Upload
andrew-sanders
View
218
Download
0
Embed Size (px)
Citation preview
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 127 Jan 2011_rev 2
HF OPERATORS
Notes on Lightning
by
John White
VA7JW
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 227 Jan 2011_rev 2
LIGHTNING
THUNDER
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 327 Jan 2011_rev 2
Generation of Lightning
Thunderstorms Cold front - air aloft sinks Warm air at ground rises Vertical air flow, up and down Friction between water droplets Droplets become charged Charges separate within cloud High voltages develop Within, cloud to cloud Cloud to Earth Air breakdown occurs LIGHTING DISCHARGE
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 427 Jan 2011_rev 2
Some Facts
Average duration 50 microseconds Average speed of Lightning stroke 20,000 mph Average Temperature 30,000 degrees C Average Length 3 km Average Energy 300,000,000 joules Average Power 10,000,000,000,000 watts (10 terawatts) Average number of strokes per flash, 4 200 thunderstorms in progress world wide any time 100 flashes per second worldwide any time Astraphobia – fear of thunder and lightning
Reference “Lightning and Lightning Protection”, William Hard and Edgar Malone. Don White Consultants publisher 1979. and other internet sources.
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 527 Jan 2011_rev 2
Forms of Lightning
Cloud to Ground – our major concern ! Cloud discharge to ground
Within a cloud Discharge in a cloud
Cloud to cloud Discharge between clouds
Heat lightning Intracloud, far away Thunder not audible
Sheet Lightning Intracloud, diffuse
Cloud to air Bolt-from-the-blue
Don White Consultants
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 627 Jan 2011_rev 2
Annual Thunderstorm Days in America
Numbers are storm days Florida is Worst - ( Adam AB4OJ/VA7OJ will vouch for that)
Don White Consultants
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 727 Jan 2011_rev 2
Annual Thunderstorm Days in Canada
We are lucky, only ~ 5 days per year
IEEE ANSI/IEEE Std 142-1982
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 827 Jan 2011_rev 2
Number of Discharges
World wide distribution of Lightning Discharges Our part of the world 10 to 30 Central Africa 5400 !
Don White Consultants
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 927 Jan 2011_rev 2
Strikes vs Tower Height
Lower Mainland @ 5 thunderstorm days per year = low risk Until you get hit of course
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 1027 Jan 2011_rev 2
Thunder
Sound of the explosion along the superheated lightning channel 30,0000 degrees
Superheated air, gas pressures 10 to 100 atmospheres
Shockwave is what we hear
Rumblings are primarily due to the various distances between observer and tortuous path of the lightning discharge
Speed of sound is ~ 1000 ft per second count the seconds between the flash and the onset of thunder to
determine your distance to strike; seconds = thousands of feet
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 1127 Jan 2011_rev 2
Strike Current Waveform
Example for a Typical Strike Rise Time ~ 5 seconds Crest ~ 25 kA Fall time ~ 50 seconds to half of crest value
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 1227 Jan 2011_rev 2
Lightning Parameters
ParameterPercentage of Strokes EXCEEDING Value indicated
90% 50% 10% Max Observed
Crest (peak) Current 2 to 8 kA 10 to 25 kA 40 to 60kA 230 kA
Rate of Rise to Crest 2 kA/us 8 kA/us 25 kA/us 50 kA/us
Time to Crest 0.3 to 2 us 1 to 4 us 5 to 7 us 10 us
Duration of Single Stroke 0.1 to 0.6 ms 0.5 to 3 ms 20 to 100 ms 400 ms
Time between Strokes 5 to 10 ms 30 to 40 ms 80 to 130 ms 500 ms
Total Stroke Duration 0.01 to 0.1 s 0.1 to 0.3 s 0.5 to 0.7 s 1.5 s
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 1327 Jan 2011_rev 2
Current Distribution
Percentage exceeding a given current
50 % will exceed 10,000 amps
Don White Consultants
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 1427 Jan 2011_rev 2
Strike Current Spectrum
Most Energy concentrated DC to 1 kHz.
Destructive energyrange < 1 kHz
Not energy > 1MHzthat destroys radio installations
It will sound loud on radio though!
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 1527 Jan 2011_rev 2
Primary Protection
Cloud to Ground discharges of concern to us
Need to direct the lightning current to earth as directly as possible
Protection of Life and Property Fire Protection Shock Protection Equipment Protection
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 1627 Jan 2011_rev 2
Ground
Cloud to Ground Strike current seeks earth ground the strike point directly to surface or via tree, tower, antenna etc.
