TechnicalInformation
Integrated Production Control System CENTUM VP System Overview (HMI Overview)
TI 33K01A11-50E
TI 33K01A11-50E©Copyright Sep. 2011 (YK)1st Edition Sep. 2011 (YK)
Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JapanTel.: 81-422-52-5634 Fax.: 81-422-52-9802
i
TI 33K01A11-50E
IntroductionCENTUM VP is an integrated production control system that manages and controls the operation of plants in a wide variety of industries, including petroleum refineries, chemical, steel, food, power, and so forth. This manual (System Overview (HMI Overview)) provides a simple overview of the HIS (Human Interface Station) of CENTUM VP HMI (Human Machine Interface). Before reading this manual, first read the separate System Overview (General Overview) manual to understand the overview of the CENTUM VP, and then read this manual. After that, proceed to detailed material, such as General Specifications.
Relevant ManualTI 33K01A10-50E CENTUM VP System Overview (General Overview)TI 33K01A12-50E CENTUM VP System Overview (FCS Overview) TI 32R01B10-01E Safety Instrumented System ProSafe-RS System Overview
Target Readership for This ManualThis manual is mainly intended for:
• Instrumentation, electric, and computer engineers who are evaluating CENTUM VP for purchase or who will be in charge of installation.
None on FiguresFigures described in this manual may be highlighted or simplified, or partially omitted for the convenience of explanation.
Trademarks• “CENTUM”, “ProSafe”, “Vnet/IP”, and “Exaopc” are registered trademarks of Yokogawa
Electric Corporation.
• “Windows” is registered trademarks of Microsoft Corporation in United States and/or other countries.
• “Ethernet” is a registered trademark of Xerox Corporation.
• Other product and company names may be registered trademarks of their respective companies (the TM or R mark is not displayed).
All Rights Reserved Copyright © 2011, Yokogawa Electric Corporation Sep. 22, 2011-00
Toc-1
TI 33K01A11-50E
Integrated Production Control System CENTUM VP System Overview (HMI Overview)
Sep. 22, 2011-00
CONTENTS
TI 33K01A11-50E 1st Edition
Introduction ..............................................................................................................i1. Overview of CENTUM VP HIS .................................................................. 1-1
1.1 Ergonomic Design Concept ............................................................................1-11.2 Consolidated Alarm Management Software (CAMS for HIS) ....................... 1-11.3 Remote Operation and Monitoring Functions ...............................................1-21.4 Multiple and Wide Monitor Support ................................................................1-21.5 High-speed Data Update ..................................................................................1-21.6 Succession of Operability ...............................................................................1-2
2. Hardware ................................................................................................... 2-12.1 Desktop Type HIS ..............................................................................................2-12.2 Console Type HIS ..............................................................................................2-22.3 Operation Keyboard .........................................................................................2-32.4 Multiple and Wide Monitor Support ................................................................2-4
3. Operation and Monitoring Functions ..................................................... 3-13.1 Overall Operation and Monitoring Functions ................................................3-2
3.1.1 Display Layout ...................................................................................3-2
3.1.2 System Message Banner ..................................................................3-3
3.1.3 Browser Bar .......................................................................................3-3
3.1.4 HIS Desktop Area ..............................................................................3-4
3.2 Operation and Monitoring Window .................................................................3-53.2.1 Graphic View with Graphic Attribute ..................................................3-5
3.2.2 Graphic View with Control Attribute ...................................................3-6
3.2.3 Faceplate View (Instrument Faceplates) ........................................... 3-7
3.2.4 Trend View .........................................................................................3-9
3.2.5 Tuning View .....................................................................................3-12
3.2.6 CAMS for HIS Message Monitor .....................................................3-13
3.3 Operation and Monitoring Support Functions ............................................3-163.3.1 Report Function ...............................................................................3-16
3.3.2 Server for Remote Operation and Monitoring Function ..................3-19
3.3.3 CENTUM Desktop ...........................................................................3-19
3.3.4 Security ............................................................................................3-20
3.3.5 HIS Utility .........................................................................................3-24
Toc-2
TI 33K01A11-50E
3.4 Windows for System Administration ............................................................3-263.4.1 System Status Overview ..................................................................3-26
3.4.2 System Alarm View ..........................................................................3-27
3.4.3 FCS Status Display View .................................................................3-28
3.4.4 HIS Status Display View ..................................................................3-29
3.4.5 HIS Setup Window ...........................................................................3-30
Sep. 22, 2011-00
1. Overview of HIS for CENTUM VP 1-1
TI 33K01A11-50E
1. Overview of CENTUM VP HISCENTUM VP introduces a new human interface station (HIS) that let operators to access information more easily, quickly and intuitively. The HIS inherited the excellent operation methods from traditional CENTUM series, and moreover, it adopts an ergonomic design for effective operating and monitoring environments.
