118
Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Aluminum) Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire Armoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire Armoured (Aluminum) Three-cores XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Three-cores XLPE Insulated PVC Sheathed Cable Unarmoured (Aluminum) Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire Armoured (Copper) Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire Armoured (Aluminum) Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape Armoured (Copper) Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape Armoured (Aluminum) Drum Handling Instructions 1 4 17 27 37 47 57 67 77 87 97 107 117

Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

  • Upload
    dokhue

  • View
    223

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Contents

Introduction

Technical Information

Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper)

Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Aluminum)

Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire Armoured (Copper)

Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire Armoured (Aluminum)

Three-cores XLPE Insulated PVC Sheathed Cable Unarmoured (Copper)

Three-cores XLPE Insulated PVC Sheathed Cable Unarmoured (Aluminum)

Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire Armoured (Copper)

Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire Armoured (Aluminum)

Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape Armoured (Copper)

Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape Armoured (Aluminum)

Drum Handling Instructions

1

4

17

27

37

47

57

67

77

87

97

107

117

Page 2: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Bahra Cables Company was established in 2008 to serve Saudi & GCC Markets. It is based in Bahra industrial city located 25km from Jeddah. Bahra Cables Factory occupies over 200,000 square me-ters of prime manufacturing space together with associated design offices, laboratories and storage area. It specializes in Manufacturing and Distributing Electric Cables.

Bahra Cables Company is committed to the production of the best product quality and service, utilizing cutting edge European Technology in its manufacturing. The core technologies in production processes, material applications and logistic procedures were provided by German experts with key functions being managed by German engineers.

The organization has a lean vertical management structure which is designed to integrate with a highly developed IT-based structure. This partnership allows the rapid flow of information through the man-agement chain and facilitates timely response in the best traditions of ‘hands on’ management. Bahra Cables Company has the flexibility to provide a versatile product range to serve the construction, elec-tric utilities, distribution, industrial, oil & gas and petrochemical sectors. The cables produced comply with both American standards ( UL, ANSI and ICEA ) and European standards ( IEC, BS, NF and VDE specifications.)

The scope of this catalogue is to provide an in depth view of the technical information of the medium voltage cables up to 36 kV, with XLPE insulation to IEC 60502-2 and BS 6622.

Introduction

1

Page 3: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Area:Bahra Cables Company has a total land area of about 200,000sqm at disposal.The built area, including offices and plant, of start up phase is more than 30,000sqm.The factory extension under construction is more than 20,000sqm already.The total available stock yard for storage is more than 20,000sqm

Product ScopeBAHRA CABLES COMPANY is committed to deliver the highest standard power cables and wires to the local market, GCC area and for export. To do so, Bahra Cables Company produces a versatile product range cover most of our customers needs:MV cables to IEC 60502-2 up to 18/30 (36) kV and to BS 6622 up to 19/33 (36) kV, which is covered in the catalogue .Additionally, other products described in separate publications covers:

• MV cables with Low Smoke and Fume-Zero Halogen LSF-ZH to BS 7835. • Flexible wires and cables up to 300 mm2 to IEC 60227 , BS 6004 & BS 6500 . • Building wires, THHN/THWN & THW to UL 83, with conductor sizes starting from 16 AWG. • Thermosetting insulated wires types XHHW-2 , XHHW, XHH, RHW-2, RHW &RHH to UL44• Building wires (NYA) to IEC 60227 and BS 6004, from 1.5 mm2 and above. • LV power Cables with PVC and XLPE insulation to IEC 60502-1, BS 5467, BS 7889 and UL 1277.• Low smoke and fume , zero halogen building wire ( LSFZH) to BS 7211 , with thermosetting insulation

which is alternative to wire type (NYA) , where the application requires higher standards of safety against the emission of smoke, fumes and toxic gases.

• LV cables with LSFZH, thermosetting insulation which under exposure of to fire generate low emission of smoke, fumes and toxic gases and zero halogens. The cables are produced according to BS 6724, IEC 60502-1 and tested to IEC 61034, IEC 60754 & IEC 60332.

• HV cables up to 132 kV to IEC 60840, and to ANSI / ICEA S-108-720, with conductor sizes up to 800 mm2.

The future product scope will be extended to Extra High Voltage cables up to 480 kV and conductor cross sections bigger than 2000 mm2.

Factory Machinery:All production machines are top of the line of the cables machinery suppliers. From start up with wire drawing lines to extrusion lines, to assembly machines up to the laboratories and the final test fields , all technical equipment is provided with the highest European standards of electronic control equip-ment and measuring devices which insures that the requirements of different quality standards are met. All machines/production lines are prepared for data communication and data exchange bottom up and top down using the most modern decentralized control software at the lines (PLC) combined with an efficient central steering and a planning system focused on the demand of cable manufacturers. This way, full traceability will be guaranteed from production start to end, by being able to follow up the machines involved and the material used.

2

Page 4: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Logistics:All material flow in BCC from incoming raw material up to outgoing cables will be planned and con-trolled by a complete software system. Herein a classical ERP system will be enhanced and completed by the most modern MES (Manufacturing Executive System) which has a unique focus on the specific problematic issues of cables manufacturing with longitudinal products being winded up and winded off.

The Manufacturing Executive System - MES - covers:PlanningThe planning system is active on several levels. For the proper function, all master data (material properties, dimensions, etc.) are saved and permanently maintained in the central database based on • Cable design • Planning of Sales Orders • Planning of Production Orders

Data CommunicationThe exchange of data is important in several areas.• Incoming inspection• Raw Materials - Status quo of production orders• Finished goods• Shipping status

3

Page 5: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Bahra Cables Company is willing to provide advice and assistance on all matters concerning XLPE insulated power cables. Please contact the Technology Department for any query.

QUALITY IS OUR MAIN TARGET

Bahra Cable Company is born to be one of the leading Power Cables Manufacturers in Saudi Arabia and the GCC area. We are working in different axes to completely fulfill customers satisfaction which is the milestone of our business, such axes are:

1. Product quality complying with the local and international standards

2. Product Reliability is starting from the time of product design to fit for the intended application and environmental conditions, to the selection of the raw material from only the highest class suppliers with internationally trusted reputation. Our state of art testing equipments and the strict quality procedures ensure the product quality and integrity so we can guarantee that our cables are defect free and suitable for the intended application through the cable service lifetime.

3. High performance of the product and service through cooperation between experienced staff from Germany and local experts who are aware of the local market requirements and the highest international standards of cables manufacturing. Such cooperation in know-how is invested to provide our customer with the best service and support.

4. Bahra Cables Company’s Quality Management System conforms to the ISO 9001: 2008 International Management Quality System Standard with scope of Design and Manufacturing of Electrical Power Cables and Wires. BCC is certified by American Systems Registrar (ASR), ANAB Accredited.

5. Bahra Cables Company is frequently testing its products at internationally reputable labs, diversity of products have been tested and confirmed compliance to the international standard at KEMA, IPH, SAG(Berlin), BSI and BASEC Labs covers all the company product range.

Technical InformationGeneral

4

Page 6: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

MV CABLES PRODUCT RANGE

MV Cables can be categorized with different criteria, for example the voltage rate, Conductor Mate-rial and Armouring type. This catalogue is intended for Medium Voltage Power Cables, Aluminum and Copper conductors of voltage range up to and includes 36 kV

CABLE TYPES 1) Copper Conductor Cables 2) Aluminum Conductor Cables 3) Armoured / Non-armoured Cables4) Voltage range U0/ U / (Umax) as : a. 3.6/6 (7.2) kV b. 6.0/10(12) kV c. 8.7/15(17.5) kV d. 12/20(24) kV e. 18/30(36) kVSingle core cables up to and including 800 mm23 core cables up to and including 400 mm2

APPLICABLE STANDARDS

IEC 60502 (Part 2) “XLPE insulated cables” Single Core / 3 coreBS 6622 for XLPE insulated armoured cablesAny other customer of International standards e.g. UL 1072, ANSI/ACEA, etc...

Technical InformationGeneral

5

Page 7: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

1. NOMINAL VOLTAGEThe Nominal voltage is to be expressed with two values of alternative current Uo/U in V (volt)Uo/U : Phase to earth voltage Uo : Voltage between conductor and earth U : Voltage between phases (conductors)

2. RESISTANCEThe Values of conductor DC resistance are dependent on temperature as given by :Rt = R20 x [l + α 20(t - 20)] Ω/kmRt : conductor DC resistance at t ° C Ω/kmR20 : conductor DC resistance at 20 ° C Ω/kmt : operating temperature ° Cα : resistance temperature coefficient = 0.00393 for copper = 0.00403 for aluminum Generally DC resistance is based on IEC 60228 To calculate AC resistance of the conductor at the operating temperature as the following:RAC = Rt x[ 1+ ys + yp ]ys : skin effect factoryp : proximity effect Generally AC resistance is based on IEC 60287

3. CAPACITANCE μF/km C : Operating capacitance μF/km D : Diameter over insulation mmd : Conductor diameter mmЄr :Relative permittivity of insulation material Єr = 4.8 for PVC Єr = 2.3 for XLPE

4. INDUCTANCEL = K + 0.2 ln ( 2s/d) mH/kmL : Inductance mH/kmK :Constant depends on number of wires of conductord: Conductor diameter S : Axial spacing between cables ( Trefoil formation ) S : 1.26 x axial spacing between cables( Flat formation)

5. REACTANCE The inductive reactance per phase of a cable may be obtained by the formula: X = 2 π f L x 10-3 Ω/km X: Reactance Ω/km f : Frequency Hz L : Inductance mH/km

6. IMPEDANCE

Z = Ω/kmZ : Phase impedance of cable Ω/kmRac : AC resistance at operating temperature Ω/kmX : Reactance Ω/km

Electrical Technical InformationCable Parameters Calculation Guide

22 XR ac +

6

Page 8: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

7. INSULATION RESISTANCE 1000 * LN (D/d) R =

2 * π

R : Insulation resistance at 20° C MΩ.kmD : Insulated conductor diameter mmd : Conductor diameter mm

8.CHARGING CURRENT I = Uo x 2Π f x C x 10-6

I : Charging current A/kmUo : voltage between phase and earth VC : Capacitance to neutral μF/km

9. DIELECTRIC LOSSESD = 2 π f C Uo2 tan δ 10-6 watt/km/phase D : Dielectric losses watt/km/phase Uo : Voltage between phase and earth VC : Capacitance to neutral μF/km tan δ : Dielectric power factor

10. CABLE SHORT CIRCUIT CAPACITYISC(t) = ISC(1) / √t kA ISC(t): Short circuit for t second kAISC(1): Short circuit for 1 second kA

Data about short circuit are tabulated in construction tables 11. VOLTAGE DROPWhen the current flows in conductor, there is a voltage drop between the ends of the conductor. For low voltage cable network of normal operation, it is advisable of a voltage drop of 3-5 %.To calculate voltage drop as the following: 1- for single phase circuit: Vd = 2I ι ( R cosφ + X sinφ ) 2- for three phase circuit : Vd = √3 I ι ( R cosφ + X sinφ ) Vd : Voltage drop V I : Load current A R : AC resistance Ω/km X : Reactance Ω/km ι : Length kmcosφ : Power factor

Electrical Technical InformationCable Parameters Calculation Guide

7

Page 9: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

1.0 CONDUCTORS A conductor is the metallic part of cables that is carrying the electric current

Conductor materials are : 1.1 Plain annealed or tin coated copper conductor (to BS EN 1977, ASTM B3, ASTM B49 & ASTM B 33) 1.2 Aluminum (to ASTM B233)

The conductor structure is complying to the requirements of BS EN 60228 (IEC 60228) class 2 stranded, non Compacted , compacted or compacted sector shaped conductors. The shape codes are rmc, round compacted stranded

2.0 CONDUCTOR SEMI-CONDUCTIVE - INSULATION – INSULATION SEMI-CONDUCTIVEThe three layers are extruded in one step using the state-of-art Centenary Continuous Vulcanization ( CCV ) technology with advanced automatic concentricity control system which can guarantee the highest quality of the insulated conductor. 2.1 Conductor Semi-conductive (Stress control layer)

Over the metallic conductor, an extruded layer of cross linked semi-conducting compound is applied. This layer acts to smooth out any irregularities and thus re-duces the probability of protrusions into the insulating layer. Such protrusions into the insulation or into the semi-conducting layer increase the localized stress that may exceed the long-term breakdown strength of the insulation, so the semi-conductive layer is acting as a stress control layer.

2.2 Insulation:Each core conductor is insulated by extruded cross-linked low density polyethylene (GP 8) conforming to BS 7655: Section 1.3 and IEC 60502-2 , the insulating com-pound is a developed material suitable for application through CCV technology. Upon customer request, a tree resistant’ XLPE (TR-XLPE) insulation is used.

Medium Voltage Cables Technical InformationCable Structure

8

Page 10: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

2.3 Insulation Semi-conductive -Stress Relief LayerOver the insulation, an extruded layer of cross linked semi-conducting compound is applied. This layer, which has a very smooth surface, is a transition form the insulating material where the electric field exists to a conductive metallic screen, where the electric field is zero, so it will reduce the stress enhancement at the insulation layer.The insulation’s shield layer could be bonded to the insulation or strippable type for easily removable to facilitate splicing and terminating. The volume resistivity of this external layer is limited to 500 meter-ohms.

3.0 Metallic Screening / Shielding The metallic screening over insulation semi-conductive layer is necessary to cancel out the electric field outside the cable and to provide a low resistance path for charging current to flow to ground. When the screening bonded to earth it will also carry out the short circuit fault current.

4.0 CABLE ASSEMBLY

For 3 core cable, the screened cores will have identification tape ( Red , Yellow & Blue) under the mettelic scrren, then the cores are laid up together to form the laid up cable cores. A non-hygro-scopic polypropylene filler is applied between laid up cores to provide a circular shape to the cable.

Polypropylene tape(s) or PETP (Polyester) tape(s) is used as a barrier tape over the laid up cores. Such tape(s) will bind the cores together and prevent them from opening out, acts as a separator between different polymers used in a cable and works as a heat barrier between the cores and the extruded bedding. 5.0 BEDDING

Extruded bedding layer serves as a bedding under cable Armouring to protect the laid up cores and as a separation sheath. The bedding is an extruded PVC type 9 Compound as per BS 7655-4.2 or suitable PE type.

The insulation thickness is selected based on the designated voltage rate complying with IEC 60502-2 & BS 6622, which as the following table:

Medium Voltage Cables Technical InformationCable Structure

Nominal cross-sectional

areaof conductor

mm2

Nominal thickness of insulation at rated voltageU0/U (Um)

3,6/6 (7,2) kVMm

6/10 (12) kVmm

8.7/15 (17.5) kVmm

12/20 (24) kVmm

18/15 (36) kVmm

up to & include185 2.5 3.4 4.5 5.5 8.0

240 2.6 3.4 4.5 5.5 8.0

300 2.8 3.4 4.5 5.5 8.0

400 3.0 3.4 4.5 5.5 8.0

500 to 1 600 3.2 3.4 4.5 5.5 8.0

9

Page 11: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

6.0 ARMOURING

The cable intended for tray application is protected enough and does not require armour in general, while it is recommended to have armour for the cable intended for Direct Burial Application. The armour provides mechanical protection against crushing forces. Armour also can serve as an Earth Continuity Conductor (ECC). The Armouring type could be: 6.1 One layer of Galvanized Round Steel Wire to BS EN 10257 is applied helically over the bedding. 6.2 Double Galvanized Steel Tape applied over each other, with a suitable overlap, one layer covers the gap of the other layer. 6.3 Aluminum wire armouring for a single core cable acts as non magnetic armour

7.0 OUTERSHEATH (OUTERJACKET)

7.1 It is the outer protection part of the cable against the surrounding environment. 7.2 Several materials can be used as oversheath based on the intended application.

General purpose 90 °C PVC Type ST2 compound as specified in IEC 60502-2, or its equivalent PVC Type 9 to BS 7655-4.2.Mediumor High density PolyethyleneMDPE / HDPE compound fulfill and exceed the requirements of Type ST7 IEC 60502-2 for cables that require to be abrasion resist-ant, protected against water ingress and strong Environmental Stress Crack Resistant (ESCR). Halogen Free Flame Retardant (HFFR) compounds complying with Types LTS 1 & LTS 4 to BS 7655: section 6 for cables installed in intrinsically safe locations and where the cables require to be low smoke, low fume and low toxic gas emitting in case of fire. Cables to this category are complying with the requirements of BS 7835.The standard sheath color is Black or Red which has a suitable UV proved additive is added to ensure resistance to sunlight. When the cable is required to ant-termite / anti-vermin, a special additive is added to the sheathing compound.

A layer of graphite coated is applied upon customer request.All cables produced at Bahra Cables Company with PVC or Halogen free jackets are complying with the flame retardant test to IEC 60332-1. Whenever a requirement for more severe tests as IEC 60332-3 is needed, a jacketing compound with Oxygen index value more than 30% will be used.

Medium Voltage Cables Technical InformationCable Structure

10

Page 12: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

1. A recommended minimum bending radius is included in Table 2; the cable jacket may be damaged if the cable is bended in diameters less than these values.

Table 2: Recommended minimum bending radius

D: Cable diameter

Type of cableMinimum Bending Radius( mm)

During Installation Adjacent to joints or terminals

Single Core Cables 15D 12D

Three Core Cables 12D 10D

Medium Voltage Cables Technical InformationCable Structure

11

Page 13: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

1. CURRENT RATING ASSUMPTIONS The calculation of the current ratings, Current rating equations (100% load factor) and calcu-lation of losses are based on IEC 60287 series , and the values of current ratings are vervied with the tabulated value in IEC 60502-2.The calculation is based on the standard dimensions of cables based on IEC 60502-2, which may have a slight difference from the applied cable dimension which are following the best common manufacturing practices. The values given in the tables are for one circuit installed thermally isolated from other circuits or any other heat source. The basis of the standard conditions is the climate conditions of the Kingdom of Saudi Arabia, which are :

Ambient Air Temperature : 40 °C Ambient Ground Temperature : 35°C Depth of laying in ground : 0.80 m Soil Thermal Resistivity : 1.2 °K.m/W

For other installation conditions or any value of different air/ ground temperature, depth of laying, different soil thermal resistivity the customer is divided to multiply the tabulated cur-rent rating by the de-rating factor values as in tables 3 to 5 for direct buried cables in ground and tables 6 to 12 for cables installed in duct

Technical InformationElectrical Characteristics Current Rating

12

Page 14: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Table 3 : Rating factors for ground temperature variation

1. INSTALLATION CONDITIONS FOR DIRECT BURIAL CABLES For a cable installed direct buried, the following tables will be used to calculate the current rates based on the actual soil thermal resistivity, Ground ambient temperature and the Depth of Laying.

Table 4 : Rating factors for depth of laying

Table 5 : Rating factors for variation in thermal resistivity of soil (average values)

Technical InformationElectrical Characteristics Current Rating

GroundTemperature 15 °C 20 °C 25 °C 30 °C 35°C 40°C 45 °C 50 °C 55 °C

Rating Factors 1.17 1.12 1.08 1.04 1.00 0.96 0.90 0.85 0.80

Depth of Laying

Single Core Cables

Three Core Cables Nominal conductor size

mm2≤ 185 mm2 > 185 mm2

0.50 1.04 1.06 1.040.60 1.02 1.04 1.030.80 1.00 1.00 1.001.00 0.98 0.97 0.981.25 0.96 0.95 0.961.50 0.95 0.93 0.952.0 0.93 0.90 0.932.5 0.91 0.88 0.913.0 0.90 0.86 0.90

Rating FactorsSoil Thermal Resistivity ( °C m / W )

0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0

Single Core Cables

≤ 50 mm2 1.19 1.16 1.11 1 0.91 0.83 0.77 0.69

> 50 mm2 & ≤ 185 mm2 1.21 1.16 1.13 1 0.92 0.82 0.76 0.69

240 mm2 and above 1.23 1.17 1.17 1 0.92 0.82 0.76 0.68

Three Core Cables

≤ 50 mm2 1.15 1.12 1.09 1 0.89 0.85 0.80 0.72

> 50 mm2 & ≤ 185 mm2 1.16 1.13 1.09 1 0.89 0.85 0.80 0.72

240 mm2 and above 1.17 1.14 1.10 1 0.90 0.85 0.79 0.72

13

Page 15: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Depth of Laying

Single Core Cables

Three Core Cables Nominal conductor size mm2

≤ 185 mm2 >185 mm2

0.50 1.04 1.06 1.030.60 1.02 1.03 1.020.80 1.00 1.00 1.001.00 0.98 0.97 0.991.25 0.96 0.95 0.971.50 0.95 0.93 0.962.0 0.93 0.91 0.942.5 0.91 0.89 0.933.0 0.90 0.88 0.92

Ground Temperature 15 °C 20 °C 25 °C 30°C 35°C 40°C 45 °C 50 °C 55 °C

All Cable Types 1.16 1.13 1.09 1.03 1 0.95 0.89 0.84 0.79

Technical InformationElectrical Characteristics Current Rating

2. INSTALLATION CONDITIONS FOR CABLES IN DUCTS A duct is an enclosure of metal or insulating material other than conduits or cable trunking, intended for the protection of cables which are drawn in after erection of the ducting.

