................................................................................... 3-80

    3.7.4 I/O Signals ....................................................................................................................... 3-80

    3.7.5 Logic ................................................................................................................................ 3-82

    3.7.6 Settings ............................................................................................................................ 3-82

    3.8 Pilot Distance Protection .............................................................................. 3-82

    3.8.1 General Application .......................................................................................................... 3-82

    3.8.2 Function Description ........................................................................................................ 3-83

    3.8.3 Function Block Diagram ................................................................................................... 3-93

    3.8.4 I/O Signals ....................................................................................................................... 3-93

    3.8.5 Settings ............................................................................................................................ 3-94

  • 3 Operation Theory

    PCS-902 Line Distance Relay 3-c

    Date: 2013-12-25

    3.9 Pilot Directional Earth-fault Protection ....................................................... 3-95

    3.9.1 General Application .......................................................................................................... 3-95

    3.9.2 Function Description ........................................................................................................ 3-96

    3.9.3 Function Block Diagram ................................................................................................. 3-101

    3.9.4 I/O Signals ..................................................................................................................... 3-101

    3.9.5 Settings .......................................................................................................................... 3-102

    3.10 Current Direction....................................................................................... 3-103

    3.10.1 General Application ...................................................................................................... 3-103

    3.10.2 Function Description .................................................................................................... 3-103

    3.10.3 Function Block Diagram ............................................................................................... 3-108

    3.10.4 I/O Signals ................................................................................................................... 3-108

    3.10.5 Settings ........................................................................................................................ 3-109

    3.11 Phase Overcurrent Protection ................................................................. 3-109

    3.11.1 General Application ...................................................................................................... 3-109

    3.11.2 Function Description..................................................................................................... 3-109

    3.11.3 Function Block Diagram ............................................................................................... 3-112

    3.11.4 I/O Signals .................................................................................................................... 3-112

    3.11.5 Logic............................................................................................................................. 3-113

    3.11.6 Settings ........................................................................................................................ 3-113

    3.12 Earth Fault Protection ................................................................................ 3-117

    3.12.1 General Application ...................................................................................................... 3-117

    3.12.2 Function Description .................................................................................................... 3-117

    3.12.3 Function Block Diagram ............................................................................................... 3-119

    3.12.4 I/O Signals ................................................................................................................... 3-120

    3.12.5 Logic ............................................................................................................................ 3-120

    3.12.6 Settings ........................................................................................................................ 3-121

    3.13 Overcurrent Protection for VT Circuit Failure ........................................ 3-125

    3.13.1 General Application ...................................................................................................... 3-125

    3.13.2 Function Block Diagram ............................................................................................... 3-126

    3.13.3 I/O Signals ................................................................................................................... 3-126

  • 3 Operation Theory

    PCS-902 Line Distance Relay 3-d

    Date: 2013-12-25

    3.13.4 Logic ............................................................................................................................ 3-127

    3.13.5 Settings ........................................................................................................................ 3-127

    3.14 Residual Current SOTF Protection .......................................................... 3-128

    3.14.1 General Application ...................................................................................................... 3-128

    3.14.2 Function Description .................................................................................................... 3-128

    3.14.3 Function Block Diagram ............................................................................................... 3-128

    3.14.4 I/O Signals ................................................................................................................... 3-128

    3.14.5 Logic ............................................................................................................................ 3-129

    3.14.6 Settings ........................................................................................................................ 3-129

    3.15 Voltage Protection ..................................................................................... 3-129

    3.15.1 Overvoltage Protection................................................................................................. 3-130

    3.15.2 Undervoltage Protection ............................................................................................... 3-136

    3.16 Frequency Protection ............................................................................... 3-142

    3.16.1 Overfrequency Protection ............................................................................................ 3-142

    3.16.2 Underfrequency Protection .......................................................................................... 3-146

    3.17 Breaker Failure Protection ....................................................................... 3-151

    3.17.1 General Application ...................................................................................................... 3-151

    3.17.2 Function Description .................................................................................................... 3-151

    3.17.3 Function Block Diagram ............................................................................................... 3-152

    3.17.4 I/O Signals ................................................................................................................... 3-153

    3.17.5 Logic ............................................................................................................................ 3-154

    3.17.6 Settings ........................................................................................................................ 3-155

    3.18 Thermal Overload Protection ................................................................... 3-155

    3.18.1 General Application ...................................................................................................... 3-155

    3.18.2 Function Description .................................................................................................... 3-156

    3.18.3 Function Block Diagram ............................................................................................... 3-157

    3.18.4 I/O Signals ................................................................................................................... 3-157

