Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
III.4 ADRESSABLE FIRE ALARM SYSTEM (CLOSED
LOOP SYSTEM) BLOCK-A
1 182 Supply and installation of photo electric analogaddressable optical smoke detectors ( multi sensor )
suitable for detecting a wide range of smoke from slow
smoldering and fast flaming fire. The detectors shall
have following features and also including supply of all
fixing materials complete as required
Each
Solid state addressing arrangement in combination
with a hand held programmer to configure the sensor
address.
Electronics free mounting baseTwin alarm LED's for 360 degree viewing and shall
have blinking LED facility.
Photo electric sensor shall have a removable chamber
for ease of cleaning or replacement.
Automatic compensation for smoke sensor
contamination.
Shall have a built in test facility which allows the fire
alarm control panel to adjust the alarm threshold levels
to compensate for contamination and shall have a
maintenance alarm display when threshold can no
longer be adjusted.
Operating Temp Range: 10 deg C to 59 deg C and
Humidity : 95% RH non-condensing.
2 5 Supply and installation of optical type duct detectors
same as no 2 above but inside a air sampling chamber
to be located inside the AC return air duct including
supply o all fixing materials.
Each
3 3 Supply and installation of analog addressable heat
detector. The detector shall have the following features
:
Each
Page 1 of 32
7/29/2019 Works for Addressable
2/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
Solid state addressing arrangement in combination
with a hand held programmer to configure the sensor
address.
Electronics free mounting base
Twin alarm LED's for 360 degree viewing and shall
have blinking LED facility.
Simple anti tamper locking mechanism
4 110 Supply and installation of visual type response
indicators with LED indicating lamp, housed in suitable
MS enclosure with acrylic cover fixed in flush with wall
to operate in conjunction with smoke / heat detectors
operating on 24VDC installed above the false ceiling
or below the false floor, complete with all accessories
and fixing materials as required and as directed by
Engineer in charge.
Each
5 4 Supply and installation of addressable manual call
stations with in build monitor module and press /
break and resettable capability constructed of high
impact LEXAN sheet with clearly visible operating
instructions on the cover and the word Fire shall
appear on front and suitable for surface mounting /
flush mounting and complete as required.
Each
6 14 Supply and installation of short circuit isolator, analog
addressable type for isolating analog devices from
short circuit, fault isolating module shall have LED that
is to indicate a short on the loop. This device shall
automatically determining an return to normal
condition of the loop and restore the isolated
segments.
Each
7 4 Supply and installation of loop powered base
addressable sounders complete with all fixing material
complete as required
Set
Page 2 of 32
7/29/2019 Works for Addressable
3/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
8 5 Supply and installationof addressable control modules
for providing tripping contacts for the AHUs ( This shall
be wired in the loop and located near the AHUs )
including supply and fixing of all fixing materials asrequired.
Set
9 1 Supply, installation, testing and commissioning of
micro processor based digital distributed processing
real time multitasking and multi user type loop analog
addressable type fire alarm control panel FACP and
control panel shall have the following features
including supply of all fixing materials interconnections
earthing complete as required. ( 2 LOOP PANEL)
Set
FACP shall be suitable for 230 V 50hz AC supply and
smoke detectors shall be powered using FACP based
smoke detection circuits. Devices shall receive power
and communication for the same pair of conductors.
FACP shall provide for resetting smoke detectors fault
isolation and sensor loop operation.
FACP shall be suitable for mixing different fire devices
and beam smoke detectors within the same loop to
optimize field wiring.
FACP shall have alarm indication of individualsensors
detectors trouble alarm indication for dust
accumulation The panel shall check detectors once in
every 24 hours for contamination for this purpose.
The FACP shall regularly supervise all the sensors and
devices on the loop and initiate fire or trouble alarm
whenever required.
FACP shall have 2 wire circuit to connect 126
addressable devices per loop
Page 3 of 32
7/29/2019 Works for Addressable
4/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
FACP shall be with repeater interface and suitable 24
batter with built in software and 2 x 40 character
alphanumeric LCD display and necessary front panel
control keys, FACP shall display the date time anddescription for analog sensors to indicate alarms and
trouble situations.
FACP switches shall allow authorized personnel to
accomplish the following
Initiate a general alarm condition
Silence the local audible
Silence the alarm signals
Reset all zones / points
FACP shall have walk test facility
Shall have facility for programming from the key boardor utilizing PC set up software via laptop / desk top
computer
Shall have memory data for panel configuration and
operation reside in non volatile memory ( EPROM )
All addressable units shall be connected to the FACP
through the loop cards and shall be addressed
through individualized numbers. The FACP shall be
able to obtain analog value for all detectors in the
circuit through a pulsed digitized current data. The
FACP shall be able to analyze all analog inputs from al
addressable units and through its own software and
ambient level screening the FACP shall be able to
identify fire, possible fire or fault condition. The unit
supervision shall be dynamic and continuous
The FACP shall itself have all loop cards in it. No
isolated motherboard or transponder shall be
considered.
Page 4 of 32
7/29/2019 Works for Addressable
5/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
Short/ open circuit units shall also be reported at the
FACP in such cases the system through the use of
fault isolators shall be able to isolate that segment
between the two fault isolators. The missing detectors/ devices shall also be reported to the FACP with
identification of the location.