Table 6 : Rating factors for ground temperature variation

Table 7: Rating factors for depth of laying (to center of cable or trefoil group of cables)

Table 8 : Rating factors for variation in thermal resistivity of soil (average values)

Rating FactorsSoil Thermal Resistivity ( °C m / W )

0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0

Single Core Cables

≤ 50 mm2 1.13 1.10 1.07 1 0.96 0.87 0.8 0.76

> 50 mm2 & ≤ 185 mm2 1.14 1.10 1.07 1 0.95 0.87 0.79 0.74

240 mm2 and above 1.15 1.11 1.08 1 0.95 0.85 0.79 0.73

Three Core Cables

≤ 50 mm2 1.16 1.12 1.08 1 0.97 0.87 0.80 0.76

> 50 mm2 & ≤ 185 mm2 1.17 1.13 1.08 1 0.96 0.87 0.79 0.73

240 mm2 and above 1.18 1.13 1.09 1 0.96 0.85 0.79 0.72

14

Page 16: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Number of Circuits

Nil (Cables Touching) Cable to Cable Clearance A

Trefoil Flat Laying 0.15m 0.30m 0.45m 0.60m

2 0.78 0.81 0.81 0.85 0.88 0.90

3 0.66 0.70 0.71 0.76 0.80 0.83

4 0.61 0.64 0.64 0.72 0.76 0.80

5 0.56 0.60 0.60 0.68 0.73 0.77

6 0.53 0.57 0.57 0.66 0.72 0.76

Technical InformationElectrical Characteristics Current Rating

Table 9: Group rating factors for circuits of three single core cables in trefoil or laid flat touching, in horizontal formation

Table 10: Group rating factors for multi-core cables in horizontal formation

A Spacing

A Spacing

Number of Cables in Group

Cable to Cable Clearance A

Touching 0.15m 0.30m 0.45m 0.60m

2 0.81 0.84 0.87 0.89 0.91

3 0.70 0.73 0.78 0.82 0.85

4 0.63 0.68 0.74 0.78 0.82

5 0.59 0.63 0.70 0.75 0.79

6 0.55 0.60 0.68 0.74 0.77

A Spacing

15

Page 17: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Number of Circuits

Cable to Cable Clearance A Touching 0.45m 0.60m2 0.86 0.88 0.903 0.75 0.80 0.834 0.70 0.76 0.805 0.67 0.73 0.776 0.64 0.71 0.76

Technical InformationElectrical Characteristics Current Rating

Table 11: Group rating factors for single core cables in trefoil Single way ducts, horizontal (average values)

Table 12: Group rating factors for multicore cables in single way ducts horizontal formation (average values)

Table 13: Rating factors for Air temperature variation

A Spacing

Number of Cables in

Group

Cable to Cable Clearance A

Nil Cables Touching 0.30m 0.45m 0.60m

2 0.87 0.89 0.92 0.93

3 0.78 0.82 0.85 0.87

4 0.73 0.78 0.82 0.85

5 0.69 0.75 0.79 0.83

6 0.67 0.73 0.78 0.82

A Spacing

3. INSTALLATION CONDITIONS FOR CABLES IN AIR

Air Temperature 25 °C 30 °C 35 °C 40 °C 45 °C 50 °C 55 °C 60 °C

Rating factors 1.19 1.10 1.05 1.00 0.96 0.90 0.84 0.78

16

Page 18: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

21010001 25 6.2 2.5 16 1.6 20 640 100021010002 35 7.2 2.5 16 1.6 22 760 100021010003 50 8.3 2.5 16 1.7 23 880 100021010004 70 10 2.5 16 1.7 25 1170 100021010005 95 11.8 2.5 16 1.8 27 1390 100021010006 120 13.1 2.5 16 1.8 28 1650 100021010007 150 14.7 2.5 25 1.9 30 2020 100021010008 185 16.1 2.5 25 1.9 32 2400 100021010009 240 18.7 2.6 25 2.0 34 2960 100021010010 300 20.8 2.8 25 2.1 37 3590 50021010011 400 24 3.0 35 2.2 41 4560 50021010012 500 27 3.2 35 2.3 45 5650 50021010013 630 30.8 3.2 35 2.4 49 7150 500

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

21020001 25 6.2 2.5 1.5 18 560 100021020002 35 7.2 2.5 1.6 20 700 100021020003 50 8.3 2.5 1.6 21 800 100021020004 70 10 2.5 1.7 23 1095 100021020005 95 11.8 2.5 1.7 25 1300 100021020006 120 13.1 2.5 1.8 26 1570 100021020007 150 14.7 2.5 1.8 28 1900 100021020008 185 16.1 2.5 1.9 30 2200 100021020009 240 18.7 2.6 2.0 32 2750 100021020010 300 20.8 2.8 2.0 35 3300 50021020011 400 24 3.0 2.1 39 4350 50021020012 500 27 3.2 2.2 43 5450 50021020013 630 30.8 3.2 2.3 47 7000 500

Single-core XLPE Insulated PVC Sheathed Cable UnarmouredCU / XLPE / PVC Copper Conductor - Copper Wire Screened 3.6/6 (7.2) kV

CU / XLPE / PVC Copper Conductor - Copper Tape Screened 3.6/6 (7.2) kV

17

Page 19: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / PVC Copper Conductor Unarmoured - 3.6/6 (7.2) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω / km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Approximate AC resistance of Conductor @ 90°C

Ω / km 0.927 0.668 0.494 0.342 0.247 0.196 0.160 0.129 0.099 0.0804 0.0647 0.0527 0.0434

Inductance at 60 Hz mH/Km 0.442 0.424 0.408 0.385 0.377 0.362 0.355 0.342 0.330 0.323 0.311 0.308 0.297

Reactance at 60 Hz Ω / km 0.17 0.16 0.15 0.15 0.14 0.14 0.13 0.13 0.12 0.12 0.12 0.12 0.11

Capacitance μF/Km 0.25 0.28 0.31 0.35 0.39 0.43 0.47 0.52 0.56 0.58 0.60 0.63 0.75

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20 71.50 90.09

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.35 0.37 0.39 0.44 0.47 0.51 0.54 0.58 0.64 0.70 0.77 0.86 0.95

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 153 175 211 250 274 315 370 415 470 530 595 680 740

Flat Formation(Approx.) A 157 181 218 258 282 323 378 420 473 525 550 640 685

2- Laid in free air

Trefoil Formation (Approx.) A 163 205 245 269 329 379 430 494 583 669 769 860 1000

Flat Formation(Approx.) A 178 217 260 324 395 455 509 580 678 770 854 895 1035

Voltage Drop per phase V/A/km 0.842 0.632 0.488 0.362 0.283 0.239 0.208 0.180 0.154 0.137 0.122 0.111 0.102

Minimum Bending radius mm 300 330 345 375 405 420 450 480 510 555 615 675 735

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

18

Page 20: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath PackagingCross

Sectional Area

Nominalmm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%22010001 25 6.2 3.4 16 1.6 22 780 100022010002 35 7.2 3.4 16 1.6 23 870 100022010003 50 8.3 3.4 16 1.7 25 1020 100022010004 70 10 3.4 16 1.7 26 1240 100022010005 95 11.8 3.4 16 1.8 28 1530 100022010006 120 13.1 3.4 16 1.8 30 1780 100022010007 150 14.7 3.4 25 1.9 32 2180 100022010008 185 16.1 3.4 25 1.9 33 2250 100022010009 240 18.7 3.4 25 2.0 36 3190 100022010010 300 20.8 3.4 25 2.1 38 3800 50022010011 400 24 3.4 35 2.2 42 4750 50022010012 500 27 3.4 35 2.3 46 5840 50022010013 630 30.8 3.4 35 2.4 51 7340 500

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

22020001 25 6.2 3.4 1.5 20 680 100022020002 35 7.2 3.4 1.6 22 770 100022020003 50 8.3 3.4 1.6 23 890 100022020004 70 10 3.4 1.7 25 1130 100022020005 95 11.8 3.4 1.7 27 1420 100022020006 120 13.1 3.4 1.8 28 1680 100022020007 150 14.7 3.4 1.8 30 2150 100022020008 185 16.1 3.4 1.9 32 2360 100022020009 240 18.7 3.4 2.0 34 3100 100022020010 300 20.8 3.4 2.0 37 3610 50022020011 400 24 3.4 2.2 41 4450 50022020012 500 27 3.4 2.2 45 5500 50022020013 630 30.8 3.4 2.4 49 7080 500

Single-core XLPE Insulated PVC Sheathed Cable UnarmouredCU / XLPE / PVC Copper Conductor - Copper Wire Screened 6/10(12) kV

CU / XLPE / PVC Copper Conductor - Copper Tape Screened 6/10(12) kV

19

Page 21: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / PVC Copper Conductor Unarmoured - 6/10 (12) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω / km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Approximate AC resistance of Conductor @ 90°C

Ω / km 0.927 0.668 0.494 0.342 0.247 0.196 0.160 0.129 0.099 0.0804 0.0647 0.0527 0.0434

Inductance at 60 Hz mH/Km 0.460 0.440 0.420 0.408 0.382 0.375 0.363 0.354 0.340 0.330 0.319 0.309 0.295

Reactance at 60 Hz Ω / km 0.17 0.17 0.16 0.15 0.14 0.14 0.14 0.13 0.13 0.12 0.12 0.12 0.11

Capacitance μF/Km 0.20 0.23 0.25 0.29 0.30 0.33 0.37 0.40 0.45 0.49 0.54 0.60 0.70

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20 71.50 90.09

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.38 0.41 0.44 0.48 0.52 0.55 0.58 0.62 0.68 0.72 0.79 0.87 0.96

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 153 175 211 250 274 315 370 415 470 530 595 680 740

Flat Formation(Approx.) A 157 181 218 258 282 323 378 420 473 525 550 640 685

2- Laid in free air

Trefoil Formation (Approx.) A 163 205 245 269 329 379 430 494 583 669 769 860 1000

Flat Formation(Approx.) A 178 217 260 324 395 455 509 580 678 770 854 895 1035

Voltage Drop per phase V/A/km 0.846 0.635 0.490 0.364 0.284 0.242 0.210 0.183 0.156 0.138 0.123 0.111 0.103

Minimum Bending radius mm 330 345 375 390 420 450 480 495 540 570 630 690 765

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

20

Page 22: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

23010001 25 6.2 4.5 16 1.7 25 870 100023010002 35 7.2 4.5 16 1.7 26 980 100023010003 50 8.3 4.5 16 1.7 27 1120 100023010004 70 10 4.5 16 1.8 29 1380 100023010005 95 11.8 4.5 16 1.8 31 1640 100023010006 120 13.1 4.5 16 1.9 32 1910 100023010007 150 14.7 4.5 25 1.9 34 2300 100023010008 185 16.1 4.5 25 2.0 36 2700 100023010009 240 18.7 4.5 25 2.1 38 3330 100023010010 300 20.8 4.5 25 2.1 41 3920 50023010011 400 24 4.5 35 2.3 44 5000 50023010012 500 27 4.5 35 2.4 47 6000 50023010013 630 30.8 4.5 35 2.5 53 7560 500

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

23020001 25 6.2 4.5 1.6 22 730 100023020002 35 7.2 4.5 1.7 24 830 100023020003 50 8.3 4.5 1.7 25 1000 100023020004 70 10 4.5 1.8 27 1220 100023020005 95 11.8 4.5 1.8 28 1500 100023020006 120 13.1 4.5 1.9 30 1780 100023020007 150 14.7 4.5 1.9 32 2100 100023020008 185 16.1 4.5 2.0 34 2500 100023020009 240 18.7 4.5 2.1 37 3200 100023020010 300 20.8 4.5 2.1 39 3720 50023020011 400 24 4.5 2.2 42 4650 50023020012 500 27 4.5 2.3 45 5700 50023020013 630 30.8 4.5 2.4 51 7200 500

Single-core XLPE Insulated PVC Sheathed Cable UnarmouredCU / XLPE / PVC Copper Conductor - Copper Wire Screened 8.7/15(17.5) kV

CU / XLPE / PVC Copper Conductor - Copper Tape Screened 8.7/15(17.5) kV

21

Page 23: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / PVC Copper Conductor Unarmoured - 8.7/15(17.5) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω / km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Approximate AC resistance of Conductor @ 90°C

Ω / km 0.927 0.668 0.494 0.342 0.247 0.196 0.160 0.129 0.099 0.0804 0.0647 0.0527 0.0434

Inductance at 60 Hz mH/Km 0.470 0.455 0.435 0.415 0.402 0.389 0.377 0.366 0.350 0.340 0.327 0.319 0.306

Reactance at 60 Hz Ω / km 0.18 0.17 0.16 0.16 0.15 0.15 0.14 0.14 0.13 0.13 0.12 0.12 0.12

Capacitance μF/Km 0.17 0.18 0.20 0.23 0.25 0.27 0.29 0.32 0.35 0.39 0.43 0.48 0.53

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20 71.50 90.09

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.44 0.46 0.49 0.53 0.56 0.60 0.63 0.67 0.72 0.77 0.84 0.92 1.01

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 153 175 211 250 274 315 370 415 470 530 595 680 740

Flat Formation(Approx.) A 157 181 218 258 282 323 378 420 473 525 550 640 685

2- Laid in free air

Trefoil Formation (Approx.) A 163 205 245 269 329 379 430 494 583 669 769 860 1000

Flat Formation(Approx.) A 178 217 260 324 395 455 509 580 678 770 854 895 1035

Voltage Drop per phase V/A/km 0.850 0.636 0.492 0.366 0.286 0.245 0.215 0.185 0.158 0.140 0.126 0.113 0.106

Minimum Bending radius mm 375 390 405 435 465 480 510 540 570 615 660 705 795

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

22

Page 24: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

24010001 35 7.2 5.5 16 1.8 27 1070 100024010002 50 8.3 5.5 16 1.8 28 1150 100024010003 70 10 5.5 16 1.9 30 1400 100024010004 95 11.8 5.5 16 1.9 32 1700 100024010005 120 13.1 5.5 16 2.0 34 1950 100024010006 150 14.7 5.5 25 2.0 35 2340 100024010007 185 16.1 5.5 25 2.1 37 2780 100024010008 240 18.7 5.5 25 2.2 39 3350 100024010009 300 20.8 5.5 25 2.2 42 4000 50024010010 400 24 5.5 35 2.3 45 5000 50024010011 500 27 5.5 35 2.4 48 6050 50024010012 630 30.8 5.5 35 2.5 53 7520 500

Cable Code

Conductor Insulation Outer Sheath PackagingCross

Sectional Area

Nominalmm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

24020001 35 7.2 5.5 1.7 26 890 100024020002 50 8.3 5.5 1.8 29 1150 100024020003 70 10 5.5 1.9 31 1450 100024020004 95 11.8 5.5 1.9 33 1730 100024020005 120 13.1 5.5 2.0 35 2000 100024020006 150 14.7 5.5 2.0 36 2450 100024020007 185 16.1 5.5 2.1 38 2800 100024020008 240 18.7 5.5 2.1 40 3410 100024020009 300 20.8 5.5 2.2 43 4100 50024020010 400 24 5.5 2.3 46 5000 50024020011 500 27 5.5 2.4 49 6100 50024020012 630 30.8 5.5 2.5 55 7600 500

Single-core XLPE Insulated PVC Sheathed Cable UnarmouredCU / XLPE / PVC Copper Conductor - Copper Wire Screened 12/20 (24) kV

CU / XLPE / PVC Copper Conductor - Copper Tape Screened 12/20 (24) kV

23

Page 25: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / PVC Copper Conductor Unarmoured - 12/20(24) kV

Technical Information

Size mm2 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω / km 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Approximate AC resistance of Conductor @ 90°C

Ω / km 0.668 0.494 0.342 0.247 0.196 0.160 0.129 0.099 0.0804 0.0647 0.0527 0.0434

Inductance at 60 Hz mH/Km 0.468 0.449 0.425 0.414 0.400 0.388 0.375 0.361 0.350 0.335 0.327 0.315

Reactance at 60 Hz Ω / km 0.18 0.17 0.16 0.16 0.15 0.15 0.14 0.14 0.13 0.13 0.12 0.12

Capacitance μF/Km 0.15 0.17 0.20 0.22 0.24 0.26 0.27 0.30 0.33 0.37 0.41 0.46

Short Circuit Current For 1 second

1- Conductor KA 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20 71.50 90.09

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.50 0.53 0.57 0.61 0.64 0.68 0.72 0.77 0.82 0.88 0.97 1.08

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 175 211 250 274 315 370 415 470 530 595 680 740

Flat Formation(Approx.) A 181 218 258 282 323 378 420 473 525 550 640 685

2- Laid in free air

Trefoil Formation (Approx.) A 205 245 269 329 379 430 494 583 669 769 860 1000

Flat Formation(Approx.) A 217 260 324 395 455 509 580 678 770 854 895 1035

Voltage Drop per phase V/A/km 0.640 0.495 0.369 0.290 0.248 0.217 0.187 0.160 0.142 0.127 0.115 0.107

Minimum Bending radius mm 405 420 450 480 510 525 555 585 630 675 720 795

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

24

Page 26: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

25010001 50 8.3 8.0 16 2.0 34 1600 100025010002 70 10 8.0 16 2.0 37 1800 100025010003 95 11.8 8.0 16 2.1 39 2000 100025010004 120 13.1 8.0 16 2.1 40 2400 100025010005 150 14.7 8.0 25 2.2 42 2790 100025010006 185 16.1 8.0 25 2.2 43 3200 50025010007 240 18.7 8.0 25 2.3 46 3780 50025010008 300 20.8 8.0 25 2.4 48 4450 50025010009 400 24 8.0 35 2.5 52 5500 50025010010 500 27 8.0 35 2.6 55 6500 50025010011 630 30.8 8.0 35 2.7 59 8300 500

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

25020001 50 8.3 8.0 1.9 32 1320 100025020002 70 10 8.0 2.0 34 1630 100025020003 95 11.8 8.0 2.1 36 1930 100025020004 120 13.1 8.0 2.1 38 2250 100025020004 150 14.7 8.0 2.2 40 2580 100025020005 185 16.1 8.0 2.2 41 3000 50025020006 240 18.7 8.0 2.3 43 3500 50025020007 300 20.8 8.0 2.4 46 4500 50025020008 400 24 8.0 2.5 50 5150 50025020010 500 27 8.0 2.6 54 6500 50025020011 630 30.8 8.0 2.7 59 8030 500

Single-core XLPE Insulated PVC Sheathed Cable UnarmouredCU / XLPE / PVC Copper Conductor - Copper Wire Screened 18/30 (36) kV

CU / XLPE / PVC Copper Conductor - Copper Tape Screened 18/30 (36) kV

25

Page 27: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / PVC Copper Conductor Unarmoured - 18/30(36) kV

Technical Information

Size mm2 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.494 0.342 0.247 0.196 0.160 0.129 0.099 0.0804 0.0647 0.0527 0.0434

Inductance at 60 Hz mH/Km 0.480 0.460 0.445 0.430 0.415 0.405 0.4390 0.375 0.360 0.350 0.340

Reactance at 60 Hz Ω/km 0.18 0.17 0.17 0.16 0.16 0.15 0.17 0.14 0.14 0.13 0.13

Capacitance μF/Km 0.14 0.15 0.17 0.18 0.20 0.21 0.23 0.25 0.27 0.30 0.34

Short Circuit Current For 1 second

1- Conductor KA 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20 71.50 90.09

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.65 0.69 0.73 0.76 0.79 0.83 0.89 0.94 1.03 1.11 1.17

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 211 250 274 315 370 415 470 530 595 680 740

Flat Formation(Approx.) A 218 258 282 323 378 420 473 525 550 640 685

2- Laid in free air

Trefoil Formation (Approx.) A 245 269 329 379 430 494 583 669 769 860 1000

Flat Formation(Approx.) A 260 324 395 455 509 580 678 770 854 895 1035

Voltage Drop per phase V/A/km 0.502 0.375 0.300 0.254 0.220 0.194 0.166 0.149 0.133 0.121 0.113

Minimum Bending radius mm 510 555 585 600 630 645 690 720 780 825 885

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

26

Page 28: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%21130001 25 5.7 2.5 16 1.5 20 540 100021130002 35 7.1 2.5 16 1.6 21 550 100021130003 50 7.9 2.5 16 1.6 22 680 100021130004 70 9.7 2.5 16 1.6 24 750 100021130005 95 11.3 2.5 16 1.7 26 920 100021130006 120 12.6 2.5 16 1.8 27 1050 100021130007 150 14.1 2.5 25 1.8 29 1220 100021130008 185 16.0 2.5 25 1.9 30 1380 100021130009 240 18.1 2.6 25 1.9 33 1630 100021130010 300 20.4 2.8 25 2.0 36 1850 50021130011 400 23.1 3.0 35 2.2 40 2350 50021130012 500 25.9 3.2 35 2.3 44 2830 50021130013 630 29.5 3.2 35 2.4 47 3325 500

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

21140001 25 5.7 2.5 1.5 18 390 100021140002 35 7.1 2.5 1.5 19 450 100021140003 50 7.9 2.5 1.6 21 520 100021140004 70 9.7 2.5 1.6 22 650 100021140005 95 11.3 2.5 1.7 24 750 100021140006 120 12.6 2.5 1.7 26 850 100021140007 150 14.1 2.5 1.8 27 970 100021140008 185 16.0 2.5 1.8 29 1200 100021140009 240 18.1 2.6 1.9 31 1380 100021140010 300 20.4 2.8 2.0 34 1600 50021140011 400 23.1 3.0 2.1 38 1980 50021140012 500 25.9 3.2 2.2 42 2500 50021140013 630 29.5 3.2 2.3 46 3100 500

Single-core XLPE Insulated PVC Sheathed Cable UnarmouredAL / XLPE / PVC Aluminum Conductor - Copper Wire Screened 3.6/6(7.2) kV

AL / XLPE / PVC Aluminum Conductor - Copper Tape Screened 3.6/6(7.2) kV

27

Page 29: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / PVC Aluminum Conductor Unarmoured - 3.6/6(7.2) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.568 0.411 0.326 0.265 0.211 0.161 0.130 0.1016 0.0799 0.0632

Inductance at 60 Hz mH/Km 0.444 0.425 0.408 0.385 0.377 0.362 0.355 0.342 0.330 0.323 0.311 0.308 0.297

Reactance at 60 Hz Ω/km 0.17 0.16 0.15 0.15 0.14 0.14 0.13 0.13 0.12 0.12 0.12 0.12 0.11

Capacitance μF/Km 0.26 0.29 0.31 0.35 0.39 0.43 0.47 0.52 0.56 0.58 0.60 0.63 0.75

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48 46.85 59.03

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.35 0.37 0.39 0.44 0.47 0.51 0.54 0.58 0.64 0.70 0.77 0.86 0.95

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 100 100 120 135 165 200 230 260 293 330 370 415 520

Flat Formation(Approx.) A 105 105 125 140 170 210 240 270 303 341 379 400 500

2- Laid in free air

Trefoil Formation (Approx.) A 116 116 140 167 209 255 295 335 386 457 525 612 705

Flat Formation(Approx.) A 139 139 168 202 253 308 356 400 459 540 616 700 790

Voltage Drop per phase V/A/

km1.332 0.987 0.751 0.542 0.414 0.342 0.293 0.246 0.206 0.178 0.153 0.134 0.119

Minimum Bending radius mm 300 315 330 360 390 405 435 450 495 540 600 660 705

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

28

Page 30: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%22130001 25 5.7 3.4 16 1.6 22 650 100022130002 35 7.1 3.4 16 1.6 23 730 100022130003 50 7.9 3.4 16 1.7 24 800 100022130004 70 9.7 3.4 16 1.7 26 900 100022130005 95 11.3 3.4 16 1.8 28 1000 100022130006 120 12.6 3.4 16 1.9 29 1150 100022130007 150 14.1 3.4 25 1.9 31 1400 100022130008 185 16.0 3.4 25 2.0 32 1450 100022130009 240 18.1 3.4 25 2.0 35 1800 100022130010 300 20.4 3.4 25 2.1 37 2000 50022130011 400 23.1 3.4 35 2.2 41 2450 50022130012 500 25.9 3.4 35 2.3 44 2850 50022130013 630 29.5 3.4 35 2.4 48 3400 500

Cable Code

Conductor Insulation Outer Sheath PackagingCross

Sectional Area

Nominalmm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

22140001 25 5.7 3.4 1.5 20 475 100022140002 35 7.1 3.4 1.6 21 540 100022140003 50 7.9 3.4 1.6 23 600 100022140004 70 9.7 3.4 1.7 24 700 100022140005 95 11.3 3.4 1.7 26 850 100022140006 120 12.6 3.4 1.8 28 950 100022140007 150 14.1 3.4 1.8 29 1100 100022140008 185 16.0 3.4 1.9 31 1200 100022140009 240 18.1 3.4 2.0 33 1450 100022140010 300 20.4 3.4 2.0 35 1730 50022140011 400 23.1 3.4 2.1 39 2000 50022140012 500 25.9 3.4 2.2 42 2440 50022140013 630 29.5 3.4 2.3 46 2930 500

Single-core XLPE Insulated PVC Sheathed Cable UnarmouredAL / XLPE / PVC Aluminum Conductor - Copper Wire Screened 6/10(12) kV

AL / XLPE / PVC Aluminum Conductor - Copper Tape Screened 6/10(12) kV

29

Page 31: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / PVC Aluminum Conductor Unarmoured - 6/10(12) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.568 0.411 0.326 0.265 0.211 0.161 0.130 0.1016 0.0799 0.0632

Inductance at 60 Hz mH/Km 0.460 0.440 0.420 0.408 0.382 0.375 0.363 0.354 0.340 0.330 0.319 0.309 0.295