    3.18.5 Logic ............................................................................................................................ 3-158

    3.18.6 Settings ........................................................................................................................ 3-159

    3.19 Stub Overcurrent Protection .................................................................... 3-159

  • 3 Operation Theory

    PCS-902 Line Distance Relay 3-e

    Date: 2013-12-25

    3.19.1 General Application ...................................................................................................... 3-159

    3.19.2 Function Block Diagram ............................................................................................... 3-160

    3.19.3 I/O Signals ................................................................................................................... 3-160

    3.19.4 Logic ............................................................................................................................ 3-161

    3.19.5 Settings ........................................................................................................................ 3-161

    3.20 Dead Zone Protection ............................................................................... 3-162

    3.20.1 General Application ...................................................................................................... 3-162

    3.20.2 Function Description .................................................................................................... 3-162

    3.20.3 Function Block Diagram ............................................................................................... 3-162

    3.20.4 I/O Signal ..................................................................................................................... 3-162

    3.20.5 Logic ............................................................................................................................ 3-163

    3.20.6 Settings ........................................................................................................................ 3-163

    3.21 Pole Discrepancy Protection .................................................................... 3-163

    3.21.1 General Application ...................................................................................................... 3-163

    3.21.2 Function Description .................................................................................................... 3-164

    3.21.3 Function Block Diagram ............................................................................................... 3-164

    3.21.4 I/O Signals ................................................................................................................... 3-164

    3.21.5 Logic ............................................................................................................................ 3-164

    3.21.6 Settings ........................................................................................................................ 3-165

    3.22 Broken Conductor Protection .................................................................. 3-165

    3.22.1 General Application ...................................................................................................... 3-165

    3.22.2 Function Description .................................................................................................... 3-166

    3.22.3 Function Block Diagram ............................................................................................... 3-166

    3.22.4 I/O Signals ................................................................................................................... 3-166

    3.22.5 Logic ............................................................................................................................ 3-167

    3.22.6 Settings ........................................................................................................................ 3-167

    3.23 Synchrocheck ........................................................................................... 3-168

    3.23.1 General Application ...................................................................................................... 3-168

    3.23.2 Function Description .................................................................................................... 3-168

    3.23.3 Function Block Diagram ............................................................................................... 3-171

  • 3 Operation Theory

    PCS-902 Line Distance Relay 3-f

    Date: 2013-12-25

    3.23.4 I/O Signals ................................................................................................................... 3-171

    3.23.5 Logic ............................................................................................................................ 3-172

    3.23.6 Settings ........................................................................................................................ 3-174

    3.24 Automatic Reclosure ................................................................................ 3-175

    3.24.1 General Application ...................................................................................................... 3-175

    3.24.2 Function Description .................................................................................................... 3-176

    3.24.3 Function Block Diagram ............................................................................................... 3-177

    3.24.4 I/O Signals ................................................................................................................... 3-177

    3.24.5 Logic ............................................................................................................................ 3-179

    3.24.6 Settings ........................................................................................................................ 3-191

    3.25 Transfer Trip .............................................................................................. 3-193

    3.25.1 General Application ...................................................................................................... 3-193

    3.25.2 Function Description .................................................................................................... 3-193

    3.25.3 Function Block Diagram ............................................................................................... 3-193

    3.25.4 I/O Signals ................................................................................................................... 3-193

    3.25.5 Logic ............................................................................................................................ 3-194

    3.25.6 Settings ........................................................................................................................ 3-194

    3.26 Trip Logic ................................................................................................... 3-194

    3.26.1 General Application ...................................................................................................... 3-194

    3.26.2 Function Description .................................................................................................... 3-194

    3.26.3 Function Block Diagram ............................................................................................... 3-195

    3.26.4 I/O Signals ................................................................................................................... 3-195

    3.26.5 Logic ............................................................................................................................ 3-196

    3.26.6 Settings ........................................................................................................................ 3-200

    3.27 VT Circuit Supervision .............................................................................. 3-200

    3.27.1 General Application ...................................................................................................... 3-200

    3.27.2 Function Description .................................................................................................... 3-201

    3.27.3 Function Block Diagram ............................................................................................... 3-201

    3.27.4 I/O Signals ................................................................................................................... 3-201

    3.27.5 Logic ............................................................................................................................ 3-202

  • 3 Operation Theory

    PCS-902 Line Distance Relay 3-g

    Date: 2013-12-25

    3.27.6 Settings ........................................................................................................................ 3-203

    3.28 CT Circuit Supervision ............................................................................. 3-203

    3.28.1 General Application ...................................................................................................... 3-203

    3.28.2 Function Description .................................................................................................... 3-203

