FD FD MSFD 1. All dimensions are in millimeter unless otherwise specified. 2. All dimensions shall be checked on site before ductwork manufacture is commenced. 3. Each piece of ductwork shall be wiped inside and out before installation and all open ends shall be capped and sealed to prevent entrance of dirt during construction. 4. Ductwork shall not touch the building structure or building finishes directly,but shall be isolated with suitable spacer. 5. Ductwork shall be rigidly suspended or supported from building structure. 6. Necessary angle iron shall be provided for bracing of ductwork or equipment, and for supporting ductwork from building structure. 7. When changes or offsets are necessary, the required cross-sectional areas shall be maintained. 8. Support the vertical ducts installed in the various shafts at each floor level with galvanized supporting irons of approved size. 9. All openings required through floors, walls, partitions etc., for the duct system are provide in the exact location required. 10. All flexible connection will be an approved manufacturer, with ratings of fire spread,strength etc., listed by a recognized Testing Authority. 11. Volume dampers shall be installed in accessible locations at all branch connections and wherever necessary to adjust the flow of air to secure correct distribution. 12. The control dampers shall be installed as required for the proper functioning of the system. 13. Fire dampers shall be provided in locations required by ordinances and codes and as indicated the contract drawing. 14. All smoke extract ductworks should be fire rated and as per approved material SUPPLY AIR GRILL FIRE DAMPERS SYMBOLS DESCRIPTION FD MOTORIZED SMOKE AND FIRE DAMPER MSFD BOTTOM OF DUCT BOD VCD TYPICAL TYP FINISH FLOOR LEVEL FFL CONCOURSE LEVEL PL EXHAUST AIR DUCT SMOKE EXTRACT FIRE RATED DUCT LEGENDS AND ABBREVIATION S.NO. MAXIMUM SPACING KG/CU.M. 1 2 3 4 5 6 7 RECOMMENDED FUS 21/2.0 SPAN 350 MM 400 450 500 550 600 650 8 700 9 750 10 800 11 850 CHANNEL HVAC DUCTING - SUPPORT SPACING SCHEDULE HEIGHT WIDTH MM MM 150 150 200 250 300 350 400 12 900 13 950 450 500 550 600 650 700 750 250 300 350 400 450 500 550 600 650 700 750 200 SUPPORT M 3.0 3.0 3.0 3.0 3.0 3.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 INSULATION DENSITY 48 48 48 48 48 48 48 48 48 48 48 48 48 FUS 21/2.0 FUS 21/2.0 FUS 21/2.0 FUS 21/2.0 FUS 21/2.0 FUS 21/2.0 FUS 21/2.0 FUS 21/2.0 FUS 21/2.0 FUS 21/2.0 FUS 21/2.0 FUS 21/2.0 THREADED ROD SIZE MM M08 M08 M08 M08 M08 M08 M08 M08 M08 M08 M08 M08 M08 WASTE ROOM EXTRACT AIR DUCT BATTERY ROOM EXTRACT AIR DUCT STAIR CASE PRESSURISATION DUCTS WITH INSULATION SAD EAD SED WRD BRD SPD EXHAUST AIR GRILL BELL MOUTH VOLUME CONTROL DAMPER SUPPLY AIR DUCT SUPPORTS 14 1000 15 1100 16 1200 17 1400 18 1450 19 1500 800 900 1000 1200 1250 1300 20 1600 21 1700 22 1800 23 2000 24 2100 1400 1500 1600 1800 1900 25 2200 26 3200 2000 3000 800 900 1000 1200 1250 1300 1400 1500 1600 1800 1900 2000 3000 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.0 2.0 2.0 2.0 2.0 2.0 48 48 48 48 48 48 48 48 48 48 48 48 48 FUS 21/2.0 FUS 21/2.0 FUS 41/2.0 FUS 41/2.0 FUS 41/2.0 FUS 41/2.0 FUS 41/2.0 FUS 62/2.5 FUS 62/2.5 FUS 62/2.5 FUS 62/2.5 FUS 62/2.5 FUS 62D/2.5 M08 M08 M08 M08 M08 M08 M08 M10 M10 M10 M10 M10 M10 15. THE HVAC DUCTING SHALL BE GI DUCTING WITH THE GAUGES OF SHEETS, REINFORCEMENTS AND VANES COMPLYING WITH SMACNA STANDARDS WITH RESPECT TO THE SIZE OF THE DUCT. 16. THE HVAC DUCTING SHALL BE PROVIDED WITH INSULATION OF THICKNESS 25MM WITH 48KG/CU.M. DENSITY 17. THIS SUPPORT SPACING SGHEDULE IS NOT APPLICABLE FOR FIRE RATED DUCT 18. FOR THE CHANGE OF DIRECTION AND LEVELS, APPLICATION OF CONCENTRATED LOADS, JOINTS POINTS AND AT FITTINGS EXTRA SUPPORT SHALL BE PROVIDED AS PER THE SITE CONDITION 19. THREADED ROD SHALL BE HOT DIPPED GALVANIZED IRON TOILET EXHAUST AIR DUCT TED MSFD/FD SCHEDULE MSFD-E-S-7 100X100 1.78 MSFD-E-EA-6 100X100 2.04 MSFD-E-S-8 100X100 MSFD-E-EA-7 MSFD-E-S-9 0.60 