The FACP shall have the facility to set smoke sensor
sensitivityremotely to either high sensitivitymanuallyor
on a pre programmed sequence ( ie day/ night ) period
When an alarm condition is sensed at the FACP from
a smoke or heat detector, a delay time / alarm
verificationperiod shall be stated. If the sensor is still in
alarm after the delay time expired , an alarm condition
is reported. The delay time shall be adjustable from 0
to 990 seconds.
FACP shall have either an in built or external printer
coupled to the FACP, which shall log all events with
time. The printout shall clearly indicate the event fire /
Pre alarm / Fault etc. with the unit address and time.
The FACP shall also be able to discriminate between
false alarms and fire conditions as well as priority
selection of alarm in case alarm activates in two or
more remotely located units simultaneously. In such
cases the manual call stations shall have the highest
priority.
The FACP also be able to actuate switches
automaticallyin case of fire condition that of AHUs and
power supply or other system such as piped
pressurized gas supply.
Page 5 of 32
7/29/2019 Works for Addressable
6/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
The system shall be fail safe and adequate safe
guards should be under taken that in the event of al
failure of a part of the system it shall not handicap the
complete system. The loop cards shall be of Modularconstruction.
The FACP shall have its own battery backup of a
minimum of 48 hrs in normal run and then half an hour
in alarm condition. The back up time calculation shall
be done as per TAC standards. The batteryshall be 2
x 12 V ( 24 V ) DC and of sealed maintenance free
type, housed inside the FACP.
It shall be able to with stand temp variations from 0deg C to 55 deg C. Further RH up to 93 % shall not
hamper its performance. The voltage rating shall be
from 17 VDC to 31 VDC, though the voltage may be
change depending upon the working voltages of a
proprietary FACP
The FACP shall be totally enclosed dust and vermin
proof type made of minimum 16 gauge dust inhibited
sheet with even baked finish. The FACP shall be of
completely solid stage design.
The logic circuitry shall be based on high noiseimmunity solid state hardware employing modular
construction. Logic cards shall be of epoxy fiber glass
construction.
The FACP shall have EN54 / UL / FM approval
The panel shall have an extra loop card to serve as
standby in case of burnout or malfunctioning of any
operating loop cards.
The FACP shall be capable of being networked (
future expansion ) with other similar FACPs located at
different part of the premises through a single RS 485bus.
Page 6 of 32
7/29/2019 Works for Addressable
7/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
The FACP shall have provision for interfacing with the
public address system.
10 1 Supply and installation of repeater panels which
display fire / fault message simultaneously with the
FACP. It shall be capable of interfacing with the FACP
on a single RS485 bus. The panel shall be capable of
operating on 24 VDC supply
Each
The panel shall have 2 x 40 characters backlit display
which shall displaydate time and description of alarm /
trouble events are that displayed in the FACP with in
built buzzer to indicate fault / fire alarm.
The panel shall be powered from the FACP
It shall have control keys for sound silence mute and
to reset the FACP from the repeater stations.
The repeater panel shall have the following LEDs
indications like supply , fault, mute, silent, disabled,
fire.
11 2200 Supply and wiring with 2C x 1,5sqmm FRLS twisted
pair shielded,1.1KV grade PVC insulated unarmoured
copper conductor cable , PVC overall sheathed cable
in already embedded conduit with ISI certification
mark, interconnections complete as required and as
directed by EIC.
Mtrs
12 100 Supply ands wiring with 4C x 1.5 sqmm FRLS twisted
pair shielded, 1.1 KV grade PVC insulated unarmored
copper conductor cable PVC overall sheathed cable in
already embedded conduit with ISI certification mark ,
interconnections complete as required and as directed
by EIC
mtrs
Page 7 of 32
7/29/2019 Works for Addressable
8/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
BLOCK-B
1 130 Supply and installation of photo electric analog
addressable optical smoke detectors ( multi sensor )
suitable for detecting a wide range of smoke from slow
smoldering and fast flaming fire. The detectors shall
have following features and also including supply of all
fixing materials complete as required
Each
Solid state addressing arrangement in combination
with a hand held programmer to configure the sensor
address.
Electronics free mounting base
Twin alarm LED's for 360 degree viewing and shall
have blinking LED facility.
Photo electric sensor shall have a removable chamberfor ease of cleaning or replacement.
Automatic compensation for smoke sensor
contamination.
Shall have a built in test facility which allows the fire
alarm control panel to adjust the alarm threshold levels
to compensate for contamination and shall have a
maintenance alarm display when threshold can no
longer be adjusted.
Operating Temp Range: 10 deg C to 59 deg C and
Humidity : 95% RH non-condensing.
2 6 Supply and installation of optical type duct detectorssame as no 2 above but inside a air sampling chamber
to be located inside the AC return air duct including
supply o all fixing materials.
Each
3 2 Supply and installation of analog addressable heat
detector. The detector shall have the following features
:
Each
Solid state addressing arrangement in combination
with a hand held programmer to configure the sensor
address.
Electronics free mounting base
Twin alarm LED's for 360 degree viewing and shall
have blinking LED facility.
Simple anti tamper locking mechanism
Page 8 of 32
7/29/2019 Works for Addressable
9/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
4 67 Supply and installation of visual type response
indicators with LED indicating lamp, housed in suitable
MS enclosure with acrylic cover fixed in flush with wall
to operate in conjunction with smoke / heat detectorsoperating on 24VDC installed above the false ceiling
or below the false floor, complete with all accessories
and fixing materials as required and as directed by
Engineer in charge.