    3.28.3 Function Block Diagram ............................................................................................... 3-203

    3.28.4 I/O Signals ................................................................................................................... 3-204

    3.28.5 Logic ............................................................................................................................ 3-204

    3.29 Control and Synchrocheck for Manual Closing ..................................... 3-204

    3.29.1 General Application ...................................................................................................... 3-204

    3.29.2 Function Description .................................................................................................... 3-204

    3.29.3 Function Block Diagram ............................................................................................... 3-211

    3.29.4 I/O Signals ................................................................................................................... 3-211

    3.29.5 Settings ........................................................................................................................ 3-213

    3.30 Faulty Phase Selection ............................................................................. 3-214

    3.30.1 General Application ...................................................................................................... 3-214

    3.30.2 Function Description .................................................................................................... 3-215

    3.30.3 Function Block Diagram ............................................................................................... 3-216

    3.30.4 I/O Signals ................................................................................................................... 3-216

    3.31 Fault Location ........................................................................................... 3-217

    3.31.1 Application .................................................................................................................... 3-217

    3.31.2 Function Description .................................................................................................... 3-217

    3.31.3 Function Block Diagram ............................................................................................... 3-220

    3.31.4 I/O Signals ................................................................................................................... 3-220

    List of Figures

    Figure 3.3-1 Logic diagram of CB position supervision......................................................... 3-4

    Figure 3.3-2 Logic diagram of trip&closing circuit supervision ............................................ 3-5

    Figure 3.4-1 Flow chart of protection program ....................................................................... 3-8

    Figure 3.4-2 Logic diagram of fault detector ........................................................................... 3-9

    Figure 3.5-1 Logic diagram of auxiliary element ................................................................... 3-19

  • 3 Operation Theory

    PCS-902 Line Distance Relay 3-h

    Date: 2013-12-25

    Figure 3.6-1 Protected reach of distance protection for each zone .................................... 3-22

    Figure 3.6-2 Operating time of single-phase fault (50Hz, SIR=1) ......................................... 3-23

    Figure 3.6-3 Operating time of single-phase fault (60Hz, SIR=1) ......................................... 3-24

    Figure 3.6-4 Operating time of two-phase fault (50Hz, SIR=1) ............................................. 3-24

    Figure 3.6-5 Operating time of two-phase fault (60Hz, SIR=1) ............................................. 3-25

    Figure 3.6-6 Operating time of three-phase fault (50Hz, SIR=1) .......................................... 3-25

    Figure 3.6-7 Operating time of three-phase fault (60Hz, SIR=1) .......................................... 3-26

    Figure 3.6-8 Operating time of single-phase fault (50Hz, SIR=30) ....................................... 3-26

    Figure 3.6-9 Operating time of single-phase fault (60Hz, SIR=30) ....................................... 3-27

    Figure 3.6-10 Operating time of two-phase fault (50Hz, SIR=30) ......................................... 3-27

    Figure 3.6-11 Operating time of two-phase fault (60Hz, SIR=30) ......................................... 3-28

    Figure 3.6-12 Operating time of three-phase fault (50Hz, SIR=30) ...................................... 3-28

    Figure 3.6-13 Operating time of three-phase fault (60Hz, SIR=30) ...................................... 3-29

    Figure 3.6-14 Operation characteristic for forward fault ...................................................... 3-30

    Figure 3.6-15 Operation characteristic for reverse fault ...................................................... 3-31

    Figure 3.6-16 Logic diagram of DPFC distance protection .................................................. 3-32

    Figure 3.6-17 Distance element with load trapezoid ............................................................. 3-33

    Figure 3.6-18 Phase-to-ground operation characteristic for forward fault ......................... 3-35

    Figure 3.6-19 Phase-to-phase operation characteristic for forward fault ........................... 3-36

    Figure 3.6-20 Operation characteristic for reverse fault ...................................................... 3-38

    Figure 3.6-21 Steady-state characteristic of three-phase short-circuit fault ...................... 3-38

    Figure 3.6-22 Operation characteristic of three-phase close up short-circuit fault ........... 3-39

    Figure 3.6-23 Shift impedance characteristic of zone 1 and zone 2 .................................... 3-40

    Figure 3.6-24 Operation characteristic of reverse Z4 distance protection ......................... 3-41

    Figure 3.6-25 Logic diagram of enabling distance protection (Mho) .................................. 3-43

    Figure 3.6-26 Logic diagram of distance protection (Mho zone 1) ...................................... 3-43

    Figure 3.6-27 Logic diagram of distance protection (Mho zone 2) ...................................... 3-44