F010001E.ai
Figure Example of HIS Window
1.1 Ergonomic Design ConceptThe HIS for CENTUM VP adopts a new design concept “Simple & Intuitive” from the viewpoint of ergonomics. Icons and information allocation based on the above design concept and the latest look-and-feel provide operators with comfortable operation and monitoring environments causing fewer physical and mental burdens on operators.
1.2 Consolidated Alarm Management Software (CAMS for HIS)
Based on the latest alarm management guidelines (*1), Yokogawa developed a Consolidated Alarm Management Software for the process operator in the HIS. This software saves operators from alarm flooding and to deliver only necessary alarms at the right timing. *1: EEMUA (Engineering Equipment and Materials Users Association) No. 191.
Sep. 22, 2011-00
1. Overview of HIS for CENTUM VP 1-2
TI 33K01A11-50E
1.3 Remote Operation and Monitoring Functions
Plants can be operated and monitored from a remote location. Remote operation and monitoring can be made from a general purpose PC in an office far from the central control room.
1.4 Multiple and Wide Monitor SupportOne HIS supports up to four monitors as well as a widescreen LCD (16:10 aspect ratio). The scope of one operator’s responsibility widens, and the amount of information to be processed is increasing. To cope with these demands, the multiple monitors display many pieces of information to improve work effectiveness.
1.5 High-speed Data UpdateData acquisition functions allow display updating as fast as 1 sec. This level of performance is required for manual control of pressure and flow.
1.6 Succession of Operability The same operability as for a conventional HMI, such as touch operations and eight-control-key operation, 64 function keys, and the like, has been achieved. In addition, when operability changes with a CENTUM evolution, such as CAMS for HIS and Multi-window mode, specific functions following the operability are provided.
Sep. 22, 2011-00
2. Hardware 2-1
TI 33K01A11-50E
2. HardwareThe HIS includes two types: a desktop type HIS with a general purpose PC and a operation keyboard, and a console type HIS incorporating a general PC, monitor and operation keyboard in a dedicated console assembly. An operation keyboard is a one-touch operation-based keyboard succeeding conventional HMI operability. One HIS supports up to four monitors.
2.1 Desktop Type HISA desktop type HIS runs on a general purpose PC (IBM PC/AT-compatible machine) with Microsoft Windows installed. The desktop type HIS achieves a simple operation and monitoring environment based on the mouse operation. Moreover, an additional operation keyboard achieves the same operability as a conventional console type HMI excluding partial functions.
Sep. 22, 2011-00
2. Hardware 2-2
TI 33K01A11-50E
2.2 Console Type HISA console type HIS is composed of dual-stacked LCDs, a touch panel function, eight-control-key operation keyboard and auxiliary contact I/Os. A number of console type HISes can be installed in a row. The console type HIS includes two types: an enclosed display style console type provided with a conventional external view, and an open display style console type using LCDs and allowing the selection of monitors and types of keyboards. The following shows external views of a console type HIS.