Each
5 4 Supply and installation of addressable manual call
stations with in build monitor module and press /
break and resettable capability constructed of high
impact LEXAN sheet with clearly visible operating
instructions on the cover and the word Fire shall
appear on front and suitable for surface mounting /
flush mounting and complete as required.
Each
6 11 Supply and installation of short circuit isolator, analog
addressable type for isolating analog devices from
short circuit, fault isolating module shall have LED that
is to indicate a short on the loop. This device shall
automatically determining an return to normal
condition of the loop and restore the isolated
segments.
Each
7 4 Supply and installation of loop powered base
addressable sounders complete with all fixing materialcomplete as required
Set
8 6 Supply and installationof addressable control modules
for providing tripping contacts for the AHUs ( This shall
be wired in the loop and located near the AHUs )
including supply and fixing of all fixing materials as
required.
Set
9 1 Supply, installation, testing and commissioning of
micro processor based digital distributed processing
real time multitasking and multi user type loop analog
addressable type fire alarm control panel FACP and
control panel shall have the following features
including supply of all fixing materials interconnections
earthing complete as required.( 2 LOOP PANEL )
Set
Page 9 of 32
7/29/2019 Works for Addressable
10/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
FACP shall be suitable for 230 V 50hz AC supply and
smoke detectors shall be powered using FACP based
smoke detection circuits. Devices shall receive power
and communication for the same pair of conductors.
FACP shall provide for resetting smoke detectors fault
isolation and sensor loop operation.
FACP shall be suitable for mixing different fire devices
and beam smoke detectors within the same loop to
optimize field wiring.
FACP shall have alarm indication of individualsensors
detectors trouble alarm indication for dust
accumulation The panel shall check detectors once inevery 24 hours for contamination for this purpose.
The FACP shall regularly supervise all the sensors and
devices on the loop and initiate fire or trouble alarm
whenever required.
FACP shall have 2 wire circuit to connect 126
addressable devices per loop
FACP shall be with repeater interface and suitable 24
batter with built in software and 2 x 40 character
alphanumeric LCD display and necessary front panel
control keys, FACP shall display the date time and
description for analog sensors to indicate alarms andtrouble situations.
FACP switches shall allow authorized personnel to
accomplish the following
Initiate a general alarm condition
Silence the local audible
Silence the alarm signals
Reset all zones / points
FACP shall have walk test facility
Shall have facility for programming from the key board
or utilizing PC set up software via laptop / desk top
computer
Page 10 of 32
7/29/2019 Works for Addressable
11/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
Shall have memory data for panel configuration and
operation reside in non volatile memory ( EPROM )
All addressable units shall be connected to the FACP
through the loop cards and shall be addressed
through individualized numbers. The FACP shall be
able to obtain analog value for all detectors in the
circuit through a pulsed digitized current data. The
FACP shall be able to analyze all analog inputs from al
addressable units and through its own software and
ambient level screening the FACP shall be able to
identify fire, possible fire or fault condition. The unit
supervision shall be dynamic and continuous
The FACP shall itself have all loop cards in it. No
isolated motherboard or transponder shall be
considered.
Short/ open circuit units shall also be reported at the
FACP in such cases the system through the use of
fault isolators shall be able to isolate that segment
between the two fault isolators. The missing detectors
/ devices shall also be reported to the FACP with
identification of the location.
The FACP shall have the facility to set smoke sensorsensitivityremotely to either high sensitivitymanuallyor
on a pre programmed sequence ( ie day/ night ) period
When an alarm condition is sensed at the FACP from
a smoke or heat detector, a delay time / alarm
verificationperiod shall be stated. If the sensor is still in
alarm after the delay time expired , an alarm condition
is reported. The delay time shall be adjustable from 0
to 990 seconds.
FACP shall have either an in built or external printer
coupled to the FACP, which shall log all events with
time. The printout shall clearly indicate the event fire /
Pre alarm / Fault etc. with the unit address and time.
Page 11 of 32
7/29/2019 Works for Addressable
12/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
The FACP shall also be able to discriminate between
false alarms and fire conditions as well as priority
selection of alarm in case alarm activates in two or
more remotely located units simultaneously. In suchcases the manual call stations shall have the highest
priority.
The FACP also be able to actuate switches
automaticallyin case of fire condition that of AHUs and
power supply or other system such as piped
pressurized gas supply.
The system shall be fail safe and adequate safe
guards should be under taken that in the event of al
failure of a part of the system it shall not handicap the
complete system. The loop cards shall be of Modular
construction.
The FACP shall have its own battery backup of a
minimum of 48 hrs in normal run and then half an hour
in alarm condition. The back up time calculation shall
be done as per TAC standards. The batteryshall be 2
x 12 V ( 24 V ) DC and of sealed maintenance free
type, housed inside the FACP.
It shall be able to with stand temp variations from 0
deg C to 55 deg C. Further RH up to 93 % shall not
hamper its performance. The voltage rating shall be
from 17 VDC to 31 VDC, though the voltage may be
change depending upon the working voltages of a
proprietary FACP
The FACP shall be totally enclosed dust and vermin
proof type made of minimum 16 gauge dust inhibited
sheet with even baked finish. The FACP shall be of
completely solid stage design.
The logic circuitry shall be based on high noise
immunity solid state hardware employing modular
construction. Logic cards shall be of epoxy fiber glass
construction.
The FACP shall have EN54 / UL / FM approval
The panel shall have an extra loop card to serve as
standby in case of burnout or malfunctioning of any
operating loop cards.