Current flows outwards from strike point through earth
Earth ground is not a good conductor
Thousands of amperes flow through ohms of resistance
Thousands of volts per foot exist outwards from strike point
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 1727 Jan 2011_rev 2
A Simple Calculation
Strike current = 20,000 A for 10 usec
Voltage along feedline = 2000 V bye bye coax
Voltage across ground rod = 200 V 4 MW for 10 usec
Voltage at top of ground rod = 200,000 V Side flashing may occur
This is called GROUND RISE This 200 kV will diminish exponentially with
distance from the ground point Voltage gradient immediate vicinity is dangerous
See cow >
0.1 ohms
0.01 ohms
10 -100 ohms Earth
Rod
Feed line& Tower
ANTENNA
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 1827 Jan 2011_rev 2
Station Grounds
Multiple grounds exist out of necessity
Electrical - AC Power “green wire” power safety
Lightning - Towers, feed lines
Signal – chassis, shields, coax,
Antenna RF – ground planes, counterpoises
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 1927 Jan 2011_rev 2
Unsafe Ground System
Multiple unconnected Grounds > Problem
Lightning currents flowing in each ground system not equal
Dangerous voltages will develop between equipments due to differentground system impedances
Extreme shock hazard.
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 2027 Jan 2011_rev 2
Safer Ground System
Multiple, Connected Grounds much Safer
Connecting all grounds together createsan EQUIPOTENTIAL environment
Voltage drop between ground systemsideally ZERO if wire has zero resistance
Ground rise will be same everywhereand differential voltages will be minimal
Multiple ground points leads to lowering resistance to ground thus lowering of Ground Rise overall
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 2127 Jan 2011_rev 2
Wire Sizing
What Gauge wire is needed to carry a strike current Wire Melt, called FUSING as in blowing a fuse, is the issue
#6 is typical code
For 50 sec, fusing
current ~ 800 kA
Don White Consultants
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 2227 Jan 2011_rev 2
Bonding
Objective is to create an EQUIPOTENTIAL AREA
Bonding means an electrical connection between equipments mechanically connected hardware is not bonding.
Independent, random unconnected ground systems where conductivity is not assured is unacceptable
All grounds and equipments must be electrically connected voltage differences are small and shock hazard is suppressed lower impedances are achieved large currents are distributed over many paths lowering voltages
“All grounds … . must be bonded together in order to protect life and property (ARRL 2010 Handbook pg 28.7)
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 2327 Jan 2011_rev 2
Grounding Impedance
Grounding is not just a simple Resistance problem
The rate of rise of current, kA / microsecond, is same as a High Frequency Signal and must be treated the same way.
LOW IMPEDANCE to Ground is the requirement
DC resistance can be achieved with large diameter copper
INDUCTANCE of the ground system is the limiting factor
(how could the inductance of straight wires be of any consequence?)
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 2427 Jan 2011_rev 2
Inductance
Conductors carrying the rapidly increasing strike current generate a rapidly changing magnetic field.
A changing magnetic field produces a back EMF that opposes the applied voltage thus constraining the rate at which the current can rise.
This is Inductance
Current cannot rise instantly in the presence of inductance
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 2527 Jan 2011_rev 2
Inductive Voltage
Relationship between Voltage and Current for an inductance
V is the voltage developed across and inductor L is the inductance value i is the current t is time di/dt is the rate of change of current with time,
i.e amps per sec
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 2627 Jan 2011_rev 2
Wire Inductance
1 foot of #6 AWG copper Inductance = 0.26 H per foot Resistance = 0.0004 ohm per foot 2 S rise time
Resistive Voltage drop / foot at 20 kA = 8 volts / foot
Inductive voltage drop / foot at 10 kA/s = 2600 volts / foot
The impedance to ground is clearly limited by L
K7MEMCalculator
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 2727 Jan 2011_rev 2
Voltage Flashover
A 50 foot vertical run of coax from feed point to ground could develop 130 kV (ignoring Ground rise)
Very difficult to make all ground and bonding systems
run in a straight line
90o corners and bends in cable runs INCREASE inductance
Higher yet voltages are developed
High voltage will flash over from cable to cable or equipments or other structures – whichever forms the lowest impedance to earth!
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 2827 Jan 2011_rev 2
Magnetic Field
Mechanical forces develop between conduction paths due to their magnetic fields
2 Conductors carrying 20,000 amps
Side x side, 1 cm separation
Force between conductors ~ 500 lbs / foot
Cable bundles burst, wires break, cables straps rupture, brackets break, cables deform etc.
ARRL Handbook 2010, sec 28.1.8
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 2927 Jan 2011_rev 2
Tower Grounding
Grounded plate at base of tower
Coax protected with arrestors
Copper strap tying off to
the system ground
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 3027 Jan 2011_rev 2
Secondary Protection
Primary Protection
Diversion of high currents and voltages to ground
Secondary Protection
Limiting dangerous Voltages to non destructive values
Divert excessive Currents to non destructive values
Lightning Arrestor Devices
Placed on cables and equipments
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 3127 Jan 2011_rev 2
Cone of Protection
A Rule of Thumb (old theory) You are protected from a strike if a tall structure is close by. Distance out (radius) = height. Defines a cone Theory - Safe inside
from a “hit”
Your Tower / Antenna
probably IS the
Air Terminal !
