Upload
syskahennessy
View
207
Download
1
Embed Size (px)
Citation preview
Can Data Center Free Cooling Be Utilized in the Middle East?
Prepared by: Noriel Ong, ASEAN Eng., MIET, PMP, PQP, ATD
05/02/2023
05/02/2023 Syska Hennessy Group / 2
Objective
• Learning the types of air economizers • Understanding the typical air
economizers configuration • Learning the advantages and
disadvantages of each type of air economizer system
• Understanding of the energy and water cost impacts of indirect evaporative cooling system.
INTRODUCTIONDATA CENTER AIR ECONOMIZERS, CONFIGURATION AND EXAMPLE PROJECTS
05/02/2023 4Syska Hennessy Group /
AIR-SIDE ECONOMIZER
AIR-SIDE ECONOMIZER is “a system that has been designed to used outdoor air for cooling – partially or fully – when outdoor air meets certain criteria” (ASHRAE).
• DIRECT AIR-SIDE ECONOMIZERS– the outside air is directly supplied into the white space– the exhaust heat is reject fully or partially recirculated back – The outside air could also be cooled by means adiabatic cooling (aka DIRECT
EVAPORATIVE COOLING).
• INDIRECT AIR-SIDE ECONOMIZERS – The outdoor air does not enter the white space.– Data center (primary air) is cooled indirectly by the outside air via heat exchanger.– The primary air/heat exchanger (cold side) could also be cooled by means adiabatic
cooling. (aka INDIRECT EVAPORATIVE COOLING).
DIRECTAIR ECONOMIZERS
05/02/2023 6Syska Hennessy Group /
DIRECT AIR-SIDE ECONOMIZER
05/02/2023 7Syska Hennessy Group /
DIRECT EVAPORATIVE COOLING
05/02/2023 8Syska Hennessy Group /
DIRECT AIR-SIDE ECONOMIZER (config.)
Fan Walls
CRAC/H or AHU
05/02/2023 9Syska Hennessy Group /
DIRECT AIR-SIDE ECONOMIZER (EXAMPLE)
CONFIDENTIAL MULTINATIONAL TECHNOLOGY COMPANY DATA CENTER PHASE 2 EXPANSION
Project Features• Tier 2 electrical design• Tier 2 mechanical design• Modular design• Scalable design• Greenfield site• 2 data halls, expandable to 5• Each data hall scalable to 3.6mW of
critical load• Adiabatic cooling to provide annual
average 1.08 PUE
Size• 186,000sf
L O C K P O R T, N Y
Services Provided• Mechanical• Electrical• Plumbing• Fire protection• Fuel Oil
Completion Date• 2014
INDIRECTAIR ECONOMIZERS
05/02/2023 11Syska Hennessy Group /
AIR-SIDE ECONOMIZER
INDIRECT AIR-SIDE ECONOMIZER
Primary Return Air
Primary Supply Air
Air-to-Air Heat Exchanger
Scavenger (Exhaust) Air
Scavenger (Outside) Air
Scavenger Fans
Primary Fans
Air FilterCooling Coil
Air Filter
05/02/2023 12Syska Hennessy Group /
AIR-SIDE ECONOMIZER
INDIRECT AIR-SIDE ECONOMIZER (INDIRECT EVAPORATIVE COOLING)
05/02/2023 13Syska Hennessy Group /
INDIRECT AIR-SIDE ECONOMIZER (config.)
