Transformerless UPSConcepts and Capabilities forLarge System UPS

Power Quality Division

Page 2: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

© 2013 Eaton Corporation. All rights reserved.

This is a photographic template – your photograph should fit precisely within this rectangle.

Large System Transformerless Architecture

Technical Details

Page 3: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

7 7

First, A Little History……

Eaton Confidential

Page 4: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

8 8

Technology and Efficiency over the Years

IGBT UPS

85 to 90%

SCR UPS

75 to 80%

Transformer-less UPS

90 to 95%

Hybrid UPS

Multilevel converters

~97 %

1975 1980 1985 1990 1995 2000 2007 2008 2013

ES/Eco mode

98 to 99+%

Transistor UPS

80 to 85%

75%

100%

Ful

l Loa

d E

ffici

ency

Harmonic mitigation & load balance

98 to 99+%

Technology advances continue to boost UPS efficiency

Page 5: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

9 9

Transformerless Advantages

• Smaller system size and weight• Transformers are big contributors to these key factors

• PWM Rectifier provides high input PF and low THD over wide line and load range• Doesn’t require large input harmonics filters

• Efficient Operation• No transformer power losses and optimized DC Link voltage

• Uses IGBT converters, all of identical make-up• Standardizes on power circuits, components, and support

• Maintains an optimally high DC buss for the inverter• Significant reduction in current handling for inverter components

• Reduce inrush current and improved generator compatibility• Technology current

• IGBT performance/cost has steadily improved over the past 10 years• Green and Sustainable

• Reduction in iron, copper, and varnish usage

Page 6: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

10 10

Simplified SCR UPS Schematic—“Your Father’s UPS….”

Input Transformer and 6-Pulse Rectifier

Force-commutated Inverter and Output Transformer

Now Replaced by Transformerless, IGBT-based Power Converters, for High Efficiency and Power Density

Page 7: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

11 11

Active (IGBT) Rectifier Current WaveformLow THDi, High Power Factor

Site Friendly and Generator Compatible

Page 8: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

12 12

Transformerless UPSAllows Significant Size and Weight Reduction

(Below – 275 & 300KVA Examples)

Page 9: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

13 13

ISBM Section UPM Section

Inside the Transformerless UPS

• X-Slot communications

• Power Xpert Web Card

• 8-line backlit LCD

• Input circuit breaker option

• Top- or bottom- entry

• Static bypass – continuous duty

• Base with inter-unit cabling

• Double-conversion topology converter/

inverter section

• Redundant power supplies

• Redundant fans

• Contactor output

• UPM easy service disconnect

UPM Section

Page 10: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

14 14

Transformerless Disadvantages

• No galvanic isolation• Battery is not isolated• No transformer based common mode noise isolation

• Requires specialized Hi Z battery fault detection equipment• Higher DC Link voltage (when compared to SCR front end)• Neutral phase leg required for L-N loads (WYE output)

Page 11: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

15 15

Eaton Confidential

Transformerless TopologySimplified Schematic Diagram

IGBT rectifier front end

Page 12: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

16 16

Hybrid and Air-core Inductor Designs—Less Space, Weight, Plus Cooler operation

Page 13: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

17 17

Eaton Confidential

Transformerless TopologyDC-DC Converter

Bidirectional battery converter charges battery, and regulates the DC link when on-battery.Makes the battery voltage independent of the DC linkRemoves inverter efficiency penalty caused by battery voltage swing

Page 14: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

18 18

The Battery Converter and Why

• Removes inverter efficiency penalty (current penalty) caused by battery voltage swing

• Makes the battery voltage independent of the DC buss voltage• Accommodates a broader range of nominal battery voltage

configurations• Provides system flexibility with many other DC sources including

flywheels, ultra-caps, PV, etc.

