CellBOX-H/BOX Energy-saving data logger for water supply network CellBOX-H/BOX v.2.0 is an advanced programmable multi-channel microprocessor logger, designed for measurement and recording of water supply network parameters, with GSM (SMS / GPRS / EDGE) data transmission to the parental system. The device is an essential element of modern SCADA-type telemetry supervisory systems, combining the benefits of new technologies for data collecting and processing with the latest methods of data transmission through wireless networks. GSM / GPRS transmission in public and private APNs Inputs: 3 analog/3 digital + pressure and temperature measurement 8 definable alarm thresholds with hysteresis Function of remote counters synchronization Dedicated management software Compatible with SCADA systems

Cell box h-box-eng

  • Upload
    atmax

  • View
    152

  • Download
    3

Embed Size (px)

Citation preview

Page 1: Cell box h-box-eng

CellBOX-H/BOXEnergy-saving data logger for water supply network

CellBOX-H/BOX v.2.0 is an advanced programmable multi-channel microprocessor logger, designed for measurement and recording of water supply network parameters,with GSM (SMS / GPRS / EDGE) data transmission to the parental system. The deviceis an essential element of modern SCADA-type telemetry supervisory systems,combining the benefits of new technologies for data collecting and processing with the latest methods of data transmission through wireless networks.

GSM / GPRS transmission in public and

private APNs

Inputs: 3 analog/3 digital + pressure and

temperature measurement

8 definable alarm thresholds with

hysteresis

Function of remote counters

synchronization

Dedicated management software

Compatible with SCADA systems

Page 2: Cell box h-box-eng

We offer preconfigured SIM cards in the private APN cellbox.pland provide managementservice as well.We offer accessto the measurement datavia the Internet (any standard WWW browser).We ensure safety at everystage of transmission: IPSectunnels with 3DES encryptionfor connections with customers servers and SSL protocolfor WWW access.

Sample SCADA visualizations athttps://telemetria.net.plLogin: demo01 pass: demo01(login and password from“demo01” up to “demo09”)

Owing to its compact design and rich configuration options, CellBOX-H/BOX v.2.0 has gained a reputation of an excellent tool facilitating the control over daily operation of complex water supply networks. Professional telemetry and monitoring systems,remote network diagnostics (gradual region testing, sectorization), detection andlocalization of bursts – all of the above can be built on the basis of the CellBOX-H BOX.The logged data (e.g. minimum night flow) can be used in water loss analyses.CellBOX-H/BOX can work either mounted in control cabinets, directly on the wallof a measuring chamber, or at intervention control measurements for a single,ad hoc registration of parameters of a water network. The device can also be used in the process of selection of appropriate measuring devices, e.g. water meters.CellBOX-H/BOX v.2.0. enables real-time measurement and logging of pressure, temperature, battery level, any three physical quantities (processed to a standard 4÷20[mA] electrical signal), or the state of 3 bi-state inputs. Analog inputs acceptany measuring transducer with a standard 4÷20 [mA] output, with its own powersupply or using the recorder’s power supply. Digital inputs accept any mechanicalconnectors, reed relay pins as well as a reed-type OC system. Digital inputs can workin event mode, registering a change of state, or in counter mode, counting successivepulses. Both the analog and digital inputs are protected against the administration of reverse polarity voltage and overvoltage.The device can analyze signals appearing at its inputs and take action according to the deployed algorithm - for example, it may react to a sudden drop in pressure or flow increase. The built-in LCD screen displays the current status of all the measured parameters. Optionally, the device is equipped with an internal pressure transducer and a quick coupler for direct connection. For the version of the recorder equippedwith an optional GSM / GPRS modem, in addition to local data recording, it is possibleto automatically transfer measurement results to the dispatch center. Data transmissionvia GPRS can be carried out in private APN networks which provide permanent IP numbers, or in public ones, where IP numbers are assigned in a dynamic way.Owing to the independent power supply, internal non-volatile FLASH memory andbuilt-in pressure (optional) and temperature transducers, the CellBOX-H/BOXperforms measurements and registration autonomously. The recorder is equipped with an internal battery pack so the device is ready to work off-hand. The internalbattery pack ensures operation of about 5 years, with data registration every 15 min. or less. To prolong its life in the GSM/GPRS mode (option with GSM/GPRS module) it is recommended that an external power supply should be used.The device is adapted for operation with all water meters equipped with pulsetransmitters, electromagnetic and ultrasonic flow meters, and all measurementdevices by renowned companies.

Page 3: Cell box h-box-eng

Analog Inputs 3 universal inputs, resolution: 12bit •Current inputs 4÷20[mA]; input resistance

100Ω, accuracy 0.1% Any scale, any description or unit +3 analog inputs, standard: battery level,

temperature, pressure

Digital inputs 3 configurable inputs – universal with

common ground; average reaction time: 10ms

Event-type (minimal interval of event duration 1s)

Counter-type (e.g. for operation with water meter pulse transmitter, fmax=60Hz)

Built-in measurement transducers Internal temperature, range: -25÷70 [°C];

accuracy ±2 °C Pressure (optional), range: 0÷16 [bar];

accuracy 0.5%

Connections RS232 interface Analog and digital inputs connectors (cables

with IP68 glands) External power supply Optional universal quick coupler Antenna connector (optional)

Communication protocols Biatel SA custom protocol Optional MODBUS protocol or any other on

request (protocol description required) OPC server

Logger functionality Cyclic or linear data logging Simultaneous logging of 16 parameters out

of 32 available measured quantities GSM: SMS, GPRS, or optional EDGE data

transmission Internal memory capacity: up to 160,000

measurement results Programmable logging interval of 1s to 31

days with 1s resolution Public or private APN data transmission

Configuration capability LCD display of any of the measured parameters Configurable display of descriptions and units of parameters on the

LCD CSQ measurement and visualization supporting optimal antenna

setting Restore to factory default settings function Full device and software identification Built-in bootloader for remote software update

Features LCD display with data scroll switch Internal real-time clock Simultaneous logging and memory reading 8 definable alarm thresholds with hysteresis Dual band GSM modem 900/1800MHz (optional) Independent alarm thresholds definition on analog and digital inputs Detection of external power supply and RS232 port activity Internal battery power level control

Modes of operation TCP Server - server forces sessions with the device (modem activity

required) TCP Client - device maintains connection with server SMS, optional UDP, CSD Constant or periodic transmission according to a given schedule Alarm start/stop SMS sent to up to 4 defined phone numbers

Schedules Tasks performed on defined days of the week or month Programmable task starting time Interval of 1 second up Separate schedules for logging, transmission, analog or digital

measurements Flow rate calculation Alarm checkup

Technical data Storage temperature: -40÷80 [°C] Operating temperature: –25 ÷70 [°C] (–20÷55[°C] with GSM modem

active) ABS IP67 housing with wall mount brackets (IP68 on request) IP68 cable glands Dimensions: 131x130x61 [mm] Weight: approx. 1kg

Power supply Internal battery (operation time of up to 5 years, depending on

configuration mode) External rechargeable accumulator (used for GSM transmission) External power supply connection (mains or battery) as an option