WAMS Analytical Approach
By : Chandan Kumar Engineer ,WRLDC
What is WAMS
WAMS In WR Grid
WAMS Application
Under Development
at WRLDC
Few Real Time
Application
Whats More on the Way
15-Feb-13 WRLDC ,POSOCO
• It is based on Phasor measurement units (PMUs) which can deliver precisely time synchronized values of voltage and current phasors and other power system related quantities like frequency, ROCOF, breaker positions.
• It’s a collective technology to monitor power system dynamics in real time, identify system stability related weakness and helps to design and implement countermeasures . (IEEE)
What is WAMS ?
15-Feb-13 WRLDC ,POSOCO
•Visualization and analysis tools •Wide area situational awareness system. •Wide area protection and control
•Phasor Measurement Unit (PMU) •Phasor Data Concentrator(PDC) •Global Positioning System (GPS for Time Synchronization of the phasors) • Communication channel( Preference to optical fiber cable )
Components of WAMS
15-Feb-13 WRLDC ,POSOCO
Advantage of PMU
1 • More number of Samples(25-100 Phasors/sec)
2 • GPS Time Synchronized data to Control Centre from All Locations
3 • Finer View of the Electrical System
4 • Adaptive protection system can be developed
5 • Post Disturbance analysis with more accuracy which helps in planning.
6 • Many more …..
15-Feb-13 WRLDC ,POSOCO
Lets Have a closer view of SCADA and PMUs
Attribute SCADA PMUs
Measurement Analogue Digital
Resolution 2-4 samples per second Up to 100 samples per second
Observability Steady State Dynamic/Transient
Monitoring Local Wide- Area
Phasor Angle Measurement No Yes
15-Feb-13 WRLDC ,POSOCO
SCADA and PMU
Data from Present SCADA (Second Information , No time synchronization)
Millisecond Information with time synchronization
15-Feb-13 WRLDC ,POSOCO
X-Ray vs. MRI of the GRID
PMU+Visulization+Analysis+ GIS + Data
(Source : California ISO and OSIsoft LLC)
15-Feb-13 WRLDC ,POSOCO
Technology can Change what we See : Lets See How
Situational Awareness : Be preplanned rather than to wait
(Source : Space Time Insight)
15-Feb-13 WRLDC ,POSOCO
On our Path to Make the grid Smart and safely operate we have :
• PMU data
• RTU data
• GIS data
• Meteorological dept data
• Outage data
• Market data
So now We have BIG DATA
Need to Analyse Process VisualizeOperate
15-Feb-13 WRLDC ,POSOCO
Lets visit the world of PMU Advancement
Real-time Applications •Wide-area situational awareness •Frequency stability monitoring and trending •Power oscillation monitoring •Voltage monitoring and trending •Alarming and setting system operating limits, event detection and avoidance •Resource integration •Real time Dynamic State estimation •Dynamic line ratings and congestion management •Outage restoration •Operations planning
More Visual Aids rather than Watching Number for Operators : A change that is required with increase in the system Complexity and Big Data
15-Feb-13 WRLDC ,POSOCO
Contd..
Offline Application • Base lining power system performance
• Event analysis
• Dynamic system model calibration and validation
• Power plant model validation
• Load characterization
• Special protection schemes and islanding
• Primary frequency (governing) response
15-Feb-13 WRLDC ,POSOCO
WAMS in Western Region
• 5 PMUs(1 Nos. Bhadrawati, 2 Nos. Jabalpur, 2Nos Raipur)
• Different Vendors : GE,SEL,NI (More on way like Hitachi, Qualitrol)
• PDC : OpenPDC, GE PDC (planning for iPDC and OSIpi)
15-Feb-13 WRLDC ,POSOCO
Application under development @ WRLDC
Data Analysis Information Planning Decision Implementation
15-Feb-13 WRLDC ,POSOCO
•Oscillation Monitoring Systems •Model validation. •Dynamic Line Loadability. •Voltage stability analysis. •Dynamic & hierarchical State estimation •Wide area situational awareness. •Online stability assessment – Early warning.
15-Feb-13 WRLDC ,POSOCO
Application 1 : Oscillation in Grid
Spring Mass System It oscillates with frequency
f = 1/2π (√(k/m)) Only one mode of frequency
•In Similar manner electrical grid has electrical inertia connected by AC lines. So have modes of oscillation due to non-linearity of the system.
Mass-Rod system No oscillation
•In similar manner system connected with DC lines do not oscillate with each other
15-Feb-13 WRLDC ,POSOCO
What oscillation are observed in Electrical Grid ?
Small Signal Stability
Local
(Intra Area)
Local plant mode
(0.7 - 2.0 Hz)
Inter-Unit
(1.5-3.0 Hz)
Global
(Inter Area)
very low frequency
(0.1 to 0.3 Hz)
Higher frequency
(0.4 to 0.7 Hz)
15-Feb-13 WRLDC ,POSOCO
What Methods are used by WRLDC ?
Methods Techniques Event
PMU Data
Modal
Prony
Matrix Pencil
FDD (Frequency Domain
Decomposition)
FFT
15-Feb-13 WRLDC ,POSOCO
Why such oscillations poses threat to the system
• In normal power system state such LFO (Low frequency Oscillations ) are well damped.
• However they get excited during any small disturbance in the system and lead to oscillation in power system parameters like rotor velocity, voltages, currents and power flows.
• Due to oscillations in parameters, protection of equipments may operate leading to cascade tripping in power system.
• That’s why the observation of such modes is very essential in respect to system reliability and security.
• Among these parameters the rotor velocities of the generators and the power flows in the network are the most important.
• The rotor velocity variation causes strain to mechanical parts in the power plant and should be limited.
• The power flow oscillations may amount to the entire rating of a power line as if they are superimposed on the stationary line flow it will limit the transfer capacity by requiring increased safety margins.
15-Feb-13 WRLDC ,POSOCO
• HVDC Damping Controller
• TCSC POD Tuning
• PSS Tuning of generators
• Proper Planning of transmission lines to Strengthen the transmission network.
• Need to adapt Global PSS Tuning
Actions Required to Damp such Oscillations
15-Feb-13 WRLDC ,POSOCO
Application 2 : GRID INERTIA CALCULATION
15-Feb-13 WRLDC ,POSOCO
•Incident :Talcher-Kolar Pole 2 Blocked on 19-05-12 16:14Hrs. •System Frequency before operation of SPS(fo) : 50.21121 Hz •Generation Loss(PL-PG) : 716.875 MW (SPS Operation) •Generation of NEW grid after Tripping (PG): 81092.99 •df/dt observed from PMU =-0.02455 Hz/sec
H= 9.04 Seconds (Nearly matched with the calculated Value)
Help in defining the response required from generation and load during such disturbance
Application 3 : Phase Angle Measurements and its importance
15-Feb-13 WRLDC ,POSOCO
Load
Generation
What Causes Power to Flow in the Grid
DC power system - Power flows from a point of high voltage to a point of low voltage.
AC power system - Power flows from a point of high voltage angle to a point of low voltage angle. The higher the angle the greater the power flow.
What more we are working on
15-Feb-13 WRLDC ,POSOCO
Collective effort from Operators-Academia-Industry to develop good PMU tools for analysis Cloud computing for analysis Performance of PMUs from different vendors Latency rate of PMUs depending on communication channel used Establishment of WAMS Lab Voltage collapse analysis using PMUs Looking for collaboration from all.
Please Find more detail on application in “Synchrophasors Initiative in India”
By POSOCO.
: chandan.wrldc@yahoo.com Mob No : 09869251460
Thank You
15-Feb-13 WRLDC ,POSOCO