Sharing our Guidance
Kitchen Hood Electrical Coordination
Kitchen Hood Electrical Coordination
Kitchen Hood Types
Type 1 Hood –
Exhausts grease and grease laden smoke
Type 2 Hood –
Exhausts heats and condensate
04/07/23 2
X
Kitchen Hood Electrical Coordination
International Mechanical Code
507.2.1.1 – Exhaust must operate automatically
508.1 – Exhaust and make up air must be interlocked
509.1 – Type 1 hoods are required to have fire suppression
National Electrical Code
210.8(B)(2) – GFCI protection required
Kitchen Hood Electrical Requirements
04/07/23 3
X
Kitchen Hood Electrical Coordination
NFPA 96 – Commercial Hoods
96-10.4.1 – Upon activation of suppression system, all sources of fuel shall shut off
96-10.4.3 – Equipment under hood not requiring protection shall also shut off
96-10.4.4 – Shut off devices shall require a manual reset
96-10.5.1.1 – Manual activation of suppression is required
96-10.6.2 – Where there is a fire alarm system, the hood suppression system shall activate the fire alarm
Kitchen Hood Electrical Requirements
04/07/23 4
X
Kitchen Hood Electrical Coordination
TES Hood Connection Block Diagram
04/07/23 5
X
Kitchen Hood Electrical Coordination
TES Exhaust Fan Block Diagram
04/07/23 6
X
Kitchen Hood Electrical Coordination
Captivaire Shop Drawing
04/07/23 7
X
Kitchen Hood Electrical Coordination
Captiveaire Shop Drawing
04/07/23 8
Kitchen Hood Electrical CoordinationCONCLUSION . . .