Upload
dmsoares1989
View
218
Download
0
Embed Size (px)
Citation preview
8/11/2019 01177804.pdf
1/6
Evaluation Methods of Polymer Insulators
under Contaminated Conditions
R.
Matsuoka,
Fellow
IEEE,
K
.Naito,
Lije
Fel low
IEEE,
T.
Irk,
Senior
Member IEEE and K. Kond o, Member IEEE
Abstract Although polymer insulators generally show
superior inaulation performance under contaminated and
wetted
conditions
due to hydrophobicity on the i r ~U rtace .
Owmg to shortage
o f
their field experience,
anti-amtam ination design criteria
are
not yet established.
Presently the same design criteria for ceramic insulators
are mostly adopted by cons idering th e hydrophobicity as
safety margin.
In order
to
establish rationalized insulation design
criteria for polymer insulator^. we made fundamental
investigation. We found ou t 1) Roughly t w o t imes
heavier contaminant deposit on hydrophobic polymer
insulators than pornla in under s low deposi t
conditions,
while such Me re nc ss become
smaller
under rapid depoait
conditione like typhoon.
2) In
spite of smaller leakage
cumnta
on hydmphohic polymer in~uhtcm, stiff power
8ource
ia sti necessary for evaluating their
contamination
hshover vol tages.
3)
Contamination flashover voltages
of hydmphohic polymer ineulat~mshould be evaluated
und er heavy wetting conditions. Combined t e s t s under
heavy fos and
rain
conditions may be good candidates for
eva lua t ing polymer insula tors .
Index
Te-
Accumulation 1Contaminants, Contamination
Flashover, Evaluation Methods, Plasbover
Voltage,
Hydrophobicity, Leakage Current, Polymer Insulston, Power
Source, Silicone Rub ber,
Wetting
Conditions
1. INTRODUCTION
Polymer insulators generally show superior
insulation performance under contaminated and wetted
conditions compared with conventional ceramic insulators
like porcelain or glass insulators. Such superior
Derformance is fundamentallv owing to hydrophobicity on
In order to establish rationalized design and maintenance
criteria for such insulators, we have conducted fundam ental
investugation works and some results are shown here.
11. ACCUMULATION OF CONTAMINANTS
Contamination flashover voltage o a hydrophobic
polymer insulator is also similarly influenced by
contamination degree with the case of porcelain insulators,
that
is,
almost proportional to 115 power
of
SDD(Salt
Deposit Density)[ I].Heavier deposit o contaminants on
hydrophobic polymer insulators compared with ceramic
insulators
has
been measured at various
sites
12)
-
C41
.
Recently we have also made comparative measurement
on
porcelain and polymer insulators at the site 50m from
seacoast located in the suburbs
of
Osaka[site
A].
Results are
shown in Tables and 2. Such heavier deposit
o f
contaminants is partly attributable to oily surface conditions.
Once contaminan ts deposit on such oily su rface, they are not
easily removed by wind
or
rain due to adhesive nature
of
their
surface. Under rapid contam ination conditions like typhoon,
Table 1 ESDDRatio of Polymer to Porcelain
Maximum
I
7.44
I 8.17 I 4.79 8.17
Minimum
I
0.81 0.93 I 0.67 0 67
Measurement period: March 1998 to January 2002.
ESDD measured on 3 month exposed insulators.
-
. .
their
surface. Hydrophobicity,
is,
however, Sometimes 10s Table 2 ESDD Measurement Results under R a i d Contamination
by surface discharge or heavy wetting, and recovered with
time by the diffusion of low molecular weight silicone onto
the surface from the bulk
of
silicone rubber. Polymer
insulators are made of organic materials and so ageing change
of
surface conditions is not avoidable. In addition, polymer
insulators are quite new comers, and so field experience
on
contamination performance of these insulators is limited.
Contamination tlashover/withstand voltage test methods of
these insu lators in laboratory
are
not yet established.
R.
Metsuoka ie with Chubu University 1200 Matsumato-do. Kesugai.
Naito
la
with Meija University, 1-601 Shiogamaguchi,
Tempaku-ku.
T. Iris iE \ntb NOK Imulatori, Lld I I 5 5 Tag-, Fulaebm
,
Komaki. 185-8566.
K. Kondo e;
\ntb
NGK
n~ulDtors.
id.
I 155
Tag-, Fulkboi,
Komaki. 485-8566,
Aiehi,487.8501. Japan
e-mail:mst4uo~se.chubu.aedp)
Nagoya 468-8502 Japan (wmsil:
kmit&%mfs.meijwu.ae.jp).