Page 12 of 32
7/29/2019 Works for Addressable
13/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
The FACP shall be capable of being networked (
future expansion ) with other similar FACPs located at
different part of the premises through a single RS 485
bus.
The FACP shall have provision for interfacing with the
public address system.
10 1 Supply and installation of repeater panels which
display fire / fault message simultaneously with the
FACP. It shall be capable of interfacing with the FACP
on a single RS485 bus. The panel shall be capable of
operating on 24 VDC supply
Each
The panel shall have 2 x 40 characters backlit display
which shall displaydate time and description of alarm /
trouble events are that displayed in the FACP with in
built buzzer to indicate fault / fire alarm.
The panel shall be powered from the FACP
It shall have control keys for sound silence mute and
to reset the FACP from the repeater stations.
The repeater panel shall have the following LEDs
indications like supply , fault, mute, silent, disabled,
fire.
11 1700 Supply and wiring with 2C x 1,5sqmm FRLS twisted
pair shielded,1.1KV grade PVC insulated unarmoured
copper conductor cable , PVC overall sheathed cable
in already embedded conduit with ISI certification
mark, interconnections complete as required and as
directed by EIC.
Mtrs
12 100 Supply ands wiring with 4C x 1.5 sqmm FRLS twisted
pair shielded, 1.1 KV grade PVC insulated unarmored
copper conductor cable PVC overall sheathed cable in
already embedded conduit with ISI certification mark ,
interconnections complete as required and as directed
by EIC
mtrs
Page 13 of 32
7/29/2019 Works for Addressable
14/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
BLOCK-C
1 210 Supply and installation of photo electric analog
addressable optical smoke detectors ( multi sensor )
suitable for detecting a wide range of smoke from slow
smoldering and fast flaming fire. The detectors shall
have following features and also including supply of all
fixing materials complete as required
Each
Solid state addressing arrangement in combination
with a hand held programmer to configure the sensor
address.
Electronics free mounting base
Twin alarm LED's for 360 degree viewing and shall
have blinking LED facility.Photo electric sensor shall have a removable chamber
for ease of cleaning or replacement.
Automatic compensation for smoke sensor
contamination.
Shall have a built in test facility which allows the fire
alarm control panel to adjust the alarm threshold levels
to compensate for contamination and shall have a
maintenance alarm display when threshold can no
longer be adjusted.
Operating Temp Range: 10 deg C to 59 deg C and
Humidity : 95% RH non-condensing.
2 6 Supply and installation of optical type duct detectorssame as no 2 above but inside a air sampling chamber
to be located inside the AC return air duct including
supply o all fixing materials.
Each
3 5 Supply and installation of analog addressable heat
detector. The detector shall have the following features
:
Each
Solid state addressing arrangement in combination
with a hand held programmer to configure the sensor
address.
Electronics free mounting base
Page 14 of 32
7/29/2019 Works for Addressable
15/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
Twin alarm LED's for 360 degree viewing and shall
have blinking LED facility.
Simple anti tamper locking mechanism
4 130 Supply and installation of visual type response
indicators with LED indicating lamp, housed in suitable
MS enclosure with acrylic cover fixed in flush with wall
to operate in conjunction with smoke / heat detectors
operating on 24VDC installed above the false ceiling
or below the false floor, complete with all accessories
and fixing materials as required and as directed by
Engineer in charge.
Each
5 4 Supply and installation of addressable manual call
stations with in build monitor module and press /
break and resettable capability constructed of high
impact LEXAN sheet with clearly visible operatinginstructions on the cover and the word Fire shall
appear on front and suitable for surface mounting /
flush mounting and complete as required.
Each
6 16 Supply and installation of short circuit isolator, analog
addressable type for isolating analog devices from
short circuit, fault isolating module shall have LED that
is to indicate a short on the loop. This device shall
automatically determining an return to normal
condition of the loop and restore the isolated
segments.
Each
7 4 Supply and installation of loop powered base
addressable sounders complete with all fixing material
complete as required
Set
8 6 Supply and installationof addressable control modules
for providing tripping contacts for the AHUs ( This shall
be wired in the loop and located near the AHUs )
including supply and fixing of all fixing materials as
required.
Set
Page 15 of 32
7/29/2019 Works for Addressable
16/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
9 1 Supply, installation, testing and commissioning of
micro processor based digital distributed processing
real time multitasking and multi user type loop analog
addressable type fire alarm control panel FACP andcontrol panel shall have the following features
including supply of all fixing materials interconnections
earthing complete as required. (2 LOOP PANEL )
Set
FACP shall be suitable for 230 V 50hz AC supply and
smoke detectors shall be powered using FACP based
smoke detection circuits. Devices shall receive power
and communication for the same pair of conductors.
FACP shall provide for resetting smoke detectors faultisolation and sensor loop operation.
FACP shall be suitable for mixing different fire devices
and beam smoke detectors within the same loop to
optimize field wiring.
FACP shall have alarm indication of individualsensors
detectors trouble alarm indication for dust
accumulation The panel shall check detectors once in
every 24 hours for contamination for this purpose.
The FACP shall regularly supervise all the sensors and
devices on the loop and initiate fire or trouble alarm
whenever required.
FACP shall have 2 wire circuit to connect 126
addressable devices per loop
FACP shall be with repeater interface and suitable 24
batter with built in software and 2 x 40 character
alphanumeric LCD display and necessary front panel
control keys, FACP shall display the date time and
description for analog sensors to indicate alarms and
trouble situations.
