The Board of Governors of Exhibition Place
June 2008
ENERGY ACTION PLAN
City of Toronto
2007 – Climate Change, Clean Air & Sustainable Action Plan
Not only achieve but exceed Kyoto Targets
Base Year 1999 Reach 6% reduction by 2012 Reduce 22 million tonnes of
CO2 annually
The Board of Governors of Exhibition Place
2004 - Exhibition Place Environmental Plan
Net Energy Self-Sufficiency by December 31, 2010
Base Year 2005
CNEA Board of Directors
Identify & address environmental impacts associated with its site
Implement programs to prevent and/or minimize its environmental footprint
Be an exemplary leader in environmental management
Reduce its electrical demand through operating initiatives
Making 2010 a Reality What Buildings?
Buildings we control – excluded tenanted buildings
Includes CNE
Reduce What? Electrical Energy only
But do not take actions that just convert use of electrical energy to natural gas energy
What target? Net Reduction of 25,177 megawatt hours by 2010
Energy Action Plan – the Why What is the connection between electrical use and greenhouse
gases Each kilowatt hour of electricity use translates into the following
greenhouse gases:
CO2 = Multiply by 0.244 kilograms
SOX = Multiply by 0.000063 kilograms
NOX = Multiply by 0.000348 kilograms
• Connection is coal-fire burning generators
Energy Action Plan – the HOW Energy Efficiencies – 33% 8,308,410Kwh achieved - 13.9% 3,499,603Kwh
• LEED Silver standard for new construction• Geothermal• Lighting Controls
Green/Clean Energy Production – 33% - 8,308,410 achieved - 3.7% 931,549Kwh
• 100 kilowatt PV .4 %• Trigen System 2.9 %• Wind Turbine .4 %
“Negawatts” – 33% - 8,308,410 achieved - 23.5% 5,916,595Kwh Operational/Energy Policy Total Reduction – 41.1% = 10,347,747Kwh
Direct Energy CentreHall A Lighting
Available Lighting
Level 1 35 lights
Level 2 66 lights
Level 3 68 lights
Emergency lights 35 lights
Total 204 lights Total Kilowatt Hours for an 8 Hour Day if all
lights are on
734 kwh
Hall A – New Lighting Plan
CLEANING – IATSE - ELECTRICAL WORK
ONLY Level 1 plus
Emergency Lights
Level 1 35
Emergency lights 35
Total Lights 70
EXHIBITORMOVE IN / MOVE OUT
ONLY Level 1 plus
Emergency Lights
Level 1 35
Emergency lights 35
Total Lights 70
SHOW EVENT DAYS
Level 1, Level 2, Level 3 plus Emergency Lights
Level 1 35
Level 2 66
Level 3 68
Emergency lights 35
Total Lights 204
Direct Energy CentreHall B Lighting
Available Lighting
Level 1 28 lights
Level 2 56 lights
Level 3 56 lights
Emergency lights 28 lights
Total Lights 168 lights Total Kilowatt Hours for an 8 Hour Day if all
lights are on
605 kwh
Hall B – New Lighting Plan
CLEANING – IATSE - ELECTRICAL WORK
ONLY Level 1 plus
Emergency Lights
Level 1 28
Emergency lights 28
Total Lights 56
EXHIBITORMOVE IN / MOVE OUT
ONLY Level 1 plus
Emergency Lights
Level 1 28
Emergency lights 28
Total Lights 56
SHOW EVENT DAYS
Level 1, Level 2, Level 3 plus Emergency Lights
Level 1 28
Level 2 56
Level 3 56
Emergency lights 28
Total Lights 168
Direct Energy CentreHall C Lighting
Available Lighting
Level 1 14 lights
Level 2 28 lights
Level 3 28 lights
Emergency lights 14 lights
Total Lights 84 lights Total Kilowatt Hours for an 8 Hour Day if all
lights are on
302 kwh
Hall C – New Lighting Plan
CLEANING – IATSE - ELECTRICAL WORK
ONLY Level 1 plus
Emergency Lights
Level 1 14
Emergency lights 14
Total Lights 28
EXHIBITORMOVE IN / MOVE OUT
ONLY Level 1 plus
Emergency Lights
Level 1 14
Emergency lights 14
Total Lights 28
SHOW EVENT DAYS
Level 1, Level 2, Level 3 plus Emergency Lights
Level 1 14
Level 2 28
Level 3 28
Emergency lights 14
Total Lights 84
Direct Energy CentreHall D Lighting
Available Lighting
Level 1 16 lights
Level 2 33 lights
Level 3 33 lights
Emergency lights 16 lights
Total Lights 98 lights Total Kilowatt Hours for an 8 Hour Day if all
lights are on
353 kwh
Hall D – New Lighting Plan
CLEANING – IATSE - ELECTRICAL WORK
ONLY Level 1 plus
Emergency Lights
Level 1 16
Emergency lights 16
Total Lights 32
EXHIBITORMOVE IN / MOVE OUT
ONLY Level 1 plus
Emergency Lights
Level 1 16
Emergency lights 16
Total Lights 32
SHOW EVENT DAYS
Level 1, Level 2, Level 3 plus Emergency Lights
Level 1 16
Level 2 33
Level 3 33
Emergency lights 16
Total Lights 98
Direct Energy CentreHeritage Court & Swing Space Lighting
Available Lighting
Level 1 19 lights
Level 2 32 lights
Level 3 32 lights
Emergency lights 12 lights
Total Lights 95 lights Total Kilowatt Hours for an 8 Hour Day if all
lights are on
342 kw/hr
Heritage Court & Swing Space – New Lighting Plan
CLEANING – IATSE -ELECTRICAL WORK
ONLY Level 1 plus
Emergency Lights
Level 1 19
Emergency lights 12
Total Lights 31
EXHIBITORMOVE IN / MOVE OUT
ONLY Level 1 plus
Emergency Lights
Level 1 19
Emergency lights 12
Total Lights 31
SHOW EVENT DAYS
Level 1, Level 2, Level 3 plus Emergency Lights
Level 1 19
Level 2 32