Page 15: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

19 19

Eaton Confidential

Transformerless Topology3 or 4-wire Inverter

IGBT inverter with neutral modulation

Page 16: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

20 20

Eaton Confidential

Transformerless Efficiency

• Efficiency = Pout / (Pin + Ploss)• Ploss is comprised of:

• IGBT switching losses and conduction losses• Magnetics copper and core losses transformer losses

• Switching losses are directly proportional• DC Link voltage• Switching frequency

• For the Transformerless UPS• Modulating the N leg reduces harmonic content and allows for a

reduction in switching frequency• Adding a zero sequence to all of the PWM vectors causes the DC

link to closely track the required three phase voltage space and effectively lowering the required DC Link

• Eliminating the transformer removes one more source of losses

Page 17: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

21 21

Eaton Confidential

UPS Fault Tolerance

• UPS is evaluated for performance under different external fault situations: battery faults, input source faults, output (load) faults, as well as its response to internal fault conditions

• Fault Tolerance - expected behavior

• No load loss

• No single point of failure

• Types of fault tolerant behavior

• Unit remains on-line

• Unit transfers to bypass

• Unit announces/alarms condition

Page 18: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

22 22

Eaton Confidential

More on Eaton Transformerless Topology• The myth

• The lack of an output transformer decreases the overall reliability of the system.• The transformer helps the inverter handle faults, protecting it from high fault

currents• Similarly, the transformer protects loads from inverter faults, preventing them

from having DC voltage applied to them when an inverter fails

• The Truth

• Low-frequency inverters, driven by low-bandwidth analog or rudimentary microprocessor controls, do benefit from the increased impedance presented by either a large inductor or a transformer in the output of the inverter, as slow response controls requires the current’s rate of rise to be slowed down in the event of a fault

• Transformerless topology has its foundation on:• High-frequency PWM power conversion• High-bandwidth advanced DSP controls, with sampling rates above 33 KHz

(once every 30 microseconds)

• High-bandwidth controls do not get any benefit from additional impedance on the output of the inverter – on the contrary, they rely on instantaneous information to maintain best performance conditions

Page 19: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

23 23

Eaton Confidential

Handling output faults

- If bypass is available, let the bypass try to clear the fault

- High-frequency PWM and “small” inductor requires fast signal sensing

- … and can quickly control power train to expedite transfer to bypass

- if bypass is not available, the inverter supplies 300ms of limited fault current

Page 20: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

24 24

Eaton Confidential

Output Fault Test• Single 9395 1100KVA 480V UPS

• 480Vin/480 Vout• Common Battery

• (8) 1085 Cabinets 475W/240 Cell• 98% Load• Bypass Not Avail (therefore no bypass intervention, all inverter)• Fault applied output Ph B to ground

• Test Results: Unit services short for 300mS without damage or without tripping breakers• Waveform: voltages are 200V/div and fault current is 4000A/div

Page 21: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

25 25

Eaton Confidential

Handling input faults…

- Similar to output faults, high-frequency PWM and “small” inductor requires fast signal sensing

- … and can quickly control power train to expedite transfer to battery mode

Page 22: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

26 26

Eaton Confidential

Input Fault Test

• Single 9395 275KVA 480V UPS• 480Vin, 480Vout• Battery

• (2) 1085 Cabinets 475W/240 Cell• 100% Load• Fault applied at UUT input Ph B to ground

• Test Results: Input breaker trips (part of test setup) and unit drops to battery• Waveform: voltages are 250V/div and fault current is 1200A/div

Page 23: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

27 27

Eaton Confidential

Protecting the Mission Critical Load…

- If inverter IGBT fails short, fuses in DC link will open. IGBTs will eventually open too.

- Load will never see DC voltage at the AC lines

Page 24: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

28 28

Eaton Confidential

IGBT Internal Fault Test• Single 9395 825KVA 480V UPS

• 480Vin/480 Vout• Common Battery - (8) 1085 Cabinets 475W/240 Cell• 100% Load• Short circuit applied collector to emitter, Rectifier IGBT, Q1, phase B on UPM1

• Test Results: Unit transfers to battery. Alarm “Check Rectifier PM1” is enunciated.• Waveform: voltages are 400V/div and fault current is 1000A/div• IGBTS Q1 and Q3 failed• Fuses F1 and F4 open

Page 25: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

29 29

Eaton Confidential

Battery Isolation

• Battery galvanic isolation in the UPS can provide a false sense of security, and should not be depended on as a safety feature • Battery terminals should be treated with the same caution and

respect given to any AC terminal in the system• If a UPS only has an input transformer, then the battery is not floating

