Panel building New power distribution equipment www.legrand.co.uk POWER SUPPLIES, TRANSFORMERS AND HEAVY DUTY TERMINALS / PRODUCT GUIDE

02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

Panel buildingNew power distribution equipment

www.legrand.co.uk

POWER SUPPLIES, TRANSFORMERS ANDHEAVY DUTY TERMINALS / PRODUCT GUIDE

Page 2: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

Switch mode stabi l ised power suppl ies Linear stabi l ised power suppl ies

Compact transformers

Innovativeadditions...established andtrusted ranges

Page 3: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

Fi l tered and non-f i l tered power suppl ies

ContentsSwitch mode stabilised 4

power supplies

Linear stabilised 6power supplies

Filtered and non-filtered 8power supplies

Compact transformers 10

Transformer selector 12

Viking 3 heavy duty 14terminal blocks

Power supplies 16technical data

Legrand has introduced anew selection of powersupplies, transformers

and heavy duty terminalblocks to its acclaimed

portfolio of industrialproducts.

These innovative solutionsincorporate a whole host

of unique features tomake installation easier.

The result... bettersolutions and a wider

choice than ever before.

Control t ransformers

Viking 3 heavy duty terminal blocks

Page 4: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

Switch mode stabilised power supplies

Size matters... especially when space is apremium. That’s why Legrand’s stylish newpower supplies are just a fraction of the sizeof traditional units.

Rapid f ix ing onto rai l 2

Twin output terminalsfor ease of connect ion

Easi ly accessible input terminals :

115 to 230 V±input vol tage

Green output LED

4

Regulate the outputvol tage :12 to 14 V=and24 to 28 V=

Modular switch modeversion also avai lable

Ul tra compact case

Act ive powerfactor correct ion

Wide operat ingtemperature : -10 to +60° C

Page 5: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

switch mode stabilised power supplies single phase

0466 13

0047 93

Pack Cat. Nos. Single phase switch mode

12 V= outputInput Power Current Rating

115-230 V (W) (A)

1 0466 13 60 51 0466 14 120 10

115-230 V 230 V 24 V= output1 0466 22 60 2·51 0466 23 120 51 0466 24 240 101 0466 25 480 20

400 V 24 V= output1 0468 45 60 2·51 0468 48 120 51 0468 51 240 101 0468 54 360 15

Technical information (opposite and p. 16)

Single phase modular

12 V= outputInput Power Current rating Number of

115-230 V (W) (A) 17·5 mm modules

1 0047 92 30 2·5 6

115-230 V 24 V= output1 0047 93 24 1 4

0466 23

0468 48

Switch mode stabilised power supplies for PLCs and other equipmentrequiring a continuous stabilised (or regulated) voltage of 12 V DC or 24 V DCInsulation 4 000 V (input/output)

Include :• twin output terminals for ease of connection (except modular)• integral fuse protection on input• electronic short circuit protection/current limiter on output• green LED output voltage indicator• adjustment of output by potentiometer (except modular)

■ Technical information (additional information p. 16)

Cat. Nos. 0466 13/14/22/23/24 and 25Conform to EN 61204, EN 60950

UL 508CAN/CSA C22.2 N° 14-M91EN 55022 Class BEN 61000-4-2,3,4,5,6,8,11 EN 61000-3-2,3

Cat. Nos. 0468 45/48/51 and 54Conform to EN 61204, EN 60950 (DBT)

EN 61000-4-2,3,4,5,6

Cat. Nos. 0047 92 and 93Conform to EN 61204, EN 60950 (DBT)

EN 55022 Class BEN 61000-4-2,3,4,5,6,8,11 and EN 61000-3-2,3

Cat. Nos. 0466 13/14/22/23/24/25

Cat. Nos. 0468 45/48/51/54

Cat. Nos. 0047 92/93

switch mode stabilised power supplies single phase

■ Dimensions

A

®

DC OK

100-240VAC 2,0A

2,5A24VDC

N L

50-60Hz

+ +

0466 41

B

C

A

DC OK

100-240VAC

ADJUST36-20V

3,5A

10A24VDC

NL

50-60Hz

+ +

++

0466 24

A

0466 44

DC OK

100-240VAC

ADJUST24-20V

4,7A

20A24VDC

NL

50-60Hz

++

A

B

D

C

5

D

A

D

A

Cat. Nos.A (mm) B (mm) C (mm) D (mm)

Ø (mm)Weight

Width Depth Height Fixing ctrs (Kg)

0047 92 105 (6 mod) 66 76 DIN – 0·32

0047 93 70 (4 mod) 66 76 DIN – 0·32

0466 13 55·5 100 125·2 DIN – 0·63

0466 14 65·5 100 125·2 DIN – 0·80

0466 22 55·5 100 125·2 DIN – 0·62

0466 23 65·5 100 125·2 DIN – 0·81

0466 24 125·5 100 125·2 DIN – 1·23

0466 25 227·5 100 125·2 DIN – 2·20

0468 45 75 200 165 150 6·5 0·90

0468 48 75 200 165 150 6·5 0·90

0468 51 150 200 165 150 x 75 6·5 1·90

0468 54 225 200 165 150 x 150 6·5 2·90

5

45

4460

C

BA

Page 6: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

Linear stabilised power supplies

With a compact new design, Legrand’s linearstabilised power supplies have changed fromblue to grey, offering space saving solutionsthat now match other equipment in the range.