MSFD-E-EA-8 0.80 TAG NECK SIZE (L/s) ROOM REFERENCE AIR FLOW IN (mm) TEL/IT MAIN ROOM 1 GAS BOTTLES 3 ELECTRICAL ROOM 2 TEL/IT MAIN ROOM 1 0.80 GAS BOTTLES 3 100X100 0.80 100X100 100X100 ELECTRICAL ROOM 2 MSFD-E-S-10 1.40 MSFD-E-EA-9 2.23 BOH CORRIDOR 3 200X200 WASTE 2 550X500 FD-E-S-11 0.40 FD-E-EA-10 0.60 TBD 100X100 100X100 TBD FD-E-S-12 2.12 FD-E-S-13 1.80 STAFF REST ROOM-F 300X250 FIRST AID ROOM 100X100 FD-E-EA-11 1.60 100X100 FIRST AID ROOM FD-E-S-14 1.85 FD-E-EA-12 2.07 STAFF ROOM -F FD-E-S-15 1.81 FD-E-EA-13 1.63 CELL 2 250X 250 FD-E-S-16 0.29 FD-E-EA-14 0.25 200X 200 FD-E-S-17 2.26 POLICE/QAF 300X250 STAFF ROOM -F 300X250 CELL 2 250X 250 CELL 1 CELL 1 200X 200 200X 200 FD-E-EA-15 2.04 FD-E-EA-13 1.63 FD-E-S-16 0.29 FD-E-EA-14 0.25 200X 200 FD-E-S-17 2.26 POLICE/QAF CELL 2 250X 250 CELL 1 CELL 1 200X 200 200X 200 POLICE/QAF 200X 200 FD-E-S-21 1.85 FD-E-EA-17 2.07 STAFF ROOM-M 300X250 FD-E-S-22 2.21 FD-E-S-23 1.99 300 X 300 FD-E-S-24 2.27 STAFF REST ROOM-M BOH CORRIDOR2 CLEANER FD-E-S-25 2.16 MSFD-E-S-26 2.11 MSFD-E-S-27 1.19 MSFD-E-EA-18 1.19 100X 100 MSFD-E-S-28 0.99 ELECTRICAL ROOM 1 UPS/BATTERY1 600X550 GAS BOTTLES 2 GARBAGE 200X 200 STAFF ROOM-M 300X250 350 X 300 300 X 300 GAS BOTTLES 2 100X 100 100X 100 MSFD-E-EA-19 1.99 ELECTRICAL ROOM 1 100X 100 FD-E-EA-21 1.91 DISABLED TOILETS FOR MEN 200X 200 MSFD-E-SE-03 1.54 1.27 450X450 BOH CORRIDOR 2 400 X 400 MSFD-E-SE-04 BOH CORRIDOR 3 1.27 400 X 400 MSFD-E-SE-05 BOH CORRIDOR 3 MSFD-E-SE-06 1.67 100X300 CORRIDOR MSFD-E-SE-07 CORRIDOR MSFD-E-SE-08 CORRIDOR MSFD-E-SE-09 CORRIDOR MSFD-E-SE-10 CORRIDOR 1.67 100X300 1.67 100X300 1.67 100X300 1.67 100X300 SUPPLY GRILL AND DIFFUSER SCHEDULE TAG NECK SIZE QTY (L/s) ROOM REFERENCE AIR FLOW TYPE IN (mm) SD-CL-E 84 32 GRILL SD-F-04 400X400 1610 1 EMERGENCY EXIT LOBBY 2 GRILL 800X750 VCD-E-EA-1 1 800X750 VCD-E-EA-2 1 250x200 SD-CL-E 84 32 GRILL 250x200 FOH MEP CORRIDOR FOH MEP CORRIDOR FOH MEP CORRIDOR FOH MEP CORRIDOR 12 13 14 15 16 B D A C FOR CONTINUATION REFER TO DRAWING No:M008-RGP-MHV-DWG-GWST050-CL-10001 FOR CONTINUATION REFER TO DRAWING No:M008-RGP-MHV-DWG-GWST050-CL-10003 1.2.13a STAFF ROOM-F SFT 2 COMBINED MEP SHAFT 2 1.3.27 TEL/IT MAIN ROOM 1 1.2.12 STAFF REST ROOM-F 1.3.17 WASTE ROOM 2 1.2.5a STAFF ROOM-M 1.2.4 STAFF REST ROOM-M 1.2.8 CLEANER 1.2.16 BOH CORRIDOR 2 1.2.17 BOH CORRIDOR 3 1.2.7 POLICE/QAF 1.2.9 GARBAGE ROOM 1.2.10 FIRST AID ROOM SFT 4 ELECTRICAL & PRES/TION SHAFT 2 1.2.11 T.B.D.2 1.3.6 UPS/ BATTERY 1 LFT 2 EE LIFT 2 1.EE2 EMERGENCY EXIT LOBBY 2 1.2.5b STAFF LOCKER-M 1.2.13b STAFF LOCKERS-F 1.2.6a CELL 1 1.2.6b CELL 2 STR2 EMERGENCY EXIT 2 1.3.58 GAS BOTTLES 3 1.3.55 ELECTRICAL ROOM 1 1.3.54 GAS BOTTLES 2 SFT 8 SHAFT 1 1.3.57 ELECTRICAL ROOM 2 1050x600 SAD BOD : 5730 600x600 SED BOD : 5730 1050x600 EAD BOD : 5730 1050x600 EAD BOD : 5730 1050x600 EAD BOD : 5730 150x200 EAD BOD : 4450 200x200 SAD BOD : 4900 1050x600 SAD BOD : 5730 600x600 SED BOD : 5730 400x400 TED BOD : 4760 200x200 SAD BOD : 5100 200x200 SAD BOD : 4510 400x400 TED BOD : 5440 ? ? BOD : ? 1050x600 EAD BOD : 5730 350x300 SAD BOD : 4950 350x350 TED BOD : 4930 1050x600 EAD BOD : 5730 550x500 SAD BOD : 5030 350x350 TED BOD : 4930 600x500 SAD BOD : 5460 200x200 EAD BOD : 4620 250x250 SAD BOD : 5080 550x800 SAD BOD : 5530 300x250 SAD BOD : 4950 300x300 EAD BOD : 5530 250x300 SAD BOD : 5050 1050x600 EAD BOD : 5730 550x500 WRD BOD : 4060 800x600 SAD BOD : 5630 550x500 SAD BOD : 4950 100x100 EAD BOD : 5150 100x100 EAD BOD : 5150 100x100 SAD BOD : 5150 250x250 SAD BOD : 3970 400x400 SED BOD : 4890 350x350 EAD BOD : 5530 150x150 EAD BOD : 5030 ? ? BOD : ? 100x100 SAD BOD : 5320 100x100 EAD BOD : 5320 100x100 EAD BOD : 5150 1050x600 EAD BOD : 5730 150x150 SAD BOD : 5460 100x100 SAD BOD : 5150 250ø SAD BOD : 4510 1050x600 SAD BOD : 5730 600x600 SED BOD : 5710 250ø SAD BOD : 4690 150x100 SAD BOD : 4890 200x200 EAD BOD : 5200 250ø SAD BOD : 4690 1050x600 EAD BOD : 5730 600x600 SED BOD : 5710 400x350 SAD BOD : 5170 200x200 EAD BOD : 5200 250x200 TED BOD : -3390 200x200 EAD BOD : 5200 350x300 SAD BOD : 4500 ? ? BOD : ? 