• An output transformer is required to isolate the battery from the energized output bus

• Concerns about safe Service associated with hot battery terminals should be addressed by:• Using plastic or rubber battery terminal covers• Service procedures or guidelines that require all battery maintenance to

include the precaution of opening battery circuit breakers• Measures that are much less expensive than transformers

• The absence of battery isolation is not detrimental to the UPS completing its stated mission: to protect the critical bus

Page 26: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

30 30

Eaton Confidential

Battery Isolation

• Battery galvanic isolation in the UPS can provide a false sense of security, and should not be depended on as a safety feature • Battery terminals should be treated with the same caution and

respect given to any AC terminal in the system• If a UPS only has an input transformer, then the battery is not floating

• An output transformer is required to isolate the battery from the energized output bus

• Concerns about safe Service associated with hot battery terminals should be addressed by:• Using plastic or rubber battery terminal covers• Service procedures or guidelines that require all battery maintenance to

include the precaution of opening battery circuit breakers• Measures that are much less expensive than transformers

• The absence of battery isolation is not detrimental to the UPS completing its stated mission: to protect the critical bus

Page 27: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

31 31

Common Mode Noise Isolation

• Data center and communications equipment today is immune to common mode noise due to improved power supply designs• It’s a good idea to confirm if galvanic isolation is “really” needed by the critical

load

• Common mode noise isolation as a requirement• This requirement is limited to some medical and industrial/processing

equipment• Often times a downstream PDU or IDC can be used to support this

requirement• PDU can be located closer to the critical load where the noise isolation is

most important

Page 28: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

© 2013 Eaton Corporation. All rights reserved.

This is a photographic template – your photograph should fit precisely within this rectangle.

What other cool stuff can we do, once the transformer is eliminated?

Page 29: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

33 33

Eaton Confidential

Variable Module Management System (VMMS)

DC

AC

AC

DC

AC

AC

DC

DC

Load < 440KVA

• UPM not required to power load• Remains Hot Tied to Critical Bus• Assumes load in < 2ms when required

AC

AC

DC

DC

Page 30: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

34 34

Eaton Confidential

3 X 825KVA Parallel System with VMMS

ISBM

UPM

UPM

ISBM

UPM

UPM

ISBM

UPM

UPM

UPM

UPM

• Maintain UPM Loading of 80% to maximize efficiency

• UPM’s in VMMS-Mode are available to assume load in less then 2ms to respond to load changes.

UPM

Page 31: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

35 35

Eaton Confidential

3X825 Parallel System Efficiency

9395 VMMS System Efficiency Curves (Typical)

70%

75%

80%

85%

90%

95%

100%

0 10 20 30 40 50 60 70 80 90 100

System Load %

Sy

ste

m E

ffic

ien

cy

%

Efficiency -VMMS Disabled

Efficiency -VMMS Enabled

Page 32: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

36 36

Eaton Confidential

Energy Saver SystemMaximum Efficiency Tracking

• Highest availability with 99% efficiency for a wide load range• 85% reduction in losses compared to legacy transformer-based UPS• Continuous power tracking and proprietary DSP algorithms combined with

transformerless topology ensures critical loads are always protected

Regular

92Efficient

95Premium

99

EFF

Premium

99Efficient

95Regular

92

Savings based on 1MW at $0.1/Kw-hr

Page 33: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

37 37

Eaton Confidential

ESS Surge Response

ESS keeps the rectifier and inverter filters tied to the critical load bus, while the storage capacitors and power train semiconductors act as a peak tracking clamp• minimizing spikes and noise• attenuating line surges

Page 34: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

38 38

Eaton Confidential

ESS with VMMS Double Conversion

• > 3% efficiency improvement over existing double conversion only approach

• ESS 99% efficiency for 50 % of the system load• VMMS >93% efficiency for 50% of the system load

• Double Conversion backup for 100% of system load

VMMS on “B”

Single or Dual Source

ESS 99% Efficiency

ESS on “A”

“A”

“B”

50% of Load

50% of Load

VMMS > 93% Efficiency

Page 35: © 2013 Eaton Corporation. All rights reserved. This is a photographic template – your photograph should fit precisely within this rectangle. Transformerless

39 39

Eaton Confidential

Questions