6

Rapid f ix ing on to rai l 2(Cat . Nos. 0470 83/86)

Regulated output : ± 10 % input resul ts in

± 1 % output

Twin output terminalsfor ease of connect ion

Wide operat ingtemperature : -10 to +60° C

Easi ly accessible input terminals : 230 to 400 V±input vol tage

Electronicprotect ion againstshort c ircui t andoverload

Green output LED

Page 7: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

linear stabilised power supplies single phase

Technical information (opposite and p. 16)

Linear stabilised power supplies for PLCs and other equipment requiringa continuous stabilised (or regulated) voltage of 12 V DC or 24 V DCRegulated output voltage : ±10 % input = ±1 % output

Include :• safety transformer with voltage control• twin output terminals for ease of connection• electronic short circuit protection/current limit on output• green LED output voltage indicator• capacitorSupplied with a connection link for quick connection between - and T

■ Dimensions

linear stabilised power supplies single phase

Cat. Nos.A (mm) B (mm) C (mm) F x G (mm)

Ø (mm)Weight

Width Depth Height Fixing ctrs (Kg)

0470 83 68 98 88 DIN – 1·00

0470 84 105 135 115 104 x (2 x 45) 4·6

0470 86 68 98 88 DIN – 1·00

0470 87 105 135 115 104 x (2 x 45) 4·6 2·40

0470 88 105 135 115 104 x (2 x 45) 4·6

0470 86 0470 88

Pack Cat. Nos. Single phase

12 V= outputTerminal capacity (mm2)

Input Power Current rating Flexible cable230-400 V (W) (A) Input Output

1 0470 83 12 1 6 61 0470 84 30 2·5 6 6

24 V= output1 0470 86 12 0·5 6 61 0470 87 24 1 6 61 0470 88 60 2·5 6 6

7

C

FG

B

A

■ Technical information (additional information p. 16)

Cat. Nos. 0470 83/84/86/87 and 88Conform to IEC/EN 61558-2-6, IEC/EN 61204

UL 60950CAN/CSA C22.22 N° 60950.00

Page 8: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

Filtered and non-filteredpower supplies

Legrand’s new filtered and non-filtered powersupplies offer the same space saving benefitsas the other ranges... and just like them, theyare quick to install and are laser engraved forclear and permanent identification.

8

Rapid f ix ing on to rai l 2(Up to 120 W)

Twin output terminalsfor ease ofconnect ion

Primary vol tageadjustment : ± 15 V±

Fuse protect ion onoutput

Green output LED

Modular f i l tered versionalso avai lable

Page 9: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

filtered and non-filtered power supplies single phase

Technical information (opposite and p. 17-18)

Filtered power supplies for PLCs and other equipment requiring a voltageof 12 V DC or 24 V DCNon-filtered power supplies for installations requiring a 24 V DC voltage Include :• twin output terminals for ease of connection• safety transformer with electrostatic screen except Cat. Nos. marked(1)

• fuse protection on output (except modular)• green LED output voltage indicator• capacitor in filtered range• PTC thermal protection on output (modular only)• class II when installed with approved protection (modular only)Supplied with a connection link for quick connection between - and Tup to 15 A (except modular)

■ Dimensions

filtered and non-filtered power supplies single phase

Cat. Nos.A (mm) B (mm) C (mm) F x G (mm)

Ø (mm)Weight

Width Depth Height Fixing ctrs (Kg)

0470 01 68 98 88 DIN – 1·00

0470 02 93 121 105 45 x 94 4·6 2·45

0470 03 105 135 115 45 x 104 4·6 3·60

0470 04 126 186 175 75 x 150 5·5 6·35

0470 20 68 98 88 DIN – 1·00

0470 21 68 98 88 DIN – 1·00

0470 22 93 121 105 45 x 94 4·6 2·45

0470 23 105 135 115 45 x 104 4·6 3·60

0470 24 126 186 175 75 x 150 5·5 6·35

0470 25 126 206 175 75 x 150 5·5 7·60

0470 51 68 98 88 DIN – 1·00

0470 52 93 106 105 45 x 94 4·6 1·70

0470 53 105 135 115 45 x 104 4·6 3·40

0470 54 126 186 175 75 x 150 5·5 6·10

0470 55 126 206 175 75 x 150 5·5 7·30

0047 95 89 66 95 DIN – 1·00

0047 97 89 66 95 DIN – 1·00

0047 98 89 66 95 DIN – 1·00

9

0470 53 0470 24 0047 98

Single phase non-filtered

24 V= output230-400 V± ± 15 V (input)24 V= (output)

Terminal capacity (mm2)Input Power Current rating Flexible cable

230-400 V (W) (A) Input Output

1 0470 51(1) 24 1 6 61 0470 52(1) 60 2·5 6 61 0470 53 120 5 6 61 0470 54 240 10 6 61 0470 55 360 15 6 6

Pack Cat. Nos. Single phase filtered

12 V= output230-400 V ± 15 V± (input) / 12 V= (output)

Terminal capacity (mm2)Input Power Current rating Flexible cable

230-400 V (W) (A) Input Output

1 0470 01(1) 12 1 6 61 0470 02(1) 30 2·5 6 61 0470 03 60 5 6 61 0470 04 120 10 6 6

24 V= output230-400 V ± 15 V± (input) / 24 V= (output)

Terminal capacity (mm2)Input Power Current rating Flexible cable

230-400 V (W) (A) Input Output

1 0470 20(1) 12 0·5 6 61 0470 21(1) 24 1 6 61 0470 22(1) 60 2·5 6 61 0470 23 120 5 6 61 0470 24 240 10 6 61 0470 25 360 15 6 6

Single phase filtered modular

12 V= output230 ± 15 V± (input) / 12 V= (output)

Terminal capacity (mm2)Input Power Current rating Flexible cable230 V (W) (A) Input Output

1 0047 95 15 1·25 6 624 V= output230 ± 15 V± (input) / 24 V= (output)

Terminal capacity (mm2)Input Power Current rating Flexible cable230 V (W) (A) Input Output

1 0047 97(1) 12 0·5 6 61 0047 98 21·5 0·9 6 6

F

B

A

C

G

B

G

C

F

A

F

B

A

CG

B

G

C

F

A

Single phase filtered

Single phase non-filtered

Single phase linear modular

45

4460

C

BA

■ Technical information (additional information p. 17-18)