500x650 SAD BOD : 5600 200x200 EAD BOD : 5530 200x200 EAD BOD : 5100 ? ? BOD : ? 250x200 SAD BOD : 5100 250ø SAD BOD : 4310 250ø SAD BOD : 4310 200x200 TED BOD : 4900 250x250 SAD BOD : 3940 250x250 SAD BOD : 3890 200x200 SAD BOD : 3950 ? ? BOD : ? 150x150 SAD BOD : 4010 250ø SAD BOD : 4510 600x600 SPD BOD : 5740 800x800 SPD BOD : 3010 250x250 SAD BOD : 3870 600x600 SED BOD : 5710 350x300 SAD BOD : 5190 200x200 SAD BOD : 4950 750x850 SAD BOD : 4420 900x900 SAD BOD : 5460 450x450 SED BOD : 3750 300x300 EAD BOD : 4520 600x600 BRD BOD : 3780 600x600 BRD BOD : 3780 150x150 EAD BOD : 5180 100x100 EAD BOD : 5200 100x100 SAD BOD : 5050 650x650 TED BOD : 4670 200x200 WRD BOD : 5120 100x100 SAD BOD : 5150 100x100 EAD BOD : 5310 1050x600 EAD BOD : 5730 11 VJ 450x450 SED BOD : 3750 300x300 EAD BOD : 4790 400x400 TED BOD : 5260 300x300 SAD BOD : 4950 800x600 SAD BOD : 5460 300x300 EAD BOD : 4520 300x200 WRD BOD : 4220 Typ: 12 VK Typ: 2 VL 250x250 SAD BOD : 3890 100x100 EAD BOD : 5150 300x300 TED BOD : 5050 0.278 200x200 TED BOD : 5000 200x200 TED BOD : 5000 300x300 TED BOD : 4950 0.256 0.128 0.128 650x650 TED BOD : 5370 FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD FD MSFD MSFD MSFD FD MSFD MSFD MSFD MSFD MSFD MSFD MSFD MSFD MSFD MSFD MSFD MSFD MSFD FD MSFD FD MSFD MSFD FD MSFD MSFD MSFD MSFD MSFD MSFD MSFD FD FD MSFD MSFD MSFD FD FD FD FD FD FD FD FD FD FD MSFD MSFD FD FD MSFD MSFD MSFD MSFD MSFD MSFD MSFD MSFD CONCOURSE LEVEL -3570 A 1050x600 SAD BOD : 5730 600x600 SED BOD : 5730 ROOF LEVEL 4300 CONCOURSE LEVEL -3570 C 450x300 TED BOD : 6520 550x800 SAD BOD : 5530 200x200 EAD BOD : 5530 ø150 CHWF ø150 CHWF ø125 CHWF ø35 CAT5 ø100 FSP ø42 BCWS ø25 SPR CONCOURSE LEVEL -3570 D 1050x600 SAD BOD : 5730 600x600 SED BOD : 5710 N QUIBLA 0 1 2 3 4 5 10 SCALE 1:100 METER N This drawing and any information or descriptive matter set out hereon is licensed to the Qatar Railways Company and is confidential and subject to copyright. It must not be disclosed, loaned, copied or used for manufacturing, tendering or for any other purpose without written permission. © Qatar Railways Company. DOHA FOR CONSTRUCTION APPROVAL S4 SCALES@A1 ISSUING OFFICE PROJECT NUMBER CLIENT APPROVAL A - APPROVED B - APPROVED WITH COMMENTS C - DO NOT USE STATUS PURPOSE OF ISSUE CONTRACTOR CONSULTANT: HOARE LEA QATAR LLC P.O. BOX 201834 DOHA QATAR PROJECT TITLE CLIENT DRAWING NUMBER REV PORR - SBG - HBK JOINT VENTURE P.O. BOX 207471 DOHA QATAR P.O. BOX 29988 DOHA QATAR © QATAR RAILWAYS COMPANY KEYPLAN REFERENCES: NOTES SUB CONTRACTOR PSC S.P.A. Viale Schiavonetti 270/E - 00173 ROMA TEL:06/72630488 FAX:06/72671393 Website: www.gruppopsc.com QATAR - ITALY Redco International W.L.L. TEL: 444-15426 FAX: 444-13786 Email: [email protected] DOHA, QATAR C1 ISSUED FOR CONSTRUCTION APPROVAL 13-11-2016 MN IM NN C2 13-11-2016 13-11-2016 1:100 D A 10 9 8 5 4 3 2 11 12 13 14 15 16 18 19 B C 7 17 6 C2 ISSUED FOR CONSTRUCTION IM JF MH 30-12-2017 30-12-2017 30-12-2017 8/10/2018 6:24:10 PM DESIGN & BUILD PACKAGE 2 GREEN LINE UNDERGROUND M008 M008-RGP-MHV-DWG-GWST050-CL-10002 QATAR RAILWAYS COMPANY SHOP DRAWINGS STATION - AL RAYYAN / AL QADEEM CONCOURSE LEVEL - VENTILATION SERVICES (STATION CENTRAL EAST) SHOP DRAWINGS STATION - AL RAYYAN / AL QADEEM CONCOURSE LEVEL - VENTILATION SERVICES (STATION CENTRAL EAST) SCALE : 1:100 SECTION-VJ SCALE : 1:50 SECTION-VK SCALE : 1:50 SECTION-VL SCALE : 1:50 M008-ARE-ARC-MD3-GWST050-CL-00101.S4.P7 M008-ARE-ARC-MD3-GWST050-ZZ-00101.S4.P11 M008-HLQ-MEP-MD3-GWST050-CL-00101.RVT M008-SSF-ARC-MD3-GWST050-CL-00301.S3.P16 M008-SSF-ARC-MD3-GWST050-ZZ-00101.S3.P19 M008-SSF-STR-MD3-GWST050-CL-00301.S3.P14 M008-SSF-STR-MD3-GWST050-ZZ-00101.S3.P24 M008-HLQ-MHV-DWG-GWST050-AA-10021-25 M008-HLQ-MHV-DWG-GWST050-AA-10031-32 M008-HLQ-MHV-DWG-GWST050-AA-10041 M008-HLQ-MHV-DWG-GWST050-AA-10051,53-54 M008-RGP-MHV-DWG-GWST050-AA-10061-63 SCHEMATICS AND DETAIL INSTALLATION REFERENCES :