    Figure 3.6-28 Logic diagram of distance protection (Mho zone 3) ...................................... 3-45

    Figure 3.6-29 Logic diagram of distance protection (Mho zone 4) ...................................... 3-46

    Figure 3.6-30 Quadrilateral forward distance element characteristics ............................... 3-50

  • 3 Operation Theory

    PCS-902 Line Distance Relay 3-i

    Date: 2013-12-25

    Figure 3.6-31 Quadrilateral reverse distance element characteristic .................................. 3-51

    Figure 3.6-32 Logic diagram of enabling distance protection (Quad) ................................. 3-53

    Figure 3.6-33 Logic diagram of distance protection (Quad zone 1) .................................... 3-53

    Figure 3.6-34 Logic diagram of distance protection (Quad zone 2) .................................... 3-54

    Figure 3.6-35 Logic diagram of distance protection (Quad zone 3) .................................... 3-55

    Figure 3.6-36 Logic diagram of distance protection (Quad zone 4) .................................... 3-56

    Figure 3.6-37 Protected zone of pilot distance protection ................................................... 3-60

    Figure 3.6-38 Pilot reverse weak infeed element .................................................................. 3-61

    Figure 3.6-39 Logic diagram of pilot distance zone (Mho characteristic) ........................... 3-61

    Figure 3.6-40 Logic diagram of pilot distance zone (Quad characteristic) ......................... 3-62

    Figure 3.6-41 Logic diagram of power swing detection ....................................................... 3-64

    Figure 3.6-42 Logic diagram of PSBR .................................................................................... 3-68

    Figure 3.6-43 Logic diagram of enabling distance SOTF protection ................................... 3-71

    Figure 3.6-44 Logic diagram of distance SOTF protection by manual closing signal ....... 3-71

    Figure 3.6-45 Logic diagram of distance SOTF protection by 1-pole or 3-pole AR ........... 3-72

    Figure 3.6-46 Logic diagram of distance SOTF protection by PD condition ...................... 3-73

    Figure 3.7-1 Direct optical link up to 2km with 850nm ......................................................... 3-76

    Figure 3.7-2 Direct optical link up to 40km with 1310nm or up to 100km with 1550nm .... 3-76

    Figure 3.7-3 Connect to a communication network via communication convertor ........... 3-76

    Figure 3.7-4 Connect to a communication network via MUX-64 .......................................... 3-77

    Figure 3.7-5 Connect to a communication network via MUX-2M ......................................... 3-77

    Figure 3.7-6 Schematic diagram of communication channel time ...................................... 3-79

    Figure 3.7-7 Logic diagram of receiving signal n ................................................................. 3-82

    Figure 3.8-1 Enabling/disabling logic of pilot distance protection ...................................... 3-83

    Figure 3.8-2 Logic diagram of receiving signal ..................................................................... 3-83

    Figure 3.8-3 Zone extension ................................................................................................... 3-84

    Figure 3.8-4 Simple schematic of PUTT ................................................................................ 3-85

    Figure 3.8-5 Logic diagram of pilot distance protection (PUTT) .......................................... 3-85

    Figure 3.8-6 Simple schematic of POTT ................................................................................ 3-86

    Figure 3.8-7 Logic diagram of pilot distance protection (POTT) ......................................... 3-86

  • 3 Operation Theory

    PCS-902 Line Distance Relay 3-j

    Date: 2013-12-25

    Figure 3.8-8 Simple schematic of system fault ..................................................................... 3-87

    Figure 3.8-9 Simple schematic of blocking ........................................................................... 3-88

    Figure 3.8-10 Logic diagram of pilot distance protection (Blocking) .................................. 3-88

    Figure 3.8-11 Logic diagram of pilot distance protection (Unblocking) .............................. 3-89

    Figure 3.8-12 Current reversal ................................................................................................ 3-89

    Figure 3.8-13 Logic diagram of current reversal blocking ................................................... 3-90

    Figure 3.8-14 Line fault description ....................................................................................... 3-91

    Figure 3.8-15 Weak infeed logic during pickup ..................................................................... 3-91

    Figure 3.8-16 Weak infeed logic without pickup ................................................................... 3-92

    Figure 3.8-17 Simplified CB Echo logic for POTT ................................................................. 3-92

    Figure 3.9-1 Enabling/disabling logic of pilot directional earth-fault protection ............... 3-96

    Figure 3.9-2 Logic diagram of receiving signal ..................................................................... 3-96

    Figure 3.9-3 Forward/reverse direction of zero-sequence power ........................................ 3-97

    Figure 3.9-4 Simple schematic of DEF (permissive scheme) .............................................. 3-97

