1MRG001848
© SA-T Training November 12, 2014 | Slide 1
PCM600 V2.6 Communication and project setup
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 2
Communication setup
IED
PC
PCM600 project setup
Create new project
Handling IED objects
License Update
Set technical key
Export/Import
Report parameters
Content
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 3
Communication protocol
TCP/IP
Ethernet ports
Front
Galvanic
Rear
Optic (one channel only)
Communication setup IED – PC
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 4
IED Front port
Default IP address 10.1.150.3 (650/670)
Default IP address 192.168.0.254
(611/615/620/630)
Default Subnet mask 255.255.255.0
PC port setting
IP address 10.1.150.xx up to 254
IP address 192.168.0.xx up to 254
Subnet mask 255.255.255.0
Crossed over Ethernet cable
IED Front has DHCP server
Dynamically assign IP addresses
Ethernet – IED – Front connection
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 5
Ethernet – Optic network
RX TX RX TX
Ethernet switch
IP: 172.16.0.11
Optical cable
IP: 172.16.0.10
IP: 172.16.0.12
IP: 172.16.0.13
IED Rear port
Default IP address 192.168.1.10
Default Subnet mask 255.255.255.0
This is an example of Class B network
addressing concept
The two first segments
Defines the Network
The two last segments
Define the Nodes
Rear Ethernet port NO DHCP server
Mask: 255.255.0.0
Mask: 255.255.0.0
Mask: 255.255.0.0
Mask: 255.255.0.0
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 6
Ethernet port settings
PC Port setting
No settings in PCM600 for Ethernet port of PC
WINDOWS controls panel
Setup corresponding network
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 7
IED Ethernet port settings
Object properties
Property group address
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 8
PCM600 Setup
PCM600 Setup
Create project
Create Plant structure
Create IED objects
Unique IP address
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 9
Project Manager
Open/Manage projects
Top menu File
Open/Manage Projects
Distinguish between versions
New Project
Delete project
Import project
.pcmp file
Export project
.pcmp file is created
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 10
Create Plant Structure
Drag and drop
Objects into Plant Structure
Right click on object
Select New/General/Object
Shows current object
The IED object
Initiates configuration wizard
Note:
Only one substation level is allowed
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 11
Online configuration
Configuration modes
Online configuration
Offline configuration
Select IED protocol
IEC61850
Note: Not possible to configure IED via SPA and LON
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 12
Online configuration
Communication Port
Front port
Rear port
Scan IED
IED Type
IED Version
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 13
Online configuration
Housing
Housing type
Display type
Complete
Summarize
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 14
Offline configuration
Select IED version
Order option file
Enables ordered SW and HW
No need to synchronize
No order option specific file
Enables all functionality
Need to synchronize
License Update Tool
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 15
Basic Plant Structure – Completed
After completed wizard
IED configurations structures
Contains base functionality
Application configuration structure
Contains the configuration data
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 16
License update Tool
Synchronize PCM600 IED object with
physical IED
Function options
Hardware options
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 17
License update
Synchronizing steps
Backup PCM 600 IED .pcmi
Yes/No
Update mode selection
Offline
Order option file is needed
Online
Scan IED, reads options
Complete
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 18
Technical Key
Unique identifier for each object in Plant
Structure
IED technical key
AA1J1Q01A1
Automatic method of naming objects
AA1 – Substations
J1 – Voltage Level
Q01 – Bay
AA1J1Q01A1– IED
PCM600 and IED technical key must match
Enables transactions
Read/Write
User defined technical key
Tool executed from Plant Structure
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 19
Set Technical Key
Set technical key steps
Information
Ok/Cancel
Reading Technical key from IED
Technical key options
Use IED Technical key
Impacts on IEC61850 configuration
Use PCM600 Technical key
Reboots IED
User-defined Technical key
Reboots IED
No special characters
Max length 13 characters
No numbers in the beginning
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 20
Export IED object
Save and reuse configured IED
Export issued from Plant structure
Right click IED object
Creates a .pcmi file
Contains all configured data
Application Configuration
Signal Matrix
Parameter Setting
Graphical Display
Communication Management (DNP)
SCL information
Hardware configuration
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 21
Import IED object
Use a configured IED object
Import issued from Plant structure
Bay level
Right click object
Select .pcmi file
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 22
Create Template
Save and reuse configured IED
In a pre-defined place
For quick access
Creation of template issued from Plant
structure
Right click IED object
Creates a .pcmt file
Ends up in PCMDatabases\Templates
Contains all configured data
Same content as pcmi file
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 23
Create new IED object from Template
Use a configured IED object
New object created from Plant
structure
Bay level
Right click object
Template Manager
Select current IED object
Press Create button
Instantiates object in Plant structure
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 24
Copy/Paste IED object
Copy/Paste issued from Plant Structure
Right click IED object
All configured data is copied
Technical Key automatically updated
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 25
IEC 61850 configuration SCD
SCD file
Substations Configuration Description
Contents
SCL information for all IED’s within the
substation
Export/Import SCD file
Engineering of SCL information
Substation level
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 26
IEC 61850 configuration ICD
ICD file
IED Capability Description
New feature
Contents
All that’s configured in IED before system configuration
No SA Section
No Communication section
IEDName = TEMPLATE
Usage
System engineering
Merging to a SCD file
Export/Import of ICD file
On IED level
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 27
IEC 61850 configuration CID
CID file
Configured IED Description
Contents
Extract of the SCD file
SCL information for one specific IED
Export/Import of ICD file
On IED level
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 28
Report Parameters
Drawing Header information
Application configuration
Local display, Graphical display editor
Parameter settings
Communication management
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 29
Drawing
Drawing size
Fixed to A3 Landscape
Margins can’t be change
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 30
Hardware Configuration
Changing configuration
Add/Remove Binary Input/Output Module
(BIO)
Alter Transformer Module (TRM)
Fixed card position
Add/Remove Analog Input Module (AIM)
Alter module
Alter Power Supply Module (PSM)
Fixed card position
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 31
Hardware Configuration
Select card in drop down menu
Add/Remove cards in fixed order
Add from p3
Remove from p6
AIM module in p4
Position 3 must be empty
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 32
Hardware Configuration
Compare configuration
Reads hardware configuration form
IED
Issue compare from toolbar menu
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 33
Hardware Configuration
Simple Parameter Setting
Parameterize hardware modules
Binary Inputs
Analog Inputs
Select module from hardware
configuration list
Press Parameter Setting button in
toolbar menu that will issue
simplePST
Can not Read/Write parameters form
simplePST
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 34
Hardware Configuration
Print hardware configuration
Print preview
1MRG001848
Section 2
© SA-T Training November 12, 2014 | Slide 35