sgkbimsolutions.com · Created Date: 8/10/2018 6:24:11 PM

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

  • FD

    FD

    MSF

    D

    1. All dimensions are in millimeter unless otherwise specified.2. All dimensions shall be checked on site before ductwork manufacture is commenced.3. Each piece of ductwork shall be wiped inside and out before installation and all open ends shall becapped and sealed to prevent entrance of dirt during construction.4. Ductwork shall not touch the building structure or building finishes directly,but shall be isolated withsuitable spacer.5. Ductwork shall be rigidly suspended or supported from building structure.6. Necessary angle iron shall be provided for bracing of ductwork or equipment, and for supportingductwork from building structure.7. When changes or offsets are necessary, the required cross-sectional areas shall be maintained.8. Support the vertical ducts installed in the various shafts at each floor level with galvanized supportingirons of approved size.9. All openings required through floors, walls, partitions etc., for the duct system are provide in the exactlocation required.10. All flexible connection will be an approved manufacturer, with ratings of fire spread,strength etc.,listed by a recognized Testing Authority.11. Volume dampers shall be installed in accessible locations at all branch connections and wherevernecessary to adjust the flow of air to secure correct distribution.12. The control dampers shall be installed as required for the proper functioning of the system.13. Fire dampers shall be provided in locations required by ordinances and codes and as indicated thecontract drawing.14. All smoke extract ductworks should be fire rated and as per approved material

    SUPPLY AIR GRILL

    FIRE DAMPERS

    SYMBOLS DESCRIPTION

    FDMOTORIZED SMOKE AND FIRE DAMPERMSFD

    BOTTOM OF DUCTBOD

    VCD

    TYPICALTYP

    FINISH FLOOR LEVELFFL

    CONCOURSE LEVELPL

    EXHAUST AIR DUCT

    SMOKE EXTRACT FIRE RATED DUCT

    LEGENDS AND ABBREVIATIONS.NO.