F020201E.ai
Upper LCD (option)
Operationkeyboard
Mouse (general purpose PC mouse)
Engineering keyboard (general purpose PC keyboard)
Drawer
General purpose PC
Touch panel (option)
LCD
Enclosed display style console assembly
Figure Enclosed Display Style Console Type HIS
Upper LCD (option)
Touch panel (option)
Mouse (general purpose PC mouse)
Drawer
Operation keyboard (option)
Engineering keyboard (general purpose PC keyboard)
Open Display StyleConsole Assembly
General purpose PC
LCD
F020202E.ai
Figure Open Display Style Console Type HIS
Sep. 22, 2011-00
2. Hardware 2-3
TI 33K01A11-50E
2.3 Operation KeyboardThe operation keyboard uses dust- and drip-proof flat keys with a functional key layout based on a one-touch operation. The operation keyboard includes an eight-control-key operation keyboard usable in a console type HIS and a one-control-key operation keyboard usable in a desktop type HIS.
Data entry keys
Mouse
Function keys (64)
Operation confirmation keys
System maintenance panelTuning keysMode Change key
F020301E.ai
Figure Eight-control-key Operation Keyboard
F020302E.ai
Mode Change key
Data entry keys
Function keys (32)
Operation confirmation keys
Tuning keys
Figure One-control-key Operation Keyboard
Sep. 22, 2011-00
2. Hardware 2-4
TI 33K01A11-50E
2.4 Multiple and Wide Monitor SupportOne HIS supports up to four monitors as well as widescreen flat panels (16:10 aspect ratio). Thus the amount of information displayed with one HIS has increased. (*1)*1: The console type HIS supports only conventional type (4:3) monitors up to two monitors at maximum.
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-1
TI 33K01A11-50E
3. Operation and Monitoring FunctionsThis chapter describes typical operation and monitoring functions. The following shows the overall configuration of operation and monitoring functions.
System Message BannerBrowser Bar
Window HierarchyOperation Screen Mode
Plant hierarchyPanel SetCirculate FunctionPrint Screen FunctionsRelated builderShortcut Key
Graphic ViewFaceplate ViewTrend ViewTuning ViewCAMS for HIS Message Monitoring View
Process Alarm ViewMessage Monitoring ViewHelp Window
Operator Guide View
Operation and Monitoring Windows
Graphic AttributeControl AttributeOverview Attribute
Common Functions
Operation and Monitoring Functions
F030001E.ai
System Maintenance FunctionsSystem Status Overview View
FCS Status Display View
BCV Status Display ViewHIS Setup WindowTime Setting Dialog
HIS Status Display View
System Alarm View
Control Status Display WindowsControl Drawing View
Logic Chart View
Device ViewerSFC View
Sequence Table View
Operation and Monitoring Support Functions
Report FunctionRemote Operation and Monitoring Function
Security FunctionsProcess Report View
CENTUM Desktop Environment Customization
Historical Message Report FunctionsLine PrinterAdvanced alarm filterConsolidated Historical Message ViewerVoice messageMultiple-Monitor FunctionFCS Data Setting/Acquisition FunctionsOpen InterfacesRemote Desktop Function
Figure Operation and Monitoring Functions
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-2
TI 33K01A11-50E
3.1 Overall Operation and Monitoring FunctionsThis section provides the following functions getting involved in overall operation and monitoring functions.
• Display layout
• System message banner
• Browser bar
• HIS desktop area
3.1.1 Display LayoutThe HIS display is composed of a system message banner, browser bar and HIS desktop area as shown below.
FI4002 FI4002
XXXXXX XXXXXX
IM500CW RE 11RM
102030405060708090100
ME IFRMGPUMP
ME IFRMGPUMP
FM001
AC1400
TI1501
PM2000
FM002
AM401
A
B
CPELMPS
Tank B trame Procese A trame Geaotine trame
Ready
Tank A trame
NAME
Name Input
OverviewTrend Plant
Search
TG0701TG0801GR0003GR0004GR0005TG0901GR0006GR0007
?
Window Name Input
Call
Default Station Information
View
CommentAddress /SYSTEM/.AL
Process Alarm
PP
SYSTEM
PRODUCT
.AL
.OG
.SO
.SH
.SA
.SF FCS0101
.SF FCS0102.PR
F030101E.ai
Favoritefavorite-1
MYPJT1
03/23/2009 19:06
?Copy
03/23/2009 19:06
TESTUSER
FCS0101 Batch Manager Ready FCS0101 RIGHT Control FCS0101 RIGHT Manual Reset Start17 00
System message banner
HIS desktop areaBrowser barFigure Display Screen
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-3
TI 33K01A11-50E
3.1.2 System Message BannerThe System Message Banner expresses the alarm occurrence status visually. The alarm occurrence status is shown by colors and flashing of operation buttons, and the message display. The System Message Banner is always displayed at the top of the display, so will never be hidden behind other windows.