Cat. Nos. 0470 01/02/03/04/20/21/22/23/24/25/51/52/53/54 and 55Conform to IEC/EN 61558-2-6

UL 60950 (up to 10 A)CAN/CSA C22.22 N° 60 950.00

Filtered products are compatible with EN 61131-2, EN 60204 andEN 60439-1 apparatus

Cat. Nos. 0047 95/97 and 98Conform to IEC/EN 61558-2-6Products are compatible with EN 61131-2, EN 60204 and EN 60439-1 apparatus

(1) Without screen, separation and attenuation by dividing flange between windings

Page 10: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

Compacttransformers

Legrand’s compact transformers are theOEM’s choice for reliability... and now thatchoice just got even better! To meet the needsof the UK market, the range has expandedand now includes versions with UK specificprimary and secondary voltages.

10

Can be f i t ted to rai l 2with f ix ing cl ips (up to 150 VA)

Dual vol tage pr imary : 240 / 415 V±

Laser engravedinformat ion vis ible ata glance

Visible terminals providerel iable connect ions

Tradi t ional s ty le : 300 VA and above

Page 11: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

compact transformers open type single phase

Technical information (opposite)

Isolating and safety isolating <50 V transformersDesigned to meet the needs of users with specific VA ratings such asoriginal equipment manufacturersThe ‘Compact’ range up to 250 VA boasts an elegant design that willenhance your panel The terminals are designed to provide easy and quick connectionsTransformers up to 150 VA can be clipped to 4 rail using accessory ordirectly fixed using screws through the easily accessible fixing pointsRecommended protection :• for 50 VA : Type T fuses (5 x 20) time delay fuse to IEC 60127• for >100 VA use MCB Type C

■ Dimensions

compact transformersopen type single phase

Cat. Nos.A (mm) B (mm) C (mm) Fixings WeightWidth Height Length F (mm) G (mm) Ø (mm) (Kg) Fig.

6425 21 84 70 98 40 86 4·5 0·9 1

6425 22 84 86 98 40 86 4·5 1·6 1

6425 23 84 104 98 40 86 4·5 2·4 1

6425 24 96 115 110 40 98 4·5 3·4 1

6425 25 96 115 110 40 98 4·5 3·4 1

6425 26 126 126 107 90 76 6·5 4·6 2

6425 27 126 126 126 90 94 6·5 6·0 2

6425 28 126 126 141 90 105 6·5 8·0 2

6425 29 220 222 150 122 120 7·0 12·4 3

6425 30 220 222 170 122 140 7·0 14·7 3

6426 21 84 70 98 40 86 4·5 0·9 1

6426 22 84 86 98 40 86 4·5 1·6 1

6426 23 84 104 98 40 86 4·5 2·4 1

6426 24 96 115 110 40 98 4·5 3·4 1

6426 25 96 115 110 40 98 4·5 3·4 1

6426 26 108 110 105 84 90 6·5 4·6 2

6426 27 126 126 108 90 94 6·5 6·0 2

6426 28 126 126 123 90 105 6·5 7.8 2

6426 29 150 144 142 122 120 7·0 11·4 2

6426 30 150 144 171 122 140 7·0 14·3 2

11

Pack Cat. Nos. Single phase

Primary : 240/415 VSecondary : 12-0-12 V

Power in VA Admissibleaccording to instantaneous Efficiency with

IEC/EN power at cos ϕ 0·5 cos ϕ = 1 (%) cos ϕ = 0·45 (%)

1 6425 21 50 VA 67 VA 0·78 0·611 6425 22 100 VA 134 VA 0·83 0·681 6425 23 150 VA 221 VA 0·83 0·691 6425 24 200 VA 284 VA 0·83 0·691 6425 25 250 VA 390 VA 0·83 0·691 6425 26 300 VA 615 VA 0·83 0·691 6425 27 450 VA 1 237 VA 0·87 0·761 6425 28 500 VA 1 654 VA 0·87 0·751 6425 29 750 VA 2 566 VA 0·83 0·681 6425 30 1 000 VA 4 010 VA 0·93 0·85

Primary : 240/415 VSecondary : 55-0-55 V

Power in VA Admissibleaccording to instantaneous Efficiency with

IEC/EN power at cos ϕ 0·5 cos ϕ = 1 (%) cos ϕ = 0·45 (%)

1 6426 21 50 VA 64 VA 0·80 0·651 6426 22 100 VA 139 VA 0·83 0·691 6426 23 150 VA 237 VA 0·83 0·691 6426 24 200 VA 347 VA 0·84 0·701 6426 25 240 VA 319 VA 0·84 0·701 6426 26 300 VA 800 VA 0·84 0·701 6426 27 450 VA 1 320 VA 0·88 0·761 6426 28 500 VA 1 610 VA 0·88 0·761 6426 29 750 VA 2 510 VA 0·83 0·681 6426 30 1 000 VA 3 330 VA 0·93 0·85

6425 21 6425 26

F

A

G

C

Slotted fixing hole

B

A

F G

C

B

Fig. 1 - 50 to 250 VA

Primary : 240 - 415 VSecondary : 12 - 0 - 12 VSecondary : 0 - 12 - 24 V

Cat. Nos. 6425 21 to 6425 30

Primary : 240 - 415 VSecondary : 110 V

Cat. Nos. 6426 21 to 6426 30

FA

GC

B

Fig. 3 - 750 to 1 000 VA (24 V)