FACP switches shall allow authorized personnel to
accomplish the followingInitiate a general alarm condition
Silence the local audible
Page 16 of 32
7/29/2019 Works for Addressable
17/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
Silence the alarm signals
Reset all zones / points
FACP shall have walk test facility
Shall have facility for programming from the key board
or utilizing PC set up software via laptop / desk top
computer
Shall have memory data for panel configuration and
operation reside in non volatile memory ( EPROM )
All addressable units shall be connected to the FACP
through the loop cards and shall be addressed
through individualized numbers. The FACP shall be
able to obtain analog value for all detectors in the
circuit through a pulsed digitized current data. The
FACP shall be able to analyze all analog inputs from al
addressable units and through its own software and
ambient level screening the FACP shall be able toidentify fire, possible fire or fault condition. The unit
supervision shall be dynamic and continuous
The FACP shall itself have all loop cards in it. No
isolated motherboard or transponder shall be
considered.
Short/ open circuit units shall also be reported at the
FACP in such cases the system through the use of
fault isolators shall be able to isolate that segment
between the two fault isolators. The missing detectors
/ devices shall also be reported to the FACP withidentification of the location.
The FACP shall have the facility to set smoke sensor
sensitivityremotely to either high sensitivitymanuallyor
on a pre programmed sequence ( ie day/ night ) period
Page 17 of 32
7/29/2019 Works for Addressable
18/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
When an alarm condition is sensed at the FACP from
a smoke or heat detector, a delay time / alarm
verificationperiod shall be stated. If the sensor is still in
alarm after the delay time expired , an alarm conditionis reported. The delay time shall be adjustable from 0
to 990 seconds.
FACP shall have either an in built or external printer
coupled to the FACP, which shall log all events with
time. The printout shall clearly indicate the event fire /
Pre alarm / Fault etc. with the unit address and time.
The FACP shall also be able to discriminate between
false alarms and fire conditions as well as priority
selection of alarm in case alarm activates in two ormore remotely located units simultaneously. In such
cases the manual call stations shall have the highest
priority.
The FACP also be able to actuate switches
automaticallyin case of fire condition that of AHUs and
power supply or other system such as piped
pressurized gas supply.
The system shall be fail safe and adequate safe
guards should be under taken that in the event of al
failure of a part of the system it shall not handicap the
complete system. The loop cards shall be of Modular
construction.
The FACP shall have its own battery backup of a
minimum of 48 hrs in normal run and then half an hour
in alarm condition. The back up time calculation shall
be done as per TAC standards. The batteryshall be 2
x 12 V ( 24 V ) DC and of sealed maintenance free
type, housed inside the FACP.
Page 18 of 32
7/29/2019 Works for Addressable
19/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
It shall be able to with stand temp variations from 0
deg C to 55 deg C. Further RH up to 93 % shall not
hamper its performance. The voltage rating shall be
from 17 VDC to 31 VDC, though the voltage may bechange depending upon the working voltages of a
proprietary FACP
The FACP shall be totally enclosed dust and vermin
proof type made of minimum 16 gauge dust inhibited
sheet with even baked finish. The FACP shall be of
completely solid stage design.
The logic circuitry shall be based on high noise
immunity solid state hardware employing modular
construction. Logic cards shall be of epoxy fiber glass
construction.
The FACP shall have EN54 / UL / FM approval
The panel shall have an extra loop card to serve as
standby in case of burnout or malfunctioning of any
operating loop cards.
The FACP shall be capable of being networked (
future expansion ) with other similar FACPs located at
different part of the premises through a single RS 485
bus.
The FACP shall have provision for interfacing with the
public address system.
10 1 Supply and installation of repeater panels whichdisplay fire / fault message simultaneously with the
FACP. It shall be capable of interfacing with the FACP
on a single RS485 bus. The panel shall be capable of
operating on 24 VDC supply
Each
The panel shall have 2 x 40 characters backlit display
which shall displaydate time and description of alarm /
trouble events are that displayed in the FACP with in
built buzzer to indicate fault / fire alarm.
The panel shall be powered from the FACP
It shall have control keys for sound silence mute andto reset the FACP from the repeater stations.
Page 19 of 32
7/29/2019 Works for Addressable
20/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
The repeater panel shall have the following LEDs
indications like supply , fault, mute, silent, disabled,
fire.
11 2600 Supply and wiring with 2C x 1,5sqmm FRLS twisted
pair shielded,1.1KV grade PVC insulated unarmoured
copper conductor cable , PVC overall sheathed cable
in already embedded conduit with ISI certification
mark, interconnections complete as required and as
directed by EIC.
Mtrs
12 100 Supply ands wiring with 4C x 1.5 sqmm FRLS twisted
pair shielded, 1.1 KV grade PVC insulated unarmored
copper conductor cable PVC overall sheathed cable in
already embedded conduit with ISI certification mark ,
interconnections complete as required and as directedby EIC
mtrs
BLOCK-D
1 260 Supply and installation of photo electric analog
addressable optical smoke detectors ( multi sensor )
suitable for detecting a wide range of smoke from slow
smoldering and fast flaming fire. The detectors shall
have following features and also including supply of all
fixing materials complete as required
Each
Solid state addressing arrangement in combination
with a hand held programmer to configure the sensor
address.