F030102E.ai
?Copy
511 6
03/23/2009 14:35
TESTUSER
PIC100 Inlet A pressure LO FIC100 Tank B flow rate LL FCS0101 IOM Fail FI01 NODE 01 SLOT 01
AF01
Message display area Date-time display YOKOGAWA symbol mark
System status icon display areaAdvanced alarm filter name display area
User information display area
Figure System Message Banner
3.1.3 Browser BarThe browser bar is used to call up operation and monitoring windows. It can display a list of operation and monitoring windows and plant hierarchical structures in a tree-like fashion, allowing the entire system to be easily confirmed. In addition, if the browser bar is not used, its display can be minimized at the end of the screen.
NAME
Name Input
OverviewTrend Plant
Search
TG0701TG0801GR0003GR0004GR0005TG0901GR0006GR0007
?
Window Name Input
Call
Default Station Information
View
CommentAddress /SYSTEM/.AL
Process Alarm
PP
SYSTEM
PRODUCT
.AL
.OG
.SO
.SH
.SA
.SF FCS0101
.SF FCS0102.PR
F030103E.ai
Favoritefavorite-1
MYPJT1
Update button
Overview toolbox
Preset menu toolbox
Tool button toolbox
Window history toolbox
Name input toolbox
Toolbox
Pin button
Minimize button
Figure Browser Bar
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-4
TI 33K01A11-50E
3.1.4 HIS Desktop AreaThe HIS desktop area displays various operation and monitoring windows. It is composed of the view, frame and container window as shown below.
E030104E.ai
My Computer
My Documents
My Network
Recycle Bin
Internet
Explorer
System Message Banner
View
Frame (tab)
Container Window
Windows Desktop
Bro
wse
r Bar
Figure HIS Desktop Area
ViewMost of the conventional CENTUM operation and monitoring windows such as graphics, trend and tuning windows are handled as views.
FrameThe frame offers a framework to arrange several views for a certain function or purpose. One frame can allocate up to four views. Tabs are attached to the frame; these tabs are displayed side by side if multiple frames are called up. Frames can be brought to the front by clicking on a tab.
Tank B trame Procese A trame Geaotine trameTank A trameOverview
Trend Plant
TG0701TG0801GR0003
View
?Copy
03/23/2009 14:35
TESTUSER
FCS0101 Batch Manager Ready FCS0101 RIGHT Control FCS0101 RIGHT Manual Reset Start17 00
Tab
F030105E.ai
Figure Tabed Browsing
Container WindowThe container window is the outermost HIS display area to be a “board” section on which frames are displayed.
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-5
TI 33K01A11-50E
3.2 Operation and Monitoring WindowThis section describes the following view for process operation and monitoring.
• Graphic view
• Faceplate view (instrument faceplate)
• Tuning view
• “CAMS for HIS” message monitor view
3.2.1 Graphic View with Graphic AttributeThe graphic view with graphic attribute displays plants in a visually easy-to-understand manner using abundant drawing objects. Plant conditions are graphically displayed and can be intuitively operated and monitored. In addition, various windows can be called up from the graphic view.
F030201E.ai
GR0001 Distillation column
LICA48.9
FIC45.7 %
FIC25.4 %
LICA38.9 °C
RC-1023.4 %
TRC49.2 °C
FIC41.4 TDT
53.8 °C
TDA37.5 °C 51.3 °C
PAC
Distillation column Tank1FIC100
TIC301
100.0
0.0
AUTNR
FIC100
100.0
0.0
20.0
40.0
60.0
80.0
PV M3/H 70.0
AUTNR
SV M3/H 50.0MV % 65.0
Columnflow
FIC001
TIC301
Ready
Figure Graphic View with Graphic Attribute
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-6
TI 33K01A11-50E
3.2.2 Graphic View with Control AttributeThe graphic view with control attribute displays function block statuses using instrument faceplates. Instrument faceplates have two different sizes: Up to eight larger size instrument faceplates can be displayed side by side; while up to 16 smaller size instrument faceplates can be displayed side by side. Both sizes of instrument faceplates can be simultaneously displayed as well.