Reactance at 60 Hz Ω/km 0.17 0.17 0.16 0.15 0.14 0.14 0.14 0.13 0.13 0.12 0.12 0.12 0.11

Capacitance μF/Km 0.20 0.23 0.25 0.29 0.30 0.33 0.37 0.40 0.45 0.49 0.54 0.60 0.70

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48 46.85 59.03

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.38 0.41 0.44 0.48 0.52 0.55 0.58 0.62 0.68 0.72 0.79 0.87 0.96

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 100 120 135 165 200 230 260 293 330 370 415 520 750

Flat Formation(Approx.) A 105 125 140 170 210 240 270 303 341 379 400 500 690

2- Laid in free air

Trefoil Formation (Approx.) A 116 140 167 209 255 295 335 386 457 525 612 705 800

Flat Formation(Approx.) A 139 168 202 253 308 356 400 459 540 616 700 790 885

Voltage Drop per phase V/A/km 1.33 0.990 0.754 0.545 0.416 0.345 0.294 0.250 0.207 0.179 0.154 0.134 0.119

Minimum Bending radius mm 330 345 360 390 420 435 465 480 525 555 615 660 720

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

30

Page 32: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%23130001 25 5.7 4.5 16 1.7 24 750 100023130002 35 7.1 4.5 16 1.7 25 830 100023130003 50 7.9 4.5 16 1.7 26 900 100023130004 70 9.7 4.5 16 1.8 28 1000 100023130005 95 11.3 4.5 16 1.8 30 1185 100023130006 120 12.6 4.5 16 1.9 31 1285 100023130007 150 14.1 4.5 25 1.9 33 1450 100023130008 185 16.0 4.5 25 2.0 34 1850 100023130009 240 18.1 4.5 25 2.1 37 1900 100023130010 300 20.4 4.5 25 2.1 39 2100 50023130011 400 23.1 4.5 35 2.3 43 2700 50023130012 500 25.9 4.5 35 2.4 47 3200 50023130013 630 29.5 4.5 35 2.5 50 3800 500

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

23140001 25 5.7 4.5 1.6 22 550 100023140002 35 7.1 4.5 1.7 24 680 100023140003 50 7.9 4.5 1.7 25 730 100023140004 70 9.7 4.5 1.7 27 820 100023140005 95 11.3 4.5 1.8 28 950 100023140006 120 12.6 4.5 1.9 30 1075 100023140007 150 14.1 4.5 1.9 32 1200 100023140008 185 16.0 4.5 2.0 33 1350 100023140009 240 18.1 4.5 2.0 36 1600 100023140010 300 20.4 4.5 2.1 38 1830 50023140011 400 23.1 4.5 2.2 42 2200 50023140012 500 25.9 4.5 2.3 45 2600 50023140013 630 29.5 4.5 2.4 50 3250 500

Single-core XLPE Insulated PVC Sheathed Cable UnarmouredAL / XLPE / PVC Aluminum Conductor - Copper Wire Screened 8.7/15(17.5) kV

AL / XLPE / PVC Aluminum Conductor - Copper Tape Screened 8.7/15(17.5) kV

31

Page 33: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / PVC Aluminum Conductor Unarmoured - 8.7/15(17.5) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.568 0.411 0.326 0.265 0.211 0.161 0.130 0.1016 0.0799 0.0632

Inductance at 60 Hz mH/Km 0.470 0.455 0.435 0.415 0.402 0.389 0.377 0.366 0.350 0.340 0.327 0.319 0.306

Reactance at 60 Hz Ω/km 0.18 0.17 0.16 0.16 0.15 0.15 0.14 0.14 0.13 0.13 0.12 0.12 0.12

Capacitance μF/Km 0.17 0.18 0.20 0.23 0.25 0.27 0.29 0.32 0.35 0.39 0.43 0.48 0.53

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48 46.85 59.03

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.44 0.46 0.49 0.53 0.56 0.60 0.63 0.67 0.72 0.77 0.84 0.92 1.01

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 100 120 135 165 200 230 260 293 330 370 415 520 750

Flat Formation(Approx.) A 105 125 140 170 210 240 270 303 341 379 400 500 690

2- Laid in free air

Trefoil Formation (Approx.) A 116 140 167 209 255 295 335 386 457 525 612 705 800

Flat Formation(Approx.) A 139 168 202 253 308 356 400 459 540 616 700 790 885

Voltage Drop per phase V/A/

km1.338 0.994 0.757 0.548 0.420 0.348 0.297 0.252 0.209 0.181 0.156 0.136 0.121

Minimum Bending radius mm 360 375 390 420 450 465 495 510 555 585 645 705 750

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

32

Page 34: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%24130001 35 5.7 5.5 16 1.8 27 930 100024140002 50 7.1 5.5 16 1.8 29 1000 100024130003 70 7.9 5.5 16 1.9 30 1220 100024130004 95 9.7 5.5 16 1.9 32 1280 100024140005 120 11.3 5.5 16 2.0 34 1400 100024130006 150 12.6 5.5 25 2.0 35 1580 100024130007 185 14.1 5.5 25 2.1 37 1780 100024130008 240 16.0 5.5 25 2.1 39 2000 100024130009 300 18.1 5.5 25 2.2 42 22500 50024130010 400 20.4 5.5 35 2.3 46 2750 50024130011 500 23.1 5.5 35 2.4 49 3175 50024130012 630 25.9 5.5 35 2.5 53 3680 500

Cable Code

Conductor Insulation Outer Sheath PackagingCross

Sectional Area

Nominalmm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

24140001 35 5.7 5.5 1.7 26 750 100024140002 50 7.1 5.5 1.8 28 830 100024140003 70 7.9 5.5 1.8 30 920 100024140004 95 9.7 5.5 1.9 31 1080 100024140005 120 11.3 5.5 2.0 32 1180 100024140006 150 12.6 5.5 2.0 34 1300 100024140007 185 14.1 5.5 2.1 36 1475 100024140008 240 16.0 5.5 2.1 38 1720 100024140009 300 18.1 5.5 2.2 40 2000 50024140010 400 20.4 5.5 2.3 44 2360 5002 4 1 4 0 0 1 1 500 23.1 5.5 2.4 47 2830 50024140012 630 25.9 5.5 2.5 52 3400 500

Single-core XLPE Insulated PVC Sheathed Cable UnarmouredAL / XLPE / PVC Aluminum Conductor - Copper Wire Screened 12/20(24) kV

AL / XLPE / PVC Aluminum Conductor - Copper Tape Screened 12/20(24) kV

33

Page 35: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / PVC Aluminum Conductor Unarmoured - 12/20(24) kV

Technical Information

Size mm2 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.113 0.822 0.568 0.411 0.326 0.265 0.211 0.161 0.130 0.1016 0.0799 0.0632

Inductance at 60 Hz mH/Km 0.468 0.449 0.425 0.414 0.400 0.388 0.375 0.361 0.350 0.335 0.327 0.315

Reactance at 60 Hz Ω/km 0.18 0.17 0.16 0.16 0.15 0.15 0.14 0.14 0.13 0.13 0.12 0.12

Capacitance μF/Km 0.15 0.17 0.20 0.22 0.24 0.26 0.27 0.30 0.33 0.37 0.41 0.46

Short Circuit Current For 1 second

1- Conductor KA 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48 46.85 59.03

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.50 0.53 0.57 0.61 0.64 0.68 0.72 0.77 0.82 0.88 0.97 1.08

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 100 120 135 165 200 230 260 293 330 370 415 520

Flat Formation(Approx.) A 105 125 140 170 210 240 270 303 341 379 400 500

2- Laid in free air

Trefoil Formation (Approx.) A 116 140 167 209 255 295 335 386 457 525 612 705

Flat Formation(Approx.) A 139 168 202 253 308 356 400 459 540 616 700 790

Voltage Drop per phase V/A/km 0.966 0.760 0.551 0.422 0.350 0.300 0.254 0.212 0.183 0.158 0.138 0.123

Minimum Bending radius mm 405 435 450 480 510 525 555 585 630 690 690 735

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

34

Page 36: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

25130001 50 7.1 8.0 16 2.0 34 1300 100025130002 70 7.9 8.0 16 2.0 35 1400 100025130003 95 9.7 8.0 16 2.1 38 1575 100025130004 120 11.3 8.0 16 2.1 39 1700 100025130005 150 12.6 8.0 25 2.2 40 1930 100025130006 185 14.1 8.0 25 2.2 42 2100 50025130007 240 16.0 8.0 25 2.3 45 2400 50025130008 300 18.1 8.0 25 2.4 47 2680 50025130009 400 20.4 8.0 35 2.5 51 3180 50025130010 500 23.1 8.0 35 2.6 54 3650 50025130011 630 25.9 8.0 35 2.7 58 4220 500

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

25140001 50 7.1 8.0 1.9 32 1100 100025140002 70 7.9 8.0 2.0 34 1200 100025140003 95 9.7 8.0 2.1 36 1370 100025140004 120 11.3 8.0 2.1 38 1500 100025140004 150 12.6 8.0 2.2 40 1630 100025140005 185 14.1 8.0 2.2 41 1800 50025140006 240 16.0 8.0 2.3 43 2100 50025140007 300 18.1 8.0 2.4 46 2350 50025140008 400 20.4 8.0 2.5 49 2775 50025140010 500 23.1 8.0 2.6 53 3220 50025140011 630 25.9 8.0 2.7 57 3800 500

Single-core XLPE Insulated PVC Sheathed Cable UnarmouredAL / XLPE / PVC Aluminum Conductor - Copper Wire Screened 18/30(36) kV

AL / XLPE / PVC Aluminum Conductor - Copper Tape Screened 18/30(36) kV

35

Page 37: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / PVC Aluminum Conductor Unarmoured - 18/30(36) kV

Technical Information

Size mm2 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.822 0.568 0.411 0.326 0.265 0.211 0.161 0.130 0.1016 0.0799 0.0632

Inductance at 60 Hz mH/Km 0.480 0.460 0.445 0.430 0.415 0.405 0.4390 0.375 0.360 0.350 0.340

Reactance at 60 Hz Ω/km 0.18 0.17 0.17 0.16 0.16 0.15 0.17 0.14 0.14 0.13 0.13

Capacitance μF/Km 0.14 0.15 0.17 0.18 0.20 0.21 0.23 0.25 0.27 0.30 0.34

Short Circuit Current For 1 second

1- Conductor KA 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48 46.85 59.03

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.65 0.69 0.73 0.76 0.79 0.83 0.89 0.94 1.03 1.11 1.17

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 100 120 135 165 200 230 260 293 330 370 415

Flat Formation(Approx.) A 105 125 140 170 210 240 270 303 341 379 400

2- Laid in free air

Trefoil Formation (Approx.) A 116 140 167 209 255 295 335 386 457 525 612

Flat Formation(Approx.) A 139 168 202 253 308 356 400 459 540 616 700

Voltage Drop per phase V/A/km 0.768 0.558 0.430 0.357 0.306 0.260 0.217 0.189 0.163 0.143 0.128

Minimum Bending radius mm 510 525 570 585 600 630 630 675 705 765 810

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

36

Page 38: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

21050001 25 6.2 2.5 16 1.2 1.6 1.8 26 1100 1000

21050002 35 7.2 2.5 16 1.2 1.6 1.8 28 1350 1000

21050003 50 8.3 2.5 16 1.2 1.6 1.8 29 1450 1000

21050004 70 10 2.5 16 1.2 1.6 1.8 31 1690 1000

21050005 95 11.8 2.5 16 1.2 1.6 1.9 33 2000 1000

21050006 120 13.1 2.5 16 1.2 1.6 1.9 35 2300 1000

21050007 150 14.7 2.5 25 1.2 2.0 2.0 37 2550 1000

21050008 185 16.1 2.5 25 1.2 2.0 2.1 40 3250 1000

21050009 240 18.7 2.6 25 1.2 2.0 2.2 42 3890 500

21050010 300 20.8 2.8 25 1.2 2.0 2.2 44 4600 500

21050011 400 24 3.0 35 1.3 2.5 2.4 51 5850 500

21050012 500 27 3.2 35 1.3 2.5 2.5 53 6950 500

21050013 630 30.8 3.2 35 1.4 2.5 2.6 58 8500 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

21060001 25 6.2 2.5 1.2 1.6 1.8 24 900 1000

21060002 35 7.2 2.5 1.2 1.6 1.8 26 1050 1000

21060003 50 8.3 2.5 1.2 1.6 1.8 28 1250 1000

21060004 70 10 2.5 1.2 1.6 1.8 30 1510 1000

21060005 95 11.8 2.5 1.2 1.6 1.9 31 1800 1000

21060006 120 13.1 2.5 1.2 1.6 1.9 33 2130 1000

21060007 150 14.7 2.5 1.2 2.0 2.0 35 2450 1000

21060008 185 16.1 2.5 1.2 2.0 2.1 37 2980 1000

21060009 240 18.7 2.6 1.2 2.0 2.1 40 3620 500

21060010 300 20.8 2.8 1.2 2.0 2.2 43 4300 500

21060011 400 24 3.0 1.2 2.5 2.3 46 5250 500

21060012 500 27 3.2 1.3 2.5 2.5 51 6720 500

21060013 630 30.8 3.2 1.4 2.5 2.6 55 8340 500

Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire ArmouredCU / XLPE / AWA / PVC Copper Conductor - Copper Wire Screened 3.6/6(7.2) kV

CU / XLPE / AWA / PVC Copper Conductor - Copper Tape Screened 3.6/6(7.2) kV

37

Page 39: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / AWA / PVC Copper Conductor Aluminum Wire Armoured - 3.6/6(7.2) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.927 0.668 0.494 0.342 0.247 0.196 0.160 0.129 0.099 0.0804 0.0647 0.0527 0.0434

Inductance at 60 Hz mH/Km 0.472 0.461 0.440 0.417 0.405 0.392 0.379 0.370 0.355 0.346 0.3335 0.328 0.315

Reactance at 60 Hz Ω/km 0.18 0.17 0.17 0.16 0.15 0.15 0.14 0.14 0.13 0.13 0.13 0.12 0.12

Capacitance μF/Km 0.25 0.28 0.31 0.35 0.39 0.43 0.47 0.52 0.56 0.58 0.60 0.63 0.75

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20 71.50 90.09

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.34 0.36 0.39 0.43 0.47 0.51 0.54 0.58 0.64 0.70 0.77 0.86 0.94

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 153 175 211 250 274 315 370 415 470 530 595 680 740

Flat Formation(Approx.) A 157 181 218 258 282 323 378 420 473 525 550 640 685

2- Laid in free air

Trefoil Formation (Approx.) A 163 205 245 269 329 379 430 494 583 669 769 860 1000

Flat Formation(Approx.) A 178 217 260 324 395 455 509 580 678 770 854 895 1035

Voltage Drop per phase V/A/km 0.850 0.641 0.492 0.365 0.289 0.246 0.215 0.185 0.159 0.140 0.127 0.115 0.107

Minimum Bending radius mm 390 420 435 465 495 525 555 600 630 630 660 765 795

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

38

Page 40: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

22050001 25 6.2 3.4 16 1.2 1.6 1.8 27 1100 1000

22050002 35 7.2 3.4 16 1.2 1.6 1.8 29 1350 1000

22050003 50 8.3 3.4 16 1.2 1.6 1.8 31 1450 1000

22050004 70 10 3.4 16 1.2 1.6 1.8 32 1690 1000

22050005 95 11.8 3.4 16 1.2 1.6 1.9 34 2000 1000

22050006 120 13.1 3.4 16 1.2 2.0 1.9 37 2300 1000

22050007 150 14.7 3.4 25 1.2 2.0 2.0 38 2550 1000

22050008 185 16.1 3.4 25 1.2 2.0 2.1 40 3250 1000

22050009 240 18.7 3.4 25 1.2 2.0 2.2 42 3890 500

22050010 300 20.8 3.4 25 1.2 2.0 2.2 45 4600 500

22050011 400 24 3.4 35 1.3 2.5 2.4 50 5850 500

22050012 500 27 3.4 35 1.3 2.5 2.5 53 6950 500

22050013 630 30.8 3.4 35 1.4 2.5 2.6 58 8500 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

22060001 25 6.2 3.4 1.2 1.6 1.8 26 900 1000

22060002 35 7.2 3.4 1.2 1.6 1.8 28 1050 1000

22060003 50 8.3 3.4 1.2 1.6 1.9 29 1250 1000

22060004 70 10 3.4 1.2 1.6 1.9 31 1510 1000

22060005 95 11.8 3.4 1.2 1.6 2.0 34 1800 1000

22060006 120 13.1 3.4 1.2 1.6 2.0 35 2130 1000

22060007 150 14.7 3.4 1.2 2.0 2.1 36 2450 1000

22060008 185 16.1 3.4 1.2 2.0 2.1 39 2980 1000

22060009 240 18.7 3.4 1.2 2.0 2.2 41 3620 500

22060010 300 20.8 3.4 1.2 2.0 2.2 44 4300 500

22060011 400 24 3.4 1.2 2.5 2.4 47 5250 500

22060012 500 27 3.4 1.3 2.5 2.5 51 6720 500

22060013 630 30.8 3.4 1.4 2.5 2.6 55 8340 500

Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire ArmouredCU / XLPE / AWA / PVC Copper Conductor - Copper Wire Screened 6/10(12) kV

CU / XLPE / AWA / PVC Copper Conductor - Copper Tape Screened 6/10(12) kV

39

Page 41: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / AWA / PVC Copper Conductor Aluminum Wire Armoured - 6/10(12) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.927 0.668 0.494 0.342 0.247 0.196 0.160 0.129 0.099 0.0804 0.0647 0.0527 0.0434

Inductance at 60 Hz mH/Km 0.489 0.472 0.450 0.429 0.415 0.401 0.390 0.378 0.364 0.352 0.338 0.328 0.317

Reactance at 60 Hz Ω/km 0.18 0.18 0.17 0.16 0.16 0.15 0.15 0.14 0.14 0.13 0.13 0.12 0.12

Capacitance μF/Km 0.20 0.23 0.25 0.29 0.30 0.33 0.37 0.40 0.45 0.49 0.54 0.60 0.70

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20 71.50 90.09

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.38 0.41 0.44 0.48 0.52 0.55 0.58 0.62 0.68 0.72 0.79 0.87 0.96

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 153 175 211 250 274 315 370 415 470 530 595 680 740

Flat Formation(Approx.) A 157 181 218 258 282 323 378 420 473 525 550 640 685

2- Laid in free air

Trefoil Formation (Approx.) A 163 205 245 269 329 379 430 494 583 669 769 860 1000

Flat Formation(Approx.) A 178 217 260 324 395 455 509 580 678 770 854 895 1035

Voltage Drop per phase V/A/km 0.851 0.641 0.495 0.370 0.292 0.248 0.215 0.187 0.160 0.142 0.125 0.117 0.106

Minimum Bending radius mm 405 435 465 480 510 555 570 600 630 675 750 795 870

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

40

Page 42: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

23050001 25 6.2 4.5 16 1.2 1.6 1.9 30 1350 1000

23050002 35 7.2 4.5 16 1.2 1.6 1.9 32 1530 1000

23050003 50 8.3 4.5 16 1.2 1.6 1.9 34 1800 1000

23050004 70 10 4.5 16 1.2 1.6 2.0 35 1970 1000

23050005 95 11.8 4.5 16 1.2 2.0 2.1 38 2400 1000

23050006 120 13.1 4.5 16 1.2 2.0 2.1 40 2800 1000

23050007 150 14.7 4.5 25 1.2 2.0 2.2 41 3180 500

23050008 185 16.1 4.5 25 1.2 2.0 2.2 43 3580 500

23050009 240 18.7 4.5 25 1.2 2.0 2.3 45 4200 500

23050010 300 20.8 4.5 25 1.3 2.5 2.4 49 5050 500

23050011 400 24 4.5 35 1.3 2.5 2.5 52 6150 500

23050012 500 27 4.5 35 1.4 2.5 2.6 56 7350 500

23050013 630 30.8 4.5 35 1.4 2.5 2.7 60 8800 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

23060001 25 6.2 4.5 1.2 1.6 1.8 28 1200 1000

23060002 35 7.2 4.5 1.2 1.6 1.9 30 1350 1000

23060003 50 8.3 4.5 1.2 1.6 1.9 32 1540 1000

23060004 70 10 4.5 1.2 1.6 1.9 33 1840 1000

23060005 95 11.8 4.5 1.2 2.0 2.0 36 2250 1000

23060006 120 13.1 4.5 1.2 2.0 2.1 37 2550 1000

23060007 150 14.7 4.5 1.2 2.0 2.1 39 2900 1000

23060008 185 16.1 4.5 1.2 2.0 2.2 42 3380 500

23060009 240 18.7 4.5 1.2 2.0 2.3 44 4050 500

23060010 300 20.8 4.5 1.2 2.0 2.3 47 4650 500

23060011 400 24 4.5 1.2 2.5 2.5 51 5900 500

23060012 500 27 4.5 1.3 2.5 2.6 54 7000 500

23060013 630 30.8 4.5 1.4 2.5 2.7 57 8650 500

Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire ArmouredCU / XLPE / AWA / PVC Copper Conductor - Copper Wire Screened 8.7/15(17.5) kV

CU / XLPE / AWA / PVC Copper Conductor - Copper Tape Screened 8.7/15(17.5) kV

41

Page 43: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / AWA / PVC Copper Conductor Aluminum Wire Armoured - 8.7/15(17.5) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.927 0.668 0.494 0.342 0.247 0.196 0.160 0.129 0.099 0.0804 0.0647 0.0527 0.0434

Inductance at 60 Hz mH/Km 0.504 0.485 0.463 0.440 0.428 0.414 0.400 0.389 0.374 0.361 0.345 0.338 0.325

Reactance at 60 Hz Ω/km 0.19 0.18 0.17 0.17 0.16 0.16 0.15 0.15 0.14 0.14 0.13 0.13 0.12

Capacitance μF/Km 0.17 0.18 0.20 0.23 0.25 0.27 0.29 0.32 0.35 0.39 0.43 0.48 0.53

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20 71.50 90.09

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.44 0.46 0.49 0.53 0.56 0.60 0.63 0.67 0.72 0.77 0.84 0.92 1.01

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 153 175 211 250 274 315 370 415 470 530 595 680 740

Flat Formation(Approx.) A 157 181 218 258 282 323 378 420 473 525 550 640 685

2- Laid in free air

Trefoil Formation (Approx.) A 163 205 245 269 329 379 430 494 583 669 769 860 1000

Flat Formation(Approx.) A 178 217 260 324 395 455 509 580 678 770 854 895 1035

Voltage Drop per phase V/A/

km0.855 0.645 0.500 0.374 0.295 0.250 0.220 0.190 0.163 0.145 0.130 0.119 0.108

Minimum Bending radius mm 450 480 510 525 570 600 615 645 675 735 780 840 900

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

42

Page 44: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

24050001 35 7.2 5.5 16 1.2 1.6 2.0 34 1650 1000

24050002 50 8.3 5.5 16 1.2 2.0 2.0 36 1900 1000

24050003 70 10 5.5 16 1.2 2.0 2.1 38 2200 1000

24050004 95 11.8 5.5 16 1.2 2.0 2.1 40 2500 1000

24050005 120 13.1 5.5 16 1.2 2.0 2.2 41 2850 500

24050006 150 14.7 5.5 25 1.2 2.0 2.2 43 3250 500

24050007 185 16.1 5.5 25 1.2 2.0 2.3 44 3700 500

24050008 240 18.7 5.5 25 1.3 2.5 2.4 48 4580 500

24050009 300 20.8 5.5 25 1.3 2.5 2.5 51 5300 500

24050010 400 24 5.5 35 1.4 2.5 2.6 54 6500 500

24050011 500 27 5.5 35 1.4 2.5 2.7 58 7500 500

24050012 630 30.8 5.5 35 1.5 2.5 2.8 63 9100 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