Perimeter Configuration Roof Configuration
05/02/2023 14Syska Hennessy Group /
INDIRECT AIR-SIDE ECONOMIZER (EXAMPLE)
T5 - EL SEGUNDO DATA CENTER CALIFORNIA
Project Features• Day 1:
• 5.5MW critical load• 85,000 s.f. white space
• Day 2 (ultimate):• 2.95MW critical load• 110,500 s.f. white space
• Brownfield site• PUE goal: 1.3• Rooftop Indirect Evaporative
Cooling Units (no chiller plant)• Diesel Generators• Goal of achieving LEED Gold• 36” Raised Floors
PROS AND CONSOF DATA CENTER AIR
ECONOMIZERS
05/02/2023 16Syska Hennessy Group /
Risks Summary
Direct Air-Side Economizers Direct Evaporative Cooling Indirect Air-Side
EconomizersIndirect Evaporative
Cooling
Energy Consumption Low Medium
Water Consumption None Medium None Medium
Temperature Variations High Medium Low
Humidity Variations High Low
Air Quality Issues High None
Water Quality Issues None Medium None Medium
Complexity High Medium
Regional Support/Experience
High High Low
CASE STUDY1MW DATA CENTER MODEL
05/02/2023 18
ASSUMPTIONS
Syska Hennessy Group, MENA /
• 1MW data center critical (IT) load. Fully loaded at static conditions.• Based comparison with Air-cooled chilled water system with variable primary system
and Computer Room Air Handlers (CRAH).• Data center cabinets are in hot and cold aisle configuration with containment system.• White Space Supply/Return Air Temp (SAT/RAT)
• 77°F [25°C]/100°F [38°C]• Power and Water Tariffs are based on the local utility slabs.
• DEWA, ADDC, Qatar KAHRAMAA, Oman MEDC & PAEW, KSA SEC& NWC, Bahrain EWA, and Kuwait MEW.
• Weather Bin Data based on IWEC 2.• IDEC Wet Bulb Depression Efficiency =60%• IDEC Air to Air Heat Exchange Efficiency = 45%• IDEC primary and secondary(scavenger) fans speed are constant. • IDEC Dry Operations: =/< 48°F [9°C] DBT OA• IDEC Wet Operations: > 48°F [9°C] DBT and < 61°F [16°C] WBT OA• IDEC Partial Free Cooling: > 61°F [16°C] OA• Both the data center is pressurized by a DOAS• Analysis focus on white space only.
05/02/2023 19Syska Hennessy Group, MENA /
AVAILABLE FREE COOLING - HOURS
Kuwait KSA, Riyadh KSA, Dhahran UAE, Dubai UAE, Abu Dhabi
Qatar, Doha Bahrain Oman, Muscat
0
876
1752
2628
3504
4380
5256
6132
7008
7884
8760
AVAILABLE FREE COOLING HOURS
Partial Free Cooling (Wet + Mechanical Operations) Wet OperationDry Operation
HOUR
S
05/02/2023 20Syska Hennessy Group, MENA /
FINANCIAL IMPACTS
Kuwait KSA, Riyadh KSA, Dhahran UAE, Dubai UAE, Abu Dhabi
Qatar, Doha Bahrain Oman, Muscat
-100%
-80%
-60%
-40%
-20%
0%
20%
40%
60%
80%
100%
Financial Impacts
OPE
RATI
ON
CO
ST
05/02/2023 Syska Hennessy Group, MENA / 21
CONCLUSIONS
• The case study revealed that Riyadh, Dhahran and Kuwait has the most free cooling hours among other places in GCC countries that were evaluated.
• Although the analysis for UAE, Qatar, Bahrain and Oman showed very limited free cooling hours, savings can still be achieved through partial free cooling.
• IDEC full and partial free cooling will reduce data center mechanical energy or overall utility cost.
• More operation cost savings could be realized if the modulation of secondary(scavenger) fans are accounted for, which is usually the case.
• Increasing the target supply air temperature limit will increase the number of full or partial free cooling hours.
• Selecting a higher supply air temperature, i.e. 77°F (25°C), will improve the economics of the economizer without even considering the option of using the allowable range.
05/02/2023 Syska Hennessy Group, MENA / 22
CONCLUSIONS
• Although the results seem favorable, there are also other considerations that need to be examined.• Water scarcity and storage. • System operation during dust/sand storms.• Although no known cases of Legionella were recorded, water
treatment may be required.• Regular maintenance of heat exchangers to mitigate fouling.
• Indirect airside economizer could be an alternative cooling solution in lieu with IDEC provided that local support will be present in the region.
Thank youAny questions?