F030202E.ai
GR0001 Distillation column
Ready
LIC301
10.0
0.0
AUTNR
LIC303
10.0
0.0
AUTNR
LIC202
10.0
0.0
AUTNR
LIC204
10.0
0.0
AUTNR
10.0
0.0
LIC100
PV M 7.3
AUTNR
SV M 5.0MV % 65.1
Tank A
100.0
0.0
AIC100
PV % 72.1SV % 63.0MV % 40.0
AUTNR
Agitator A
100.0
0.0
LIC101
PV % 72.1SV % 63.0MV % 40.0
AUTNR
Tank B
100.0
0.0
AJC100
PV % 72.1SV % 63.0MV % 40.0
AUTNR
Agitator BLIC302
10.0
0.0
AUTNR
LIC304
10.0
0.0
AUTNR
LIC203
10.0
0.0
AUTNR
LIC201
10.0
0.0
AUTNR
Figure Graphic View with Control Attribute
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-7
TI 33K01A11-50E
3.2.3 Faceplate View (Instrument Faceplates)The faceplate view allows compact and graphical displays of data values, the mode of function blocks, status of contact inputs, and the like. Some representative faceplate views are shown below.
F030203E.ai
PV DEGC 33.1SV DEGC 33.1MV % 33.1
OPN
CLS
T301 Jackettemp. control
AUTNR AOFCAL
IMAN
ST
Run
0.0
20.0
40.0
60.0
80.0
100.0
1TIC-1301
SV 1
AUTNR
Tank 102 abnormal
1AL-1102
0.0
FV % 0.0
MANOOP
NRIMAN
SV 100.0MV 2
OPE.MARK
100.0
REVERS
DIRECT
STOP
P201 RUN/STOP
1MC-1201
0.0
PV % 40.0
AUTNR
20.0
40.0
60.0
80.0
100.0
Tank liquid level
1LI-1001
MV 30.0
MANNR
OPE.MARK
0.0
20.0
40.0
60.0
80.0
100.0
Flow control valve
1MLD-100
Manipulated Variable (MV) value
Engineering Unit Symbol
Instrument faceplate scale high limit
Instrument faceplate scale low limitLow-low limit alarm setting (red)
High-high limit alarm setting (red)
Low limit alarm setting (green)
Setpoint value (SV) pointer
High limit alarm setting (green)
Setpoint value (SV)
Cascade mark CMP (computer) markSelf-tuning markBlock statusCalibration status Alarm OFF status
Operation mark/comment
Output value index
Output value index
Open/close mark
Tag name
Manipulated output value (MV) pointer
Manipulated output value limit bar
Process Variable (PV) bar
Open/close mark
Tag commentTag mark
Block modeAlarm status
Data item namesProcess Variable (PV) value
Process Variable (PV) value
Instrument faceplate scale
Process Variable(PV) bar
Tag nameTag comment
Tag mark
Block mode/block statusAlarm status
Figure PVI Input Indicator BlockFigure PID Controller Block
Manipulated Variable(MV) valueInstrument faceplate scale
Operation mark/comment
Output value index
Output value index
Manipulated output value (MV) pointer
Tag nameTag comment
Block mode/block statusAlarm status
Figure MLD Manual Loader Block
Feedback input scale
Manipulated Variable (MV) value
Setpoint value (SV)
Feedback input value(FV)
Setpoint (SV) pointerFeedback input high limit alarm setting
Feedback input low limit alarm setting
Feedback input value (FV)Operation mark/
comment
Manipulated output value (MV)
Instrumentfaceplate label
Answerback value
Operation inhibit frame
Tag nameTag comment
Tag markBlock mode/block statusAlarm status
Figure MC-2 Two-Position Motor Control Block
Tag nameTag comment
Tag mark
Block mode/block statusAlarm status
Representative alarm processing enabled
Figure ALM-R Representative Alarm Block
Tag mark
Figure SIO-12 Switch Instrument Block with 1 Input, 2 Outputs
PV 2
