This technical presentation provides an in-depth analysis of the multiple configurations of data centre cooling systems available. Drawing on 40 years’ experience in the industry, Airedale International discusses the options available to achieve the optimum balance between energy efficiency, reliability and footprint, whilst reviewing capital and operational costs. The presentation looks at the complete landscape from mechanical cooling through to full fresh air free cooling where PUEs of near 1.1 can be achieved, with and without adiabatic, and will take into account varied footprints. Aimed at senior Technical and Financial decision-makers, the audience can expect a thorough analysis of current and future data centre cooling systems from the UK’s leading IT cooling solutions provider, as a basis for informed decision-making.

Citation preview

Page 1: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

An Apples for Apples Comparison of the Data Centre Cooling Landscape

To provide integrated thermal management solutions, differentiated through innovation and service

George HannahProduct Development Director

Page 2: An Apples for Apples comparison of the data centre cooling landscape

What Do We Do?

40 years experience

Design to delivery3kW to 2.0MW

www.airedale.com

Global provider of

efficient cooling

solutions

A pioneer in free-cooling

technology

An industry leader in rack level cooling

Largest UK manufacturer of IT cooling

solutions

Page 3: An Apples for Apples comparison of the data centre cooling landscape

What Do We Do?

TurboChill™ Freecool 200 - 1100kW

DeltaChill™ Freecool140 - 1080kW

NEW IMAGE TO COME

Page 4: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Our Clients

Page 5: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Global Presence

50,000+ applications since 1974

1,400 last year2012

Page 6: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Key Driver - “Increasing Digitalisation”

The data centre market is growing on a global scale The need for data is growing…

Power demand is rising

and thus cooling needsare increasing

Page 7: An Apples for Apples comparison of the data centre cooling landscape

Business Issues

Efficiency

Capital Costs

Operational Costs

Footprintand Density Uptime

Solution

Page 8: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Definitions

Adiabatic

Free Cooling

Mechanical Cooling

Direct Indirect

Page 9: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Apples For Apples

500kW heat load

10kW per rack

50 racks

UK ambient dry and wet bulb profile

Fixed return air temperatures

Page 10: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Cooling Landscape

-10 -5 0 5 10 15 20 25 30 35 40

20

40

60

80

100

120

Ambient Dry Bulb Temperature (°C)

DX CRAC’s

Chiller’s

Free Cooling AHU’s

Power Consumption(kWhour)

Page 11: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Cooling Landscape

-10 -5 0 5 10 15 20 25 30 35 40

20

40

60

80

100

120

Ambient Dry Bulb Temperature (°C)

Power Consumption(kW/hour)

DX CRAC’s

Chiller’s

Free Cooling AHU’s

Page 12: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Cooling Landscape – CRAC and AHUs

System TypePrimary Cooling Medium

IndoorProduct

OutdoorProduct

IndirectFree

CoolingConcurrent

Mechanical Cooling

Adiabatic

Chiller System+ Adiabatic Chiller

DX CRAC System Condenser

Chiller System

Standard Chiller

Chiller System+ Free Cool Chiller

FREE

COOL

Chiller System+ Adiabatic & Free Cool Chiller

FREE

COOL

System TypePrimaryCoolingMedium

OutdoorProduct

Direct/IndirectFree

CoolingConcurren

tMechanical

CoolingAdiabatic

Direct AHU+ Concurrent AHU

FREE

COOL

Direct AHU + Adiabatic AHU

FREE

COOL

Indirect AHU+ Concurrent AHU

FREE

COOL

Indirect AHU+ Adiabatic AHU

FREE

COOL

Page 13: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Cooling Landscape – CRAC Unit Options

Chiller System + Adiabatic & Free

Cool Chiller

FREE

COOL

Chiller SystemStandard Chiller

Chiller System + Free Cool Chiller

FREE

COOL

System Type IndoorProduct

OutdoorProduct

FreeCooling

AdiabaticPrimary Cooling Medium

Indirect

DX CRAC SystemCondenser

Chiller System+ Adiabaitic Chiller

Page 14: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Cooling Landscape – Air Handling Unit Options