240 - 415 V

P max

P max

12 12

0 12

00 2412

240 - 415 V

Centretap

110 V0 110

For full range of transformersrefer to the currentIndustrial catalogue

■ Technical informationConform to IEC/EN 61558-2-4 for 55 V and 110 V

IEC/EN 61558-2-6 for 12 V and 24 V secondary

IP 2x or xxB up to 250 VA - IK 04Ambient temperature : ≤ 35 °C without de-rating

Single phase 50-60 Hz - class I Insulation voltage : Primary/Secondary 3 550 V

Primary/Earth 2 400 V Secondary/Earth (12 - 24 V) = 250 V > 24 V = 1500 V

Max. ambient operating temperature : 35 °CProtected against accidental contact with live parts up to 250 VA

Fig. 2 - 300 to 500 VA (24 V)1 000 VA (110 V)

Page 12: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

compact transformers open type single phase

12

Primary 240 - 415 V 230 - 400 V 230 - 400 V 240 - 415 V 230 - 400 V 230 - 400 V 230 - 400 V115 V PMS or

Secondary 12 V - 0 - 12 V 24 V or 2 x 12 V 48 V or 2 x 24 V 55 V - 0 - 55 V 2 x 57·5 V 115 V/230 V 230 VEarth centre tap

Transformer 6425 00 6425 40 6425 60 6425 80 6426 0040 VA Fuse T 1·6 A L T 0·8 A L T 0·4 A L T 0·2 A L T 0·2 A L

T 3·15 A L (1) T 1·6 A L (2) T 0·4 A L (3)

Transformer 6425 21 6426 2150 VA Fuse T 2 A L T 0·4 A L

Transformer 6425 02 6425 42 6425 62 6425 82 6426 0263 VA Fuse T 2·5 A L T 1·25 A L T 0·5m A L T 0·25m A L T 0·25 A L

T 5 A L (1) T 2·5 A L (2) T 0·5 A L (3)

Transformer 6425 22 6425 03 6425 43 6426 22 6425 63 6425 83 6426 03100 VA Fuse T 4 A L T 4 A E T 2 A L T 0·8 A L T 0·8 A L T 0·4 A L T 0·4 A L

T 8 A E(1) T 4 A E(2) T 0·8 A L (3)

Transformer 6425 23 6426 23150 VA Fuse T 6 A L T 1·25 A L

Transformer 6425 04 6425 44 6425 64 6425 84 6426 04160 VA Fuse/MCB T 6·3 A E T 3·15 A E T 1·25 A L T 0·63 A L T 0·63 A L

13 A(1) T 6·3 A E(2) T 1·25 A L (3)

Transformer 6425 24 6426 24200 VA Fuse T 8 A L T 2 A L

Transformer 6425 05 6425 45 6425 65 6425 85 6426 05220 VA Fuse/MCB T 10 A E T 5 A E T 2 A L T 1 A L T 1 A L

20 A(1) T 10 A E(2) T 2 A L (3)

Transformer 6426 25240 VA Fuse T 2 A L

Transformer 6425 25250 VA MCB 10 A C

Transformer 6425 26 6426 26300 VA MCB 13 A C T 2·5 A L

Transformer 6425 06 6425 46 6425 66 6425 86 6426 06310 VA MCB 13 A 6 A 3 A C T 1·25 A L T 1·25 A L

25 A(1) 13 A(2) T 2·5 A E(3)

Transformer 6425 27 6425 07 6425 47 6426 27 6425 67 6425 87 6426 07450 VA MCB 20 A C 20 A 10 A 4 A C 4 A C 2 A 2 A

40 A (1) 20 A (2) 4 A (3)

Transformer 6425 28 6426 28500 VA MCB 20 A C 6 A C

Transformer 6425 08 6425 48 6425 68 6425 88 6426 08630 VA MCB 25 A 13 A 6 A C 2 A 3 A

50 A (1) 25 A(2) 6 A (3)

Transformer 6425 29 6426 29750 VA MCB 32 A C 8 A C

Transformer 6425 09 6425 49 6425 69 6425 89 6426 09800 VA MCB 32 A 16 A 8 A C 4 A 4 A

63 A (1) 32 A(2) 8 A (3)

Transformer 6425 30 6425 10 6425 50 6426 30 6425 70 6425 90 6426 101 000 VA MCB 40 A C 40 A 20 A 10 A C 8 A 4 A 4 A

80 A (1) 40 A(2) 8 A (3)

Transformer 6425 11 6425 51 6425 71 6425 91 6426 111 250 VA MCB 50 A 25 A 10 A 6 A 6 A

100 A (1) 50 A (2) 10 A (3)

Transformer 6425 12 6425 52 6425 72 6425 92 6426 121 600 VA MCB 63 A 32 A 13 A C 8 A 8 A

125 A (1) 63 A (2) 16 A (3)

Transformer 6425 13 6425 53 6425 73 6425 93 6426 132 000 VA MCB 80 A 40 A 16 A 8 A 8 A

160 A (1) 80 A (2) 16 A (3)

Transformer 6425 14 6425 54 6425 74 6425 94 6426 142 500 VA MCB 100 A 50 A 20 A 10 A 10 A

200 A (1) 100 A (2) 20 A (3)

T type fuse is time delay (5 x 20 mm)L type fuse is low breaking capacity : 35 AH type fuse is high breaking capacity : 1 500 AE type fuse is enhanced breaking capacity

Type gG fuse : 10 x 38 up to 25 A, 14 x 51 up to 50 A, 22 x 58 over 50 AType C MCB : single pole up to 63 A and double pole 80-100 A

Fuse rating :(1) If using 1 x 12 V(2) If using 1 x 24 V(3) If using 1 x 115 V

40 VA - 250 VA 300 VA - 1 250 VA (subject to voltage)NEW NEW

Page 13: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

13

control transformers open type single phase

Primary 230 - 400 V 230 - 400 V 230 - 400 V

Secondary 24 V 115 V 230 V

Transformer 6421 01 6421 61 6422 0140 VA Fuse *T 200 mA L *T 400 mA L *T 200 mA L