MV 2
MANNR
NR
STOP
START
PAUSE
V102 open-shut command
2XV-0921
Manipulated output value (MV)
Operation inhibit frame
Answerback value (PV)
Instrument faceplate label
Answerback value
Manipulated output value (MV)
Tag nameTag comment
Tag mark
Block mode/block statusAlarm status
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-8
TI 33K01A11-50E
MANNR
OPE.MARK
1
16
START
HALT
STOP
Phase display2BSI-1001
Load(reactor)Heat(phase)
MANNR
START
END
SUSPEND
RESTART
PAUSE
P200 Lo-pPump
2P-1200
0
2
1
SW 2
3
Flow switch1SW-1001
1FC-1102
PV % 60.0SV % 60.0MV % 50.0
F102 flow ctl valve
MANNR
OPE.MARK
0.0
20.0
40.0
60.0
80.0
100.0ENDSTART
END
SUSPEND
RESTART
PAUSE
STIME 1000 300
AUTNR
RUN
T311 reaction time
1TM-1311
Instrument faceplatelabel
Operation mark/comment
Phase name
Scale high limit
Scale low limit
Phase switchStatus display
Operation inhibit frame
Tag nameTag comment
Tag mark
Block mode/block statusAlarm status
Tag nameTag comment
Tag mark
Block mode/block statusAlarm status
Switch position (SW)
Instrument faceplate label
Switch position
Tag name
Tag commentTag mark
Timer settingTimer elapsed time
Tag nameTag comment
Tag mark
Block mode/block statusAlarm status
Figure BSI Batch Status Indicator Block
Figure SW-33 Three-Pole Three-Position Selector Switch Block
Figure TM Timer Block
Instrument faceplate label
Operation inhibit frame
Manipulated Variable (MV) value
Setpoint value(SV)
Process Variable(PV) value
Instrument faceplate labelOperation inhibit frame
Operation mark/comment
Instrument faceplate scale
Setpoint (SV) pointer
Manipulated output bar(MV) pointer
Process Variable (PV) bar
Tag nameTag comment
Block mode/block statusAlarm status
Figure PBS5C Extended 5-Push-Button Switch Block
Figure HAS3C Extended Hybrid Manual Station Block
F030204E.ai
Tag mark
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-9
TI 33K01A11-50E
3.2.4 Trend ViewThe trend view graphically displays various process data changes with time. Time-series changes in the process data are called trend data. The trend view allows the selection and display of up to eight pens from multiple trend display modes. In addition, trend data of different sampling periods can be displayed on one trend view. Moreover, the trend data can be easily used in other applications.
13:3403/23/2009
●●●●●●●●
□□□□□□□□
Tag Name
13:36 13:38 13:4003/23/2009
13:42 13:44
82.3
62.3
42.3
22.3
2.3
VP.100
CIF
102.3
Tag Comment Value Unit Lower Upper
Gathering 00:12:00 100%
FIC001. PVFIC002. PVLIC100. PVTIC100. PVTIC200. PV
12345678
Inlet flowOutlet flowLevelTemp ATemp B
M3/hM3/hMDEGCDEGC
0.00.00.00.00.0
100.0100.0100.0100.0100.0
72.153.33.8
25.714.1
TG1001 Block:10 Group:011
2
F030205E.ai
Figure Trend View
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-10
TI 33K01A11-50E
Trend Display ModeIn addition to normal trend graph display, trend graphs can be tiled. The normal display mode displays the data of eight pens in one graph. The tile trend modes tiles and displays separately for each pen or data type.The following shows three types of the tile trend modes.
