Understanding

“VFD”

nfiWelcome to

Connecting Engineering Students to Industries…

Variable Frequency Drive

INSTRUCTIONAL OBJECTIVES

What is VFD? How it Works?Induction Motor FactsVFD Practical Examples

INSTRUCTIONAL OBJECTIVES

What is VFD ?

Variable Frequency DriveUsed to control the speed of MotorAnd make the system intelligent & Saves energy

Speed of Motor directly Proportional toFrequency

rmp = 120f/p

F: FrequencyP: Number of Poles

INSTRUCTIONAL OBJECTIVES

Electric Motor Facts

Electric motors account for more than two-thirds of all energy

used in industry

63% of the energy consumed is linked to air & liquid flow

A typical 50HP industrial motor, with an efficiency of 90%, costs over

$25,000 to operate continuously over a year.

INSTRUCTIONAL OBJECTIVES

Energy Usage in Office Building

Other

17%

Ventilation

& Cooling

52%Lighting

31%

How Does VFD Works?

INSTRUCTIONAL OBJECTIVES

How Does VFD vary Frequency?A VFD, AC inverter, or electronic speed controller for AC motors converts the AC supply to DC using a rectifier (diode), then converts it back to a variable frequency by using a inverter bridge.

Switches

(IGBT’s)

VFD Block Diagram

Main

Power

Rectifier Capacitor

Motor

Lets see how we can save energy using

Variable Frequency Drives

FAN CURVE – BASIC CHARACTERISTIC OF A FAN

FLOW (Q)

PR

ESSU

RE

(P)

AT A GIVEN SPEED

At decreasing speed

FAN OPERATING POINT WITH LOAD

FLOW (Q)

PR

ESSU

RE

(P)

Operating Point

P = K X Q.Q

Now lets talk about varying the flow….

SYSTEM LOAD PROFILE

1

2

3

4

5

6

7

8

9

10

11

12

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95

CFM range

% T

IME

RA

NG

E

CFMDUTY CYCLE (% OF TIME)

100 % 10 %

80 % 40 %

60 % 40 %

40 % 10 %

Now let’s see the different ways of Air Flow Control…

Basic ON/OFF Control

OFFON

Q max

Average Flow rate: Q max x Ton/ (Ton + Toff)

SIMPLE METHOD

TEMPERATURE FLUCTUATION

HOME APPLIANCES

Outlet Damper Control

OUTLET DAMPER CHARACTERISTICS

% FLOW (Q)

% P

RES

SUR

E (P

)

CURVES SHIFTS AS DAMPER CLOSES

60 80 100

100

120

Energy = P X Q

OUTLET DAMPER CHARACTERISTICS

% FLOW (Q)

% P

RES

SUR

E (P

)

CURVES SHIFTS AS DAMPER CLOSES

60 80 100

100

120

Energy = P X Q

Energy Saving = Difference in Area

OUTLET DAMPER CHARACTERISTICS

CFM DUTY CYCLEHORSE POWER

WEIGHTEDHP

100 10 35 3.5

80 40 35 14.0

60 40 31 12.4

40 10 27 2.7

TOTAL AVERAGE HORSE POWER REQUIREMENT 32.6

VARIABLE SPEED FAN CONTROL

FLOW (Q)

PR

ESSU

RE

(P)

At decreasing speed100

50

20

1008050

VARIABLE SPEED FAN CONTROL

FLOW (Q)

PR

ESSU

RE

(P)

At decreasing speed100

50

20

1008050

CFM DUTY CYCLEHORSE POWER

WEIGHTEDHP

100 10 35 3.5

80 40 18 7.2

60 40 7.56 3.024

40 10 2.24 0.224

TOTAL AVERAGE HORSE POWER REQUIREMENT 13.948

VFD CHARACTERISTICS

CFM DUTY CYCLEHORSE POWER

WEIGHTEDHP

100 10 35 3.5

80 40 18 7.2

60 40 7.56 3.024

40 10 2.24 0.224

VFD CHARACTERISTICS

OUTLET DAMPER CHARACTERISTICS

CFM DUTY CYCLEHORSE POWER

WEIGHTED HP

100 10 35 3.5

80 40 35 14.0

60 40 31 12.4

40 10 27 2.7TOTA

L A

VER

AG

E H

OR

SEP

OW

ER R

EQU

IREM

ENT

32

.6

TOTA

L A

VER

AG

E H

OR

SE

PO

WER

REQ

UIR

EMEN

T

13

.94

8

OUTLETDAMPER

VARIABLE SPEED

WEIGHTED HORSEPOWER

32.6 13.948

x KW/HP .746 .746

x HR/MONTH 730 730

= KWH/MONTH 17753 7596

x COST (INR) 2.5 2.5

= TOTAL COST (INR) 44382.5 18990

SAVING CALCULATION:

Saving per month on a single fan…?