Electronics free mounting base
Twin alarm LED's for 360 degree viewing and shall
have blinking LED facility.
Photo electric sensor shall have a removable chamber
for ease of cleaning or replacement.
Automatic compensation for smoke sensor
contamination.
Page 20 of 32
7/29/2019 Works for Addressable
21/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
Shall have a built in test facility which allows the fire
alarm control panel to adjust the alarm threshold levels
to compensate for contamination and shall have a
maintenance alarm display when threshold can nolonger be adjusted.
Operating Temp Range: 10 deg C to 59 deg C and
Humidity : 95% RH non-condensing.
2 11 Supply and installation of optical type duct detectors
same as no 2 above but inside a air sampling chamber
to be located inside the AC return air duct including
supply o all fixing materials.
Each
3 5 Supply and installation of analog addressable heat
detector. The detector shall have the following features
:
Each
Solid state addressing arrangement in combination
with a hand held programmer to configure the sensor
address.
Electronics free mounting base
Twin alarm LED's for 360 degree viewing and shall
have blinking LED facility.
Simple anti tamper locking mechanism
4 155 Supply and installation of visual type response
indicators with LED indicating lamp, housed in suitable
MS enclosure with acrylic cover fixed in flush with wall
to operate in conjunction with smoke / heat detectors
operating on 24VDC installed above the false ceilingor below the false floor, complete with all accessories
and fixing materials as required and as directed by
Engineer in charge.
Each
5 6 Supply and installation of addressable manual call
stations with in build monitor module and press /
break and resettable capability constructed of high
impact LEXAN sheet with clearly visible operating
instructions on the cover and the word Fire shall
appear on front and suitable for surface mounting /
flush mounting and complete as required.
Each
Page 21 of 32
7/29/2019 Works for Addressable
22/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
6 18 Supply and installation of short circuit isolator, analog
addressable type for isolating analog devices from
short circuit, fault isolating module shall have LED that
is to indicate a short on the loop. This device shallautomatically determining an return to normal
condition of the loop and restore the isolated
segments.
Each
7 6 Supply and installation of loop powered base
addressable sounders complete with all fixing material
complete as required
Set
8 11 Supply and installationof addressable control modules
for providing tripping contacts for the AHUs ( This shall
be wired in the loop and located near the AHUs )
including supply and fixing of all fixing materials asrequired.
Set
9 1 Supply, installation, testing and commissioning of
micro processor based digital distributed processing
real time multitasking and multi user type loop analog
addressable type fire alarm control panel FACP and
control panel shall have the following features
including supply of all fixing materials interconnections
earthing complete as required.(3LOOP PANEL )
Set
FACP shall be suitable for 230 V 50hz AC supply andsmoke detectors shall be powered using FACP based
smoke detection circuits. Devices shall receive power
and communication for the same pair of conductors.
FACP shall provide for resetting smoke detectors fault
isolation and sensor loop operation.
FACP shall be suitable for mixing different fire devices
and beam smoke detectors within the same loop to
optimize field wiring.
Page 22 of 32
7/29/2019 Works for Addressable
23/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
FACP shall have alarm indication of individualsensors
detectors trouble alarm indication for dust
accumulation The panel shall check detectors once in
every 24 hours for contamination for this purpose.
The FACP shall regularly supervise all the sensors and
devices on the loop and initiate fire or trouble alarm
whenever required.
FACP shall have 2 wire circuit to connect 126
addressable devices per loop
FACP shall be with repeater interface and suitable 24
batter with built in software and 2 x 40 character
alphanumeric LCD display and necessary front panel
control keys, FACP shall display the date time and
description for analog sensors to indicate alarms and
trouble situations.
FACP switches shall allow authorized personnel to
accomplish the following
Initiate a general alarm condition
Silence the local audible
Silence the alarm signals
Reset all zones / points
FACP shall have walk test facility
Shall have facility for programming from the key board
or utilizing PC set up software via laptop / desk top
computer
Shall have memory data for panel configuration and
operation reside in non volatile memory ( EPROM )
All addressable units shall be connected to the FACP
through the loop cards and shall be addressed
through individualized numbers. The FACP shall be
able to obtain analog value for all detectors in the
circuit through a pulsed digitized current data. The
FACP shall be able to analyze all analog inputs from al
addressable units and through its own software and
ambient level screening the FACP shall be able to
identify fire, possible fire or fault condition. The unit
supervision shall be dynamic and continuous
Page 23 of 32
7/29/2019 Works for Addressable
24/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
The FACP shall itself have all loop cards in it. No
isolated motherboard or transponder shall be
considered.
Short/ open circuit units shall also be reported at the
FACP in such cases the system through the use of
fault isolators shall be able to isolate that segment
between the two fault isolators. The missing detectors
/ devices shall also be reported to the FACP with
identification of the location.
The FACP shall have the facility to set smoke sensor
sensitivityremotely to either high sensitivitymanuallyor
on a pre programmed sequence ( ie day/ night ) period
When an alarm condition is sensed at the FACP from
a smoke or heat detector, a delay time / alarm
verificationperiod shall be stated. If the sensor is still in
alarm after the delay time expired , an alarm condition
is reported. The delay time shall be adjustable from 0
to 990 seconds.
FACP shall have either an in built or external printer
coupled to the FACP, which shall log all events with
time. The printout shall clearly indicate the event fire /
Pre alarm / Fault etc. with the unit address and time.