• Pen Split Display
13:0103/23/2009
13:00
A001.PV1 A001.PV2 A001.PV3 A002.PV3 SW01.PV1 SW01.PV1
50.00
0.00
150.00100.00
50.00
0.00
13:02 13:03 13:0403/23/2009
13:05
TG0201 Block:02 Group:01
F030206E.ai
Figure Pen Split Display
• Analog/Discrete Split Display
F030207E.ai
13:0103/23/2009
13:00
A001.PV1 A001.PV2 A001.PV3 A002.PV3 SW01.PV1 SW01.PV1
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
13:02 13:03 13:0403/23/2009
13:05
TG0201 Block:02 Group:01
Figure Analog/Discrete Split Display
• Trend Data/Reference Pattern Split DisplayTG0201 Block:02 Group:01
20:29 20:3003/23/2009
10:25 10:2603/23/2009
10:27 10:28 10:2903/23/2009
10:30
20:31 20:32 20:3303/23/2009
20:34
500.0400.0300.0200.0100.0
0.0
500.0400.0300.0200.0100.0
0.0
Tag Name Tag Comment Value Unit Lower Upper
Tag Name Tag Comment Value Unit Lower Upper
●●●
FC05.SVFC05.MVFC05.PV
123
KL/h%KL/h
0.00.00.0
500.0100.0500.0
480.0191.0142.5
●●●
BL01.SVFC01.MVFC02.PV
134
KL/hKL/hKL/h
0.00.00.0
500.0500.0500.0
480.0195.5146.6
□□□
□□□
F030208E.ai
Figure Reference Pattern Split Display
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-11
TI 33K01A11-50E
Clipboard CopyImages and numeric data on a graph displayed in the trend view can easily be used in other applications by Copy & Paste operation of Windows.
• Trend view image copy to clipboard Copies trend view display images. The displayed contents, except the window pane, are copied.
• Trend data copy to clipboard Copies trend data values displayed in the trend view to the clipboard. Data copied to the clipboard can be used in spreadsheet application software. The following Information is copied: For each trend pen: the number of data points, tag name, data item, tag comment, low-limit value, high-limit value, number of decimal point digits, and engineering unit, For each data points: date and time, data value, and data status.
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-12
TI 33K01A11-50E
3.2.5 Tuning ViewA tuning view displays the tuning parameters and tuning trend of each instrument. The display magnification of the tuning trend time and data axes can be changed.
FIC100 TUN Tank inlet flow
CAL RAW
Ready
14:02 14:03 14:04 14:05 14:06
FIC100 Tank inlet flow
SH : 100.0 HH = 100.0 MH = 100.0SL : 0.0 PH = 100.0 ML = 0.0PV = 63.2 M3/H PL = 0.0 P = 100.0SV = 30.0 M3/H LL = 0.0 I = 20.0MV = 20.1 % VL = 100.0 D = 0.0DV : 33.2 DL = 100.0 GW = 0.0SUM : 0 SVH = 100.0 DB = 0.0
100.0
0.0
20.0
40.0
60.0
80.0
MANNR
PV M3/H 63.2SV M3/H 30.0MV % 20.1
MODE = MAN ALRM : NR
FIC100Tankinlet flow
F030209E.ai
100%00:07
Figure Tuning View
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-13
TI 33K01A11-50E
3.2.6 CAMS for HIS Message MonitorThe CAMS for HIS (Consolidated Alarm Management Software for HIS) message monitor displays consolidated alarms and events from various systems. Setting filter conditions allows the selection and display of necessary alarms and events only. In addition, value-added information can be displayed to help take action for alarms quickly and accurately.