24060001 35 7.2 5.5 1.2 1.6 1.9 32 1450 1000

24060002 50 8.3 5.5 1.2 1.6 2.0 34 1650 1000

24060003 70 10 5.5 1.2 2.0 2.1 37 2050 1000

24060004 95 11.8 5.5 1.2 2.0 2.1 38 2400 1000

24060005 120 13.1 5.5 1.2 2.0 2.2 40 2750 1000

24060006 150 14.7 5.5 1.2 2.0 2.2 42 3050 1000

24060007 185 16.1 5.5 1.2 2.0 2.3 43 3400 500

24060008 240 18.7 5.5 1.2 2.0 2.3 46 4200 500

24060009 300 20.8 5.5 1.3 2.5 2.5 49 5080 500

24060010 400 24 5.5 1.3 2.5 2.6 53 6100 500

24060011 500 27 5.5 1.4 2.5 2.7 56 7200 500

24060012 630 30.8 5.5 1.4 2.5 2.8 61 8500 500

Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire ArmouredCU / XLPE / AWA / PVC Copper Conductor - Copper Wire Screened 12/20(24) kV

CU / XLPE / AWA / PVC Copper Conductor - Copper Tape Screened 12/20(24) kV

43

Page 45: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / AWA / PVC Copper Conductor Aluminum Wire Armoured - 12/20(24) kV

Technical Information

Size mm2 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.668 0.494 0.342 0.247 0.196 0.160 0.129 0.099 0.0804 0.0647 0.0527 0.0434

Inductance at 60 Hz mH/Km 0.495 0.474 0.452 0.438 0.423 0.412 0.398 0.393 0.371 0.356 0.346 0.334

Reactance at 60 Hz Ω/km 0.19 0.18 0.17 0.17 0.16 0.16 0.15 0.15 0.14 0.13 0.13 0.13

Capacitance μF/Km 0.15 0.17 0.20 0.22 0.24 0.26 0.27 0.30 0.33 0.37 0.41 0.46

Short Circuit Current For 1 second

1- Conductor KA 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20 71.50 90.09

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.51 0.53 0.57 0.61 0.64 0.68 0.72 0.77 0.82 0.88 0.97 1.08

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 175 211 250 274 315 370 415 470 530 595 680 740

Flat Formation(Approx.) A 181 218 258 282 323 378 420 473 525 550 640 685

2- Laid in free air

Trefoil Formation (Approx.) A 205 245 269 329 379 430 494 583 669 769 860 1000

Flat Formation(Approx.) A 217 260 324 395 455 509 580 678 770 854 895 1035

Voltage Drop per phase V/A/km 0.645 0.500 0.377 0.300 0.254 0.221 0.192 0.165 0.148 0.133 0.120 0.112

Minimum Bending radius mm 510 540 570 600 615 645 660 720 765 810 870 945

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

44

Page 46: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

25050001 50 8.3 8.0 16 1.2 2.0 2.2 41 2300 1000

25050002 70 10 8.0 16 1.2 2.0 2.3 44 2600 500

25050003 95 11.8 8.0 16 1.2 2.0 2.3 46 2690 500

25050004 120 13.1 8.0 16 1.3 2.5 2.4 48 3500 500

25050005 150 14.7 8.0 25 1.3 2.5 2.5 50 3920 500

25050006 185 16.1 8.0 25 1.3 2.5 2.5 52 4350 500

25050007 240 18.7 8.0 25 1.4 2.5 2.6 54 5100 500

25050008 300 20.8 8.0 25 1.4 2.5 2.7 56 5850 500

25050009 400 24 8.0 35 1.5 2.5 2.8 60 6950 500

25050010 500 27 8.0 35 1.5 2.5 2.9 63 8100 500

25050011 630 30.8 8.0 35 1.6 2.5 3.0 68 9800 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

25060001 50 8.3 8.0 1.2 2.0 2.2 39 1650 1000

25060002 70 10 8.0 1.2 2.0 2.3 41 2050 500

25060003 95 11.8 8.0 1.2 2.0 2.3 44 2400 500

25060004 120 13.1 8.0 1.2 2.0 2.4 46 2750 500

25060005 150 14.7 8.0 1.3 2.5 2.5 48 3050 500

25060006 185 16.1 8.0 1.3 2.5 2.5 50 3400 500

25060007 240 18.7 8.0 1.3 2.5 2.6 53 4200 500

25060008 300 20.8 8.0 1.4 2.5 2.7 56 5080 500

25060009 400 24 8.0 1.4 2.5 2.8 60 6100 500

25060010 500 27 8.0 1.5 2.5 2.9 62 7200 500

25060011 630 30.8 8.0 1.5 2.5 3.0 67 8500 500

Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire ArmouredCU / XLPE / AWA / PVC Copper Conductor - Copper Wire Screened 18/30(36) kV

CU / XLPE / AWA / PVC Copper Conductor - Copper Tape Screened 18/30(36) kV

45

Page 47: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / AWA / PVC Copper Conductor Aluminum Wire Armoured - 18/30(36) kV

Technical Information

Size mm2 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.494 0.342 0.247 0.196 0.160 0.129 0.099 0.0804 0.0647 0.0527 0.0434

Inductance at 60 Hz mH/Km 0.505 0.481 0.467 0.450 0.438 0.425 0.408 0.395 0.378 0.368 0.358

Reactance at 60 Hz Ω/km 0.19 0.18 0.18 0.17 0.17 0.16 0.15 0.15 0.14 0.14 0.13

Capacitance μF/Km 0.14 0.15 0.17 0.18 0.20 0.21 0.23 0.25 0.27 0.30 0.34

Short Circuit Current For 1 second

1- Conductor KA 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20 71.50 90.09

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.65 0.69 0.73 0.76 0.79 0.83 0.89 0.94 1.03 1.11 1.17

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 211 250 274 315 370 415 470 530 595 680 740

Flat Formation(Approx.) A 218 258 282 323 378 420 473 525 550 640 685

2- Laid in free air

Trefoil Formation (Approx.) A 245 269 329 379 430 494 583 669 769 860 1000

Flat Formation(Approx.) A 260 324 395 455 509 580 678 770 854 895 1035

Voltage Drop per phase V/A/km 0.509 0.383 0.305 0.260 0.228 0.198 0.171 0.153 0.137 0.125 0.116

Minimum Bending radius mm 615 660 690 720 750 780 810 840 900 945 1020

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

46

Page 48: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

21170001 25 5.7 2.5 16 1.2 1.6 1.8 26 1000 1000

21170002 35 7.1 2.5 16 1.2 1.6 1.8 27 1075 1000

21170003 50 7.9 2.5 16 1.2 1.6 1.8 28 1150 1000

21170004 70 9.7 2.5 16 1.2 1.6 1.8 30 1250 1000

21170005 95 11.3 2.5 16 1.2 1.6 1.9 32 1450 1000

21170006 120 12.6 2.5 16 1.2 1.6 1.9 33 1550 1000

21170007 150 14.1 2.5 25 1.2 2.0 2.0 35 1900 1000

21170008 185 16.0 2.5 25 1.2 2.0 2.1 40 2050 1000

21170009 240 18.1 2.6 25 1.2 2.0 2.2 42 2350 500

21170010 300 20.4 2.8 25 1.2 2.0 2.2 44 2800 500

21170011 400 23.1 3.0 35 1.3 2.5 2.4 47 3400 500

21170012 500 25.9 3.2 35 1.3 2.5 2.5 52 3900 500

21170013 630 29.5 3.2 35 1.4 2.5 2.6 57 4500 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

21180001 25 5.7 2.5 1.2 1.6 1.8 24 800 1000

21180002 35 7.1 2.5 1.2 1.6 1.8 25 875 1000

21180003 50 7.9 2.5 1.2 1.6 1.8 27 1000 1000

21180004 70 9.7 2.5 1.2 1.6 1.8 29 1050 1000

21180005 95 11.3 2.5 1.2 1.6 1.9 30 1250 1000

21180006 120 12.6 2.5 1.2 1.6 1.9 31 1300 1000

21180007 150 14.1 2.5 1.2 2.0 2.0 34 1700 1000

21180008 185 16.0 2.5 1.2 2.0 2.1 36 1850 1000

21180009 240 18.1 2.6 1.2 2.0 2.1 38 2200 500

21180010 300 20.4 2.8 1.2 2.0 2.2 41 2650 500

21180011 400 23.1 3.0 1.2 2.5 2.3 46 3200 500

21180012 500 25.9 3.2 1.3 2.5 2.4 50 3700 500

21180013 630 29.5 3.2 1.4 2.5 2.5 54 4300 500

Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire ArmouredAL / XLPE / AWA / PVC Aluminum Conductor - Copper Wire Screened 3.6/6(7.2) kV

AL / XLPE / AWA / PVC Aluminum Conductor - Copper Tape Screened 3.6/6(7.2) kV

47

Page 49: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / AWA / PVC Aluminum Conductor Aluminum Wire Armoured - 3.6/6(7.2) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.568 0.411 0.326 0.265 0.211 0.161 0.130 0.1016 0.0799 0.0632

Inductance at 60 Hz mH/Km 0.472 0.461 0.440 0.417 0.405 0.392 0.379 0.370 0.355 0.346 0.3335 0.328 0.315

Reactance at 60 Hz Ω/km 0.18 0.17 0.17 0.16 0.15 0.15 0.14 0.14 0.13 0.13 0.13 0.12 0.12

Capacitance μF/Km 0.25 0.28 0.31 0.35 0.39 0.43 0.47 0.52 0.56 0.58 0.60 0.63 0.75

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48 46.85 59.03

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.34 0.36 0.39 0.43 0.47 0.51 0.54 0.58 0.64 0.7 0.77 0.86 0.94

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 100 120 135 165 200 230 260 293 330 370 415 520 750

Flat Formation(Approx.) A 105 125 140 170 210 240 270 303 341 379 400 500 690

2- Laid in free air

Trefoil Formation (Approx.) A 116 140 167 209 255 295 335 386 457 525 612 705 800

Flat Formation(Approx.) A 139 168 202 253 308 356 400 459 540 616 700 790 885

Voltage Drop per phase V/A/

km1.338 0.995 0.758 0.549 0.421 0.349 0.298 0.252 0.210 0.182 0.157 0.138 0.122

Minimum Bending radius mm 390 405 420 450 480 495 525 600 630 660 705 780 855

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

48

Page 50: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

22170001 25 5.7 3.4 16 1.2 1.6 1.8 27 1020 1000

22170002 35 7.1 3.4 16 1.2 1.6 1.8 29 1130 1000

22170003 50 7.9 3.4 16 1.2 1.6 1.8 31 1300 1000

22170004 70 9.7 3.4 16 1.2 1.6 1.9 32 1380 1000

22170005 95 11.3 3.4 16 1.2 1.6 1.9 34 1550 1000

22170006 120 12.6 3.4 16 1.2 2.0 2.0 37 1800 1000

22170007 150 14.1 3.4 25 1.2 2.0 2.0 38 2000 1000

22170008 185 16.0 3.4 25 1.2 2.0 2.1 40 2150 1000

22170009 240 18.1 3.4 25 1.2 2.0 2.2 42 2400 500

22170010 300 20.4 3.4 25 1.2 2.0 2.2 45 2700 500

22170011 400 23.1 3.4 35 1.3 2.5 2.4 50 3300 500

22170012 500 25.9 3.4 35 1.3 2.5 2.5 53 3700 500

22170013 630 29.5 3.4 35 1.4 2.5 2.6 58 4300 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

22180001 25 5.7 3.4 1.2 1.6 1.8 26 850 1000

22180002 35 7.1 3.4 1.2 1.6 1.8 28 900 1000

22180003 50 7.9 3.4 1.2 1.6 1.9 29 1100 1000

22180004 70 9.7 3.4 1.2 1.6 1.9 31 1200 1000

22180005 95 11.3 3.4 1.2 1.6 2.0 34 1350 1000

22180006 120 12.6 3.4 1.2 1.6 2.0 35 1640 1000

22180007 150 14.1 3.4 1.2 2.0 2.1 36 1800 1000

22180008 185 16.0 3.4 1.2 2.0 2.1 39 2000 1000

22180009 240 18.1 3.4 1.2 2.0 2.2 41 2225 500

22180010 300 20.4 3.4 1.2 2.0 2.2 44 2500 500

22180011 400 23.1 3.4 1.2 2.5 2.4 47 3100 500

22180012 500 25.9 3.4 1.3 2.5 2.5 51 3500 500

22180013 630 29.5 3.4 1.4 2.5 2.6 55 4150 500

Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire ArmouredAL / XLPE / AWA / PVC Aluminum Conductor - Copper Wire Screened 6/10(12) kV

AL / XLPE / AWA / PVC Aluminum Conductor - Copper Tape Screened 6/10(12) kV

49

Page 51: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / AWA / PVC Aluminum Conductor Aluminum Wire Armoured - 6/10(12) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.568 0.411 0.326 0.265 0.211 0.161 0.130 0.1016 0.0799 0.0632

Inductance at 60 Hz mH/Km 0.489 0.472 0.450 0.429 0.415 0.401 0.390 0.378 0.364 0.352 0.338 0.328 0.317

Reactance at 60 Hz Ω/km 0.18 0.18 0.17 0.16 0.16 0.15 0.15 0.14 0.14 0.13 0.13 0.12 0.12

Capacitance μF/Km 0.20 0.23 0.25 0.29 0.30 0.33 0.37 0.40 0.45 0.49 0.54 0.60 0.70

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48 46.85 59.03

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.38 0.41 0.44 0.48 0.52 0.55 0.58 0.62 0.68 0.72 0.79 0.87 0.96

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 100 120 135 165 200 230 260 293 330 370 415 520 750

Flat Formation(Approx.) A 105 125 140 170 210 240 270 303 341 379 400 500 690

2- Laid in free air

Trefoil Formation (Approx.) A 116 140 167 209 255 295 335 386 457 525 612 705 800

Flat Formation(Approx.) A 139 168 202 253 308 356 400 459 540 616 700 790 885

Voltage Drop per phase V/A/

km1.343 0.997 0.761 0.551 0.423 0.351 0.300 0.254 0.212 0.183 0.158 0.139 0.123

Minimum Bending radius mm 405 435 465 480 510 555 570 600 630 675 750 795 870

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

50

Page 52: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

23170001 25 5.7 4.5 16 1.2 1.6 1.9 30 1200 1000

23170002 35 7.1 4.5 16 1.2 1.6 1.9 31 1300 1000

23170003 50 7.9 4.5 16 1.2 1.6 1.9 33 1400 1000

23170004 70 9.7 4.5 16 1.2 1.6 2.0 34 1530 1000

23170005 95 11.3 4.5 16 1.2 2.0 2.1 38 1850 1000

23170006 120 12.6 4.5 16 1.2 2.0 2.1 39 1950 1000

23170007 150 14.1 4.5 25 1.2 2.0 2.2 40 2180 500

23170008 185 16.0 4.5 25 1.2 2.0 2.2 41 2350 500

23170009 240 18.1 4.5 25 1.2 2.0 2.3 45 2700 500

23170010 300 20.4 4.5 25 1.3 2.5 2.4 48 3150 500

23170011 400 23.1 4.5 35 1.3 2.5 2.5 51 3700 500

23170012 500 25.9 4.5 35 1.4 2.5 2.6 55 4280 500

23170013 630 29.5 4.5 35 1.4 2.5 2.7 60 4900 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

23180001 25 5.7 4.5 1.2 1.6 1.8 28 1000 1000

23180002 35 7.1 4.5 1.2 1.6 1.9 30 1080 1000

23180003 50 7.9 4.5 1.2 1.6 1.9 32 1180 1000

23180004 70 9.7 4.5 1.2 1.6 1.9 33 1300 1000

23180005 95 11.3 4.5 1.2 2.0 2.0 36 1580 1000

23180006 120 12.6 4.5 1.2 2.0 2.1 37 1750 1000

23180007 150 14.1 4.5 1.2 2.0 2.1 39 1880 1000

23180008 185 16.0 4.5 1.2 2.0 2.2 42 2050 500

23180009 240 18.1 4.5 1.2 2.0 2.3 44 2400 500

23180010 300 20.4 4.5 1.2 2.0 2.3 47 2850 500

23180011 400 23.1 4.5 1.2 2.5 2.5 51 3700 500

23180012 500 25.9 4.5 1.3 2.5 2.6 54 3800 500

23180013 630 29.5 4.5 1.4 2.5 2.7 57 4430 500

Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire ArmouredAL / XLPE / AWA / PVC Aluminum Conductor - Copper Wire Screened 8.7/15(17.5) kV

AL / XLPE / AWA / PVC Aluminum Conductor - Copper Tape Screened 8.7/15(17.5) kV

51

Page 53: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / AWA / PVC Aluminum Conductor Aluminum Wire Armoured - 8.7/15(17.5) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.568 0.411 0.326 0.265 0.211 0.161 0.130 0.1016 0.0799 0.0632

Inductance at 60 Hz mH/Km 0.504 0.485 0.463 0.440 0.428 0.414 0.400 0.389 0.374 0.361 0.345 0.338 0.325

Reactance at 60 Hz Ω/km 0.19 0.18 0.17 0.17 0.16 0.16 0.15 0.15 0.14 0.14 0.13 0.13 0.12

Capacitance μF/Km 0.17 0.18 0.20 0.23 0.25 0.27 0.29 0.32 0.35 0.39 0.43 0.48 0.53

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48 46.85 59.03

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.44 0.46 0.49 0.53 0.56 0.6 0.63 0.67 0.72 0.77 0.84 0.92 1.01

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 100 120 135 165 200 230 260 293 330 370 415 520 750

Flat Formation(Approx.) A 105 125 140 170 210 240 270 303 341 379 400 500 690

2- Laid in free air

Trefoil Formation (Approx.) A 116 140 167 209 255 295 335 386 457 525 612 705 800

Flat Formation(Approx.) A 139 168 202 253 308 356 400 459 540 616 700 790 885

Voltage Drop per phase V/A/

km1.345 1.001 0.765 0.554 0.426 0.353 0.303 0.257 0.214 0.186 0.160 0.141 0.125

Minimum Bending radius mm 450 465 495 510 570 585 600 615 675 720 765 825 900

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

52

Page 54: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

24170001 35 7.1 5.5 16 1.2 1.6 2.0 33 1450 1000

24170002 50 7.9 5.5 16 1.2 2.0 2.0 35 1650 1000

24170003 70 9.7 5.5 16 1.2 2.0 2.1 37 1820 1000

24170004 95 11.3 5.5 16 1.2 2.0 2.1 39 2000 1000

24170005 120 12.6 5.5 16 1.2 2.0 2.2 40 2120 500

24170006 150 14.1 5.5 25 1.2 2.0 2.2 42 2300 500

24170007 185 16.0 5.5 25 1.2 2.0 2.3 44 2550 500

24170008 240 18.1 5.5 25 1.3 2.5 2.4 48 3050 500

24170009 300 20.4 5.5 25 1.3 2.5 2.5 50 3400 500

24170010 400 23.1 5.5 35 1.4 2.5 2.6 54 4000 500

24170011 500 25.9 5.5 35 1.4 2.5 2.7 57 4500 500

24170012 630 29.5 5.5 35 1.5 2.5 2.8 61 5200 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

24180001 35 7.1 5.5 1.2 1.6 1.9 32 1200 1000

24180002 50 7.9 5.5 1.2 2.0 2.0 34 1420 1000

24180003 70 9.7 5.5 1.2 2.0 2.0 36 1550 1000

24180004 95 11.3 5.5 1.2 2.0 2.1 37 1750 1000

24180005 120 12.6 5.5 1.2 2.0 2.1 39 1900 1000

24180006 150 14.1 5.5 1.2 2.0 2.2 40 2040 1000

24180007 185 16.0 5.5 1.2 2.0 2.2 42 2250 500

24180008 240 18.1 5.5 1.2 2.5 2.3 45 2600 500

24180009 300 20.4 5.5 1.3 2.5 2.4 47 3000 500

24180010 400 23.1 5.5 1.3 2.5 2.5 52 3500 500

24180011 500 25.9 5.5 1.4 2.5 2.6 56 4000 500

24180012 630 29.5 5.5 1.4 2.5 2.8 60 5000 500

Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire ArmouredAL / XLPE / AWA / PVC Aluminum Conductor - Copper Wire Screened 12/20(24) kV

AL / XLPE / AWA / PVC Aluminum Conductor - Copper Tape Screened 12/20(24) kV

53

Page 55: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / AWA / PVC Aluminum Conductor Aluminum Wire Armoured - 12/20(24) kV

Technical Information

Size mm2 35 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.113 0.822 0.568 0.411 0.326 0.265 0.211 0.161 0.130 0.1016 0.0799 0.0632

Inductance at 60 Hz mH/Km 0.495 0.474 0.452 0.438 0.423 0.412 0.398 0.393 0.371 0.356 0.346 0.334

Reactance at 60 Hz Ω/km 0.19 0.18 0.17 0.17 0.16 0.16 0.15 0.15 0.14 0.13 0.13 0.13

Capacitance μF/Km 0.15 0.17 0.20 0.22 0.24 0.26 0.27 0.30 0.33 0.37 0.41 0.46

Short Circuit Current For 1 second

1- Conductor KA 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48 46.85 59.03

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.5 0.53 0.57 0.61 0.64 0.68 0.72 0.77 0.82 0.88 0.97 1.08

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 100 120 135 165 200 230 260 293 330 370 415 520

Flat Formation(Approx.) A 105 125 140 170 210 240 270 303 341 379 400 500

2- Laid in free air

Trefoil Formation (Approx.) A 116 140 167 209 255 295 335 386 457 525 612 705

Flat Formation(Approx.) A 139 168 202 253 308 356 400 459 540 616 700 790

Voltage Drop per phase V/A/km 1.003 0.766 0.557 0.428 0.356 0.305 0.259 0.216 0.188 0.162 0.142 0.126

Minimum Bending radius mm 495 525 555 585 600 630 660 720 750 810 855 915

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

54

Page 56: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

25170001 50 7.9 8.0 16 1.2 2.0 2.2 41 2100 1000

25170002 70 9.7 8.0 16 1.2 2.0 2.3 42 2230 500

25170003 95 11.3 8.0 16 1.2 2.0 2.3 44 2500 500

25170004 120 12.6 8.0 16 1.3 2.5 2.4 47 2900 500

25170005 150 14.1 8.0 25 1.3 2.5 2.5 49 3200 500

25170006 185 16.0 8.0 25 1.3 2.5 2.5 50 3300 500

25170007 240 18.1 8.0 25 1.4 2.5 2.6 53 3700 500

25170008 300 20.4 8.0 25 1.4 2.5 2.7 55 4000 500

25170009 400 23.1 8.0 35 1.5 2.5 2.8 60 4700 500

25170010 500 25.9 8.0 35 1.5 2.5 2.9 63 5200 500

25170011 630 29.5 8.0 35 1.6 2.5 3.0 67 5900 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of Aluminum

WireNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

25180001 50 7.9 8.0 1.2 2.0 2.2 39 1900 1000

25180002 70 9.7 8.0 1.2 2.0 2.2 41 2050 500

25180003 95 11.3 8.0 1.2 2.0 2.3 43 2150 500

25180004 120 12.6 8.0 1.2 2.0 2.3 46 2500 500

25180005 150 14.1 8.0 1.3 2.5 2.4 47 2700 500

25180006 185 16.0 8.0 1.3 2.5 2.5 49 2950 500

25180007 240 18.1 8.0 1.3 2.5 2.6 52 3280 500

25180008 300 20.4 8.0 1.4 2.5 2.7 55 3600 500

25180009 400 23.1 8.0 1.4 2.5 2.8 59 4300 500

25180010 500 25.9 8.0 1.5 2.5 2.9 61 4800 500

25180011 630 29.5 8.0 1.5 2.5 3.0 66 5500 500

Single-core XLPE Insulated PVC Sheathed Cable Aluminum Wire ArmouredAL / XLPE / AWA / PVC Aluminum Conductor - Copper Wire Screened 18/30(36) kV

AL / XLPE / AWA / PVC Aluminum Conductor - Copper Tape Screened 18/30(36) kV

55

Page 57: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / AWA / PVC Aluminum Conductor Aluminum Wire Armoured - 18/30(36) kV

Technical Information

Size mm2 50 70 95 120 150 185 240 300 400 500 630

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.822 0.568 0.411 0.326 0.265 0.211 0.161 0.130 0.1016 0.0799 0.0632

Inductance at 60 Hz mH/Km 0.505 0.481 0.467 0.450 0.438 0.425 0.408 0.395 0.378 0.368 0.358

Reactance at 60 Hz Ω/km 0.19 0.18 0.18 0.17 0.17 0.16 0.15 0.15 0.14 0.14 0.13

Capacitance μF/Km 0.14 0.15 0.17 0.18 0.20 0.21 0.23 0.25 0.27 0.30 0.34

Short Circuit Current For 1 second

1- Conductor KA 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48 46.85 59.03

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18 5.18 5.18

3- Copper Tape Screen KA 0.65 0.69 0.73 0.76 0.79 0.83 0.89 0.94 1.03 1.11 1.17

Current Rating Capacity

1- Laid direct in ground

Trefoil Formation (Approx.) A 100 120 135 165 200 230 260 293 330 370 415

Flat Formation(Approx.) A 105 125 140 170 210 240 270 303 341 379 400

2- Laid in free air

Trefoil Formation (Approx.) A 116 140 167 209 255 295 335 386 457 525 612

Flat Formation(Approx.) A 139 168 202 253 308 356 400 459 540 616 700

Voltage Drop per phase V/A/km 0.773 0.563 0.434 0.362 0.311 0.265 0.222 0.193 0.167 0.147 0.131

Minimum Bending radius mm 615 630 660 705 735 750 795 825 900 945 1005

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

56

Page 58: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

21030001 25 6.2 2.5 16 2.1 40 2050 50021030002 35 7.2 2.5 16 2.2 43 2500 50021030003 50 8.3 2.5 16 2.3 45 3000 50021030004 70 10 2.5 16 2.4 50 3650 50021030005 95 11.8 2.5 16 2.5 53 4680 50021030006 120 13.1 2.5 16 2.6 58 5580 50021030007 150 14.7 2.5 25 2.8 61 6500 50021030008 185 16.1 2.5 25 2.9 65 7600 50021030009 240 18.7 2.6 25 3.0 71 9800 50021030010 300 20.8 2.8 25 3.2 77 12000 50021030011 400 24 3.0 35 3.5 83 14500 500

Cable Code

Conductor Insulation Outer Sheath PackagingCross

Sectional Area

Nominalmm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

21040001 25 6.2 2.5 2.1 39 1950 50021040002 35 7.2 2.5 2.1 41 2380 50021040003 50 8.3 2.5 2.2 44 2820 50021040004 70 10 2.5 2.3 48 3600 50021040005 95 11.8 2.5 2.5 52 4500 50021040006 120 13.1 2.5 2.6 56 5400 50021040007 150 14.7 2.5 2.7 59 6300 50021040008 185 16.1 2.5 2.8 63 7600 50021040009 240 18.7 2.6 3.0 69 9500 50021040010 300 20.8 2.8 3.2 75 11800 50021040011 400 24 3.0 3.5 81 14200 500

Three-cores XLPE Insulated PVC Sheathed Cable UnarmouredCU / XLPE / PVC Copper Conductor - Copper Wire Screened 3.6/6(7.2) kV

CU / XLPE / PVC Copper Conductor - Copper Tape Screened 3.6/6(7.2) kV

57

Page 59: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / PVC Copper Conductor Unarmoured - 3.6/6(7.2) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.927 0.669 0.494 0.344 0.247 0.196 0.161 0.129 0.099 0.0815 0.0660

Inductance at 60 Hz mH/Km 0.305 0.294 0.283 0.273 0.267 0.260 0.253 0.250 0.244 0.236 0.226

Reactance at 60 Hz Ω/km 0.115 0.111 0.107 0.103 0.101 0.098 0.095 0.094 0.092 0.089 0.085

Capacitance μF/Km 0.26 0.30 0.32 0.36 0.39 0.44 0.46 0.53 0.56 0.58 0.60

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.02 1.08 1.17 1.29 1.41 1.53 1.62 1.74 1.92 2.1 2.31

Current Rating Capacity

1- Laid direct in ground (Approx.) A 140 168 195 248 275 310 346 395 445 505 565

2- Laid in free air (Approx.) A 130 155 186 231 277 320 363 415 486 552 635

Voltage Drop per phase V/A/km 0.812 0.603 0.460 0.335 0.259 0.215 0.185 0.160 0.134 0.117 0.102

Minimum Bending radius mm 480 516 540 600 636 696 732 780 852 924 996

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

58

Page 60: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

22030001 25 6.2 3.4 16 2.2 46 2350 50022030002 35 7.2 3.4 16 2.3 48 2800 50022030003 50 8.3 3.4 16 2.4 51 3200 50022030004 70 10 3.4 16 2.5 55 4000 50022030005 95 11.8 3.4 16 2.7 60 5000 50022030006 120 13.1 3.4 16 2.8 63 5800 50022030007 150 14.7 3.4 25 2.9 64 6800 50022030008 185 16.1 3.4 25 3.0 70 8200 50022030009 240 18.7 3.4 25 3.2 76 10200 50022030010 300 20.8 3.4 25 3.3 81 12000 50022030011 400 24 3.4 35 3.5 85 14800 500

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

22040001 25 6.2 3.4 2.2 43 2250 50022040002 35 7.2 3.4 2.3 46 2700 50022040003 50 8.3 3.4 2.4 49 3200 50022040004 70 10 3.4 2.5 52 4000 50022040005 95 11.8 3.4 2.6 56 4900 50022040006 120 13.1 3.4 2.7 60 5800 50022040007 150 14.7 3.4 2.8 63 6650 50022040008 185 16.1 3.4 2.9 67 8100 50022040009 240 18.7 3.4 3.1 73 9950 50022040010 300 20.8 3.4 3.3 78 12000 50022040011 400 24 3.4 3.5 81 13900 500

Three-cores XLPE Insulated PVC Sheathed Cable UnarmouredCU / XLPE / PVC Copper Conductor - Copper Wire Screened 6/10(12) kV

CU / XLPE / PVC Copper Conductor - Copper Tape Screened 6/10(12) kV

59

Page 61: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / PVC Copper Conductor Unarmoured - 6/10(12) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.927 0.669 0.494 0.344 0.247 0.196 0.161 0.129 0.099 0.0815 0.0660

Inductance at 60 Hz mH/Km 0.332 0.318 0.306 0.292 0.284 0.276 0.270 0.263 0.256 0.248 0.239

Reactance at 60 Hz Ω/km 0.125 0.120 0.115 0.110 0.107 0.104 0.102 0.099 0.097 0.093 0.090

Capacitance μF/Km 0.20 0.23 0.25 0.29 0.30 0.33 0.37 0.40 0.45 0.49 0.54

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.14 1.23 1.32 1.44 1.56 1.65 1.74 1.86 2.04 2.16 2.37

Current Rating Capacity

1- Laid direct in ground (Approx.) A 140 168 195 248 275 310 346 395 445 505 565

2- Laid in free air (Approx.) A 130 155 186 231 277 320 363 415 486 552 635

Voltage Drop per phase V/A/km 0.815 0.606 0.465 0.340 0.263 0.220 0.190 0.162 0.132 0.120 0.106

Minimum Bending radius mm 552 576 612 660 720 756 768 840 912 972 1020

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

60

Page 62: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

23030001 25 6.2 4.5 16 2.4 50 2900 50023030002 35 7.2 4.5 16 2.5 54 3200 50023030003 50 8.3 4.5 16 2.6 56 3800 50023030004 70 10 4.5 16 2.7 61 4700 50023030005 95 11.8 4.5 16 2.8 64 5600 50023030006 120 13.1 4.5 16 2.9 68 6500 50023030007 150 14.7 4.5 25 3.1 71 7500 50023030008 185 16.1 4.5 25 3.2 76 8600 50023030009 240 18.7 4.5 25 3.3 81 10500 50023030010 300 20.8 4.5 25 3.5 86 12600 50023030011 400 24 4.5 35 3.7 90 15500 500

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

23040001 25 6.2 4.5 2.4 47 2800 50023040002 35 7.2 4.5 2.5 50 3000 50023040003 50 8.3 4.5 2.6 52 3600 50023040004 70 10 4.5 2.7 56 4600 50023040005 95 11.8 4.5 2.8 60 5500 50023040006 120 13.1 4.5 2.9 63 6450 50023040007 150 14.7 4.5 3.0 65 7350 50023040008 185 16.1 4.5 3.1 72 8400 50023040009 240 18.7 4.5 3.3 76 10100 50023040010 300 20.8 4.5 3.4 82 12500 50023040011 400 24 4.5 3.7 87 15400 500

Three-cores XLPE Insulated PVC Sheathed Cable UnarmouredCU / XLPE / PVC Copper Conductor - Copper Wire Screened 8.7/15(17.5) kV

CU / XLPE / PVC Copper Conductor - Copper Tape Screened 8.7/15(17.5) kV

61

Page 63: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / PVC Copper Conductor Unarmoured - 8.7/15(17.5) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.927 0.669 0.494 0.344 0.247 0.196 0.161 0.129 0.099 0.0815 0.0655

Inductance at 60 Hz mH/Km 0.360 0.345 0.330 0.315 0.306 0.295 0.288 0.280 0.270 0.260 0.251

Reactance at 60 Hz Ω/km 0.14 0.13 0.12 0.12 0.12 0.11 0.11 0.11 0.10 0.10 0.09

Capacitance μF/Km 0.17 0.18 0.2 0.23 0.25 0.27 0.29 0.32 0.35 0.39 0.43

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.32 1.38 1.47 1.59 1.68 1.8 1.89 2.01 2.16 2.31 2.52

Current Rating Capacity

1- Laid direct in ground (Approx.) A 140 168 195 248 275 310 346 395 445 505 565

2- Laid in free air (Approx.) A 130 155 186 231 277 320 363 415 486 552 635

Voltage Drop per phase V/A/km 0.823 0.613 0.472 0.345 0.266 0.225 0.194 0.166 0.141 0.123 0.107

Minimum Bending radius mm 600 648 672 732 768 816 852 912 972 1032 1080

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

62

Page 64: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%24030001 35 7.2 5.5 16 2.7 59 3550 50024030002 50 8.3 5.5 16 2.8 61 3900 50024030003 70 10 5.5 16 2.9 63 4800 50024030004 95 11.8 5.5 16 3.0 68 5800 50024030005 120 13.1 5.5 16 3.1 72 6700 50024030006 150 14.7 5.5 25 3.2 76 7800 50024030007 185 16.1 5.5 25 3.3 80 9100 50024030008 240 18.7 5.5 25 3.5 86 11000 50024030009 300 20.8 5.5 25 3.6 90 13000 40024030010 400 24 5.5 35 3.8 97 15800 400

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

24040001 35 7.2 5.5 2.6 56 3400 50024040002 50 8.3 5.5 2.7 59 3800 50024040003 70 10 5.5 2.8 63 4700 50024040004 95 11.8 5.5 2.9 66 5650 50024040005 120 13.1 5.5 3.0 70 6650 50024040006 150 14.7 5.5 3.1 73 7700 50024040007 185 16.1 5.5 3.3 78 9000 50024040008 240 18.7 5.5 3.4 83 10800 50024040009 300 20.8 5.5 3.6 88 12800 40024040010 400 24 5.5 3.8 93 15500 400

Three-cores XLPE Insulated PVC Sheathed Cable UnarmouredCU / XLPE / PVC Copper Conductor - Copper Wire Screened 12/20(24) kV

CU / XLPE / PVC Copper Conductor - Copper Tape Screened 12/20(24) kV

63

Page 65: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / PVC Copper Conductor Unarmoured - 12/20(24) kV

Technical Information

Size mm2 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.668 0.494 0.344 0.247 0.196 0.161 0.129 0.099 0.0810 0.0650

Inductance at 60 Hz mH/Km 0.365 0.350 0.333 0.322 0.312 0.303 0.295 0.285 0.270 0.262

Reactance at 60 Hz Ω/km 0.14 0.13 0.13 0.12 0.12 0.11 0.11 0.11 0.10 0.10

Capacitance μF/Km 0.15 0.17 0.2 0.22 0.24 0.26 0.27 0.3 0.33 0.37

Short Circuit Current For 1 second

1- Conductor KA 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.5 1.59 1.71 1.83 1.92 2.04 2.16 2.31 2.46 2.64

Current Rating Capacity

1- Laid direct in ground (Approx.) A 168 195 248 275 310 346 395 445 505 565

2- Laid in free air (Approx.) A 155 186 231 277 320 363 415 486 552 635

Voltage Drop per phase V/A/km 0.620 0.475 0.350 0.271 0.228 0.198 0.170 0.143 0.125 0.111

Minimum Bending radius mm 708 732 756 816 864 912 960 1032 1080 1164

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

64

Page 66: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

25030001 50 8.3 8.0 16 3.1 73 5250 50025030002 70 10 8.0 16 3.2 78 6100 50025030003 95 11.8 8.0 16 3.4 81 7300 50025030004 120 13.1 8.0 16 3.5 84 8200 50025030005 150 14.7 8.0 25 3.6 88 9200 50025030006 185 16.1 8.0 25 3.7 92 10500 30025030007 240 18.7 8.0 25 3.9 97 12800 30025030008 300 20.8 8.0 25 4.0 101 14800 300

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

25040001 50 8.3 8.0 3.1 71 5100 50025040002 70 10 8.0 3.2 76 6000 50025040003 95 11.8 8.0 3.3 78 7200 50025040004 120 13.1 8.0 3.4 82 8050 50025040005 150 14.7 8.0 3.5 85 9100 50025040006 185 16.1 8.0 3.6 89 10400 30025040007 240 18.7 8.0 3.8 95 12600 30025040008 300 20.8 8.0 4.0 100 14700 300

Three-cores XLPE Insulated PVC Sheathed Cable UnarmouredCU / XLPE / PVC Copper Conductor - Copper Wire Screened 18/30(36) kV

CU / XLPE / PVC Copper Conductor - Copper Tape Screened 18/30(36) kV

65

Page 67: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / PVC Copper Conductor Unarmoured - 18/30(36) kV

Technical Information

Size mm2 50 70 95 120 150 185 240 300

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.494 0.341 0.247 0.196 0.161 0.128 0.098 0.0801

Inductance at 60 Hz mH/Km 0.398 0.380 0.369 0.355 0.345 0.335 0.320 0.308

Reactance at 60 Hz Ω/km 0.15 0.14 0.14 0.13 0.13 0.13 0.12 0.12

Capacitance μF/Km 0.14 0.15 0.17 0.18 0.2 0.21 0.23 0.25

Short Circuit Current For 1 second

1- Conductor KA 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7

3- Copper Tape Screen KA 1.95 2.07 2.19 2.28 2.37 2.49 2.67 2.82

Current Rating Capacity

1- Laid direct in ground (Approx.) A 195 248 275 310 346 395 445 505

2- Laid in free air (Approx.) A 186 231 277 320 363 415 486 552

Voltage Drop per phase V/A/km 0.485 0.361 0.280 0.237 0.206 0.178 0.153 0.134

Minimum Bending radius mm 876 936 972 1008 1056 1104 1164 1212

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

66

Page 68: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%21150001 25 5.7 2.5 16 2.1 43 1550 50021150002 35 7.1 2.5 16 2.2 45 1950 50021150003 50 7.9 2.5 16 2.3 48 2300 50021150004 70 9.7 2.5 16 2.4 51 2600 50021150005 95 11.3 2.5 16 2.5 56 3150 50021150006 120 12.6 2.5 16 2.6 59 3500 50021150007 150 14.1 2.5 25 2.8 63 4000 50021150008 185 16.0 2.5 25 2.9 67 4500 50021150009 240 18.1 2.6 25 3.0 72 5400 50021150010 300 20.4 2.8 25 3.2 78 6500 50021150011 400 23.1 3.0 35 3.5 85 8000 500

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

21160001 25 5.7 2.5 2.1 40 1400 50021160002 35 7.1 2.5 2.1 42 1800 50021160003 50 7.9 2.5 2.2 45 2150 50021160004 70 9.7 2.5 2.3 49 2400 50021160005 95 11.3 2.5 2.5 53 3000 50021160006 120 12.6 2.5 2.6 57 3300 50021160007 150 14.1 2.5 2.7 60 3950 50021160008 185 16.0 2.5 2.8 63 4350 50021160009 240 18.1 2.6 3.0 70 5200 50021160010 300 20.4 2.8 3.2 76 6300 50021160011 400 23.1 3.0 3.5 81 7750 500

Three-cores XLPE Insulated PVC Sheathed Cable UnarmouredAL / XLPE / PVC Aluminum Conductor - Copper Wire Screened 3.6/6(7.2) kV

AL / XLPE / PVC Aluminum Conductor - Copper Tape Screened 3.6/6(7.2) kV

67

Page 69: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / PVC Aluminum Conductor Unarmoured - 3.6/6(7.2) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131 0.1034

Inductance at 60 Hz mH/Km 0.305 0.294 0.283 0.273 0.267 0.260 0.253 0.250 0.244 0.236 0.226

Reactance at 60 Hz Ω/km 0.115 0.111 0.107 0.103 0.101 0.098 0.095 0.094 0.092 0.089 0.085

Capacitance μF/Km 0.26 0.30 0.32 0.36 0.39 0.44 0.46 0.53 0.56 0.58 0.60

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.02 1.08 1.17 1.29 1.41 1.53 1.62 1.74 1.92 2.1 2.31

Current Rating Capacity

1- Laid direct in ground (Approx.) A 108 127 148 178 210 238 265 298 341 383 435

2- Laid in free air (Approx.) A 100 120 144 178 215 248 281 323 378 432 502

Voltage Drop per phase V/A/km 1.300 0.957 0.722 0.516 0.389 0.319 0.269 0.225 0.185 0.157 0.133

Minimum Bending radius mm 516 540 576 612 672 708 756 804 864 936 1020

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

68

Page 70: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

22150001 25 5.7 3.4 16 2.2 46 1750 50022150002 35 7.1 3.4 16 2.3 48 2200 50022150003 50 7.9 3.4 16 2.4 51 2500 50022150004 70 9.7 3.4 16 2.5 55 2900 50022150005 95 11.3 3.4 16 2.7 60 3500 50022150006 120 12.6 3.4 16 2.8 63 3900 50022150007 150 14.1 3.4 25 2.9 66 4500 50022150008 185 16.0 3.4 25 3.0 70 4900 50022150009 240 18.1 3.4 25 3.2 76 5800 50022150010 300 20.4 3.4 25 3.3 81 6800 50022150011 400 23.1 3.4 35 3.5 85 7500 500

Cable Code

Conductor Insulation Outer Sheath PackagingCross

Sectional Area

Nominalmm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

22160001 25 5.7 3.4 2.2 44 1650 50022160002 35 7.1 3.4 2.3 47 2200 50022160003 50 7.9 3.4 2.4 50 2350 50022160004 70 9.7 3.4 2.5 53 2750 50022160005 95 11.3 3.4 2.7 58 3400 50022160006 120 12.6 3.4 2.7 61 3700 50022160007 150 14.1 3.4 2.8 64 4350 50022160008 185 16.0 3.4 2.9 67 4700 50022160009 240 18.1 3.4 3.1 74 5600 50022160010 300 20.4 3.4 3.3 79 6650 50022160011 400 23.1 3.4 3.5 83 7250 500

Three-cores XLPE Insulated PVC Sheathed Cable UnarmouredAL / XLPE / PVC Aluminum Conductor - Copper Wire Screened 6/10(12) kV

AL / XLPE / PVC Aluminum Conductor - Copper Tape Screened 6/10(12) kV

69

Page 71: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / PVC Aluminum Conductor Unarmoured - 6/10(12) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131 0.1034

Inductance at 60 Hz mH/Km 0.332 0.318 0.306 0.292 0.284 0.276 0.270 0.263 0.256 0.248 0.239

Reactance at 60 Hz Ω/km 0.125 0.120 0.115 0.110 0.107 0.104 0.102 0.099 0.097 0.093 0.090

Capacitance μF/Km 0.20 0.23 0.25 0.29 0.30 0.33 0.37 0.40 0.45 0.49 0.54

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.14 1.23 1.32 1.44 1.56 1.65 1.74 1.86 2.04 2.16 2.37

Current Rating Capacity

1- Laid direct in ground (Approx.) A 108 127 148 178 210 238 265 298 341 383 435

2- Laid in free air (Approx.) A 100 120 144 178 215 248 281 323 378 432 502

Voltage Drop per phase V/A/km 1.306 0.962 0.727 0.520 0.393 0.322 0.273 0.228 0.187 0.160 0.134

Minimum Bending radius mm 552 576 612 660 720 756 792 840 912 972 1020

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

70

Page 72: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

23150001 25 5.7 4.5 16 2.4 52 2150 50023150002 35 7.1 4.5 16 2.5 55 2700 50023150003 50 7.9 4.5 16 2.6 57 3000 50023150004 70 9.7 4.5 16 2.7 61 3400 50023150005 95 11.3 4.5 16 2.8 65 4000 50023150006 120 12.6 4.5 16 2.9 68 4300 50023150007 150 14.1 4.5 25 3.1 72 4850 50023150008 185 16.0 4.5 25 3.2 76 5500 50023150009 240 18.1 4.5 25 3.3 81 6400 50023150010 300 20.4 4.5 25 3.5 86 7300 50023150011 400 23.1 4.5 35 3.7 90 9800 500

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

23160001 25 5.7 4.5 2.4 49 2050 50023160002 35 7.1 4.5 2.5 52 2600 50023160003 50 7.9 4.5 2.6 55 2850 50023160004 70 9.7 4.5 2.7 58 3250 50023160005 95 11.3 4.5 2.8 63 3900 50023160006 120 12.6 4.5 2.9 66 4200 50023160007 150 14.1 4.5 3.0 69 4700 50023160008 185 16.0 4.5 3.1 73 5300 50023160009 240 18.1 4.5 3.3 79 6300 50023160010 300 20.4 4.5 3.4 84 7150 50023160011 400 23.1 4.5 3.7 88 9700 500

Three-cores XLPE Insulated PVC Sheathed Cable UnarmouredAL / XLPE / PVC Aluminum Conductor - Copper Wire Screened 8.7/15(17.5) kV

AL / XLPE / PVC Aluminum Conductor - Copper Tape Screened 8.7/15(17.5) kV

71

Page 73: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / PVC Aluminum Conductor Unarmoured - 8.7/15(17.5) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131 0.1034