The FACP shall also be able to discriminate between
false alarms and fire conditions as well as priority
selection of alarm in case alarm activates in two or
more remotely located units simultaneously. In such
cases the manual call stations shall have the highest
priority.
The FACP also be able to actuate switches
automaticallyin case of fire condition that of AHUs and
power supply or other system such as piped
pressurized gas supply.
Page 24 of 32
7/29/2019 Works for Addressable
25/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
The system shall be fail safe and adequate safe
guards should be under taken that in the event of al
failure of a part of the system it shall not handicap the
complete system. The loop cards shall be of Modularconstruction.
The FACP shall have its own battery backup of a
minimum of 48 hrs in normal run and then half an hour
in alarm condition. The back up time calculation shall
be done as per TAC standards. The batteryshall be 2
x 12 V ( 24 V ) DC and of sealed maintenance free
type, housed inside the FACP.
It shall be able to with stand temp variations from 0
deg C to 55 deg C. Further RH up to 93 % shall nothamper its performance. The voltage rating shall be
from 17 VDC to 31 VDC, though the voltage may be
change depending upon the working voltages of a
proprietary FACP
The FACP shall be totally enclosed dust and vermin
proof type made of minimum 16 gauge dust inhibited
sheet with even baked finish. The FACP shall be of
completely solid stage design.
The logic circuitry shall be based on high noise
immunity solid state hardware employing modularconstruction. Logic cards shall be of epoxy fiber glass
construction.
The FACP shall have EN54 / UL / FM approval
The panel shall have an extra loop card to serve as
standby in case of burnout or malfunctioning of any
operating loop cards.
The FACP shall be capable of being networked (
future expansion ) with other similar FACPs located at
different part of the premises through a single RS 485
bus.
The FACP shall have provision for interfacing with thepublic address system.
Page 25 of 32
7/29/2019 Works for Addressable
26/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
10 1 Supply and installation of repeater panels which
display fire / fault message simultaneously with the
FACP. It shall be capable of interfacing with the FACP
on a single RS485 bus. The panel shall be capable ofoperating on 24 VDC supply
Each
The panel shall have 2 x 40 characters backlit display
which shall displaydate time and description of alarm /
trouble events are that displayed in the FACP with in
built buzzer to indicate fault / fire alarm.
The panel shall be powered from the FACP
It shall have control keys for sound silence mute and
to reset the FACP from the repeater stations.
The repeater panel shall have the following LEDs
indications like supply , fault, mute, silent, disabled,
fire.
11 3100 Supply and wiring with 2C x 1,5sqmm FRLS twisted
pair shielded,1.1KV grade PVC insulated unarmoured
copper conductor cable , PVC overall sheathed cable
in already embedded conduit with ISI certification
mark, interconnections complete as required and as
directed by EIC.
Mtrs
12 100 Supply ands wiring with 4C x 1.5 sqmm FRLS twisted
pair shielded, 1.1 KV grade PVC insulated unarmoredcopper conductor cable PVC overall sheathed cable in
already embedded conduit with ISI certification mark ,
interconnections complete as required and as directed
by EIC
mtrs
Page 26 of 32
7/29/2019 Works for Addressable
27/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
CONNECTING CORRIDOOR FOR 4BLOCKS
1 115 Supply and installation of photo electric analog
addressable optical smoke detectors ( multi sensor )
suitable for detecting a wide range of smoke from slow
smoldering and fast flaming fire. The detectors shall
have following features and also including supply of all
fixing materials complete as required
Each
Solid state addressing arrangement in combination
with a hand held programmer to configure the sensor
address.
Electronics free mounting base
Twin alarm LED's for 360 degree viewing and shall
have blinking LED facility.
Photo electric sensor shall have a removable chamberfor ease of cleaning or replacement.
Automatic compensation for smoke sensor
contamination.
Shall have a built in test facility which allows the fire
alarm control panel to adjust the alarm threshold levels
to compensate for contamination and shall have a
maintenance alarm display when threshold can no
longer be adjusted.
Operating Temp Range: 10 deg C to 59 deg C and
Humidity : 95% RH non-condensing.
2 10 Supply and installation of short circuit isolator, analog
addressable type for isolating analog devices from
short circuit, fault isolating module shall have LED that
is to indicate a short on the loop. This device shall
automatically determining an return to normal
condition of the loop and restore the isolated
segments.
Each
Page 27 of 32
7/29/2019 Works for Addressable
28/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
3 1 Supply, installation, testing and commissioning of
micro processor based digital distributed processing
real time multitasking and multi user type loop analog
addressable type fire alarm control panel FACP andcontrol panel shall have the following features
including supply of all fixing materials interconnections
earthing complete as required.( 2 LOOP PANEL )
Set
FACP shall be suitable for 230 V 50hz AC supply and
smoke detectors shall be powered using FACP based
smoke detection circuits. Devices shall receive power
and communication for the same pair of conductors.
FACP shall provide for resetting smoke detectors faultisolation and sensor loop operation.
FACP shall be suitable for mixing different fire devices
and beam smoke detectors within the same loop to
optimize field wiring.
FACP shall have alarm indication of individualsensors
detectors trouble alarm indication for dust
accumulation The panel shall check detectors once in
every 24 hours for contamination for this purpose.
The FACP shall regularly supervise all the sensors anddevices on the loop and initiate fire or trouble alarm
whenever required.