1ap.n
(e-mail:ir*lak@n&k.~.jp)
lopsn s-mul:
kavbk@gkOojp)
Condi t ions
0-7803-7525-4/02/ 17.00 2002 IEEE.
2197
8/11/2019 01177804.pdf
2/6
oily substances are washed
off
by heavy rain and/or strong
wind, and
so
difference in contamina tion degree between
porcelain and polymer insulators becomes smaller. So,
dependin g on the critical contam ination conditions in
a
given
site, rapid or slow accumulation
of
contaminants, a pertinent
correction factor for the design contamination degree of
polym er insulators at a given site agains t the refe rence
contamination degree measured on conventional porcelain
insulators must
he
selected for rationalized design of
hydrophobic polymer insulators. Influence of insulator
diameter on deposit o f contamin ants on polymer insulatoi
surface was investigated under rapid contamination
conditions at sites A and
B.
Site
B
i s located near seac oast in
Okinawa island. Results are shown in Fig.1. Reduction
in
ESDD can be found with the increase of average diametei
also in the case of polymer insulators
1.2 r
I
2
3
4
P a l p e r
Lang-md
R eg r e ss i o n c u w e
/
o f
p o r c e l a in i n s u l a t o r s
12615W 7 350-
980-
126150
12
600
1680
166170
9
450 1602
166170 7 350
1246
9
0.2
-
5
6
7
Porcelain
standard
Disc
166,
136137.5
430 1648
166,126135
365
I445
615
(LonglShon)
515
LonglShon)
2541-
(146)
280
0 1
0 200
400
600 800
Average
diameter. D. rnm
Fig. 1 Influence of Average Diameter of Insulator on
Contamination Degree under Rapid
Contamination Conditions
111. EFFECT
OF
POWER SOURCE
ON
WITHSTAND VOLTAGE
In the case o f porcelain/
glass
insulators, heavy
leakage currents flow along the surface of specimen
insulators in contam ination flashover/ withstand voltage tests
especially
ust
before flashover, and
so
stiff power source is
specified for such evaluation ests[fi].
In the case
of
hydrophobic polymer insulators, however,
relatively smaller magnitudes of leakage currents have been
measured both in fields and in laboratories.
So,
it is
expected that stiff power source may not be necessary for
flashover/withstand voltage tests
of
contaminated
hydroph obic polymer insulators. We examin ed the effect of
stiffness of power source on contam ination flashover voltages
of
hydrophobic polymer insulators using a stiff and a weak
power
sources.
A . Test Method
Comparative flashover voltage tests were conducted hy
using the two pow er sources shown in Table 3.Dimensional
particulars of specime n insulators are shown in Table
4.
Table 3 AC Power Sources for Insulator Contam ination
Tests
Power S a u n e A
I
PowerSourceB
I hour) (Continuous)
nmary
(1
hour) (Ihour)
Y mpedance : 7.0
Rated Voltage : 0kVl26.3kV
RatedCapaciiy : I40kVA
Impedance
:
2.03
(
1
hour)
Table 4 Dimensional Particulars
of
Specimen Insulators
Speeimen Shed Dial EffectiveLength
NO. I Shedpitch No'ofSheds
[
(ConneetionLength)
[
wgeDirtance
hed Shape
pecimen
Insulators
I
2198
8/11/2019 01177804.pdf
3/6
Tests were conducted according to the clean fog method
specified in IEC Pub. 507 except for m odified fog density and
special pretreatment for uniform contamination layer on
hydrophobic insulator surface based on our investigation
results
[ I ]
Heavier fog such as 13-15
g/m
gives much lower
flashover voltages to hydrophobic polymer insulators
compared with the case of thin fog conditions used for
ceramic insulators. Special pre-treatment was conducted in
order to get uniform and continuous contaminant layer on
hydrophobic insulators simulating actual contaminant deposit
conditions in fields. Time variations o f fog density in both
chambers for conventional thin and special dense fogs are
shown in Fig.
2.
In case of polymer insulators, however, discernible
differences cannot be found in the flashover voltage between
the two power sources under the contamination conditions of
0.03 and 0.12 mp/ cm2 while significant difference can be
recognized between the two power sources under heavy
Contamination conditions of
0.5
mg/
cm2.
1.6
q
1.4
1.2
m
.
h 1.0
1
0.8
0
10
20 30 M 50
60
0 1 0 2 0 3 0 1 0 y 1 6 0
Tim b e . min
Tim Lapse.
min
( i
1 Chamber A ii) Chamber B
Fig. 2 Time Variation of Fog Density
B. Test Results
Some typical leakage current and applied voltage wave
forms at the time of flashover by Power Source
A
are shown
in Fig. 3. In this test facility, in order to minimize the
voltage drop of power supply system, protecting resistor of 25
or 50 kn was inserted between testing transformer and
specimen. So short circuit current was limited to around 1 A.