    Figure 3.9-5 Logic diagram of DEF (permissive scheme) .................................................... 3-98

    Figure 3.9-6 Simple schematic of blocking ........................................................................... 3-99

    Figure 3.9-7 Logic diagram of DEF (Blocking scheme) ........................................................ 3-99

    Figure 3.9-8 Logic diagram for unblocking ......................................................................... 3-100

    Figure 3.10-1 Line fault description ..................................................................................... 3-103

    Figure 3.10-2 Vector diagram of current and voltage ......................................................... 3-104

    Figure 3.10-3 Vector diagram of zero-sequence power ...................................................... 3-106

    Figure 3.11-1 Logic diagram of phase overcurrent protection .......................................... 3-113

    Figure 3.12-1 Logic diagram of earth fault protection ........................................................ 3-120

    Figure 3.13-1 Logic diagram of overcurrent protection for VT circuit failure ................... 3-127

    Figure 3.14-1 Logic diagram of residual current SOTF protection .................................... 3-129

    Figure 3.15-1 Logic diagram of stage x of overvoltage protection .................................... 3-134

    Figure 3.15-2 Blocking logic of undervoltage protection ................................................... 3-140

    Figure 3.15-3 Logic diagram of stage x of undervoltage protection ................................. 3-140

    Figure 3.16-1 Logic diagram of overfrequency protection (stage 1) ................................. 3-143

    Figure 3.16-2 Logic diagram of overfrequency protection (stage 2) ................................. 3-144

  • 3 Operation Theory

    PCS-902 Line Distance Relay 3-k

    Date: 2013-12-25

    Figure 3.16-3 Logic diagram of overfrequency protection (stage 3) ................................. 3-144

    Figure 3.16-4 Logic diagram of overfrequency protection (stage 4) ................................. 3-144

    Figure 3.16-5 Logic diagram of overfrequency protection (start) ...................................... 3-145

    Figure 3.16-6 Logic diagram of underfrequency protection (stag1) .................................. 3-148

    Figure 3.16-7 Logic diagram of underfrequency protection (stag2) .................................. 3-148

    Figure 3.16-8 Logic diagram of underfrequency protection (stag3) .................................. 3-149

    Figure 3.16-9 Logic diagram of underfrequency protection (stag4) .................................. 3-149

    Figure 3.16-10 Logic diagram of underfrequency protection (start) ................................. 3-150

    Figure 3.17-1 Logic diagram of breaker failure protection ................................................. 3-154

    Figure 3.18-1 Characteristic curve of the thermal overload model ................................... 3-157

    Figure 3.18-2 Logic diagram of thermal overload protection (stage 1) ............................. 3-158

    Figure 3.18-3 Logic diagram of thermal overload protection (stage 2) ............................. 3-158

    Figure 3.19-1 3/2 breakers arrangement .............................................................................. 3-160

    Figure 3.19-2 Logic diagram of stub overcurrent protection ............................................. 3-161

    Figure 3.20-1 Dead zone protection ..................................................................................... 3-163

    Figure 3.21-1 Logic diagram of pole discrepancy protection ............................................ 3-165

    Figure 3.22-1 Logic diagram of broken conductor protection ........................................... 3-167

    Figure 3.23-1 Relationship between reference voltage and synchronism voltage .......... 3-168

    Figure 3.23-2 Line voltage circuit failure supervision logic ............................................... 3-170

    Figure 3.23-3 Bus Voltage Circuit Failure Supervision logic ............................................. 3-170

    Figure 3.23-4 Synchronism check ........................................................................................ 3-173

    Figure 3.23-5 Dead charge check logic ............................................................................... 3-173

    Figure 3.23-6 Synchrocheck logic ........................................................................................ 3-174

    Figure 3.24-1 Logic diagram of AR block ............................................................................ 3-180

    Figure 3.24-2 Logic diagram of AR ready ............................................................................ 3-181

    Figure 3.24-3 Logic diagram of tripping condition output ................................................. 3-182

    Figure 3.24-4 Single-phase tripping initiating AR ............................................................... 3-183

    Figure 3.24-5 Three-phase tripping initiating AR ................................................................ 3-183

    Figure 3.24-6 1-pole AR initiation ......................................................................................... 3-184

    Figure 3.24-7 3-pole AR initiation ......................................................................................... 3-184

  • 3 Operation Theory

    PCS-902 Line Distance Relay 3-l

    Date: 2013-12-25

    Figure 3.24-8 One-shot AR .................................................................................................... 3-185

    Figure 3.24-9 Extra time delay of AR .................................................................................... 3-185

    Figure 3.24-10 Reclosing output logic ........................................