    MAXIMUM

    SPACING

    KG/CU.M.1

    2

    3

    4

    5

    6

    7

    RECOMMENDED

    FUS 21/2.0

    SPAN

    350

    MM

    400

    450

    500

    550

    600

    650

    8 700

    9 750

    10 800

    11 850

    CHANNEL

    HVAC DUCTING - SUPPORT SPACING SCHEDULE

    HEIGHT WIDTH

    MM MM

    150 150

    200

    250

    300

    350

    400

    12 900

    13 950

    450

    500

    550

    600

    650

    700

    750

    250

    300

    350

    400

    450

    500

    550

    600

    650

    700

    750

    200

    SUPPORT

    M

    3.0

    3.0

    3.0

    3.0

    3.0

    3.0

    2.5

    2.5

    2.5

    2.5

    2.5

    2.5

    2.5

    INSULATIONDENSITY

    48

    48

    48

    48

    48

    48

    48

    48

    48

    48

    48

    48

    48

    FUS 21/2.0

    FUS 21/2.0

    FUS 21/2.0

    FUS 21/2.0

    FUS 21/2.0

    FUS 21/2.0

    FUS 21/2.0

    FUS 21/2.0

    FUS 21/2.0

    FUS 21/2.0

    FUS 21/2.0

    FUS 21/2.0

    THREADEDRODSIZE

    MM

    M08

    M08

    M08

    M08

    M08

    M08

    M08

    M08

    M08

    M08

    M08

    M08

    M08

    WASTE ROOM EXTRACT AIR DUCT

    BATTERY ROOM EXTRACT AIR DUCT

    STAIR CASE PRESSURISATION

    DUCTS WITH INSULATION

    SAD

    EAD

    SED

    WRD

    BRD

    SPD

    EXHAUST AIR GRILL

    BELL MOUTH

    VOLUME CONTROL DAMPER

    SUPPLY AIR DUCT

    SUPPORTS14 1000

    15 1100

    16 1200

    17 1400

    18 1450

    19 1500

    800

    900

    1000

    1200

    1250

    1300

    20 1600

    21 1700

    22 1800

    23 2000

    24 2100

    1400

    1500

    1600

    1800

    1900

    25 2200

    26 3200

    2000

    3000

    800

    900

    1000

    1200

    1250

    1300

    1400

    1500

    1600

    1800

    1900

    2000

    3000

    2.5

    2.5

    2.5

    2.5

    2.5

    2.5

    2.5

    2.0

    2.0

    2.0

    2.0

    2.0

    2.0

    48

    48

    48

    48

    48

    484848

    48

    48

    48

    4848

    FUS 21/2.0

    FUS 21/2.0

    FUS 41/2.0

    FUS 41/2.0

    FUS 41/2.0

    FUS 41/2.0

    FUS 41/2.0

    FUS 62/2.5

    FUS 62/2.5

    FUS 62/2.5

    FUS 62/2.5

    FUS 62/2.5

    FUS 62D/2.5

    M08

    M08

    M08

    M08

    M08

    M08

    M08

    M10

    M10

    M10

    M10

    M10

    M10

    15. THE HVAC DUCTING SHALL BE GI DUCTING WITH THE GAUGES OF SHEETS, REINFORCEMENTS AND VANES COMPLYING WITH SMACNA STANDARDS WITH RESPECT TO THE SIZE OF THE DUCT.16. THE HVAC DUCTING SHALL BE PROVIDED WITH INSULATION OF THICKNESS

    25MM WITH 48KG/CU.M. DENSITY17. THIS SUPPORT SPACING SGHEDULE IS NOT APPLICABLE FOR FIRE RATED DUCT18. FOR THE CHANGE OF DIRECTION AND LEVELS, APPLICATION OF

    CONCENTRATED LOADS, JOINTS POINTS AND AT FITTINGS EXTRA SUPPORTSHALL BE PROVIDED AS PER THE SITE CONDITION

    19. THREADED ROD SHALL BE HOT DIPPED GALVANIZED IRON

    TOILET EXHAUST AIR DUCTTED

    MSFD/FD SCHEDULE

    MSFD-E-S-7 100X100 1.78

    MSFD-E-EA-6 100X100 2.04

    MSFD-E-S-8 100X100

    MSFD-E-EA-7

    MSFD-E-S-9 0.60

    MSFD-E-EA-8 0.80

    TAGNECK SIZE

    (L/s)ROOM REFERENCE AIR FLOW

    IN (mm)