In the case of porcelain insulators, leakage current increases
gradually to flashover while polymer insulators flash over in
shorter
periods
after start of increase of leakage current
especially in the case of light contamination conditions.
Comparative
50
flashover voltages obtained by Power
Source A referenced to the corresponding flashover voltages
obtained by Power Source
B
are shown in Fig. 4. As
expected, higher flashover voltages were obtained by weak
Power Source A in case
of
porcelain insulators irrespective of
contamina tion degrees.
02
0
Fig.4 Comparative 50% Flashov er Voltage
by
Two
Power Sources
IV. CONTAM INATION TEST METHODS
In case of artificial contamination tests of ceramic
insulators, artificial fog is specified for wetting the
contaminated insulators in solid layer methods since it gives
lowest flashover/ withstand voltages. In case of
hydrophobic polymer insulators, however, heavy wetting
conditions such as heavier
fog
than conventional
fog
used for
ceramic insulators or rain, give lower flashover/ withstand
voltages
[SI
171. In order
to
find
out
the severest w etting
conditions giving the lowest flashover voltages for
hydroph obic polyme r insulators, we investigated the effect of
rain conditions on flashover voltages of polymer insu lators.
A. Test
Methoak
Based on the investigation results explained in the form er
section, we installed a new power source stiff enough for
contamin ation tests [ 8 ] [ 9 ] .
(
i
Pomelain/SDD :0.07mg/cm2
( U )
Polymer/SDD 0.03
mg/cmz
id Polymer/SDD 0.6mg/cm2
Leakage C urrent and Applied Voltage at
the
Time of Flashoverig.3
2199
8/11/2019 01177804.pdf
4/6
8/11/2019 01177804.pdf
5/6
Such lower flashover voltages are attributable to the water
streams flowing down along individual shed s as illustrated in
Fig. 9. Again much higher ratios were obtained on the
Such
explained by the saturation of salt soluble into the water film
deposited on the surface of specimen insulators under heavy
fog conditions. Enough quantity
of
water
is,
however,
supplied under simulated rain conditions even with the SDD
of
0.5 mg/cm2. Relationship between
SDD
and flashover
voltage may be explained qualitatively by two curves shown
in
Fig. IO
insulators contaminated with SD D of 0.12 mg/ cm2.
different ratios between
0.12
and 0.5 mg/ cm may be
2
ri
I
, I
0.03
0.12
0.5
SDD. mgIcm2
Fig. 10 Contamination F.O.V. Characteristics
40
of A Polymer Insulator
V. CONCLUSIONS
Based on our investigation results, the followings should
he taken into consideration at the time of evaluation and
design
of
polymer insulators
I)
Heavier contaminant deposit should be considered on
hydrophobic polymer insulators compared with
conventional ceramic insulators.
(2) A stiff power source should be used for evaluation of
contamination flashover/withstand voltages of
hydrophobic polymer insulators, especially under
heavily contaminated conditions,
in
spite
of
smaller
leakage currents measured both in fields and
laboratories.
(3)
Contamination flashovedwithstand voltages of
hydrophobic polymer insulators should be evaluated
Fig. 7 Com parative Flasho ver Voltages under heavy wetting conditions. Both heavy
fog
and
simulated rain tests mav be
eood
candidates for standard
contamination flashoveriwithsland voltage test methods
for hydrophobic polymer insulators.
VI. REFERENCES
Il l
K. Naito, K. Immi, K.T h u nd R. Malsuoka, Performance of
Comwsi te lnsulalom
under Polluted
Conditions. ClGRE Session
f
i
) S t r a i g h t S h e d s f
ii 1
A l t e r n a t e S h e d s
PapeiNo.
33-301, 1996.
H. l rnapawa
R.
Matsuoka S .
110.
K. SAanishi. K. Kondo. N. Okada21
,
~ ~~
.
~
.
and T.Yonezawa,
Comparative Contaminatio Degrees
on
Porcelain
and Sil iw ne Rubber
Insulators
in Fields, ClGRE SC33 Colloquium,
Paper No.
3 3 - 4 3 , Toronto,
September IW7.
Y. Hi&whimori, 2. akao, S. Nishimura, J. X. Zhu, 2. Iha,
T.
Tmaki,
I. Kat. R. Kimata T.Mugushima and T. Kohayashi, Studies on Salt
Conrnminalian and
Leakage
Current of Silicone Rubber InsuIafors,
ICE. pp.744-748, Beijing, China,
1996.
K.
Kondo, M .