Transformer 6421 02 6421 62 6422 0263 VA Fuse *T 315 mA L *T 630 mA L *T 315 mA L

Transformer 6421 03 6421 63 6422 03100 VA MCB 4 A C 1 A C 0·5 A C

Transformer 6421 04 6421 64 6422 04160 VA MCB 8 A C 2 A C 1 A C

Transformer 6421 05 6421 65 6422 05250 VA MCB 10 A C 2 A C 1 A C

Transformer 6421 06 6421 66 6422 06400 VA MCB 16 A C 4 A C 2 A C

Transformer 6421 08 6421 68 6422 08630 VA MCB 25 A C 6 A C 3 A C

Transformer 6421 10 6421 70 6422 101 000 VA MCB 40 A C 8 A C 4 A C

Transformer 6421 11 6421 71 6422 111 600 VA MCB 63 A C 13 A C 8 A C

Transformer 6421 12 6421 72 6422 122 500 VA MCB 100 A C 20 A C 10 A C

Transformer 6421 73 6422 134 000 VA MCB 32 A C 16 A C

160 VA - 1 000 VA40 VA - 100 VA

* Supplied with transformerT type fuse is time delay (5 x 20 mm) (replacement fuse must be time delay type)L type fuse is low breaking capacity : 35 A

H type fuse is high breaking capacity : 1 500 AType gG fuse : 10 x 38 up to 25 A, 14 x 51 up to 50 A, 22 x 58 over 50 AType C MCB : single pole up to 63 A, double pole 80-100 A

Legrand is a leading European manufacturer of high quality transformers and power supplies,meeting ISO 9001.Our transformers conform to IEC/EN 61558 and offer advanced insulation. In addition to the standard range of control and compact transformers, Legrand also offers custom-made solutions to meet your exact requirements... all manufactured to the same high quality.

Contact our technical department for moredetails or to receive a specific quotation.

■ Contact our technical department

TRANSFORMERS TO MEET YOUR NEEDS…>

■ Enclosed transformersup to 250 kVA

■ Single and three phaseauto-transformers

■ 24 V power supply forthe automobile industry

Page 14: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

Viking 3 heavy duty terminal blocksDeveloped in direct response to marketneeds, this unique new range accepts bothcopper and aluminium cables... and with avariety of simple, flexible and easy to readmarking systems, Viking 3 is now thecomplete package that guarantees excellenceevery time.

14

Cable clamp / cable clamp Stud / s tud Cable clamp / s tud Stud / cable clamp

Terminals can be jo inedusing threaded rods

Accepts CAB 3 andDupl ix markers

Screw orrai l 2f ix ing

Inlet for testprobe

Covers can bebroken to length

Provision forshunt l ink

Page 15: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

Viking 3heavy duty terminal blocks

Technical information (opposite)

■ Dimensions

Viking 3heavy duty terminal blocks

15

■ Technical informationConform to IEC/EN 60947-7-1, UL 1059 and 486E - CSA 22-2IK 04Fire resistance according to IEC 60695-2-1 : 960 °C 30 seconds

750 °C 5 seconds for coverV2 according to UL 94Insulation voltage : Ui 1000 VImpulse voltage (surge) Uimp : 8 kV

Cable equivalents

Pack Cat. Nos. Viking 3 heavy duty terminal blocks

Fix to 15 mm deep symmetrical DIN rail EN 607154and/or screw fixInsulation material :• Base - polyamide –30 to +100 °C• Break to length cover - polypropylene –25 to +100 °CProvision for shunt (Cat. Nos. 0394 46/47) to jointerminals togetherProvision for testing with 4 mm dia. plugable holesAccept CAB 3 and Duplix markers

Cable clamp/Cable clamp

Contractor Panel builderNominal cable Nominal cable Widthcapacity (mm2) capacity (mm2) (mm)

5 0390 10 Cu 35 - 120 Cu 35 - 70 (95)(1) 42Al 35 - 120

5 0390 11 Cu 70 - 300 Cu 70 - 120 (150)(1) 55Al 70 - 300

Stud/Stud

Contractor Panel builderNom. cable Nom. cable

capacity Flat bar Stud Ø capacity Flat bar Stud Ø Width(mm2) (mm) (mm) (mm2) (mm) (mm) (mm)

5 0390 13 95 28 M 8 95 28 M 8 365 0390 14 150 34 M 10 150 34 M 10 425 0390 15 300 46 M 12 300 46 M 12 55

Stud/Cable clamp

Contractor Panel builderNom. cable

capacity Flat bar Stud Ø Nominal cable Width(mm2) (mm) (mm) capacity (mm) (mm)

5 0390 17 150 34 M 10 Cu 35 - 70 (95)(1) 425 0390 18 300 46 M 12 Cu 70 - 120 (150)(1) 55

Cable clamp/Stud

Contractor Panel builderNominal Nom. cable

cable capacity capacity Flat bar Stud Ø Width(mm2) (mm) (mm) (mm2) (mm)

5 0390 20 Cu 35 - 120 70 34 M 10 42Al 35 - 120

5 0390 21 Cu 70 - 300 150 46 M 12 55Al 70 - 300

Accessories

Shunt : enables one terminal to be connected to another Supplied with fixing screws and washers

5 0394 46 For 36 and 42 mm pitch terminals5 0394 47 For 55 mm pitch terminals

Terminals may be joined into blocks using threadedtie rods (not supplied) for stability

0390 180390 21

with CAB 3 and Duplix markers

mm2 35 70 95 120 150 185 300

AWG 2 2/0 4/0 250 300 350 600

Cat. Nos.A max. A min. B C D E F G H(mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm)

0390 13 227 155 36 82 73 88 176 185 191

0390 10/14/17/20 296 200 42 83·5 74·5 89·5 212 221 227

0390 11/15/18/21 337 216 55 107·3 98·5 113·5 257 266 272

Cat. Nos. A

0390 17 M 10

0390 18 M 12

Cat. Nos. A

0390 10 M 6

0390 11 M 8

Cat. Nos. A

0390 13 M 8

0390 14 M 10

0390 15 M 12

Cat. Nos. A B

0390 20 M 6 M 10

0390 21 M 8 M 12

B

A min.A max.