    TEL/IT MAIN ROOM 1

    GAS BOTTLES 3

    ELECTRICAL ROOM 2

    TEL/IT MAIN ROOM 1

    0.80

    GAS BOTTLES 3 100X100 0.80

    100X100

    100X100ELECTRICAL ROOM 2

    MSFD-E-S-10 1.40

    MSFD-E-EA-9 2.23

    BOH CORRIDOR 3 200X200

    WASTE 2 550X500

    FD-E-S-11 0.40

    FD-E-EA-10 0.60

    TBD 100X100

    100X100TBD

    FD-E-S-12 2.12

    FD-E-S-13 1.80

    STAFF REST ROOM-F 300X250

    FIRST AID ROOM 100X100

    FD-E-EA-11 1.60100X100FIRST AID ROOM

    FD-E-S-14 1.85

    FD-E-EA-12 2.07

    STAFF ROOM -F

    FD-E-S-15 1.81

    FD-E-EA-13 1.63

    CELL 2 250X 250

    FD-E-S-16 0.29

    FD-E-EA-14 0.25

    200X 200

    FD-E-S-17 2.26POLICE/QAF

    300X250

    STAFF ROOM -F 300X250

    CELL 2 250X 250

    CELL 1

    CELL 1 200X 200

    200X 200

    FD-E-EA-15 2.04

    FD-E-EA-13 1.63

    FD-E-S-16 0.29

    FD-E-EA-14 0.25

    200X 200

    FD-E-S-17 2.26POLICE/QAF

    CELL 2 250X 250

    CELL 1

    CELL 1 200X 200

    200X 200

    POLICE/QAF 200X 200

    FD-E-S-21 1.85

    FD-E-EA-17 2.07

    STAFF ROOM-M 300X250

    FD-E-S-22 2.21

    FD-E-S-23 1.99

    300 X 300

    FD-E-S-24 2.27STAFF REST ROOM-M

    BOH CORRIDOR2

    CLEANER

    FD-E-S-25 2.16

    MSFD-E-S-26 2.11

    MSFD-E-S-27 1.19

    MSFD-E-EA-18 1.19

    100X 100

    MSFD-E-S-28 0.99ELECTRICAL ROOM 1

    UPS/BATTERY1 600X550

    GAS BOTTLES 2

    GARBAGE 200X 200

    STAFF ROOM-M 300X250

    350 X 300

    300 X 300

    GAS BOTTLES 2 100X 100

    100X 100

    MSFD-E-EA-19 1.99ELECTRICAL ROOM 1 100X 100

    FD-E-EA-21 1.91DISABLED TOILETSFOR MEN

    200X 200

    MSFD-E-SE-03 1.54

    1.27

    450X450BOH CORRIDOR 2

    400 X 400MSFD-E-SE-04 BOH CORRIDOR 3

    1.27400 X 400MSFD-E-SE-05 BOH CORRIDOR 3

    MSFD-E-SE-06 1.67100X300 CORRIDOR

    MSFD-E-SE-07 CORRIDOR

    MSFD-E-SE-08 CORRIDOR

    MSFD-E-SE-09 CORRIDOR

    MSFD-E-SE-10 CORRIDOR

    1.67100X300

    1.67100X300

    1.67100X300

    1.67100X300

    SUPPLY GRILL AND DIFFUSER SCHEDULE

    TAGNECK SIZE QTY

    (L/s)ROOM REFERENCE AIR FLOWTYPE

    IN (mm)

    SD-CL-E 84 32GRILL

    SD-F-04 400X400 1610 1EMERGENCY EXIT LOBBY 2 GRILL

    800X750VCD-E-EA-1 1

    800X750VCD-E-EA-2 1

    250x200

    SD-CL-E 84 32GRILL 250x200

    FOH MEP CORRIDOR

    FOH MEP CORRIDOR

    FOH MEP CORRIDOR

    FOH MEP CORRIDOR

    12 13 14 15 16

    B

    D

    A

    C

    FOR

    CONT

    INUA

    TION

    REF

    ER TO

    DRA

    WIN

    G No

    :M00

    8-RGP

    -MHV

    -DW

    G-GW

    ST05

    0-CL-1

    0001

    FOR

    CONT

    INUA

    TION

    REF

    ER TO

    DRA

    WIN

    G No

    :M00

    8-RGP

    -MHV

    -DW

    G-GW

    ST05

    0-CL-1

    0003

    1.2.13aSTAFF ROOM-F

    SFT 2COMBINED MEP SHAFT 2

    1.3.27TEL/IT MAIN ROOM 1

    1.2.12STAFF REST ROOM-F

    1.3.17WASTE ROOM 2

    1.2.5aSTAFF ROOM-M

    1.2.4STAFF REST ROOM-M

    1.2.8CLEANER

    1.2.16BOH CORRIDOR 2

    1.2.17BOH CORRIDOR 3

    1.2.7POLICE/QAF

    1.2.9GARBAGE ROOM

    1.2.10FIRST AID ROOM

    SFT 4ELECTRICAL & PRES/TION SHAFT 2

    1.2.11T.B.D.2

    1.3.6UPS/ BATTERY 1

    LFT 2EE LIFT 21.EE2

    EMERGENCY EXIT LOBBY 2

    1.2.5bSTAFF LOCKER-M

    1.2.13bSTAFF LOCKERS-F

    1.2.6aCELL 1

    1.2.6bCELL 2

    STR2EMERGENCY EXIT 2

    1.3.58GAS BOTTLES 3

    1.3.55ELECTRICAL ROOM 1

    1.3.54GAS BOTTLES 2

    SFT 8SHAFT 1

    1.3.57ELECTRICAL ROOM 2

    1050x600 SADBOD : 5730

    600x600 SEDBOD : 5730

    1050x600 EADBOD : 5730

    1050x600 EADBOD : 5730

    1050x600 EADBOD : 5730

    150x200 EADBOD : 4450

    200x200 SADBOD : 4900

    1050x600 SADBOD : 5730

    600x600 SEDBOD : 5730

    400x400 TEDBOD : 4760

    200x200 SADBOD : 5100

    200x200 SADBOD : 4510

    400x400 TEDBOD : 5440

    ? ?BOD : ?