Ishiwari, S.
Ito,
I.
Irie, Y.
Suzuki and K.
Amkawa.
Pollution Performance of Polymer Insulaon under The Marine
Conditions in
Japan. ISH-2001.
Paper No. 5-19, Bangalore, India,
August 2001.
IEC Pub.
507.
Ar t i f ic ia l
Pollution Testson
High-Voltape
lrrsulamn
lo be Used on
A .
C. Systems,
1991.
A. de la and
R.
. Gorur. Flashover of Conlaminated Nonce ramic
Outdoor lnsulator~n A
Wet
Alrnosphcre,
IEEE Trans. On DEI, Vol .
5,
No. 6,
December
1998.
M . Ishiwirri. S. 110, K. Arakawa, T. Nakachi and K. Kondo. Various
Altificial Contamination Withstand Voltsge Test Methods
and A
Fig. 8 Dripping of Water at the Tips of Sheds
(Precipitation: 4mmlmin)
[3]
141
51
16
[7]
q
(
i )Vertical Installation
( li1
Horizontal lnatallation
Fig. 9 Flashover Paths in Simulated Rain Tests
2201
8/11/2019 01177804.pdf
6/6
Comparison of Their
Results
on Polymer and Porcelain Insulalops,
paper presented at the I
I ISH, London
U ~ U S I1 .
[SI N.0 K. Ikeda, S Sumi, R Matsuaka K. Kondo and S Ito,
Contamination Withstand Voltage
Chamcleristics
of Hydrophobic
Polymer Insulators under Simulated Rain Conditions, Paper to be
presented
at lSEl
in
Boston,
April 2002.
K. Ikeda, N. Okada, S Sumi,
R.
Mauuoka, K. Takemato, T. Ito, T.
Ono
and
Y.
Komiya A New Power
Source
for
Insulator
Contamination Tests, h f the Twelfth Annual Conference o f
Power Energy Society, IEE o f Japan,
Vol.
B.
P a p
No. 493, 2001
( In
Japanex ).
[ 9 ]
VII. BIOGRAPHIES
Rymuke Mabuoks SMW- F96)
was
born
in Gifu Prefecture,
J a m
n
1941.He received the BS, MS and the Ph.D. degrees, dl in Elsuical
Engineering fmm the Nagoya University in 1964 1966 and 1994,
respectively.
He
joined NGK Insulators Ltd. in 1966. He served asGeneral
Manager of NGK High Voltage
Laboratory.
He w e d also as manager of
Insulate(.
Engineering, in h k c nsulators Inc. fmm 1981 to 1986. He
retired NGK an d joined Chubu University as a full time mfessor
in
1598.
Pmf. Mauuoha is a Member o f C E R E and IEE of
Japan,
Katsuhiko N d o M66SM8C-FW)
was
born n Aichi P refenm,
Japan,
in
1934.He received the EIS, MS and the Ph.D. de- all
in
Electrical
Engineering fmm the Nagoya University in
1958,
1 0
and
1976
respectively. He oined NGK Insulators Ltd. in 1964. H e
served as
General
Manager of Design Deparunent,G e n d Manager
of
NGK, High Voltage
Laboratory, and later
as
Executive Chief Engineer of Power Business
Group
of
the Company. He joinedNagoya lnstiate afTechnalogy in 1991
BS a
full-time
Professor. In 1998, he &red
fmm
Nagoya Institute o f
Technology and joined Meijo University
as a
ful l-ti m Fmfessor. Prof.
Naito is a Member o f CIGRE and B Fel low of
IEEE
of U.S.A. H e is a
Member of Insulator and Lightning Arrester Subso mm inee of IEEE.
Takarbl
l r i r
SM91) as born in Tottori Prefecture,
Japan.
in 1944.He
received the BSc. and Ph.D.
de
oth in elenrical engineering from
Yokohama National University in 1968 and 1995, respectively. In 1968 he
joined NGK Insulators Lid. He is now the General Manager of NGK High
Voltage Labamtory, Power Buincss Gmup. His
f ields
o f interest include
insulator contamination, ightning
arrester
and in sulation smength o f large
air
W .
Kunhki
Kondo ( M Y 8 ) WBS
barn in Aichi
Prefechue,
Japan
in 1967.
He received the
B. Sc.
M.
Sc.
and Ph. D. d e p s n electrical engineering
fmm Nagoya lnstitutc
of
Technology in
IWO,
IW2 and 1997. respectively.
In
1992
he joined NGK Insulators, Lld. He has
been
engaged in rereareh
of
insulator commination. He
is
now a Supervisor of NGK High Voltage
I.aboratory, Power Business Gmup.
2202