E C

HGF

D

A

AA B

A A

AA

(1) Stranded

Page 16: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

switch mode and linear stabilised power suppliesopen type single phase

■ Technical informationFrequency range : 47 Hz to 63 HzInsulation voltage : Input/Output 4 000 V, Input/Earth 3 500 V

Output/Earth 500 VHumidity tolerance : 20 - 90 %Cooling by natural convectionElectronic protection on output against over voltage (105 to 150 % In)and short circuitsIntegral fuse protection on inputProtection class : I, Over voltage category : II, Pollution degree : 2Output voltage variation/supply voltage variation : ±0·5 %Output voltage variation/power variation : ±1 % (±0·5 % for Lexic)MTBF >100000h (Mean time before failure)Fix to symmetrical rail 4 7·5 mm or 15 mm depth EN 50022 (7·5 mmonly for Cat. Nos. 0468 45/48)Power supplies can be connected in parallel, except modular and Cat.Nos. 0468 45/48

16

■ Switch mode Cat. Nos. 0466 13/14/22/23/24 and 25Conform to EN 61204, EN 60950

UL 508CAN/CSA C22.2 N° 14-M91EN 55022 (Class B), EN 61000-4-2,3,4,5,6,8,11EN 61000-3-2,3 and ENV 50204

Input voltage :115/230 V± single phase (Cat. Nos. 0466 13/14/22/23 and 24)230 V± single phase (Cat. No. 0466 25)Output voltage ±0·5 % : 12 V= (Cat. Nos. 0466 13 and 14)

24 V= (Cat. Nos. 0466 22/23/24 and 25)Output voltage adjustment : 12 to 14 V=, 24 to 28 V=

■ Switch mode Cat. Nos. 0468 45/48/51 and 54Conform to EN 61204, EN 60950 (DBT)

EN 61000-4-2,3,4,5,6 and ENV 55011Input voltage : 400 V± single phaseOutput voltage ±0·5 % : 24 V=

■ Switch mode Cat. Nos. 0047 92 and 93 (modular)Conform to EN 61204, EN 60950 (DBT) and EN 55022 (Class B)

EN 61000-4-2,3,4,5,6,8,11, EN 61000-3-2,3 and ENV 50204Input voltage : 115/230 V± single phaseOutput voltage ±0·5 % : 12 V= (Cat. No. 0047 92), 24 V= (Cat. No. 0047 93)

Output InputConstant

Circuit protectionMax. working

Cat. Max. Max. Max. Power Power up running Working temp. Derating Temp. Over Ripple temp.Nos. Voltage Current Voltage absorbed inrush output absorbed at Efficiency time delay time without factor protection voltage factor Fuse MCB without

rating current current current max. temp. (s) (230 V) derating limiter cut off peak to peak derating(V) (A) (V) (A) (A) (A) (W) (%) 230 V/115 V (ms) (°C) W/°C (°C) (V) (mVpp) (A) (A) - type (°C)

0047 92 12 2·5 109-264 0·3/0·55 11 2·5 30 75 10/3·7 115 –10/+50 – – – 20 1A aM 2A/C 50

0047 93 24 1 109-264 0·25/0·45 13 1 24 73 2·6/1 124 –110/+50 – – – 80 2A aM 6A/C 50

0466 13 12 5 85-264 1·2/2 60 6·3 75 76 1/1·8 50 –110/+45 1·6 85+/–5 15-16·5 100 4A aM 6A/C 60

0466 14 12 10 88-132/176-264 1·7/2·8 60 10 120 80 0·5 30 –110/+45 3·2 85+/–5 15-16·5 80 4A aM 6A/C 60

0466 22 24 2·5 85-264 1·2/2 60 3·2 75 80 1/1·8 50 –110/+50 2 85+/–5 29-34 150 4A aM 6A/C 60

0466 23 24 5 88-132/176-264 1·7/2·8 60 5 120 84 0·5 30 –110/+45 3·2 90+/–5 29-33 80 4A aM 6A/C 60

0466 24 24 10 85-264 1·8/3·5 50 10 240 84 0·8 20 –110/+55 6·4 100+/–5 30-36 80 4A aM 6A/C 70

0466 25 24 20 180-264 6/- 50 20 480 89 0·8 16 –110/+50 9·6 95+/–5 30-36 120 8A aM 10A/C 70

0468 45 24 2·5 360-424 0·34 8 2·5 80 75 – 15 –110/+50 – – – 45 1A aM 10A/C 50

0468 48 24 5 360-424 0·64 5 5 147 82 – 20 –110/+50 – – – 160 1A aM 10A/C 50

0468 51 24 10 360-424 1·27 18 10 284 86 – 40 –110/+50 – – – 400 2A aM 6A/C 50

0468 54 24 15 360-424 1·82 10 15 424 86 – 40 –110/+50 – – – 1 000 4A aM 6A/C 50

Single phase Input 230 V Input 400 V

P U Protection 12 V 24 V 24 V

1 APower supply 0047 93

MCB 0069 16 (6 A)

2·5 APower supply 0047 92(1) 0466 22 0468 45

MCB 0069 13 (2 A) 0069 16 (6 A) 0069 18 (10 A)

5 APower supply 0466 13 0466 23 0468 48

MCB 0069 16 (6 A) 0069 16 (6 A) 0069 18 (10 A)