    1050x600 EADBOD : 5730

    350x300 SADBOD : 4950

    350x350 TEDBOD : 4930

    1050x600 EADBOD : 5730

    550x500 SADBOD : 5030 350x350 TED

    BOD : 4930600x500 SAD

    BOD : 5460

    200x200 EADBOD : 4620

    250x250 SADBOD : 5080

    550x800 SADBOD : 5530

    300x250 SADBOD : 4950

    300x300 EADBOD : 5530

    250x300 SADBOD : 5050

    1050x600 EADBOD : 5730

    550x500 WRDBOD : 4060

    800x600 SADBOD : 5630

    550x500 SADBOD : 4950

    100x100 EADBOD : 5150

    100x100 EADBOD : 5150

    100x100 SADBOD : 5150

    250x250 SADBOD : 3970

    400x400 SEDBOD : 4890

    350x350 EADBOD : 5530

    150x150 EADBOD : 5030

    ? ?BOD : ?

    100x100 SADBOD : 5320

    100x100 EADBOD : 5320

    100x100 EADBOD : 5150

    1050x600 EADBOD : 5730

    150x150 SADBOD : 5460100x100 SAD

    BOD : 5150

    250ø SADBOD : 4510

    1050x600 SADBOD : 5730

    600x600 SEDBOD : 5710

    250ø SADBOD : 4690

    150x100 SADBOD : 4890

    200x200 EADBOD : 5200

    250ø SADBOD : 4690

    1050x600 EADBOD : 5730

    600x600 SEDBOD : 5710

    400x350 SADBOD : 5170

    200x200 EADBOD : 5200

    250x200 TEDBOD : -3390

    200x200 EADBOD : 5200

    350x300 SADBOD : 4500

    ? ?BOD : ?

    500x650 SADBOD : 5600

    200x200 EADBOD : 5530

    200x200 EADBOD : 5100

    ? ?BOD : ?

    250x200 SADBOD : 5100

    250ø SADBOD : 4310

    250ø SADBOD : 4310

    200x200 TEDBOD : 4900

    250x250 SADBOD : 3940

    250x250 SADBOD : 3890

    200x200 SADBOD : 3950

    ? ?BOD : ?

    150x150 SADBOD : 4010

    250ø SADBOD : 4510

    600x600 SPDBOD : 5740

    800x800 SPDBOD : 3010

    250x250 SADBOD : 3870

    600x600 SEDBOD : 5710

    350x300 SADBOD : 5190

    200x200 SADBOD : 4950

    750x850 SADBOD : 4420

    900x900 SADBOD : 5460

    450x450 SEDBOD : 3750

    300x300 EADBOD : 4520

    600x600 BRDBOD : 3780

    600x600 BRDBOD : 3780

    150x150 EADBOD : 5180

    100x100 EADBOD : 5200

    100x100 SADBOD : 5050

    650x650 TEDBOD : 4670

    200x200 WRDBOD : 5120

    100x100 SADBOD : 5150

    100x100 EADBOD : 5310

    1050x600 EADBOD : 5730

    11VJ

    450x450 SEDBOD : 3750

    300x300 EADBOD : 4790

    400x400 TEDBOD : 5260

    300x300 SADBOD : 4950

    800x600 SADBOD : 5460

    300x300 EADBOD : 4520

    300x200 WRDBOD : 4220

    Typ:

    12VK

    Typ:

