Upload
elmodesto
View
4
Download
0
Embed Size (px)
Citation preview
ELPRO E&U/ /Dimitry Taranenko 12.08.2011
Revision 1 31.5MVA-Trafo / Schutz
© CTDim3.4 P632
CT-Core Dimensioning for Protection Relay P632 (87T) GENERAL PROJECT DATA:
Issued by: Dimitry Taranenko Our reference: Date: 12.08.2011 Remark: GENERAL SYSTEM AND SUBSTATION DATA: Nominal voltage: 10 kV Nominal frequency: 50 Hz Power system time constant: 200 ms Rated short-circuit current of station: 31.5 kA Remark:
DATA OF CT 1 ACCORDING TO IEC:
CT type: IEC Class 5P Transformation ratio: 200 A / 1 A nominal accuracy limiting factor Knalf : 20
CT nominal burden Pn: 30 VA
Internal resistance Rct: 4.5 Ω
Remark: Max.Außenbürde 2 Ohm
DATA OF CT 1 ACCORDING TO IEC:
CT type: IEC class 5P Transformation ratio: 200 A / 1 A Kneepoint voltage Uknee: 530.769 V Mag. current Iknee at Uknee: 0.049 A Internal resistance Rct: 4.5 Ω Remark: Max.Außenbürde 2 Ohm
DATA OF CT 2 ACCORDING TO IEC:
CT type: IEC Class 5P Transformation ratio: 2000 A / 1 A nominal accuracy limiting factor Knalf : 20
CT nominal burden Pn: 30 VA
Internal resistance Rct: 4.5 Ω
Remark: Max.Außenbürde 2 Ohm
DATA OF CT 2 ACCORDING TO IEC:
CT type: IEC class 5P
ELPRO E&U/ /Dimitry Taranenko 12.08.2011
Revision 2 31.5MVA-Trafo / Schutz
© CTDim3.4 P632
Transformation ratio: 2000 A / 1 A Kneepoint voltage Uknee: 530.769 V Mag. current Iknee at Uknee: 0.049 A Internal resistance Rct: 4.5 Ω Remark: Max.Außenbürde 2 Ohm RELAY DATA: Manufacturer: Areva Type: P632 Nominal Current: 1 A Relay burden: 0.1 VA Remark: CT REQUIREMENTS FOR P632 according to AREVA P63x technical description, publication P63X/EN M/B11 (AFSV.12.066661):
The transformer differential protection device is equipped with a saturation discriminator. This function will generate a stabilizing blocking signal if a differential current occurs as a consequence of transformer saturation with an external fault (in contrast to an internal fault). For the passing maximum fault current in the case of an external fault, overdimensioning is, therefore, obviated (k1=1).
In order to ensure correct operation of the connected relay, the knee-point voltage Uknee of the CT
should fulfill the following requirement:
( )pn
sn
thrtotalctsatkneeI
IIkRRUU ⋅⋅⋅+=≥
max,11,
(Requirement 1) where : Uknee : knee-point voltage of CT
Usat,1 : saturation voltage for internal fault
Rct : CT burden
Rtotal : total connected burden
k1 = 1 dimensioning factor
Imax,thr : non-offset maximum primary short circuit current for through faults
Ipn : CT primary rated current Isn : CT secondary rated current Moreover, for the maximum fault current with an internal fault, static saturation up to a maximum saturation factor of 4 is permissible. This corresponds to an overdimensioning factor k2 of 0.25. In
order to ensure correct operation of the connected relay, the knee-point voltage Uknee of the CT
should fulfill the following requirement:
( )pn
sn
ktotalctsatkneeI
IIkRRUU ⋅⋅⋅+=≥
max,22,
(Requirement 2) where : Uknee : knee-point voltage of CT
Usat,2 : saturation voltage for external fault
ELPRO E&U/ /Dimitry Taranenko 12.08.2011
Revision 3 31.5MVA-Trafo / Schutz
© CTDim3.4 P632
Rct : CT burden
Rtotal : total connected burden
k2 = 0.25 dimensioning factor
Ik,max : non-offset maximum primary short circuit current for through faults
Ipn : CT primary rated current Isn : CT secondary rated current CALCULATION OF TOTAL CONNECTED BURDENS:
CURRENT TRANSFORMER 1
The performance of the current transformer depends on the connected burdens at the secondary terminals. The total burden includes the relay burden and additional burdens, the burden of cables and the burden of an eventually connected matching transformer.
Resistance [Ω] Transformation ratio
Relay burden: Rrelay = 0.1 Ω --- ---
Additional relay burdens:
Radd = 0 Ω --- ---
Burden of matching transformer:
Rmat,1 = 0 Ω trmat,1 = 1
Rmat,2 = 0 Ω trmat,2 = 1
CALCULATION OF CABLE BURDEN:
The cable burden is calculated by the single length, the cross section, the specific resistivity for copper and an effective factor for the wire length. This factor kwire is 2 if the return wire is to be considered.