10 APower supply 0466 14 0466 24 0468 51

MCB 0069 16 (6 A) 0069 16 (6 A) 0069 16 (6 A)

15 APower supply 0468 54

MCB 0069 16 (6 A)

20 APower supply 0466 25

MCB 0069 18 (10 A)

■ Circuit protection (double pole MCB)

■ Electrical characteristics

■ Technical informationInsulation voltage : Input/Output 4 510 V

Input/Earth 2 260 VOutput/Earth 500 V

60 °C max. ambient temperature without deratingRipple factor : 30 mV eff (0·11% at 24 V)Cooling by natural convectionElectronic protection against over voltage and short circuits providedAll can be fixed to symmetrical rail 47·5 mm or 15 mm depth EN 50022Screw fix or clip on to DIN rail Cat. Nos. 0047 84, 87 and 88

■ Linear stabilised Cat. Nos. 0470 83/84/86/87 and 88Conform to IEC/EN 61558-2-6, IEC/EN 61204

UL 60950CAN/CSA C22.22 N° 60950.00

Input voltage : 230/400 V±Output voltage : 12 V= or 24 V=±10 % input voltage variation will result in ±1 % output voltage variation

■ Electrical characteristics

(1) Modular power supply

Single phase Input 230/400 V

U 12 V 24 V

PProtection

Internal External Internal External

0·5 APower supply 0470 86

MCB/Fuse (1) 0069 12 (1 A)

1 APower supply 0470 83 0470 87

MCB/Fuse (1) 0069 12 (1 A) (1) 0069 12 (1 A)

2·5 APower supply 0470 84 0470 88

MCB/Fuse (1) 0069 14 (3 A) (1) 0069 14 (3 A)

■ Circuit protection (double pole MCB)

(1) Electronic protection provided

Max. Total loss Max.Cat. Voltage Current Weight absorbed at nominal absorbedNos. current load 100% power

(V) (A) (Kg) (A) (W) (W)

0470 83 12 1 1 0·15 5·49 30·7

0470 84 12 2·5 2·45 0·40 8·52 87·1

0470 86 24 0·5 1 0·16 5·51 32·0

0470 87 24 1 2·4 0·24 4·40 55·6

0470 88 24 2·5 2·45 0·62 8·76 146·2

Page 17: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

17

filtered power suppliesopen type single phase

■ Circuit protection (double pole MCB)■ Cat. Nos. 0470 01/02/03/04/20/21/22/23/24 and 25Conform to IEC/EN 61558-2-6

UL 60950 (up to 10 A)CAN/CSA C22.22 N° 60 950.00

Products are compatible with EN 61131-2, EN 60204 and EN 60439-1 apparatus

Input voltage : 230/400 V± ±15 V single phase 50/60 Hz - Class IOutput voltage : 12 V= or 24 V=Insulation voltage : Input/Output 4 510 V

Input/Earth 2 260 VOutput/Earth 500 V

Max. ambient temperature without derating : 60 °CRipple factor : <3 % filteredCooling by natural convectionIntegral fuse protection on outputAll except Cat. Nos. 0470 04/24 and 25 can be fixed to symmetrical rail4 7·5 mm or 15 mm depth EN 50022Screw fix only Cat. Nos. 0470 04/24 and 25Screw fix or clip on to DIN rail Cat. Nos. 0470 02/03/04,22 and 23Supplied with a connection link for quick connection between terminalsand earth up to 15 A

■ Cat. Nos. 0047 95/97 and 98Conform to IEC/EN 61558-2-6Products are compatible with EN 61131-2, EN 60204 and EN 60439-1 apparatus

Input voltage : 230 V± ±15 V single phase 50/60 HzOutput voltage : 12 V= or 24 V=Ripple factor : <5 %PTC thermal protection on outputInsulation : Class II after enclosing behind insulated modular protectionFix to symmetrical rail 4 7·5 mm or 15 mm depth EN 50022 (5 x 17·5 mm modules)

(1) T type fuse is a time delay fuse (5 x 20 mm)(2) Filtered modular power supply(3) Type gG fuse 10 x 38 mm

Single phase Input 230/400 V ±15V

U 12 V 24 V

PProtection

Internal External Internal External

Power supply 0470 20

MCB/Fuse T 0·5 A L(1) 0069 12 (1 A)0·5 A

Power supply 0047 97(2)

MCB/Fuse CTP 0069 12 (1 A)

0·9 APower supply 0047 98(2)

MCB/Fuse CTP 0069 12 (1 A)

1 APower supply 0470 01 0470 21

MCB/Fuse T 1 A L(1) 0069 12 (1 A) T 1 A L(1) 0069 12 (1 A)

1·25 APower supply 0047 95(2)

MCB/Fuse CTP 0069 13 (2 A)

2·5 APower supply 0470 02 0470 22

MCB/Fuse T 2·5 A L(1) 0069 14 (3 A) T 2·5 A L(1) 0069 14 (3 A)

5 APower supply 0470 03 0470 23

MCB/Fuse T 5 A L(1) 0069 16 (6 A) T 5 A L(1) 0069 16 (16 A)

10 APower supply 0470 04 0470 24

MCB/Fuse T 10 A L(1) 0069 18 (10 A) T 10 A L(1) 0069 18 (10 A)

15 APower supply 0470 25

MCB/Fuse 0133 16(3) 0069 20 (16 A)

■ Operating diagramOperating current up to 15 A

■ Electrical characteristicsFiltered

Filtered modular

400 V

230 V

-15 V

0

+15 V

++

Input Operating voltage Total lossCat. Voltage Current Weight under load – No-load Underload With 100 mA load With nominal No-load at nominal VoltageNos. rating 230 V load input voltage load input voltage loss load 100 % drop

(V) (A) (Kg) (A) (V) (V) +10% –15% (W) (W) (%)