    2VL

    250x250 SADBOD : 3890

    100x100 EADBOD : 5150

    300x300 TEDBOD : 5050

    0.278

    200x200 TEDBOD : 5000

    200x200 TEDBOD : 5000

    300x300 TEDBOD : 4950

    0.256

    0.128

    0.128

    650x650 TEDBOD : 5370

    FD

    FD

    FD

    FD

    FD

    FD

    FD

    FD

    FD

    FD

    FD

    FD

    FD FD

    FD FDFD FD

    FD

    FD FDFDFD FDFD

    FD

    FD

    FD

    MSFD

    MSFDMSFD

    FDMSFD

    MSFD

    MSFD

    MSFD

    MSFDMSFD

    MSFD

    MSFD

    MSFD

    MSFD

    MSFD

    MSFD

    MSFD FD

    MSFD

    FD

    MSFD

    MSFD

    FD

    MSFD

    MSFD

    MSFD

    MSFD

    MSFDMSFD

    MSFDFD

    FD

    MSFD MSFD

    MSFD FD

    FD

    FD

    FD

    FDFD

    FD FD

    FDFD

    MSFD

    MSFD

    FD

    FD

    MSFD

    MSFD

    MSFD

    MSFDMSFD

    MSFD MSFD

    MSFD

    CONCOURSE LEVEL-3570

    A

    1050x600 SADBOD : 5730

    600x600 SEDBOD : 5730

    ROOF LEVEL4300

    CONCOURSE LEVEL-3570

    C

    450x300 TEDBOD : 6520

    550x800 SADBOD : 5530

    200x200 EADBOD : 5530

    ø150 CHWF

    ø150 CHWFø125 CHWFø35 CAT5

    ø100 FSP

    ø42 BCWS

    ø25 SPR

    CONCOURSE LEVEL-3570

    D

    1050x600 SADBOD : 5730

    600x600 SEDBOD : 5710

    NQ

    UIB

    LA

    0 1 2 3 4 5 10

    SCALE 1:100 METER

    QIBLA

    N

    This drawing and any information or descriptive matter set out hereon is licensedto the Qatar Railways Company and is confidential and subject to copyright.It must not be disclosed, loaned, copied or used for manufacturing, tendering orfor any other purpose without written permission. © Qatar Railways Company.

    DOHA

    FOR CONSTRUCTION APPROVALS4

    SCALES@A1 ISSUING OFFICE PROJECT NUMBER

    CLIENT APPROVAL

    A - APPROVED

    B - APPROVED WITH COMMENTS

    C - DO NOT USE

    STATUS PURPOSE OF ISSUE

    CONTRACTOR

    CONSULTANT:

    HOARE LEA QATAR LLCP.O. BOX 201834 DOHAQATAR

    PROJECT

    TITLE

    CLIENT

    DRAWING NUMBER REV

    PORR - SBG - HBK JOINT VENTUREP.O. BOX 207471 DOHAQATAR

    P.O. BOX 29988 DOHAQATAR

    © QATAR RAILWAYS COMPANY

    KEYPLAN

    REFERENCES:

    NOTES

    SUB CONTRACTORPSC S.P.A.

    Viale Schiavonetti270/E - 00173 ROMA

    TEL:06/72630488FAX:06/72671393

    Website: www.gruppopsc.comQATAR - ITALY

    Redco International W.L.L.TEL: 444-15426FAX: 444-13786

    Email: [email protected], QATAR

    C1 ISSUED FOR CONSTRUCTION APPROVAL13-11-2016MNIMNN

    C2

    13-11-201613-11-2016

    1:100

    D

    A

    10985432 11 12 13 14 15 16 18 19

    B

    C

    7 176

    C2 ISSUED FOR CONSTRUCTIONIMJFMH 30-12-201730-12-2017 30-12-2017

    8/10/2018 6:24:10 PM

    DESIGN & BUILD PACKAGE 2GREEN LINE UNDERGROUND

    M008

    M008-RGP-MHV-DWG-GWST050-CL-10002

    QATAR RAILWAYS COMPANY

    SHOP DRAWINGS STATION - AL RAYYAN/ AL QADEEM CONCOURSE LEVEL -VENTILATION SERVICES (STATION

    CENTRAL EAST)

    SHOP DRAWINGS STATION - AL RAYYAN / AL QADEEM CONCOURSE LEVEL- VENTILATION SERVICES (STATION CENTRAL EAST)

    SCALE : 1:100

    SECTION-VJSCALE : 1:50

    SECTION-VKSCALE : 1:50

    SECTION-VLSCALE : 1:50

    M008-ARE-ARC-MD3-GWST050-CL-00101.S4.P7M008-ARE-ARC-MD3-GWST050-ZZ-00101.S4.P11M008-HLQ-MEP-MD3-GWST050-CL-00101.RVTM008-SSF-ARC-MD3-GWST050-CL-00301.S3.P16M008-SSF-ARC-MD3-GWST050-ZZ-00101.S3.P19M008-SSF-STR-MD3-GWST050-CL-00301.S3.P14M008-SSF-STR-MD3-GWST050-ZZ-00101.S3.P24

    M008-HLQ-MHV-DWG-GWST050-AA-10021-25M008-HLQ-MHV-DWG-GWST050-AA-10031-32M008-HLQ-MHV-DWG-GWST050-AA-10041M008-HLQ-MHV-DWG-GWST050-AA-10051,53-54M008-RGP-MHV-DWG-GWST050-AA-10061-63

    SCHEMATICS AND DETAIL INSTALLATION REFERENCES :

    M008-ARE-ARC-MD3-GWST050-CL-00101.S4.P7M008-ARE-ARC-MD3-GWST050-ZZ-00101.S4.P11M008-HLQ-MEP-MD3-GWST050-CL-00101.RVTM008-SSF-ARC-MD3-GWST050-CL-00301.S3.P16M008-SSF-ARC-MD3-GWST050-ZZ-00101.S3.P19M008-SSF-STR-MD3-GWST050-CL-00301.S3.P14M008-SSF-STR-MD3-GWST050-ZZ-00101.S3.P24

    M008-HLQ-MHV-DWG-GWST050-AA-10021-25M008-HLQ-MHV-DWG-GWST050-AA-10031-32M008-HLQ-MHV-DWG-GWST050-AA-10041M008-HLQ-MHV-DWG-GWST050-AA-10051,53-54M008-RGP-MHV-DWG-GWST050-AA-10061-63

    SCHEMATICS AND DETAIL INSTALLATION REFERENCES :

    http://www.gruppopsc.commailto:[email protected]