Now Lets see the Practical Demonstration of

VFD

Important Parameters used in various Applications

Source of Frequency Command

• Master frequency determined by digital keypad • Master frequency determined by 0 to +10 V input on

AVI terminal • Master frequency determined by 4 to 20mA input on

ACI terminal • Master frequency determined by potentiometer on

digital keypad

Source of Operation Command

• Operation determined by digital keypad • Operation determined by external control terminals,

keypad STOP is effective• Operation determined by external control terminals,

keypad STOP is ineffective

Important Parameters used in various Applications

STOP Method

• Ramp Stop• Coast Stop

Important Parameters used in various Applications

Maximum Output Frequency

Range

0 ~ 400 Hz

Important Parameters used in various Applications

Acc./ Dec. Time

Voltage / Frequency Setting for various Applications

Important Parameters used in various Applications

Acc S CurveTo Smooth the Acc/ Dec. Operation

Range 0 - 7

Important Parameters used in various Applications

Jog FrequencyTo adjust the Speed of Motor at Jog Mode

Jog Acc./ Dec Time

0.1 to 600.0 sec or 0.01 to 600.0 sec

Important Parameters used in various Applications

Over–Voltage Stall PreventionOver-Current Stall Prevention during Acceleration

Important Parameters used in various Applications

Operation Control of VFD

2 Wire Control (1)– On/Off & Direction from Toggle Button

Important Parameters used in various Applications

Operation Control of VFD

2 Wire Control (2) – On/Off & Direction from Toggle Button

Important Parameters used in various Applications

Operation Control of VFD

3 Wire Control – On/Off from Push Button & Toggle Button for Direction Control

Important Parameters used in various Applications

Analog Output SignalAnalog Frequency Meter (0 to Maximum Output Frequency)

Analog Current Meter (0 to 250% of the rated AC drive current)

Analog Output Gain 0 ~ 200%

Important Parameters used in various Applications

Bias Adjustment

Important Parameters used in various Applications

Bias Adjustment

Important Parameters used in various Applications

Bias Adjustment

Important Parameters used in various Applications

Gain Adjustment

Important Parameters used in various Applications

Gain Adjustment

Important Parameters used in various Applications

Gain Adjustment

Important Parameters used in various Applications

Second Source of Frequency Command

Keypad Up/DownAVI (0-10V)ACI (4-20mA)Keypad Potentiometer

Important Parameters used in various Applications

Reverse Operation InhibitionParameter LockPLC Operation

Jog Acc./ Dec Time0.1 to 600.0 sec or 0.01 to 600.0 sec

Important Parameters used in various Applications

VFD saves Energy & make Motor

Control Mechanism Intelligent

Learn 4 PLC’s in a Day100+ Video Tutorials

Life time Access

nfipresents

Lear

n t

o C

od

e |

Co

de

to L

earn

Coupon Code https://www.udemy.com/nfi-plc-online-leaning/?couponCode=slideshare

in $99 $49

For more courses visit www.nfiautomation.org

Course Outline

• 100+ PLC Video Tutorials

• Doubt Clearing Complementary LIVE Sessions on Team Viewer

• Ladder Logic Programming

• PLC Presentations, PLC Circuits, PLC Codes

• FREE PLC Simulation Software for Practice

PLC – Programmable Logic Controller

Delta DVP 14 SS + 16 SP

Allen Bradley M1000

Siemens S7 200

Schneider

Analog Cards Programming

04 AD – Analog to Digital

04DA- Digital to Analog

PLC & VFD Advanced

Course4 PLC’s Training

Platforms

For more courses visit www.nfiautomation.org

Course Highlights:

• 30 Live Practical Classes on PLC, Analog Cards & AC drives- VFD

• 100+ PLC Video Tutorials with Lifetime Access & FREE PLC Simulator

• FREE Circuits Diagram

$149

Course Link:http://www.wiziq.com/course/28882-plc-and-ac-drives-online-certificate-trainaing-course

nfi

Connecting Engineering Students to Industries…

T h a n k Y o u

Recommended