Level 3 32
Emergency lights 12
Total Lights 95
What does this mean? SAVINGS KW/HRDirect Energy Centre
Avoided Greenhouse Gas Emissions
Saving
Kwh/day
Saving
Kwh/year
CO2
Tonnes
SOX
kilograms
NOX
kilograms
Hall A 1,375 101,750 24.8 6.4 35.4
Hall B 1,191 84,561 20.6 5.32 29.42
Hall C 346 33,450 8.16 2.1 11.6
Hall D 692 17,966 4.38 1.13 6.25
Heritage Court & Swing Space
810 34,830 2.19 2.19 12.12
Total Savings = 272,557 kwh/yr
Direct Energy Centre
HALL LIGHTING
HALL LIGHTING ENERGY CONSUMPTIONCleaning - Move in/out
020000
4000060000
80000100000
120000140000
160000180000
A B C D HER.CRT
74 71 75 26 43
Present Kwh
Previous Kwh
Saving in Kwh & Greenhouse Gas Avoided
KWH/DAY(8HR) SAVING
-
500
1,000
1,500
2,000
2,500
A B C D HER.CRT
Present
Previous
Savingkw h/day
Saving in Kwh & Greenhouse Gas Avoided (Cont’d)
AVOIDED Greenhouse Gas EMISSIONS
05
10152025303540
A B C D
HER.CRT
CO2 tonnes
Sox kg
Nox kg
Other Buildings
BLC
Other Buildings (Cont’d)
QE Hall
DOOR GUIDELINES EXTERIOR DOORS All roll up doors exceeding 16 feet will be limited year round to opening of 16
feet high – only exception will be during defined periods for movement of large items as authorized by Operations
All to default to a closed mode when interior space is air conditioned Automatically close on timers once opened unless scheduled as open for a
defined period by Operations All man doors to remain at default closed mode position – only when a man door
is required on a continuous basis will Security key door open for defined periodINTERIOR DOORS All perimeter roll up doors & man doors that section the floor space must
conform to this policy if the sectioned area requires air conditioningOTHER Supply of air conditioning implemented upon door policy being followed Unconditioned areas - doors may remain open if not connected to conditioned
space
Temperature Guidelines Cooling is provided to maintain air conditioned facilities at or about 25º
C during normal show or occupied hours
During off hours, air conditioning will be shut off & temperatures may rise above 25º C
Temperatures in the 23-26ºC (73 ºF-78 ºF) range are comfortable for most people as researched by ASHRAE (standard 55-400) Thermal Environmental Conditions for Human Occupancy
In non-air conditioned space - exhaust or ventilation fans in ventilation mode during normal show or occupied hours & off at all other times.
During show move-in & move-out - there will be no air conditioning only ventilation
Building Interior Lighting Guidelines
Except when required for security purposes all lighting will be turned off when buildings & facilities are unoccupied i.e. end of day when no activities are in progress.
Off settings still allow for required emergency lighting levels in accordance with the Fire Code
Office lighting will be on according to office hours of operations while office is occupied & otherwise lighting will be off
Exhibit hall lighting will be on as required by schedules for show or event activities – each show will have a Light Hall Schedules
Exterior Lighting All Year Including CNE
Exterior Building Lighting Façade & Point of Interest Lighting will be “on” as required from dusk to end
of show then off unless required for security
Parking Lot Lighting Parking Lot Lighting where separate from street lighting will be on only when
required for event parking, scheduled cleaning services, scheduled midway servicing, otherwise it will be off
Street Lighting will be on one half hour before dusk and one half hour after dawn.
Midway Concessions Midway booths, rides, tents, external exhibits will have lights “on” from dusk
till end of day activities then off, unless LED lights are utilized & then may be on during the day for attraction
Exterior Lighting All Year Including CNE (Cont’d)
.
Fountains Fountains will be on from 9 a.m. until show closing time that day - this
includes fountain pumps and lights
Pathway Lights Pathway lights will be on from dusk until 2 a.m. unless required for security
Escalators and Elevators During Show Period
Passenger escalators and elevators will be put in service half an hour before the show starts & be out of service half an hour after the show finishes
During move-in and move- out Freight elevators will be put in service based on the schedule submitted by Exhibition Place Senior Event
Coordinator to Fire Safety & Energy Management Coordinator/Building Operator. Non Show Day
Passenger elevators will be in service Monday – Friday 9:00AM until 5:00PM Total Kilowatt Hour Savings per year
225,798 kWh
WHAT WE NEED TO ACHIEVE OUR GOAL
Turning off one computer at the end of each day – savings of 726 KwH and $94 each year
Turning off radios at end of day – savings of 17 KwH - $1.97 per radio
Turning off individual office lights – savings of 70 Kwh per year – $63 a year each office
Recommended