    Dual 50A 5X5 GMT TFA Fuse Alarm PanelWith Surge ProtectionModel 009-0112-6001RE Specification Sheet

    Telect, Inc. USA +1.509.926.6000 Mexico +1.52.33.3836.3700

    Poland +1.48.713.239.100 UK +1.44.1489.889500 www.telect.com

    Copyright 2002 Telect, Inc., All Rights Reserved Telect Publication 127878-1 A2

    NOTE

    Inspect equipment after unpacking. Immediately report

    any shipping damage, defects, or missing parts to Telectat 1-800-551-4567. Keep all documentation that comes

    with your shipment

    FEATURES& SPECIFICATIONS

    Dual-Feed, 50A @ -48V Per Feed

    5 GMT Outputs Per Feed

    Diode-Clamped Output Surge Suppression

    Power On & Fuse Alarm LEDs

    Total Front Access

    Inputs: Specifications:

    Voltage & Range -48Vdc, -40V to -60V

    Max. Input Load Rating 50A per side

    Nominal Power Loss at FullLoad

    20W per side @ 2400W full loadper side (50Ax48V)

    Percentage of Full Load PowerDissipation at Nominal Voltage

    less than 1%

    Max. Input Interrupt Device 60A

    Input Terminal Studs (WithKEPS Nuts) for Dual-HoleCompression Lugs

    Two pairs ofdual#8-32 studs on5/8 in. centers. [Torque nut(using 11/32 in. or 9 mm socket)

    to ~17 in.-lb (~1.8 Nm)]

    Input Wire Size depends on input interruptdevice

    GMT Outputs: Specifications:

    Max. GMT Output Fuse (ea.) 15A.

    Max. GMT Output Load (ea.) -continuous

    12A

    GMT Output Terminal Bare wire, ring, or forked lugunder #6-32 panhead screws.[~9 in.lb (~1 Nm) max, torque.)

    GMT Output Wire Size #12 - #22 AWG (depends on out-put fuse rating)

    Surge Protection > 68Vdc

    Grounding: Specifications:

    Earth GND terminal studs(With KEPS nut) for single-holdcompression lug (supplied)

    Single #6-32 stud. Torque LEPSnut (using 5/16 in. or 8 mmsocket to ~8 in.lb (~1 Nm)

    Ground Wire Size #10 - #18 AWG (depends oninput interrupt device)

    Model 009-0112-6001RE is RoHS Exempt.

    Alarms: Speci ficati ons:

    Alarm Relay Contacts: Power Fail contacts are

    normal when power is

    applied to both feeds.

    Fuse Alarm contacts are

    normal if all installed fuses

    are functioning

    2A. @ 30 Vdc0.6A @ 60 Vdc

    Max. Alarm Card Power Rating 1.9W (40mA @ -48Vdc)

    Alarm Connection Wire binding plates under #2-56screws

    Indicators: Specifications:INPUT POWER LEDs (Green) Lights when power is applied to

    that feed

    FUSE ALARM LED ((Red) Lights if any GMT fuse blows

    Dimensions: Specifications:

    Nominal, without brackets:*WidthHeightDepth* See Page 3 for details

    17.25 in. (438 mm)1.75 in. (44 mm)4.00 in. (100 mm)

    Weight: Specifications:

    Weight, Without Packaging 5.75 lb (2.6 kg)

    Weight, Shipping ~8 lb (~3.5 kg)

    Environment: Specifications:

    Operating Temperature Range -10C (14F) to 55C (131F)

  • 8/10/2019 009-0012-6001RE

    2/4

    Telect, Inc. USA +1.509.926.6000 Mexico +1.52.33.3836.3700

    Poland +1.48.713.239.100 UK +1.44.1489.889500 www.telect.com

    Copyright 2002 Telect, Inc., All Rights Reserved Page 2

    ADMONISHMENTS

    WARNING!WARNING! WARNING! Failure to properly ground thi s equipment can create hazardous condit ions to installa-

    tion personnel and to the equipment.

    WARNUNG! Bei unsachgemer Erdung besteht Gefahr fr das Installationspersonal und das Gert!

    AVISO! La conexin i ncorrecta a tierra puede ser peligrosa tanto para los instaladores como para el equipo.

    AVERTISSEMENT ! Si vous ne rel iez pas cor rectement cet quipement la terre, son uti li sat ion prsente des

    dangers pour la personne qui l'installe ainsi que pour l'quipement.

    WARNING!WARNING! WARNING! Before connecting i nput power cables, make sure input power to panel is turned off.

    WARNUNG! Vor Ansch luss der Eingangsstromkabel ist sicherzustellen, dass der Eingangsstrom ausge-

    schaltet ist.

    AVISO! Antes de conectar los cables de entrada de la alimentacin, compruebe que la alimentacin de

    entrada al panel est cortada.

    AVERTISSEMENT ! Avan t de connecter l es cbles d 'entre d'alimentat ion, assurez-vous que l'alimentat ion

    lectrique est coupe au panneau.

    SCHEMATICDRAWINGt

    Note: The installer should

    verify that a readily accessi-

    ble 60-amp maximum over-

    current protection device is

    part of the building installa-

    tion wiring feeding the fuse

    panel.

    ALARM PCB

    1

    INPUT A POWER

    FUSE ALARM

    C GND

    -48V

    RTN

    RTN

    -48V

    INPUT A

    INPUT B POWER

    NO

    C

    NC

    NC

    C

    NO

    5

    INPUT B

    4

    3

    2

    1

    5

    3

    4

    2

    RTNGMT OUTPUT A

    RTNGMT OUTPUT B

    GMT OUTPUT B-48V

    GMT OUTPUT A-48V

    FUSE ALARM

    POWER FAIL

    5

    1

    3

    4

    2

    3

    5

    4

    1

    2

  • 8/10/2019 009-0012-6001RE

    3/4

    Telect, Inc. USA +1.509.926.6000 Mexico +1.52.33.3836.3700

    Poland +1.48.713.239.100 UK +1.44.1489.889500 www.telect.com

    Copyright 2002 Telect, Inc., All Rights Reserved Page 3

    OUTLINEDRAWING

    Telect assumes no liability from the application or use of these products. Neither does Telect convey any license under its patent

    rights or the patent rights of others. This document and the products described herein are subject to change without notice.

    NOTES:1. Dimensions are in in. (mm) or2. Panel not supplied with fuses.

    in.mm

    FRONT VIEW

    TOP VIEW

    B Input ShownWithout Cover

    -48V Outputs Shown Without Cover

    .625 (16.0)

    8 - 32Studs

    .19 (4.8)

    6 - 32 Stud,KEPS Nut, & Lug

    4.65 (118.1)3.99 (101.2)

    17.25 [438.2]

    1.73 [43.8]

  • 8/10/2019 009-0012-6001RE

    4/4

    Telect, Inc. USA +1.509.926.6000 Mexico +1.52.33.3836.3700

    Poland +1.48.713.239.100 UK +1.44.1489.889500 www.telect.com

    Copyright 2002 Telect, Inc., All Rights Reserved Page 4