A big tree might help
but don’t depend on it
Don White Consultants
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 3227 Jan 2011_rev 2
Arrestors
Coax’s, Rotor Cables, any wires, to outdoor antennas are prime conduits for destructive energy to enter house / shack.
Arrestors are placed across cables to ground
Zero current flow to ground under normal conditions Does not shunt your signal to ground
Elevated voltages to ground will cause conduction to ground to divert harmful current and limit excessive voltages
Don White Consultants
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 3327 Jan 2011_rev 2
Arrestor Requirements
Designed for TRANSIENT performance, the strike.
NOT for continuous application of high voltage or current
Excessive power dissipation will cause failure
Industry Standard test waveform is 8 x 20 s Rises to peak in 8 s and falls to 50% in 20 s
Arrestors pass currents / clamp voltages for the 8 x 20 s test without self destructing
Don White Consultants
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 3427 Jan 2011_rev 2
Gas Tubes
Gas filled ceramic or glass cylinder Metal ends for circuit connection Often in a fuse-like holder, replaceable Fire on transient, divert current, clamp voltage to safe level
Don White Consultants
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 3527 Jan 2011_rev 2
Gas Tubes
Available with various firing and clamping voltages and current ratings
Operating voltage up to 250 VDC Transient strike voltage 500 VDC Clamp voltage 100 V High current conduction
Don White Consultants
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 3627 Jan 2011_rev 2
Varistors
Commonly called MOV - Metal Oxide Varistor A resistor that changes value when voltage is applied Resistance decreases with increasing voltage Clamps excessive voltage Conducts high surge currents to ground
Don White Consultants
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 3727 Jan 2011_rev 2
Surge Rated Zener Diodes
Low Operating Voltage Applications High surge current rating 100A / 10 s Clamps voltage to rated Zener Voltage Used singly or back to back Power supply rails, AC signal lines
General Semi
Vz = 24V
Vpwr = +15V
Vz = 24V
Vz = 24V
Vsig = +/1 15V
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 3827 Jan 2011_rev 2
System Approach
Combination MOV - Gas Tube protector for Lines
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 3927 Jan 2011_rev 2
Comparison’s
Comparison of common arrestors
Use Gas Tubes and then MOV’s closer to threat
Use Diode clamps closer to protected equipment
TYPE SURGE CURRENT NUMBER of SURGES RESPONSE TIMEGAS TUBE > 20 kA > 20 @ 20 kA 5 uS
MOV to 70 kA 1000 @ 100A 1 nSDIODE 100 A infinite @ 50 A 1 uS
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 4027 Jan 2011_rev 2
Coax Surge Suppressors
Placement in series with Coax Typically gas tube Place on grounded Service Entrance Plate
RF Parts $55
DX Engineering$55
MFJ $35
Alpha Delta$50
R & L Electronics$45
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 4127 Jan 2011_rev 2
Cable Suppressors
For use on rotors or other control lines Internal arrestor devices not known Place on Grounded Entrance Plate
Array Solutions$46
DX Engineering$133
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 4227 Jan 2011_rev 2
NSARC Antenna Protection
Copper Plate
Connected to Building
ground System
(big bare copper wire)
In Roof Top Equipment
Room
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 4327 Jan 2011_rev 2
NSARC Rotor Protection
Copper Plate
Connected to Building
ground System
(green wire)
In Roof Top Equipment
Room
- • - • - - • - - • • • • • • - • - - • • • - • • • • • - •
NSARC HF Operators 4427 Jan 2011_rev 2
Home System
RADIO
Service Entrance
Pan
el
Line Cord
Branch Circuit
PlugSocket
COAX
COAX
DIPOLE
TOWER
ENTRANCE PLATESurge Supressors
1. TOWER TO BE GROUNDED
2. TOWER COAX TO BE GROUNDED
3. ENTRANCE PLATE TO BE GROUNDED
4. RADIO TO BE GROUNDED TO ENTRANCE PLATE
5. RADIO IS GROUNDED TO ELECTRICAL SYSTEM BY LINE CORD CODE
6. ELECTRICAL SYSTEM IS GROUNDED AT SERVICE ENTRANCE BY CODE
7. SERVICE ENTRANCE IS GROUNDED BY CODE
8. GROUND SYSTEMS TO BE TIED TOGETHER
ORANGE WIRING OWNER INSTALLED
GREEN WIRING EQUIPMENT INSTALLED
SYSTEM GROUNDING
GROUND RODS
GROUND RODS
SERVICE ENTRANCE GROUND SYSTEM (Hydro)
Eqpt
Eqpt