FACP shall have 2 wire circuit to connect 126
addressable devices per loop
FACP shall be with repeater interface and suitable 24
batter with built in software and 2 x 40 character
alphanumeric LCD display and necessary front panel
control keys, FACP shall display the date time and
description for analog sensors to indicate alarms and
trouble situations.
FACP switches shall allow authorized personnel to
accomplish the following
Page 28 of 32
7/29/2019 Works for Addressable
29/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
Initiate a general alarm condition
Silence the local audible
Silence the alarm signals
Reset all zones / points
FACP shall have walk test facility
Shall have facility for programming from the key board
or utilizing PC set up software via laptop / desk top
computer
Shall have memory data for panel configuration and
operation reside in non volatile memory ( EPROM )
FACP shall have facility for speech processor ( to
record pre recorded message of 20 S ) and also have
auto dialer facility ( can dial up to 8 different lines )
All addressable units shall be connected to the FACP
through the loop cards and shall be addressed
through individualized numbers. The FACP shall be
able to obtain analog value for all detectors in the
circuit through a pulsed digitized current data. The
FACP shall be able to analyze all analog inputs from al
addressable units and through its own software and
ambient level screening the FACP shall be able to
identify fire, possible fire or fault condition. The unit
supervision shall be dynamic and continuous
The FACP shall itself have all loop cards in it. No
isolated motherboard or transponder shall be
considered.
Short/ open circuit units shall also be reported at the
FACP in such cases the system through the use of
fault isolators shall be able to isolate that segment
between the two fault isolators. The missing detectors
/ devices shall also be reported to the FACP with
identification of the location.
Page 29 of 32
7/29/2019 Works for Addressable
30/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
The FACP shall have the facility to set smoke sensor
sensitivityremotely to either high sensitivitymanuallyor
on a pre programmed sequence ( ie day/ night ) period
When an alarm condition is sensed at the FACP from
a smoke or heat detector, a delay time / alarm
verificationperiod shall be stated. If the sensor is still in
alarm after the delay time expired , an alarm condition
is reported. The delay time shall be adjustable from 0
to 990 seconds.
FACP shall have either an in built or external printer
coupled to the FACP, which shall log all events with
time. The printout shall clearly indicate the event fire /
Pre alarm / Fault etc. with the unit address and time.
The FACP shall also be able to discriminate between
false alarms and fire conditions as well as priority
selection of alarm in case alarm activates in two or
more remotely located units simultaneously. In such
cases the manual call stations shall have the highest
priority.
The FACP also be able to actuate switches
automaticallyin case of fire condition that of AHUs and
power supply or other system such as pipedpressurized gas supply.
The system shall be fail safe and adequate safe
guards should be under taken that in the event of al
failure of a part of the system it shall not handicap the
complete system. The loop cards shall be of Modular
construction.
Page 30 of 32
7/29/2019 Works for Addressable
31/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
The FACP shall have its own battery backup of a
minimum of 48 hrs in normal run and then half an hour
in alarm condition. The back up time calculation shall
be done as per TAC standards. The batteryshall be 2x 12 V ( 24 V ) DC and of sealed maintenance free
type, housed inside the FACP.
It shall be able to with stand temp variations from 0
deg C to 55 deg C. Further RH up to 93 % shall not
hamper its performance. The voltage rating shall be
from 17 VDC to 31 VDC, though the voltage may be
change depending upon the working voltages of a
proprietary FACP
The FACP shall be totally enclosed dust and vermin
proof type made of minimum 16 gauge dust inhibited
sheet with even baked finish. The FACP shall be of
completely solid stage design.
The logic circuitry shall be based on high noise
immunity solid state hardware employing modular
construction. Logic cards shall be of epoxy fiber glass
construction.
The FACP shall have EN54 / UL / FM approval
The panel shall have an extra loop card to serve as
standby in case of burnout or malfunctioning of any
operating loop cards.
The FACP shall be capable of being networked (
future expansion ) with other similar FACPs located at
different part of the premises through a single RS 485
bus.
The FACP shall have provision for interfacing with the
public address system.
Page 31 of 32
7/29/2019 Works for Addressable
32/32
Package-I Part-III Electrical Works- Addressble Fire Alarm System
Sl. NO QUANTITY DESCRIPTION UNITS RATE
(IN FIGURES
& WORDS)
AMOUNT
4 1 Supply and installation of repeater panels which
display fire / fault message simultaneously with the
FACP. It shall be capable of interfacing with the FACP
on a single RS485 bus. The panel shall be capable ofoperating on 24 VDC supply
Each
The panel shall have 2 x 40 characters backlit display
which shall displaydate time and description of alarm /
trouble events are that displayed in the FACP with in
built buzzer to indicate fault / fire alarm.
The panel shall be powered from the FACP
It shall have control keys for sound silence mute and
to reset the FACP from the repeater stations.
The repeater panel shall have the following LEDs
indications like supply , fault, mute, silent, disabled,
fire.
5 1300 Supply and wiring with 2C x 1,5sqmm FRLS twisted
pair shielded,1.1KV grade PVC insulated unarmoured
copper conductor cable , PVC overall sheathed cable
in already embedded conduit with ISI certification
mark, interconnections complete as required and as
directed by EIC.
Mtrs
6 120 Supply ands wiring with 4C x 1.5 sqmm FRLS twisted
pair shielded, 1.1 KV grade PVC insulated unarmored
copper conductor cable PVC overall sheathed cable inalready embedded conduit with ISI certification mark,
interconnections complete as required and as directed
by EIC
mtrs
TOTAL Rs