Upload
hector-rubio
View
8.454
Download
4
Tags:
Embed Size (px)
DESCRIPTION
This presentation explains the code requirements for active and passive building systems used to protect buildings and their occupants and contents from fire.
Citation preview
Understanding Fire-Rated Assemblies
Presented by:Hector Rubio, RA
Governing CodesInternational Building Code
California Building Code
Standards, Testing and CertificationUL Fire-Resistance DirectoryNational Fire Protection Association (NFPA)
NFPA 80 Standard for Fire Doors and Other Opening Protectives
Gypsum Association (GA)Fire Resistance Design Manual
Standards, Testing and CertificationIntertek – Warnock HerseyFactory Mutual (FM)
FM Approval Guide
Code RequirementsOccupancy Separations (Table 508.4)Building Elements (Table 601)Fire Separation Distance (Table 602)Fire Barrier Assemblies (Table 707.3.9)
Fire PartitionsSmoke PartitionsShaft Enclosures
Fire Doors and Fire Shutters (Table 715.4)Fire Windows (Table 715.5)Fire Dampers (Table 716.3.2.1)
UL Listed Fire-Rated Assemblies2-hour fire-rated composite floor slabUL Design D711
UL Listed Fire-Rated Assemblies1-hour to 4-hour fire-rated partitionsUL Design U419
UL Listed Fire-Rated AssembliesTwo-hour fire-rated shaft wallUL Design U428Installation from finished side of the wall
Fire-Rated AssembliesShaft Enclosures
Stairs / Elevators / Duct Shafts
Passive protection system
Fire-Rated AssembliesSpray-Applied Fireproofing
Passive protection systemThickness of application
determines fire-rating
Testing Standards & ProceduresASTM E119 / UL 263 / NFPA 251Laboratory Mock-UpFire Test – Gas Furnace
Testing Standards & ProceduresASTM E119 / UL 263 / NFPA 251Laboratory Mock-UpFire Test – Glazing Systems
Testing Standards & ProceduresASTM E119 / UL 263 / NFPA 251Laboratory Mock-UpHose Stream Test
Testing Standards & ProceduresLabels and Listing
Listed products are fabricated with permanent labels identifying the type of fire-rated assembly
Periodic Inspections of Fabrication PlantsUnannounced inspections of fabrication plants
to ensure compliance with listing requirements
Openings in Fire-Rated Assemblies
Fire Doors – Swing TypeOverhead Coiling Fire DoorsHorizontal Sliding Fire DoorsFire Windows and GlazingFire/Smoke DampersFirestopping Pipe PenetrationsHead of Wall
Openings in Fire-Rated AssembliesFire Doors – Swing Type
Self-closing and self-latchingMagnetic hold-open devices are acceptableManual hold open devices are NOT permitted
Openings in Fire-Rated AssembliesOverhead Coiling Fire Doors
Concealed above the ceilingSurface mounted to the rated wallActivated by smoke detector, fire alarm,
power failure, or fusible link
Openings in Fire-Rated AssembliesHorizontal Sliding Fire Doors
Motorized, automatic closing Open plan designConcealed in pocket until needed
Openings in Fire-Rated AssembliesHorizontal Sliding Fire Doors
Industrial type with chain and fusible linkMotorized and self-closing
Openings in Fire-Rated AssembliesFire Windows and Glazed Walls and Doors
Passive systemSafety glazing compliant
Openings in Fire-Rated AssembliesFire / Smoke Dampers
Connected inline with the ductwork
Prevents passage of flame, smoke and heated gasses
Openings in Fire-Rated AssembliesFirestopping Pipe Penetrations
Intumescent sealants are used to fill the annular space (the gap) between the pipe penetration and the fire-rated assembly.
Sealant will expand greatly under high temperatures, and
Closes the opening against the passage of flame and heated gasses
Openings in Fire-Rated AssembliesFirestopping Pipe Penetrations
Intumescent sealants and caulks – red color for visual inspection
Sealant expands greatly under high temperatures
Openings in Fire-Rated AssembliesHead of Wall
Mineral wool insulation fills the void in the flutesIntumescent sealant is sprayed across the face of
the insulation
RecapGoverning CodesStandards, Testing and CertificationCode RequirementsFire-Rated AssembliesTesting Standards and ProceduresProtected Openings in Fire-Rated
Assemblies
Questions???