Inductance at 60 Hz mH/Km 0.360 0.345 0.330 0.315 0.306 0.295 0.288 0.280 0.270 0.260 0.251

Reactance at 60 Hz Ω/km 0.14 0.13 0.12 0.12 0.12 0.11 0.11 0.11 0.10 0.10 0.09

Capacitance μF/Km 0.17 0.18 0.2 0.23 0.25 0.27 0.29 0.32 0.35 0.39 0.43

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.32 1.38 1.47 1.59 1.68 1.8 1.89 2.01 2.16 2.31 2.52

Current Rating Capacity

1- Laid direct in ground (Approx.) A 108 127 148 178 210 238 265 298 341 383 435

2- Laid in free air (Approx.) A 100 120 144 178 215 248 281 323 378 432 502

Voltage Drop per phase V/A/km 1.313 0.968 0.733 0.525 0.390 0.327 0.277 0.232 0.191 0.163 0.136

Minimum Bending radius mm 624 660 684 732 780 816 864 912 972 1032 1080

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

72

Page 74: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%24150001 35 7.1 5.5 16 2.7 60 3100 50024150002 50 7.9 5.5 16 2.8 61 3200 50024150003 70 9.7 5.5 16 2.9 64 3800 50024150004 95 11.3 5.5 16 3.0 69 4400 50024150005 120 12.6 5.5 16 3.1 73 4850 50024150006 150 14.1 5.5 25 3.2 77 5400 50024150007 185 16.0 5.5 25 3.3 80 6000 50024150008 240 18.1 5.5 25 3.5 86 7100 50024150009 300 20.4 5.5 25 3.6 91 7800 40024150010 400 23.1 5.5 35 3.8 97 8400 400

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

24160001 35 7.1 5.5 2.6 57 3000 50024160002 50 7.9 5.5 2.7 60 3250 50024160003 70 9.7 5.5 2.8 63 3650 50024160004 95 11.3 5.5 2.9 67 4200 50024160005 120 12.6 5.5 3.0 70 4700 50024160006 150 14.1 5.5 3.1 72 5200 50024160007 185 16.0 5.5 3.3 78 5800 50024160008 240 18.1 5.5 3.4 83 6900 50024160009 300 20.4 5.5 3.6 88 7700 40024160010 400 23.1 5.5 3.8 93 8200 400

Three-cores XLPE Insulated PVC Sheathed Cable UnarmouredAL / XLPE / PVC Aluminum Conductor - Copper Wire Screened 12/20(24) kV

AL / XLPE / PVC Aluminum Conductor - Copper Tape Screened 12/20(24) kV

73

Page 75: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / PVC Aluminum Conductor Unarmoured - 12/20(24) kV

Technical Information

Size mm2 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.113 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131 0.1034

Inductance at 60 Hz mH/Km 0.365 0.350 0.333 0.322 0.312 0.303 0.295 0.285 0.270 0.262

Reactance at 60 Hz Ω/km 0.14 0.13 0.13 0.12 0.12 0.11 0.11 0.11 0.10 0.10

Capacitance μF/Km 0.15 0.17 0.2 0.22 0.24 0.26 0.27 0.3 0.33 0.37

Short Circuit Current For 1 second

1- Conductor KA 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.5 1.59 1.71 1.83 1.92 2.04 2.16 2.31 2.46 2.64

Current Rating Capacity

1- Laid direct in ground (Approx.) A 127 148 178 210 238 265 298 341 383 435

2- Laid in free air (Approx.) A 120 144 178 215 248 281 323 378 432 502

Voltage Drop per phase V/A/km 1.320 0.973 0.737 0.530 0.402 0.331 0.281 0.236 0.194 0.165

Minimum Bending radius mm 720 732 768 828 876 924 960 1032 1092 1164

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

74

Page 76: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Nominalsectionalarea of

Screeningmm2

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

25150001 50 7.9 8.0 16 3.1 74 4500 50025150002 70 9.7 8.0 16 3.2 77 5100 50025150003 95 11.3 8.0 16 3.4 82 5700 50025150004 120 12.6 8.0 16 3.5 85 6200 50025150005 150 14.1 8.0 25 3.6 88 6800 50025150006 185 16.0 8.0 25 3.7 92 7400 30025150007 240 18.1 8.0 25 3.9 98 8600 30025150008 300 20.4 8.0 25 4.0 102 9700 300

Cable Code

Conductor Insulation Outer Sheath Packaging

Cross Sectional

Area Nominal

mm2

DiameterNominal

mm

Thickness Nominal

mm

Thickness Nominal

mm

Overall Diameter

Approx.mm

Net Weight

Approx.Kg/Km

Standard Drum

m+/-5%

25160001 50 7.9 8.0 3.1 72 4350 50025160002 70 9.7 8.0 3.2 75 4900 50025160003 95 11.3 8.0 3.3 79 5500 50025160004 120 12.6 8.0 3.4 82 6000 50025160005 150 14.1 8.0 3.5 85 6500 50025160006 185 16.0 8.0 3.6 89 7200 30025160007 240 18.1 8.0 3.8 95 8400 30025160008 300 20.4 8.0 4.0 100 9500 300

Three-cores XLPE Insulated PVC Sheathed Cable UnarmouredAL / XLPE / PVC Aluminum Conductor - Copper Wire Screened 18/30(36) kV

AL / XLPE / PVC Aluminum Conductor - Copper Tape Screened 18/30(36) kV

75

Page 77: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / PVC Aluminum Conductor Unarmoured - 18/30(36) kV

Technical Information

Size mm2 50 70 95 120 150 185 240 300

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131

Inductance at 60 Hz mH/Km 0.398 0.380 0.369 0.355 0.345 0.335 0.320 0.308

Reactance at 60 Hz Ω/km 0.15 0.14 0.14 0.13 0.13 0.13 0.12 0.12

Capacitance μF/Km 0.14 0.15 0.17 0.18 0.2 0.21 0.23 0.25

Short Circuit Current For 1 second

1- Conductor KA 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7

3- Copper Tape Screen KA 1.95 2.07 2.19 2.28 2.37 2.49 2.67 2.82

Current Rating Capacity

1- Laid direct in ground (Approx.) A 148 178 210 238 265 298 341 383

2- Laid in free air (Approx.) A 144 178 215 248 281 323 378 432

Voltage Drop per phase V/A/km 0.749 0.540 0.412 0.340 0.290 0.244 0.202 0.174

Minimum Bending radius mm 888 924 984 1020 1056 1104 1176 1224

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

76

Page 78: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

21110001 25 6.2 2.5 16 1.2 2.0 2.3 47 3600 50021110002 35 7.2 2.5 16 1.3 2.5 2.5 51 4500 50021110003 50 8.3 2.5 16 1.4 2.5 2.6 55 5200 50021110004 70 10 2.5 16 1.4 2.5 2.7 59 6100 50021110005 95 11.8 2.5 16 1.5 2.5 2.8 63 7300 50021110006 120 13.1 2.5 16 1.5 2.5 2.9 67 8300 50021110007 150 14.7 2.5 25 1.6 2.5 3.0 70 9500 50021110008 185 16.1 2.5 25 1.7 2.5 3.2 74 11800 50021110009 240 18.7 2.6 25 1.8 2.5 3.4 82 14100 50021110010 300 20.8 2.8 25 1.9 3.15 3.6 88 16200 50021110011 400 24 3.0 35 2.0 3.15 3.9 95 21000 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

21120001 25 6.2 2.5 1.2 2.0 2.3 43 3400 50021120002 35 7.2 2.5 1.2 2.5 2.3 47 4350 50021120003 50 8.3 2.5 1.3 2.5 2.5 49 5000 50021120004 70 10 2.5 1.4 2.5 2.6 55 5900 50021120005 95 11.8 2.5 1.4 2.5 2.7 59 7100 50021120006 120 13.1 2.5 1.5 2.5 2.8 63 8100 50021120007 150 14.7 2.5 1.5 2.5 2.9 65 9250 50021120008 185 16.1 2.5 1.6 2.5 3.0 70 11500 50021120009 240 18.7 2.6 1.7 2.5 3.2 75 14000 50021120010 300 20.8 2.8 1.8 3.15 3.5 82 15800 50021120011 400 24 3.0 1.9 3.15 3.8 92 20500 500

Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire ArmouredCU / XLPE / SWA / PVC Copper Conductor - Copper Wire Screened 3.6/6 (7.2) kV

CU / XLPE / SWA / PVC Copper Conductor - Copper Tape Screened 3.6/6 (7.2) kV

77

Page 79: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / SWA / PVC Copper Conductor Steel Wire Armoured - 3.6/6 (7.2) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.927 0.669 0.494 0.344 0.247 0.196 0.161 0.129 0.099 0.0815 0.0660

Inductance at 60 Hz mH/Km 0.365 0.345 0.334 0.322 0.316 0.10 0.303 0.300 0.294 0.286 0.279

Reactance at 60 Hz Ω/km 0.14 0.13 0.13 0.12 0.12 0.04 0.11 0.11 0.11 0.11 0.11

Capacitance μF/Km 0.26 0.30 0.32 0.36 0.39 0.44 0.46 0.53 0.56 0.58 0.60

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.02 1.08 1.17 1.29 1.41 1.53 1.62 1.74 1.92 2.1 2.31

Current Rating Capacity

1- Laid direct in ground (Approx.) A 140 170 196 245 278 310 344 390 440 490 530

2- Laid in free air (Approx.) A 132 158 189 240 285 320 365 415 484 545 615

Voltage Drop per phase V/A/km 0.820 0.613 0.471 0.345 0.269 0.228 0.197 0.170 0.145 0.130 0.121

Minimum Bending radius mm 564 612 660 708 756 804 840 888 984 1056 1140

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

78

Page 80: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

22110001 25 6.2 3.4 16 1.3 2.5 2.5 53 4550 50022110002 35 7.2 3.4 16 1.4 2.5 2.6 55 5000 50022110003 50 8.3 3.4 16 1.4 2.5 2.7 57 5700 50022110004 70 10 3.4 16 1.5 2.5 2.8 62 6700 50022110005 95 11.8 3.4 16 1.6 2.5 2.9 66 7700 50022110006 120 13.1 3.4 16 1.6 2.5 3.0 69 8550 50022110007 150 14.7 3.4 25 1.7 2.5 3.2 72 9800 50022110008 185 16.1 3.4 25 1.7 2.5 3.3 76 11200 50022110009 240 18.7 3.4 25 1.8 3.15 3.5 82 14300 50022110010 300 20.8 3.4 25 1.9 3.15 3.6 88 16600 40022110011 400 24 3.4 35 2.0 3.15 3.9 96 21000 400

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath PackagingCross

Sectional Area

Nominalmm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

22120001 25 6.2 3.4 1.3 2.5 2.4 50 4300 500

22120002 35 7.2 3.4 1.3 2.5 2.5 52 4700 500

22120003 50 8.3 3.4 1.4 2.5 2.6 55 5500 500

22120004 70 10 3.4 1.4 2.5 2.7 59 6500 500

22120005 95 11.8 3.4 1.5 2.5 2.9 63 7500 500

22120006 120 13.1 3.4 1.6 2.5 3.0 65 8300 500

22120007 150 14.7 3.4 1.6 2.5 3.1 70 9500 500

22120008 185 16.1 3.4 1.7 2.5 3.2 73 11000 500

22120009 240 18.7 3.4 1.8 3.15 3.4 79 14150 500

22120010 300 20.8 3.4 1.9 3.15 3.6 85 16400 400

22120011 400 24 3.4 2.0 3.15 3.9 95 20700 400

Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire ArmouredCU / XLPE / SWA / PVC Copper Conductor - Copper Wire Screened 6/10(12) kV

CU / XLPE / SWA / PVC Copper Conductor - Copper Tape Screened 6/10(12) kV

79

Page 81: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / SWA / PVC Copper Conductor Steel Wire Armoured - 6/10(12) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.927 0.669 0.494 0.344 0.247 0.196 0.161 0.129 0.099 0.0815 0.0660

Inductance at 60 Hz mH/Km 0.387 0.369 0.355 0.342 0.335 0.326 0.320 0.313 0.305 0.298 0.290

Reactance at 60 Hz Ω/km 0.15 0.14 0.13 0.13 0.13 0.12 0.12 0.12 0.11 0.11 0.11

Capacitance μF/Km 0.20 0.23 0.25 0.29 0.30 0.33 0.37 0.40 0.45 0.49 0.54

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.14 1.23 1.32 1.44 1.56 1.65 1.74 1.86 2.04 2.16 2.37

Current Rating Capacity

1- Laid direct in ground (Approx.) A 140 168 195 248 275 310 346 395 445 505 565

2- Laid in free air (Approx.) A 130 155 186 231 277 320 363 415 486 552 635

Voltage Drop per phase V/A/km 0.829 0.618 0.475 0.352 0.274 0.231 0.200 0.173 0.149 0.132 0.117

Minimum Bending radius mm 636 660 684 744 792 828 864 912 912 984 1056

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

80

Page 82: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

23110001 25 6.2 4.5 16 1.4 2.5 2.6 55 5450 50023110002 35 7.2 4.5 16 1.5 2.5 2.7 59 5700 50023110003 50 8.3 4.5 16 1.5 2.5 2.8 62 6400 50023110004 70 10 4.5 16 1.6 2.5 2.9 66 7400 50023110005 95 11.8 4.5 16 1.7 2.5 3.1 71 8500 50023110006 120 13.1 4.5 16 1.7 2.5 3.2 74 9700 50023110007 150 14.7 4.5 25 1.8 3.15 3.4 79 11800 50023110008 185 16.1 4.5 25 1.8 3.15 3.5 83 13500 50023110009 240 18.7 4.5 25 1.9 3.15 3.7 89 15800 50023110010 300 20.8 4.5 25 2.0 3.15 3.8 94 18500 40023110011 400 24 4.5 35 2.1 3.15 4.0 100 21500 400

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

23120001 25 6.2 4.5 1.4 2.5 2.6 52 5200 50023120002 35 7.2 4.5 1.4 2.5 2.7 56 5500 50023120003 50 8.3 4.5 1.5 2.5 2.8 60 6200 50023120004 70 10 4.5 1.5 2.5 2.9 63 7200 50023120005 95 11.8 4.5 1.6 2.5 3.0 67 8300 50023120006 120 13.1 4.5 1.7 2.5 3.2 72 9500 50023120007 150 14.7 4.5 1.7 3.15 3.3 75 11500 50023120008 185 16.1 4.5 1.8 3.15 3.4 80 13300 50023120009 240 18.7 4.5 1.9 3.15 3.6 86 15500 50023120010 300 20.8 4.5 2.0 3.15 3.8 91 18300 40023120011 400 24 4.5 2.1 3.15 4.0 96 21300 400

Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire ArmouredCU / XLPE / SWA / PVC Copper Conductor - Copper Wire Screened 8.7/15(17.5) kV

CU / XLPE / SWA / PVC Copper Conductor - Copper Tape Screened 8.7/15(17.5) kV

81

Page 83: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / SWA / PVC Copper Conductor Steel Wire Armoured - 8.7/15(17.5) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.927 0.669 0.494 0.344 0.247 0.196 0.161 0.129 0.099 0.0815 0.0655

Inductance at 60 Hz mH/Km 0.415 0.395 0.380 0.365 0.356 0.345 0.339 0.330 0.321 0.312 0.302

Reactance at 60 Hz Ω/km 0.16 0.15 0.14 0.14 0.13 0.13 0.13 0.12 0.12 0.12 0.11

Capacitance μF/Km 0.17 0.18 0.2 0.23 0.25 0.27 0.29 0.32 0.35 0.39 0.43

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.32 1.38 1.47 1.59 1.68 1.8 1.89 2.01 2.16 2.31 2.52

Current Rating Capacity

1- Laid direct in ground (Approx.) A 140 168 195 248 275 310 346 395 445 505 565

2- Laid in free air (Approx.) A 130 155 186 231 277 320 363 415 486 552 635

Voltage Drop per phase V/A/km 0.835 0.625 0.480 0.358 0.277 0.235 0.204 0.178 0.152 0.135 0.118

Minimum Bending radius mm 660 708 744 792 852 888 948 996 1068 1128 1200

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

82

Page 84: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of Steel Wire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

24110001 35 7.2 5.5 16 1.5 2.5 2.9 65 6500 50024110002 50 8.3 5.5 16 1.6 2.5 3.1 68 7400 50024110003 70 10 5.5 16 1.7 2.5 3.2 72 8500 50024110004 95 11.8 5.5 16 1.7 2.5 3.3 77 9800 50024110005 120 13.1 5.5 16 1.8 3.15 3.4 81 11800 50024110006 150 14.7 5.5 25 1.9 3.15 3.6 85 13000 50024110007 185 16.1 5.5 25 1.9 3.15 3.7 89 14600 40024110008 240 18.7 5.5 25 2.0 3.15 3.8 95 17000 40024110009 300 20.8 5.5 25 2.1 3.15 4.0 100 19500 30024110010 400 24 5.5 35 2.2 3.15 4.2 104 24000 300

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

24120001 35 7.2 5.5 1.5 2.5 2.9 63 6200 50024120002 50 8.3 5.5 1.6 2.5 3.0 65 7100 50024120003 70 10 5.5 1.6 2.5 3.1 69 8200 50024120004 95 11.8 5.5 1.7 2.5 3.2 75 9500 50024120005 120 13.1 5.5 1.7 3.15 3.3 78 11500 50024120006 150 14.7 5.5 1.8 3.15 3.5 82 12700 50024120007 185 16.1 5.5 1.9 3.15 3.6 86 14400 40024120008 240 18.7 5.5 2.0 3.15 3.7 91 16800 40024120009 300 20.8 5.5 2.0 3.15 3.9 97 19300 30024120010 400 24 5.5 2.1 3.15 4.1 102 23800 300

Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire ArmouredCU / XLPE / SWA / PVC Copper Conductor - Copper Wire Screened 12/20(24) kV

CU / XLPE / SWA / PVC Copper Conductor - Copper Tape Screened 12/20(24) kV

83

Page 85: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / SWA / PVC Copper Conductor Steel Wire Armoured - 12/20(24) kV

Technical Information

Size mm2 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.668 0.494 0.344 0.247 0.196 0.161 0.129 0.099 0.0810 0.0650

Inductance at 60 Hz mH/Km 0.415 0.400 0.381 0.374 0.362 0.354 0.345 0.335 0.320 0.305

Reactance at 60 Hz Ω/km 0.16 0.15 0.14 0.14 0.14 0.13 0.13 0.13 0.12 0.11

Capacitance μF/Km 0.15 0.17 0.2 0.22 0.24 0.26 0.27 0.3 0.33 0.37

Short Circuit Current For 1 second

1- Conductor KA 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.5 1.59 1.71 1.83 1.92 2.04 2.16 2.31 2.46 2.64

Current Rating Capacity

1- Laid direct in ground (Approx.) A 168 195 248 275 310 346 395 445 505 565

2- Laid in free air (Approx.) A 155 186 231 277 320 363 415 486 552 635

Voltage Drop per phase V/A/km 0.630 0.486 0.361 0.283 0.240 0.210 0.180 0.156 0.137 0.120

Minimum Bending radius mm 780 816 864 924 972 1020 1068 1140 1200 1248

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

84

Page 86: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

25110001 50 8.3 8.0 16 1.8 3.15 3.5 82 10100 40025110002 70 10 8.0 16 1.9 3.15 3.6 86 11500 40025110003 95 11.8 8.0 16 2.0 3.15 3.7 90 12800 40025110004 120 13.1 8.0 16 2.0 3.15 3.8 93 14000 40025110005 150 14.7 8.0 25 2.1 3.15 4.0 97 15200 40025110006 185 16.1 8.0 25 2.1 3.15 4.1 101 16800 40025110007 240 18.7 8.0 25 2.2 3.15 4.2 106 19500 30025110008 300 20.8 8.0 25 2.3 3.15 4.4 112 21000 300

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

25120001 50 8.3 8.0 1.8 3.15 3.4 79 9800 40025120002 70 10 8.0 1.9 3.15 3.5 83 11200 40025120003 95 11.8 8.0 2.0 3.15 3.6 87 12500 40025120004 120 13.1 8.0 2.0 3.15 3.7 90 13700 40025120005 150 14.7 8.0 2.1 3.15 3.9 94 14900 40025120006 185 16.1 8.0 2.1 3.15 4.0 98 16500 40025120007 240 18.7 8.0 2.2 3.15 4.1 103 19100 30025120008 300 20.8 8.0 2.3 3.15 4.3 109 20700 300

Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire ArmouredCU / XLPE / SWA / PVC Copper Conductor - Copper Wire Screened 18/30(36) kV

CU / XLPE / SWA / PVC Copper Conductor - Copper Tape Screened 18/30(36) kV

85

Page 87: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / SWA / PVC Copper Conductor Steel Wire Armoured - 18/30(36) kV

Technical Information

Size mm2 50 70 95 120 150 185 240 300

Maximum DC resistance of Conductor @ 20° C

Ω/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.494 0.341 0.247 0.196 0.161 0.128 0.098 0.0801

Inductance at 60 Hz mH/Km 0.450 0.432 0.420 0.405 0.395 0.385 0.372 0.360

Reactance at 60 Hz Ω/km 0.17 0.16 0.16 0.15 0.15 0.15 0.14 0.14

Capacitance μF/Km 0.14 0.15 0.17 0.18 0.2 0.21 0.23 0.25

Short Circuit Current For 1 second

1- Conductor KA 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7

3- Copper Tape Screen KA 1.95 2.07 2.19 2.28 2.37 2.49 2.67 2.82

Current Rating Capacity

1- Laid direct in ground (Approx.) A 195 248 275 310 346 395 445 505

2- Laid in free air (Approx.) A 186 231 277 320 363 415 486 552

Voltage Drop per phase V/A/km 0.497 0.372 0.292 0.248 0.217 0.190 0.164 0.143

Minimum Bending radius mm 984 1032 1080 1116 1164 1212 1272 1344

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

86

Page 88: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

21230001 25 5.7 2.5 16 1.2 2.0 2.3 47 3150 50021230002 35 7.1 2.5 16 1.3 2.5 2.4 51 4100 50021230003 50 7.9 2.5 16 1.4 2.5 2.5 53 4400 50021230004 70 9.7 2.5 16 1.4 2.5 2.6 57 4950 50021230005 95 11.3 2.5 16 1.5 2.5 2.8 61 5600 50021230006 120 12.6 2.5 16 1.5 2.5 2.9 64 6150 50021230007 150 14.1 2.5 25 1.6 2.5 3.0 68 6900 50021230008 185 16.0 2.5 25 1.7 2.5 3.1 73 7800 50021230009 240 18.1 2.6 25 1.8 2.5 3.4 80 9900 50021230010 300 20.4 2.8 25 1.9 3.15 3.6 87 11200 50021230011 400 23.1 3.0 35 2.0 3.15 3.9 94 11500 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

21240001 25 5.7 2.5 1.2 2.0 2.3 44 2950 50021240002 35 7.1 2.5 1.2 2.5 2.3 41 3800 50021240003 50 7.9 2.5 1.3 2.5 2.5 51 4200 50021240004 70 9.7 2.5 1.4 2.5 2.6 54 4700 50021240005 95 11.3 2.5 1.4 2.5 2.7 58 5400 50021240006 120 12.6 2.5 1.5 2.5 2.8 62 5900 50021240007 150 14.1 2.5 1.5 2.5 2.9 65 6650 50021240008 185 16.0 2.5 1.6 2.5 3.1 70 7550 50021240009 240 18.1 2.6 1.7 2.5 3.2 76 9700 50021240010 300 20.4 2.8 1.8 3.15 3.5 83 11000 50021240011 400 23.1 3.0 1.9 3.15 3.8 88 11300 500

Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire ArmouredAL / XLPE / SWA / PVC Aluminum Conductor - Copper Wire Screened 3.6/6(7.2) kV

AL / XLPE / SWA / PVC Aluminum Conductor - Copper Tape Screened 3.6/6(7.2) kV

87

Page 89: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / SWA / PVC Aluminum Conductor Steel Wire Armoured - 3.6/6(7.2) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131 0.1034

Inductance at 60 Hz mH/Km 0.365 0.345 0.334 0.322 0.316 0.10 0.303 0.300 0.294 0.286 0.279

Reactance at 60 Hz Ω/km 0.14 0.13 0.13 0.12 0.12 0.04 0.11 0.11 0.11 0.11 0.11

Capacitance μF/Km 0.26 0.30 0.32 0.36 0.39 0.44 0.46 0.53 0.56 0.58 0.60

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.02 1.08 1.17 1.29 1.41 1.53 1.62 1.74 1.92 2.1 2.31

Current Rating Capacity

1- Laid direct in ground (Approx.) A 108 127 148 178 211 238 264 297 339 379 426

2- Laid in free air (Approx.) A 101 121 145 178 217 249 281 322 378 430 496

Voltage Drop per phase V/A/km 1.313 0.968 0.733 0.527 0.400 0.330 0.281 0.237 0.196 0.169 0.140

Minimum Bending radius mm 564 612 636 684 732 768 816 876 960 1044 1128

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

88

Page 90: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

22230001 25 5.7 3.4 16 1.3 2.5 2.5 52 4000 50022230002 35 7.1 3.4 16 1.4 2.5 2.6 55 4600 50022230003 50 7.9 3.4 16 1.4 2.5 2.7 58 5000 50022230004 70 9.7 3.4 16 1.5 2.5 2.8 61 5550 50022230005 95 11.3 3.4 16 1.6 2.5 2.9 65 7000 50022230006 120 12.6 3.4 16 1.6 2.5 3.0 69 6900 50022230007 150 14.1 3.4 25 1.7 2.5 3.2 72 7700 50022230008 185 16.0 3.4 25 1.7 2.5 3.3 76 8300 50022230009 240 18.1 3.4 25 1.8 3.15 3.5 84 10600 50022230010 300 20.4 3.4 25 1.9 3.15 3.6 89 11650 40022230011 400 23.1 3.4 35 2.0 3.15 3.9 94 14000 400

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

22240001 25 5.7 3.4 1.3 2.5 2.4 49 3750 50022240002 35 7.1 3.4 1.3 2.5 2.5 52 4300 50022240003 50 7.9 3.4 1.4 2.5 2.6 55 4800 50022240004 70 9.7 3.4 1.4 2.5 2.7 58 5300 50022240005 95 11.3 3.4 1.5 2.5 2.9 63 6800 50022240006 120 12.6 3.4 1.6 2.5 3.0 66 6700 50022240007 150 14.1 3.4 1.6 2.5 3.1 70 7500 50022240008 185 16.0 3.4 1.7 2.5 3.2 73 8100 50022240009 240 18.1 3.4 1.8 3.15 3.4 80 10400 50022240010 300 20.4 3.4 1.9 3.15 3.6 85 11400 40022240011 400 23.1 3.4 2.0 3.15 3.9 93 13700 400

Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire ArmouredAL / XLPE / SWA / PVC Aluminum Conductor - Copper Wire Screened 6/10(12) kV

AL / XLPE / SWA / PVC Aluminum Conductor - Copper Tape Screened 6/10(12) kV

89

Page 91: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / SWA / PVC Aluminum Conductor Steel Wire Armoured - 6/10(12) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131 0.1034

Inductance at 60 Hz mH/Km 0.387 0.369 0.355 0.342 0.335 0.326 0.320 0.313 0.305 0.298 0.290

Reactance at 60 Hz Ω/km 0.15 0.14 0.13 0.13 0.13 0.12 0.12 0.12 0.11 0.11 0.11

Capacitance μF/Km 0.20 0.23 0.25 0.29 0.30 0.33 0.37 0.40 0.45 0.49 0.54

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.14 1.23 1.32 1.44 1.56 1.65 1.74 1.86 2.04 2.16 2.37

Current Rating Capacity

1- Laid direct in ground (Approx.) A 108 127 148 178 210 238 265 298 341 383 435

2- Laid in free air (Approx.) A 100 120 144 178 215 248 281 323 378 432 502

Voltage Drop per phase V/A/km 1.319 0.974 0.739 0.532 0.405 0.334 0.284 0.240 0.199 0.172 0.142

Minimum Bending radius mm 624 660 696 732 780 828 864 912 1008 1068 1128

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

90

Page 92: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

23230001 25 5.7 4.5 16 1.4 2.5 2.6 58 4600 50023230002 35 7.1 4.5 16 1.5 2.5 2.7 60 5150 50023230003 50 7.9 4.5 16 1.5 2.5 2.8 63 5700 50023230004 70 9.7 4.5 16 1.6 2.5 2.9 66 6200 50023230005 95 11.3 4.5 16 1.7 2.5 3.1 71 7150 50023230006 120 12.6 4.5 16 1.7 2.5 3.2 74 7700 50023230007 150 14.1 4.5 25 1.8 3.15 3.4 80 9300 50023230008 185 16.0 4.5 25 1.8 3.15 3.5 83 10100 50023230009 240 18.1 4.5 25 1.9 3.15 3.7 89 11500 50023230010 300 20.4 4.5 25 2.0 3.15 3.8 94 12700 40023230011 400 23.1 4.5 35 2.1 3.15 4.0 100 13000 400

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

23240001 25 5.7 4.5 1.4 2.5 2.6 55 4350 50023240002 35 7.1 4.5 1.4 2.5 2.7 57 4950 50023240003 50 7.9 4.5 1.5 2.5 2.8 60 5500 50023240004 70 9.7 4.5 1.5 2.5 2.9 64 6000 50023240005 95 11.3 4.5 1.6 2.5 3.0 68 7000 50023240006 120 12.6 4.5 1.7 2.5 3.2 72 7500 50023240007 150 14.1 4.5 1.7 3.15 3.3 75 9100 50023240008 185 16.0 4.5 1.8 3.15 3.4 80 10000 50023240009 240 18.1 4.5 1.9 3.15 3.6 86 11300 50023240010 300 20.4 4.5 2.0 3.15 3.8 92 12500 40023240011 400 23.1 4.5 2.1 3.15 4.0 96 12800 400

Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire ArmouredAL / XLPE / SWA / PVC Aluminum Conductor - Copper Wire Screened 8.7/15(17.5) kV

AL / XLPE / SWA / PVC Aluminum Conductor - Copper Tape Screened 8.7/15(17.5) kV

91

Page 93: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / SWA / PVC Aluminum Conductor Steel Wire Armoured - 8.7/15(17.5) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131 0.1034

Inductance at 60 Hz mH/Km 0.415 0.395 0.380 0.365 0.356 0.345 0.339 0.330 0.321 0.312 0.302

Reactance at 60 Hz Ω/km 0.16 0.15 0.14 0.14 0.13 0.13 0.13 0.12 0.12 0.12 0.11

Capacitance μF/Km 0.17 0.18 0.2 0.23 0.25 0.27 0.29 0.32 0.35 0.39 0.43

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.32 1.38 1.47 1.59 1.68 1.8 1.89 2.01 2.16 2.31 2.52

Current Rating Capacity

1- Laid direct in ground (Approx.) A 108 127 148 178 210 238 265 298 341 383 435

2- Laid in free air (Approx.) A 100 120 144 178 215 248 281 323 378 432 502

Voltage Drop per phase V/A/km 1.325 0.980 0.744 0.537 0.410 0.338 0.289 0.243 0.202 0.175 0.145

Minimum Bending radius mm 696 720 756 792 852 888 960 996 1068 1128 1200

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

92

Page 94: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of Steel Wire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

24230001 35 7.1 5.5 16 1.5 2.5 2.9 65 5450 50024230002 50 7.9 5.5 16 1.6 2.5 3.1 66 5800 50024230003 70 9.7 5.5 16 1.7 2.5 3.2 72 6200 50024230004 95 11.3 5.5 16 1.7 2.5 3.3 76 7000 50024230005 120 12.6 5.5 16 1.8 3.15 3.4 81 7900 50024230006 150 14.1 5.5 25 1.9 3.15 3.6 84 9400 50024230007 185 16.0 5.5 25 1.9 3.15 3.7 88 10150 40024230008 240 18.1 5.5 25 2.0 3.15 3.8 94 11000 40024230009 300 20.4 5.5 25 2.1 3.15 4.0 99 12300 30024230010 400 23.1 5.5 35 2.2 3.15 4.2 104 13600 300

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

24240001 35 7.1 5.5 1.5 2.5 2.8 62 5300 50024240002 50 7.9 5.5 1.6 2.5 2.9 65 5600 50024240003 70 9.7 5.5 1.6 2.5 3.1 68 6000 50024240004 95 11.3 5.5 1.7 2.5 3.2 73 6800 50024240005 120 12.6 5.5 1.7 3.15 3.4 78 7700 50024240006 150 14.1 5.5 1.8 3.15 3.5 82 9250 50024240007 185 16.0 5.5 1.9 3.15 3.6 85 10000 40024240008 240 18.1 5.5 2.0 3.15 3.8 91 10800 40024240009 300 20.4 5.5 2.0 3.15 3.9 96 12100 30024240010 400 23.1 5.5 2.1 3.15 4.1 100 13400 300

Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire ArmouredAL / XLPE / SWA / PVC Aluminum Conductor - Copper Wire Screened 12/20(24) kV

AL / XLPE / SWA / PVC Aluminum Conductor - Copper Tape Screened 12/20(24) kV

93

Page 95: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / SWA / PVC Aluminum Conductor Steel Wire Armoured - 12/20(24) kV

Technical Information

Size mm2 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.113 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131 0.1034

Inductance at 60 Hz mH/Km 0.415 0.400 0.381 0.374 0.362 0.354 0.345 0.335 0.320 0.305

Reactance at 60 Hz Ω/km 0.16 0.15 0.14 0.14 0.14 0.13 0.13 0.13 0.12 0.11

Capacitance μF/Km 0.15 0.17 0.2 0.22 0.24 0.26 0.27 0.3 0.33 0.37

Short Circuit Current For 1 second

1- Conductor KA 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.5 1.59 1.71 1.83 1.92 2.04 2.16 2.31 2.46 2.64

Current Rating Capacity

1- Laid direct in ground (Approx.) A 127 148 178 210 238 265 298 341 383 435

2- Laid in free air (Approx.) A 120 144 178 215 248 281 323 378 432 502

Voltage Drop per phase V/A/km 0.984 0.749 0.541 0.413 0.342 0.292 0.247 0.205 0.176 0.147

Minimum Bending radius mm 780 792 864 912 972 1008 1056 1128 1188 1248

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

94

Page 96: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

25230001 50 7.9 8.0 16 1.8 3.15 3.5 82 9200 40025230002 70 9.7 8.0 16 1.9 3.15 3.6 86 9900 40025230003 95 11.3 8.0 16 2.0 3.15 3.7 90 10800 40025230004 120 12.6 8.0 16 2.0 3.15 3.8 93 11500 40025230005 150 14.1 8.0 25 2.1 3.15 4.0 97 12300 40025230006 185 16.0 8.0 25 2.1 3.15 4.1 101 13200 40025230007 240 18.1 8.0 25 2.2 3.15 4.2 106 14600 30025230008 300 20.4 8.0 25 2.3 3.15 4.4 112 16000 300

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Dia. Of SteelWire

Nominalmm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

25240001 50 7.9 8.0 1.8 3.15 3.4 79 8900 40025240002 70 9.7 8.0 1.9 3.15 3.5 83 9600 40025240003 95 11.3 8.0 2.0 3.15 3.6 87 10500 40025240004 120 12.6 8.0 2.0 3.15 3.7 90 11150 40025240005 150 14.1 8.0 2.1 3.15 3.9 94 12100 40025240006 185 16.0 8.0 2.1 3.15 4.0 98 13000 40025240007 240 18.1 8.0 2.2 3.15 4.1 103 14300 30025240008 300 20.4 8.0 2.3 3.15 4.3 108 15700 300

Three-cores XLPE Insulated PVC Sheathed Cable Steel Wire ArmouredAL / XLPE / SWA / PVC Aluminum Conductor - Copper Wire Screened 18/30(36) kV

AL / XLPE / SWA / PVC Aluminum Conductor - Copper Tape Screened 18/30(36) kV

95

Page 97: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / SWA / PVC Aluminum Conductor Steel Wire Armoured - 18/30(36) kV

Technical Information

Size mm2 50 70 95 120 150 185 240 300

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131

Inductance at 60 Hz mH/Km 0.450 0.432 0.420 0.405 0.395 0.385 0.372 0.360

Reactance at 60 Hz Ω/km 0.17 0.16 0.16 0.15 0.15 0.15 0.14 0.14

Capacitance μF/Km 0.14 0.15 0.17 0.18 0.2 0.21 0.23 0.25

Short Circuit Current For 1 second

1- Conductor KA 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7

3- Copper Tape Screen KA 1.95 2.07 2.19 2.28 2.37 2.49 2.67 2.82

Current Rating Capacity

1- Laid direct in ground (Approx.) A 148 178 210 238 265 298 341 383

2- Laid in free air (Approx.) A 144 178 215 248 281 323 378 432

Voltage Drop per phase V/A/km 0.760 0.552 0.424 0.352 0.301 0.256 0.214 0.185

Minimum Bending radius mm 984 1032 1080 1116 1164 1212 1272 1344

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

96

Page 98: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Thickness of Steel

TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

21090001 25 6.2 2.5 16 1.2 0.5 2.3 45 2900 50021090002 35 7.2 2.5 16 1.3 0.5 2.4 48 3200 50021090003 50 8.3 2.5 16 1.4 0.5 2.5 50 3700 50021090004 70 10 2.5 16 1.4 0.5 2.6 54 4700 50021090005 95 11.8 2.5 16 1.5 0.5 2.7 58 5600 50021090006 120 13.1 2.5 16 1.5 0.5 2.8 62 6450 50021090007 150 14.7 2.5 25 1.6 0.5 2.9 66 7600 50021090008 185 16.1 2.5 25 1.7 0.5 3.1 70 8850 50021090009 240 18.7 2.6 25 1.8 0.5 3.2 75 11000 50021090010 300 20.8 2.8 25 1.9 0.5 3.4 81 13200 50021090011 400 24 3.0 35 2.0 0.5 3.7 90 17900 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Thickness of Steel TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

21100001 25 6.2 2.5 1.2 0.5 2.2 42 2700 50021100002 35 7.2 2.5 1.2 0.5 2.3 45 3100 50021100003 50 8.3 2.5 1.3 0.5 2.4 47 3600 50021100004 70 10 2.5 1.4 0.5 2.5 51 4500 50021100005 95 11.8 2.5 1.4 0.5 2.6 55 5500 50021100006 120 13.1 2.5 1.5 0.5 2.7 59 6300 50021100007 150 14.7 2.5 1.5 0.5 2.8 63 7400 50021100008 185 16.1 2.5 1.6 0.5 2.9 66 8700 50021100009 240 18.7 2.6 1.7 0.5 3.1 72 10800 50021100010 300 20.8 2.8 1.8 0.5 3.3 79 13000 50021100011 400 24 3.0 1.9 0.5 3.6 88 17650 500

Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape ArmouredCU / XLPE / STA / PVC Copper Conductor - Copper Wire Screened 3.6/6 (7.2) kV

CU / XLPE / STA / PVC Copper Conductor - Copper Tape Screened 3.6/6 (7.2) kV

97

Page 99: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / STA / PVC Copper Conductor Steel Tape Armoured - 3.6/6 (7.2) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.927 0.669 0.494 0.344 0.247 0.196 0.161 0.129 0.099 0.0815 0.0660

Inductance at 60 Hz mH/Km 0.364 0.344 0.333 0.322 0.316 0.310 0.303 0.300 0.295 0.286 0.275

Reactance at 60 Hz Ω/km 0.14 0.13 0.13 0.12 0.12 0.12 0.11 0.11 0.11 0.11 0.10

Capacitance μF/Km 0.26 0.30 0.32 0.36 0.39 0.44 0.46 0.53 0.56 0.58 0.60

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.02 1.08 1.17 1.29 1.41 1.53 1.62 1.74 1.92 2.1 2.31

Current Rating Capacity

1- Laid direct in ground (Approx.) A 140 170 196 245 278 310 344 390 440 490 530

2- Laid in free air (Approx.) A 132 165 186 240 284 320 365 418 484 545 620

Voltage Drop per phase V/A/km 0.820 0.614 0.417 0.346 0.270 0.228 0.197 0.170 0.145 0.130 0.116

Minimum Bending radius mm 540 576 600 648 696 744 792 840 900 972 1080

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

98

Page 100: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Thickness of Steel

TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

22090001 25 6.2 3.4 16 1.3 0.5 2.4 50 3250 50022090002 35 7.2 3.4 16 1.4 0.5 2.5 52 3700 50022090003 50 8.3 3.4 16 1.4 0.5 2.6 56 4200 50022090004 70 10 3.4 16 1.5 0.5 2.7 60 5200 50022090005 95 11.8 3.4 16 1.6 0.5 2.9 65 6100 50022090006 120 13.1 3.4 16 1.6 0.5 3.0 68 7400 50022090007 150 14.7 3.4 25 1.7 0.5 3.1 72 8400 50022090008 185 16.1 3.4 25 1.7 0.5 3.2 75 9500 50022090009 240 18.7 3.4 25 1.8 0.5 3.4 81 11700 50022090010 300 20.8 3.4 25 1.9 0.5 3.6 88 13800 50022090011 400 24 3.4 35 2.0 0.8 3.7 89 17600 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Thickness of Steel TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

22100001 25 6.2 3.4 1.3 0.5 2.3 48 3000 50022100002 35 7.2 3.4 1.3 0.5 2.4 50 3500 50022100003 50 8.3 3.4 1.4 0.5 2.5 53 4000 50022100004 70 10 3.4 1.4 0.5 2.6 57 5000 50022100005 95 11.8 3.4 1.5 0.5 2.7 60 5850 50022100006 120 13.1 3.4 1.6 0.5 2.9 64 7150 50022100007 150 14.7 3.4 1.6 0.5 3.0 68 8200 50022100008 185 16.1 3.4 1.7 0.5 3.1 71 9300 50022100009 240 18.7 3.4 1.8 0.5 3.3 78 11500 50022100010 300 20.8 3.4 1.9 0.5 3.4 83 13550 50022100011 400 24 3.4 2.0 0.8 3.6 86 17400 500

Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape ArmouredCU / XLPE / STA / PVC Copper Conductor - Copper Wire Screened 6/10(12) kV

CU / XLPE / STA / PVC Copper Conductor - Copper Tape Screened 6/10(12) kV

99

Page 101: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / STA / PVC Copper Conductor Steel Tape Armoured - 6/10(12) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.927 0.669 0.494 0.344 0.247 0.196 0.161 0.129 0.099 0.0815 0.0660

Inductance at 60 Hz mH/Km 0.388 0.369 0.358 0.342 0.335 0.326 0.320 0.315 0.306 0.298 0.290

Reactance at 60 Hz Ω/km 0.15 0.14 0.13 0.13 0.13 0.12 0.12 0.12 0.12 0.11 0.11

Capacitance μF/Km 0.20 0.23 0.25 0.29 0.30 0.33 0.37 0.40 0.45 0.49 0.54

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.14 1.23 1.32 1.44 1.56 1.65 1.74 1.86 2.04 2.16 2.37

Current Rating Capacity

1- Laid direct in ground (Approx.) A 140 168 195 248 275 310 346 395 445 505 565

2- Laid in free air (Approx.) A 130 155 186 231 277 320 363 415 486 552 635

Voltage Drop per phase V/A/km 0.830 0.618 0.477 0.350 0.274 0.231 0.200 0.173 0.147 0.131 0.117

Minimum Bending radius mm 600 624 672 720 780 816 864 900 972 1056 1068

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

100

Page 102: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Thickness of Steel

TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

23090001 25 6.2 4.5 16 1.4 0.5 2.6 53 4100 50023090002 35 7.2 4.5 16 1.5 0.5 2.7 58 4300 50023090003 50 8.3 4.5 16 1.5 0.5 2.8 61 4800 50023090004 70 10 4.5 16 1.6 0.5 2.9 65 5800 50023090005 95 11.8 4.5 16 1.7 0.5 3.0 69 6700 50023090006 120 13.1 4.5 16 1.7 0.5 3.1 73 7800 50023090007 150 14.7 4.5 25 1.8 0.5 3.3 76 8900 50023090008 185 16.1 4.5 25 1.8 0.5 3.4 80 10200 50023090009 240 18.7 4.5 25 1.9 0.5 3.6 83 12500 50023090010 300 20.8 4.5 25 2.0 0.8 3.7 91 15500 40023090011 400 24 4.5 35 2.1 0.8 3.8 93 18700 400

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Thickness of Steel TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

23100001 25 6.2 4.5 1.4 0.5 2.5 49 3900 50023100002 35 7.2 4.5 1.4 0.5 2.6 55 4100 50023100003 50 8.3 4.5 1.5 0.5 2.7 57 4500 50023100004 70 10 4.5 1.5 0.5 2.8 61 5500 50023100005 95 11.8 4.5 1.6 0.5 2.9 66 6500 50023100006 120 13.1 4.5 1.7 0.5 3.0 69 7600 50023100007 150 14.7 4.5 1.7 0.5 3.1 73 8700 50023100008 185 16.1 4.5 1.8 0.5 3.3 77 9950 50023100009 240 18.7 4.5 1.9 0.5 3.4 81 12200 50023100010 300 20.8 4.5 2.0 0.8 3.6 88 15000 40023100011 400 24 4.5 2.1 0.8 3.8 92 18500 400

Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape ArmouredCU / XLPE / STA / PVC Copper Conductor - Copper Wire Screened 8.7/15(17.5) kV

CU / XLPE / STA / PVC Copper Conductor- Copper Tape Screened, 8.7/15(17.5) kV

101

Page 103: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / STA / PVC Copper Conductor Steel Tape Armoured - 8.7/15(17.5) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.927 0.669 0.494 0.344 0.247 0.196 0.161 0.129 0.099 0.0815 0.0655

Inductance at 60 Hz mH/Km 0.413 0.395 0.382 0.365 0.355 0.346 0.339 0.330 0.321 0.312 0.303

Reactance at 60 Hz Ω/km 0.16 0.15 0.14 0.14 0.13 0.13 0.13 0.12 0.12 0.12 0.11

Capacitance μF/Km 0.17 0.18 0.2 0.23 0.25 0.27 0.29 0.32 0.35 0.39 0.43

Short Circuit Current For 1 second

1- Conductor KA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.32 1.38 1.47 1.59 1.68 1.8 1.89 2.01 2.16 2.31 2.52

Current Rating Capacity

1- Laid direct in ground (Approx.) A 140 168 195 248 275 310 346 395 445 505 565

2- Laid in free air (Approx.) A 130 155 186 231 277 320 363 415 486 552 635

Voltage Drop per phase V/A/km 0.835 0.625 0.480 0.357 0.278 0.235 0.205 0.178 0.152 0.135 0.118