0047 95 12 1·3 1 0·15 – 15·1 11·8 16·3 10·4 3·4 8·7 28·5

0047 97 24 0·5 1 0·13 – 28·9 23·6 30·6 20·7 3·4 7·1 22·3

0047 98 24 0·9 1 0·17 – 29·9 22·8 32·0 20·3 3·4 10·4 31·0

Input Input Operating voltage Total loss Cat. Voltage Current Weight under load under load No-load Underload With 100 mA load With nominal No-load at nominal VoltageNos. rating 230 V 400 V and input voltage load input voltage loss load 100 % drop

(V) (A) (Kg) (A) (A) (V) (V) +10% –15% (W) (W) (%)

Output 12 V

0470 01 12 1 1 0·12 0·06 14·4 11·7 15·5 10·3 4·4 7·3 23·5

0470 02 12 2·5 2·45 0·33 0·19 13·9 11·6 15·2 10·2 8·3 11·9 19·4

0470 03 12 5 3·6 0·60 0·34 14·1 12·1 15·5 10·5 11·4 17·1 17·2

0470 04 12 10 6·35 1·24 0·72 14·7 11·8 16·1 10·4 20·2 33·7 24·7

Output 24 V

0470 20 24 0·5 1 0·12 0·06 27·6 22·9 29·4 20·1 4·4 7·3 20·66

0470 21 24 1 1 0·18 0·10 29·0 22·8 31·2 20·2 4·4 10·3 27·03

0470 22 24 2·5 2·45 0·47 0·27 27·8 23·3 30·4 20·4 8·3 16·3 19·46

0470 23 24 5 3·6 0·88 0·51 27·5 23·2 30·2 20·3 11·4 25·4 18·68

0470 24 24 10 6·35 1·88 1·09 27·7 23·5 30·5 20·5 20 45·3 18·20

0470 25 24 15 7·6 2·53 1·46 27·5 23·2 30·2 20·2 23 54·7 18·70

Page 18: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

18

non-filtered power suppliesopen type single phase

■ Technical informationInput voltage : 230/400 V± ±15 V single phase 50/60 Hz - Class IOutput voltage : 24 V=Insulation voltage : Input/Output 4 510 V

Input/Earth 2 260 VOutput/Earth 500 V

Max. ambient temperature without derating : 60 °CRipple factor : 48 %Cooling by natural convectionIntegral fuse protection on outputAll except Cat. Nos. 0470 54 and 55 can be fixed to symmetrical rail4 7·5 mm or 15 mm depth EN 50022Screw fix or clip on to DIN rail Cat. Nos. 0470 52 and 53Screw fix only Cat. Nos. 0470 54 and 55Supplied with a connection link for quick connection between terminalsand earth up to 15 A

■ Cat. Nos. 0470 51/52/53/54 and 55Conform to IEC/EN 61558-2-6

■ Circuit protection (double pole MCB)

(1) T type fuse is a time delay fuse (5 x 20 mm)(2) Type gG fuse 10 x 38 mm

Single phase Input 230/400 V ±15V

U 24 V

PProtection

Internal External

1 APower supply 0470 51

Fuse/MCB T 1 A L(1) 0069 12 (1 A)

2·5 APower supply 0470 52

Fuse/MCB T 2·5 A L(1) 0069 14 (3 A)

5 APower supply 0470 53

Fuse/MCB T 5 A L(1) 0069 16 (6 A)

10 APower supply 0470 54

Fuse/MCB T 10 A L(1) 0069 18 (10 A)

15 APower supply 0470 55

Fuse/MCB 0133 16(2) 0069 20 (16 A)

■ Operating diagramOperating current up to 15 A

400 V

230 V

-15 V

0

+15 V

++

■ Electrical characteristics

Input under load Operating voltage Total loss Cat. Voltage Current Weight No-load at nominal VoltageNos. rating 230 V 400 V No-load Underload loss load 100 % drop

(V) (A) (Kg) (A) (A) (V) (V) (W) (W) (%)

0470 51 24 1 1 0·17 0·10 28·7 24·4 4·4 10·2 17·8

0470 52 24 2·5 1·7 0·39 0·23 27·5 23·4 6·2 17·8 17·5

0470 53 24 5 3·4 0·77 0·44 27·0 24·0 11·4 26·9 12·7

0470 54 24 10 6·1 1·49 0·86 26·3 23·8 20 43 10·7

0470 55 24 15 7·3 2·13 1·22 25·5 23·5 23 47·6 8·6

Page 19: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

Seen the best?Get the rest!

With thousands of items manufactured forinstallations all over the world, Legrand iscertain to have the right solutions for you. Torequest our latest catalogue, visitwww.legrand.co.uk or contact our CustomerServices team on 0870 608 9009.

Outgoing protect ion,control and signal l ing

Plugs and sockets Time switches

Cabl ing accessories Wal l mount ing enclosures

Page 20: 02558 LG Transformers · Switch mode stabilised 4 power supplies Linear stabilised 6 power supplies Filtered and non-filtered 8 power supplies Compact transformers 10 Transformer

Distributor :

LEGRAND ELECTRIC LIMITEDGreat King Street North, Birmingham, B19 2LFTel : (0870) 608 9000 Fax : (0870) 608 9004Customer services : Tel : (0870) 608 9009 Fax : (0870) 608 9008Technical : Tel : (0870) 608 9020 Fax : (0870) 608 9021E-mail : [email protected] Website : www.legrand.co.ukTR

AN

SFO

RM

ERS

LFT.

12.2

004.

10K

The Legrand logo is a registeredtrademark of the Legrand groupof companies.

REGIONAL SALES OFFICES

1. LeedsTel : 0113 233 9971Fax : 0113 233 9973

2. BirminghamTel : 0870 608 9015Fax : 0870 608 9016

3. DunstableTel : 01582 676 700Fax : 01582 676 778

1

2

3