Length: lwire = 100 m
Cross section: αwire = 2.5 mm2
Spec. resistivity (Cu): ρcu = 0.02171 Ω mm2/m at 75 °C
Eff. wire length in p.u.: kwire = 2
wire
wireCuwire
wire
lkR
αρ ⋅⋅
=
= 1.7368 Ω
The total effective resistance is given by the sum of all resistances:
Total resistance:
++++=
2
2,
2,1,
1
2
,
1
mat
addrelay
matmatwire
mat
totaltr
RRRRR
trR
= 1.8368 Ω
CURRENT TRANSFORMER 2
ELPRO E&U/ /Dimitry Taranenko 12.08.2011
Revision 4 31.5MVA-Trafo / Schutz
© CTDim3.4 P632
The performance of the current transformer depends on the connected burdens at the secondary terminals. The total burden includes the relay burden and additional burdens, the burden of cables and the burden of an eventually connected matching transformer.
Resistance [Ω] Transformation ratio
Relay burden: Rrelay = 0.1 Ω --- ---
Additional relay burdens:
Radd = 0.1 Ω --- ---
Burden of matching transformer:
Rmat,1 = 0 Ω trmat,1 = 1
Rmat,2 = 0 Ω trmat,2 = 1
CALCULATION OF CABLE BURDEN:
The cable burden is calculated by the single length, the cross section, the specific resistivity for copper and an effective factor for the wire length. This factor kwire is 2 if the return wire is to be considered.
Length: lwire = 100 m
Cross section: αwire = 2.5 mm2
Spec. resistivity (Cu): ρcu = 0.02171 Ω mm2/m at 75 °C
Eff. wire length in p.u.: kwire = 2
wire
wireCuwire
wire
lkR
αρ ⋅⋅
=
= 1.7368 Ω
The total effective resistance is given by the sum of all resistances:
Total resistance:
++++=
2
2,
2,1,
1
2
,
1
mat
addrelay
matmatwire
mat
totaltr
RRRRR
trR
= 1.9368 Ω
CHECK OF CT REQUIREMENTS:
CT side 1
Check of requirement 1: Required saturation voltage Usat,1:
( ) =⋅⋅⋅+=≥pn
sn
thrtotalctsatkneeI
IIkRRUU
max,11,
38.338 V
where Usat,1: saturation knee-point voltage
Imax,thr: non-offset maximum primary short circuit current for through faults
= 1.21 kA
Rct: CT burden = 4.5 Ω
Rtotal: actual connected total burden = 1.837 Ω
ELPRO E&U/ /Dimitry Taranenko 12.08.2011
Revision 5 31.5MVA-Trafo / Schutz
© CTDim3.4 P632
k1 : dimensioning factor = 1
Ipn: primary CT current rating = 200 A Isn: secondary CT current ratio = 1 A
Check of requirement 2: Required saturation voltage Usat,2:
( ) =⋅⋅⋅+=≥pn
sn
ktotalctsatkneeI
IIkRRUU
max,22,
249.513 V
where Usat,2: saturation knee-point voltage
Ik,max non-offset internal fault current = 31.5 kA
Rct: CT burden = 4.5 Ω
Rtotal: actual connected total burden = 1.837 Ω
k2 : dimensioning factor = 0.25
Ipn: primary CT current rating = 200 A Isn: secondary CT current ratio = 1 A
CT side 2:
Check of requirement 1: Required saturation voltage Usat,1:
( ) =⋅⋅⋅+=≥pn
sn
thrtotalctsatkneeI
IIkRRUU
max,11,
41.84 V
where Usat,1: saturation knee-point voltage
Imax,thr: non-offset maximum primary short circuit current for through faults
= 13 kA
Rct: CT burden = 4.5 Ω
Rtotal: actual connected total burden = 1.937 Ω
k1 : dimensioning factor = 1
Ipn: primary CT current rating = 2000 A Isn: secondary CT current ratio = 1 A
Check of requirement 2: Required saturation voltage Usat,2:
( ) =⋅⋅⋅+=≥pn
sn
ktotalctsatkneeI
IIkRRUU
max,22,
10.46 V
where Usat,2: saturation knee-point voltage
Ik,max non-offset internal fault current = 13 kA
Rct: CT burden = 4.5 Ω
ELPRO E&U/ /Dimitry Taranenko 12.08.2011
Revision 6 31.5MVA-Trafo / Schutz
© CTDim3.4 P632
Rtotal: actual connected total burden = 1.937 Ω
k2 : dimensioning factor = 0.25
Ipn: primary CT current rating = 2000 A Isn: secondary CT current ratio = 1 A CT-DIMENSIONING CHECK:
For the protection relay P632 the following requirement has to be fulfilled.
1,satknee UU ≥ (Requirement 1)
2,satknee UU ≥ (Requirement 2)
Check of CT 1: Uknee = 530.769 V
Usat,1 = 38.338 V
Usat,2 = 249.513 V Meets requirement
Check of CT 2: Uknee = 530.769 V
Usat,1 = 41.84 V
Usat,2 = 10.46 V Meets requirement
The current transformers are correctly dimensioned!