Minimum Bending radius mm 636 696 732 780 828 876 912 960 996 1092 1116

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

102

Page 104: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Thickness of Steel

TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

24090001 35 7.2 5.5 16 1.5 0.5 2.8 62 4500 50024090002 50 8.3 5.5 16 1.6 0.5 2.9 65 5200 50024090003 70 10 5.5 16 1.7 0.5 3.1 69 6000 50024090004 95 11.8 5.5 16 1.7 0.5 3.2 72 7200 50024090005 120 13.1 5.5 16 1.8 0.5 3.3 75 8100 50024090006 150 14.7 5.5 25 1.9 0.5 3.4 80 9300 50024090007 185 16.1 5.5 25 1.9 0.5 3.6 83 10700 50024090008 240 18.7 5.5 25 2.0 0.8 3.7 90 13800 50024090009 300 20.8 5.5 25 2.1 0.8 3.9 95 16000 40024090010 400 24 5.5 35 2.2 0.8 4.1 98 18500 400

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Thickness of Steel TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

24100001 35 7.2 5.5 1.5 0.5 2.8 59 4300 50024100002 50 8.3 5.5 1.6 0.5 2.9 62 5000 50024100003 70 10 5.5 1.6 0.5 3.0 66 5800 50024100004 95 11.8 5.5 1.7 0.5 3.2 68 7000 50024100005 120 13.1 5.5 1.7 0.5 3.3 70 7850 50024100006 150 14.7 5.5 1.8 0.5 3.4 74 9150 50024100007 185 16.1 5.5 1.9 0.5 3.5 80 10500 50024100008 240 18.7 5.5 2.0 0.8 3.7 88 13550 50024100009 300 20.8 5.5 2.0 0.8 3.9 92 15850 40024100010 400 24 5.5 2.1 0.8 4.0 96 18300 400

Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape ArmouredCU / XLPE / STA / PVC Copper Conductor - Copper Wire Screened 12/20(24) kV

CU / XLPE / STA / PVC Copper Conductor - Copper Tape Screened 12/20(24) kV

103

Page 105: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / STA / PVC Copper Conductor Steel Tape Armoured - 12/20(24) kV

Technical Information

Size mm2 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.668 0.494 0.344 0.247 0.196 0.161 0.129 0.099 0.0810 0.0650

Inductance at 60 Hz mH/Km 0.415 0.402 0.381 0.374 0.362 0.353 0.345 0.336 0.320 0.305

Reactance at 60 Hz Ω/km 0.16 0.15 0.14 0.14 0.14 0.13 0.13 0.13 0.12 0.11

Capacitance μF/Km 0.15 0.17 0.2 0.22 0.24 0.26 0.27 0.3 0.33 0.37

Short Circuit Current For 1 second

1- Conductor KA 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90 57.20

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.5 1.59 1.71 1.83 1.92 2.04 2.16 2.31 2.46 2.64

Current Rating Capacity

1- Laid direct in ground (Approx.) A 168 195 248 275 310 346 395 445 505 565

2- Laid in free air (Approx.) A 155 186 231 277 320 363 415 486 552 635

Voltage Drop per phase V/A/km 0.630 0.485 0.360 0.283 0.239 0.208 0.180 0.156 0.136 0.119

Minimum Bending radius mm 744 780 828 864 900 960 996 1080 1140 1176

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

104

Page 106: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Thickness of Steel

TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

25090001 50 8.3 8.0 16 1.8 0.5 3.3 78 6800 40025090002 70 10 8.0 16 1.9 0.5 3.4 81 7850 40025090003 95 11.8 8.0 16 2.0 0.5 3.5 86 8900 40025090004 120 13.1 8.0 16 2.0 0.8 3.7 90 10900 40025090005 150 14.7 8.0 25 2.1 0.8 3.8 92 12000 40025090006 185 16.1 8.0 25 2.1 0.8 3.9 96 13500 40025090007 240 18.7 8.0 25 2.2 0.8 4.1 102 15900 30025090008 300 20.8 8.0 25 2.3 0.8 4.2 108 18100 300

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Thickness of Steel TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

25100001 50 8.3 8.0 1.8 0.5 3.2 75 6650 40025100002 70 10 8.0 1.8 0.5 3.3 78 7650 40025100003 95 11.8 8.0 1.9 0.5 3.5 83 8700 40025100004 120 13.1 8.0 2.0 0.8 3.6 87 10700 40025100005 150 14.7 8.0 2.0 0.8 3.7 90 11750 40025100006 185 16.1 8.0 2.1 0.8 3.9 94 13500 40025100007 240 18.7 8.0 2.2 0.8 4.0 100 15500 30025100008 300 20.8 8.0 2.3 0.8 4.2 106 17800 300

Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape ArmouredCU / XLPE / STA / PVC Copper Conductor - Copper Wire Screened 18/30(36) kV

CU / XLPE / STA / PVC Copper Conductor - Copper Tape Screened 18/30(36) kV

105

Page 107: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

CU / XLPE / STA / PVC Copper Conductor Steel Tape Armoured - 18/30(36) kV

Technical Information

Size mm2 50 70 95 120 150 185 240 300

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.494 0.341 0.247 0.196 0.161 0.128 0.098 0.0801

Inductance at 60 Hz mH/Km 0.450 0.430 0.419 0.403 0.395 0.381 0.371 0.359

Reactance at 60 Hz Ω/km 0.17 0.16 0.16 0.15 0.15 0.14 0.14 0.14

Capacitance μF/Km 0.14 0.15 0.17 0.18 0.2 0.21 0.23 0.25

Short Circuit Current For 1 second

1- Conductor KA 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7

3- Copper Tape Screen KA 1.95 2.07 2.19 2.28 2.37 2.49 2.67 2.82

Current Rating Capacity

1- Laid direct in ground (Approx.) A 195 248 275 310 346 395 445 505

2- Laid in free air (Approx.) A 186 231 277 320 363 415 486 552

Voltage Drop per phase V/A/km 0.496 0.325 0.293 0.250 0.218 0.190 0.165 0.145

Minimum Bending radius mm 936 972 1032 1080 1104 1152 1224 1296

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

106

Page 108: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Thickness of Steel

TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

21210001 25 5.7 2.5 16 1.2 0.5 2.2 45 2300 50021210002 35 7.1 2.5 16 1.3 0.5 2.3 48 2700 50021210003 50 7.9 2.5 16 1.4 0.5 2.4 50 3100 50021210004 70 9.7 2.5 16 1.4 0.5 2.5 54 3350 50021210005 95 11.3 2.5 16 1.5 0.5 2.6 58 3900 50021210006 120 12.6 2.5 16 1.5 0.5 2.8 61 4400 50021210007 150 14.1 2.5 25 1.6 0.5 2.9 66 5000 50021210008 185 16.0 2.5 25 1.7 0.5 3.0 69 5600 50021210009 240 18.1 2.6 25 1.8 0.5 3.2 75 6600 50021210010 300 20.4 2.8 25 1.9 0.5 3.4 81 7700 50021210011 400 23.1 3.0 35 2.0 0.5 3.7 88 9800 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Thickness of Steel TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

21220001 25 5.7 2.5 1.2 0.5 2.2 42 2150 50021220002 35 7.1 2.5 1.2 0.5 2.3 45 2600 50021220003 50 7.9 2.5 1.3 0.5 2.4 48 2950 50021220004 70 9.7 2.5 1.4 0.5 2.5 51 3200 50021220005 95 11.3 2.5 1.4 0.5 2.6 55 3700 50021220006 120 12.6 2.5 1.5 0.5 2.7 59 4200 50021220007 150 14.1 2.5 1.5 0.5 2.8 62 4800 50021220008 185 16.0 2.5 1.6 0.5 2.9 66 5400 50021220009 240 18.1 2.6 1.7 0.5 3.1 71 6400 50021220010 300 20.4 2.8 1.8 0.5 3.3 77 7500 50021220011 400 23.1 3.0 1.9 0.5 3.6 85 9600 500

Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape ArmouredAL / XLPE / STA / PVC Aluminum Conductor - Copper Wire Screened 3.6/6(7.2) kV

AL / XLPE / STA / PVC Aluminum Conductor - Copper Tape Screened 3.6/6(7.2) kV

107

Page 109: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / STA / PVC Aluminum Conductor Steel Tape Armoured - 3.6/6(7.2) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131 0.1034

Inductance at 60 Hz mH/Km 0.365 0.345 0.334 0.322 0.316 0.10 0.303 0.300 0.294 0.286 0.279

Reactance at 60 Hz Ω/km 0.14 0.13 0.13 0.12 0.12 0.04 0.11 0.11 0.11 0.11 0.11

Capacitance μF/Km 0.26 0.30 0.32 0.36 0.39 0.44 0.46 0.53 0.56 0.58 0.60

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.02 1.08 1.17 1.29 1.41 1.53 1.62 1.74 1.92 2.1 2.31

Current Rating Capacity

1- Laid direct in ground (Approx.) A 108 127 148 178 211 238 264 297 339 379 426

2- Laid in free air (Approx.) A 101 121 145 178 217 249 281 322 378 430 496

Voltage Drop per phase V/A/km 1.313 0.968 0.733 0.527 0.400 0.330 0.281 0.237 0.196 0.169 0.140

Minimum Bending radius mm 540 576 600 648 696 732 792 828 900 972 1056

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

108

Page 110: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Thickness of Steel

TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

22210001 25 5.7 3.4 16 1.3 0.5 2.4 49 2600 50022210002 35 7.1 3.4 16 1.4 0.5 2.5 52 3100 50022210003 50 7.9 3.4 16 1.4 0.5 2.6 55 3400 50022210004 70 9.7 3.4 16 1.5 0.5 2.7 58 3900 50022210005 95 11.3 3.4 16 1.6 0.5 2.8 63 4500 50022210006 120 12.6 3.4 16 1.6 0.5 2.9 66 5000 50022210007 150 14.1 3.4 25 1.7 0.5 3.0 70 5500 50022210008 185 16.0 3.4 25 1.7 0.5 3.1 73 6150 50022210009 240 18.1 3.4 25 1.8 0.5 3.3 79 7200 50022210010 300 20.4 3.4 25 1.9 0.5 3.5 84 8200 50022210011 400 23.1 3.4 35 2.0 0.8 3.6 87 9500 500

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Thickness of Steel TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

22220001 25 5.7 3.4 1.3 0.5 2.3 46 2450 50022220002 35 7.1 3.4 1.3 0.5 2.4 50 2950 50022220003 50 7.9 3.4 1.4 0.5 2.5 51 3200 50022220004 70 9.7 3.4 1.4 0.5 2.6 56 3700 50022220005 95 11.3 3.4 1.5 0.5 2.7 60 4300 50022220006 120 12.6 3.4 1.6 0.5 2.8 63 4800 50022220007 150 14.1 3.4 1.6 0.5 3.0 66 5300 50022220008 185 16.0 3.4 1.7 0.5 3.1 70 6000 50022220009 240 18.1 3.4 1.8 0.5 3.3 77 7000 50022220010 300 20.4 3.4 1.9 0.5 3.5 81 8000 50022220011 400 23.1 3.4 2.0 0.8 3.6 84 9300 500

Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape ArmouredAL / XLPE / STA / PVC Aluminum Conductor - Copper Wire Screened 6/10(12) kV

AL / XLPE / STA / PVC Aluminum Conductor - Copper Tape Screened 6/10(12) kV

109

Page 111: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / STA / PVC Aluminum Conductor Steel Tape Armoured - 6/10(12) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131 0.1034

Inductance at 60 Hz mH/Km 0.387 0.369 0.355 0.342 0.335 0.326 0.320 0.313 0.305 0.298 0.290

Reactance at 60 Hz Ω/km 0.15 0.14 0.13 0.13 0.13 0.12 0.12 0.12 0.11 0.11 0.11

Capacitance μF/Km 0.20 0.23 0.25 0.29 0.30 0.33 0.37 0.40 0.45 0.49 0.54

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.14 1.23 1.32 1.44 1.56 1.65 1.74 1.86 2.04 2.16 2.37

Current Rating Capacity

1- Laid direct in ground (Approx.) A 108 127 148 178 210 238 265 298 341 383 435

2- Laid in free air (Approx.) A 100 120 144 178 215 248 281 323 378 432 502

Voltage Drop per phase V/A/km 1.319 0.974 0.739 0.532 0.405 0.334 0.284 0.240 0.199 0.172 0.142

Minimum Bending radius mm 588 624 660 696 756 792 840 876 948 1008 1044

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

110

Page 112: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Thickness of Steel

TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

23210001 25 5.7 4.5 16 1.4 0.5 2.5 53 3000 50023210002 35 7.1 4.5 16 1.5 0.5 2.6 57 3550 50023210003 50 7.9 4.5 16 1.5 0.5 2.7 60 3900 50023210004 70 9.7 4.5 16 1.6 0.5 2.8 63 4400 50023210005 95 11.3 4.5 16 1.7 0.5 3.0 68 5000 50023210006 120 12.6 4.5 16 1.7 0.5 3.1 72 5550 50023210007 150 14.1 4.5 25 1.8 0.5 3.2 75 6150 50023210008 185 16.0 4.5 25 1.8 0.5 3.3 79 6700 50023210009 240 18.1 4.5 25 1.9 0.5 3.5 83 7850 50023210010 300 20.4 4.5 25 2.0 0.8 3.7 90 9700 40023210011 400 23.1 4.5 35 2.1 0.8 3.8 93 10200 400

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Thickness of Steel TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

23220001 25 5.7 4.5 1.4 0.5 2.5 51 2900 50023220002 35 7.1 4.5 1.4 0.5 2.6 55 3400 50023220003 50 7.9 4.5 1.5 0.5 2.7 57 3750 50023220004 70 9.7 4.5 1.5 0.5 2.8 61 4200 50023220005 95 11.3 4.5 1.6 0.5 2.9 66 4800 50023220006 120 12.6 4.5 1.7 0.5 3.0 69 5350 50023220007 150 14.1 4.5 1.7 0.5 3.1 73 6000 50023220008 185 16.0 4.5 1.8 0.5 3.3 77 6500 50023220009 240 18.1 4.5 1.9 0.5 3.4 81 7650 50023220010 300 20.4 4.5 2.0 0.8 3.6 88 9500 40023220011 400 23.1 4.5 2.1 0.8 3.8 92 10000 400

Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape ArmouredAL / XLPE / STA / PVC Aluminum Conductor - Copper Wire Screened 8.7/15(17.5) kV

AL / XLPE / STA / PVC Aluminum Conductor - Copper Tape Screened 8.7/15(17.5) kV

111

Page 113: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / STA / PVC Aluminum Conductor Steel Tape Armoured - 8.7/15(17.5) kV

Technical Information

Size mm2 25 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.54 1.113 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131 0.1034

Inductance at 60 Hz mH/Km 0.415 0.395 0.380 0.365 0.356 0.345 0.339 0.330 0.321 0.312 0.302

Reactance at 60 Hz Ω/km 0.16 0.15 0.14 0.14 0.13 0.13 0.13 0.12 0.12 0.12 0.11

Capacitance μF/Km 0.17 0.18 0.2 0.23 0.25 0.27 0.29 0.32 0.35 0.39 0.43

Short Circuit Current For 1 second

1- Conductor KA 2.34 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.32 1.38 1.47 1.59 1.68 1.8 1.89 2.01 2.16 2.31 2.52

Current Rating Capacity

1- Laid direct in ground (Approx.) A 108 127 148 178 210 238 265 298 341 383 435

2- Laid in free air (Approx.) A 100 120 144 178 215 248 281 323 378 432 502

Voltage Drop per phase V/A/km 1.325 0.980 0.744 0.537 0.410 0.338 0.289 0.243 0.202 0.175 0.145

Minimum Bending radius mm 636 684 720 756 816 864 900 948 996 1080 1116

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

112

Page 114: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Thickness of Steel

TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

24210001 35 7.1 5.5 16 1.5 0.5 2.8 62 4100 50024210002 50 7.9 5.5 16 1.6 0.5 2.9 64 4300 50024210003 70 9.7 5.5 16 1.7 0.5 3.0 69 5000 50024210004 95 11.3 5.5 16 1.7 0.5 3.1 72 5600 50024210005 120 12.6 5.5 16 1.8 0.5 3.3 75 6150 50024210006 150 14.1 5.5 25 1.9 0.5 3.4 79 6700 50024210007 185 16.0 5.5 25 1.9 0.5 3.5 83 7400 50024210008 240 18.1 5.5 25 2.0 0.8 3.7 90 9300 50024210009 300 20.4 5.5 25 2.1 0.8 3.9 95 10500 40024210010 400 23.1 5.5 35 2.2 0.8 4.1 97 12000 400

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Thickness of Steel TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

24220001 35 7.1 5.5 1.5 0.5 2.7 61 3950 50024220002 50 7.9 5.5 1.6 0.5 2.8 62 4100 50024220003 70 9.7 5.5 1.6 0.5 3.0 67 4850 50024220004 95 11.3 5.5 1.7 0.5 3.1 71 5400 50024220005 120 12.6 5.5 1.7 0.5 3.2 75 6000 50024220006 150 14.1 5.5 1.8 0.5 3.3 78 6500 50024220007 185 16.0 5.5 1.9 0.5 3.4 81 7200 50024220008 240 18.1 5.5 2.0 0.8 3.7 89 9150 50024220009 300 20.4 5.5 2.0 0.8 3.8 94 10300 40024220010 400 23.1 5.5 2.1 0.8 4.0 96 11800 400

Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape ArmouredAL / XLPE / STA / PVC Aluminum Conductor - Copper Wire Screened 12/20(24) kV

AL / XLPE / STA / PVC Aluminum Conductor - Copper Tape Screened 12/20(24) kV

113

Page 115: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / STA / PVC Aluminum Conductor Steel Tape Armoured - 12/20(24) kV

Technical Information

Size mm2 35 50 70 95 120 150 185 240 300 400

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778

Approximate AC resistance of Conductor @ 90°C

Ω/km 1.113 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131 0.1034

Inductance at 60 Hz mH/Km 0.415 0.400 0.381 0.374 0.362 0.354 0.345 0.335 0.320 0.305

Reactance at 60 Hz Ω/km 0.16 0.15 0.14 0.14 0.14 0.13 0.13 0.13 0.12 0.11

Capacitance μF/Km 0.15 0.17 0.2 0.22 0.24 0.26 0.27 0.3 0.33 0.37

Short Circuit Current For 1 second

1- Conductor KA 3.28 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11 37.48

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7 5.18

3- Copper Tape Screen KA 1.5 1.59 1.71 1.83 1.92 2.04 2.16 2.31 2.46 2.64

Current Rating Capacity

1- Laid direct in ground (Approx.) A 127 148 178 210 238 265 298 341 383 435

2- Laid in free air (Approx.) A 120 144 178 215 248 281 323 378 432 502

Voltage Drop per phase V/A/km 0.984 0.749 0.541 0.413 0.342 0.292 0.247 0.205 0.176 0.147

Minimum Bending radius mm 744 768 828 864 900 948 996 1080 1140 1164

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

114

Page 116: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cable Code

Conductor Insulation Screening Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

Nominalsectionalarea of

Screeningmm2

ThicknessNominal

mm

Thickness of Steel

TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

25210001 50 7.9 8.0 16 1.8 0.5 3.3 77 5900 40025210002 70 9.7 8.0 16 1.9 0.5 3.4 80 6400 40025210003 95 11.3 8.0 16 2.0 0.5 3.5 85 7150 40025210004 120 12.6 8.0 16 2.0 0.8 3.7 89 8600 40025210005 150 14.1 8.0 25 2.1 0.8 3.8 91 9150 40025210006 185 16.0 8.0 25 2.1 0.8 3.9 95 10100 40025210007 240 18.1 8.0 25 2.2 0.8 4.1 101 11300 30025210008 300 20.4 8.0 25 2.3 0.8 4.2 107 12600 300

Cable Code

Conductor Insulation Inner Sheath Armouring Outer Sheath Packaging

Cross Sectional

AreaNominal

mm2

DiameterNominal

mm

ThicknessNominal

mm

ThicknessNominal

mm

Thickness of Steel TapeNominal

mm

ThicknessNominal

mm

Overall Diameter

Approx.mm

NetWeight

Approx.Kg/Km

Standard Drum

m+/-5%

25220001 50 7.9 8.0 1.8 0.5 3.2 74 5700 40025220002 70 9.7 8.0 1.8 0.5 3.3 77 6200 40025220003 95 11.3 8.0 1.9 0.5 3.5 82 7000 40025220004 120 12.6 8.0 2.0 0.8 3.6 86 8400 40025220005 150 14.1 8.0 2.0 0.8 3.7 89 9000 40025220006 185 16.0 8.0 2.1 0.8 3.9 93 9850 40025220007 240 18.1 8.0 2.2 0.8 4.0 100 11100 30025220008 300 20.4 8.0 2.3 0.8 4.2 104 12400 300

Three-cores XLPE Insulated PVC Sheathed Cable Steel Tape ArmouredAL / XLPE / STA / PVC Aluminum Conductor - Copper Wire Screened 18/30(36) kV

AL / XLPE / STA / PVC Aluminum Conductor - Copper Tape Screened 18/30(36) kV

115

Page 117: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

AL / XLPE / STA / PVC Aluminum Conductor Steel Tape Armoured - 18/30(36) kV

Technical Information

Size mm2 50 70 95 120 150 185 240 300

Maximum DC resistance of Conductor @ 20°C

Ω/km 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100

Approximate AC resistance of Conductor @ 90°C

Ω/km 0.822 0.569 0.411 0.325 0.265 0.212 0.163 0.131

Inductance at 60 Hz mH/Km 0.450 0.432 0.420 0.405 0.395 0.385 0.372 0.360

Reactance at 60 Hz Ω/km 0.17 0.16 0.16 0.15 0.15 0.15 0.14 0.14

Capacitance μF/Km 0.14 0.15 0.17 0.18 0.2 0.21 0.23 0.25

Short Circuit Current For 1 second

1- Conductor KA 4.69 6.56 8.90 11.24 14.06 17.33 22.49 28.11

2- Copper Wire Screen KA 2.39 2.39 2.39 2.39 3.7 3.7 3.7 3.7

3- Copper Tape Screen KA 1.95 2.07 2.19 2.28 2.37 2.49 2.67 2.82

Current Rating Capacity

1- Laid direct in ground (Approx.) A 148 178 210 238 265 298 341 383

2- Laid in free air (Approx.) A 144 178 215 248 281 323 378 432

Voltage Drop per phase V/A/km 0.760 0.552 0.424 0.352 0.301 0.256 0.214 0.185

Minimum Bending radius mm 924 960 1020 1068 1092 1140 1212 1284

The Previous Values are based on the following conditions: Ambient Air Temperature: 40 °CAmbient Ground Temperature: 35 °CDepth of laying in ground: 0.80 mSoil Thermal Resistivity: 1.2 °K.m/W

116

Page 118: Contents · Contents Introduction Technical Information Single-core XLPE Insulated PVC Sheathed Cable Unarmoured (Copper) Single-core XLPE Insulated PVC Sheathed Cable …

Cables and Conductors should be installed by trained personnel in accordance with good engi-

neering practices, recognized codes of practise, statutory local requirements, IEE wiring regula-

tions and where relevant, in accordance with any specific instructions issued by the company.

Cables are often supplied in heavy cable reels and handling these reels can constitute a safety

hazard. In particular, dangers may arise during the removal of steel binding straps and during the

removal of retaining battens and timbers which may expose projecting nails.

Drum Handling Instructions

86 117