System TypePrimary Cooling Medium

Outdoor Product

Direct/

Indirect

FreeCooling

Concurrent Adiabatic

Direct AHU + Adiabatic AHU

FREE

COOL

Indirect AHU + Adiabatic AHU

FREE

COOL

Direct AHU + Concurrent AHU

FREE

COOL

Indirect AHU + Concurrent AHU

FREE

COOL

Page 15: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Primary Cooling Medium

Direct / Indirect

FREE

COOL

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Systems

Refrigerant CRAC System and Condenser

Page 16: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Systems

Chilled Water CRAC System + Chiller

Page 17: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Systems

Chilled Water CRAC System + Adiabatic Chiller

Page 18: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Systems

Chilled Water CRAC System + Free Cooling Chiller

Page 19: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Systems

Chilled Water CRAC System + Adiabatic Free Cooling Chiller

Page 20: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Systems

Direct Air Free Cooling Air Handling Unit

Page 21: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Systems

Direct Air Free Cooling Air Handling Unit + Adiabatic

Page 22: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Systems

Indirect Air Free Cooling Air Handling Unit

Page 23: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Systems

Indirect Air Free Cooling Air Handling Unit + Adiabatic

Page 24: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Free Cooling Potential

Wet Bulb atPeak Dry Bulb

Peak Dry Bulb

35

15

0

10

5

20

25

30

Jan May Jun Jul Aug Sep Oct Nov DecFeb Mar Apr

°C

Data obtained from London Gatwick

FREE

COOL

Free CoolingThreshold

Page 25: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Total Cost of Ownership (5yrs) – 500kW System

DX CRAC

Chiller

Adiabatic Chiller

FC Chiller

Adiabatic FC Chiller

Direct + Concurrent

Direct + Adiabatic

Indirect + Concurrent

Indirect + Adiabatic

0 400 800£k

Operational Costs

Capital Costs

Page 26: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Annualised PUE – 500kW System

1.10 1.25 1.45

DX CRAC

Chiller

Adiabatic Chiller

FC Chiller

Adiabatic FC Chiller

Direct + Concurrent

Direct + Adiabatic

Indirect + Concurrent

Indirect + Adiabatic

Page 27: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Total Cost of Ownership – 500kW System

700

200

Year 1

Year 2

Year 3

Year 4

Year 5

400

0

£k Chiller - Standard£676,000

Chiller + Adiabatic£686,000

Chiller + Free Cooling£384,000

Chiller + Adiabatic & Free Cooling

£359,000

Direct AHU + Concurrent£272,000

Direct AHU + Adiabatic£271,000

Indirect + Concurrent£358,000

Indirect + Adiabatic£354,000

DX CRAC£628,000

£357,573£270,079

100

300

500

600

Page 28: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Cooling Equipment Footprint

0 25 50m2

Indoor Footprint

Total System Footprint

DX CRAC

Chiller

Adiabatic Chiller

FC Chiller

Adiabatic FC Chiller

Direct + Concurrent

Direct + Adiabatic

Indirect + Concurrent

Indirect + Adiabatic

Indoor Footprint

Page 29: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Cooling Landscape

-10 -5 0 5 10 15 20 25 30 35 40

20

40

60

80

100

120

Ambient Dry Bulb Temperature (°C)

DX CRAC’s

Chiller’s

Free Cooling AHU’s

Power Consumption(kW/hour)

Page 30: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Cooling Landscape

-10 -5 0 5 10 15 20 25 30 35 40

20

40

60

80

100

120

Ambient Dry Bulb Temperature (°C)

Power Consumption(kW/hour)

DX CRAC’s

Chiller’s

Free Cooling AHU’s

Page 31: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Data Centre Solutions

AireFlowTM

AHUs100-300kW

SmartCoolTM

16-233kWInRakTM

10-63kWCondensers/Dry Coolers12-174kW

Free-coolingChillers20kW-1.6MW

OnRakTM

3-35kW

Page 32: An Apples for Apples comparison of the data centre cooling landscape

www.airedale.com

Data Centre Solutions

ACISTM Integrated Controls Solutions

Page 33: An Apples for Apples comparison of the data centre cooling landscape

Business Issues - Recap

Efficiency

Capital Costs

Operational Costs

Footprintand Density Uptime