CAMS for HIS : Message MonitorFile Edit View Operation Tools
Filter
All Filters Favorites
ShelvingShelf 01(2/7/11/1)Continuous_test 16:59
1 day 6 hr 30 min
1 hr
4 hr
Shelf 02(3/8/15/0)Auto_test1h Shelving(3/5/7/2)OneShot_1h_test4h Shelving(7/2/13/3)OneShot_4h_test
USER1SIS
PRM
Shift01
Shift02
SystemProcess
ProcessOperator Guide
--
System
10/22/2010 2:36:53 PM 2FIC1204.HI 2FIC1204 Flow Lower LineB UnitE PV = 50.0 KM3/H HI Recover10/22/2010 2:36:53 PM 2FIC1203.HI 2FIC1203 Flow Lower LineB UnitE PV = 50.0 KM3/H HI Recover10/22/2010 2:36:53 PM 2FIC1202.HI 2FIC1202 Flow Lower LineB UnitE PV = 50.0 KM3/H HI Recover10/22/2010 2:36:53 PM 2FIC1201.HI 2FIC1201 Flow Lower LineB UnitE PV = 50.0 KM3/H HI Recover10/22/2010 2:36:53 PM 1FIC1205.LO 1FIC1205 Flow Upper LineA UnitB PV = 50.0 KM3/H LO Recover10/22/2010 2:36:53 PM 1FIC1204.LO 1FIC1204 Flow Upper LineA UnitB PV = 50.0 KM3/H LO Recover10/22/2010 2:36:53 PM 1FIC1203.LO 1FIC1203 Flow Upper LineA UnitB PV = 50.0 KM3/H LO Recover10/22/2010 2:36:53 PM 1FIC1202.LO 1FIC1202 Flow Upper LineA UnitB PV = 50.0 KM3/H LO Recover10/22/2010 2:36:53 PM 1FIC1201.LO 1FIC1201 Flow Upper LineA UnitB PV = 50.0 KM3/H LO Recover10/22/2010 2:36:51 PM 2FIC1205.HI 2FIC1205 Flow Lower LineB UnitE PV = 68.9 KM3/H HI10/22/2010 2:36:53 PM 2FIC1204.HI 2FIC1204 Flow Lower LineB UnitE PV = 68.9 KM3/H HI10/22/2010 2:36:51 PM 2FIC1203.HI 2FIC1203 Flow Lower LineB UnitE PV = 68.9 KM3/H HI10/22/2010 2:36:51 PM 2FIC1202.HI 2FIC1202 Flow Lower LineB UnitE PV = 68.9 KM3/H HI10/22/2010 2:36:51 PM 2FIC1201.HI 2FIC1201 Flow Lower LineB UnitE PV = 68.9 KM3/H HI
Date Source Message
□10/22/2010 2:36:53 PM 2FIC1201.HI 2FIC1201 Flow Lower LineB UnitE PV = 50.0 KM3/H HI Recover□10/22/2010 2:36:53 PM 1FIC1205.LO 1FIC1205 Flow Upper LineA UnitB PV = 50.0 KM3/H LO Recover□10/22/2010 2:36:53 PM 1FIC1204.LO 1FIC1204 Flow Upper LineA UnitB PV = 50.0 KM3/H LO Recover□10/22/2010 2:36:53 PM 1FIC1203.LO 1FIC1203 Flow Upper LineA UnitB PV = 50.0 KM3/H LO Recover□10/22/2010 2:36:53 PM 1FIC1202.LO 1FIC1202 Flow Upper LineA UnitB PV = 50.0 KM3/H LO Recover□10/22/2010 2:36:53 PM 1FIC1201.LO 1FIC1201 Flow Upper LineA UnitB PV = 50.0 KM3/H LO Recover■10/22/2010 2:36:51 PM 2FIC1205.HI 2FIC1205 Flow Lower LineB UnitE PV = 68.9 KM3/H HI 10/22/2010 2:36:51 PM 2FIC1205.LO 2FIC1205 Flow Lower LineB UnitE PV = 68.9 KM3/H LO Recover 10/22/2010 2:36:51 PM 2FIC1205.LL 2FIC1205 Flow Lower LineB UnitE PV = 68.9 KM3/H LL Recover■10/22/2010 2:36:53 PM 2FIC1204.HI 2FIC1204 Flow Lower LineB UnitE PV = 68.9 KM3/H HI 10/22/2010 2:36:51 PM 2FIC1204.LO 2FIC1204 Flow Lower LineB UnitE PV = 68.9 KM3/H LO Recover 10/22/2010 2:36:51 PM 2FIC1204.LL 2FIC1204 Flow Lower LineB UnitE PV = 68.9 KM3/H LL Recover■10/22/2010 2:36:51 PM 2FIC1203.HI 2FIC1203 Flow Lower LineB UnitE PV = 68.9 KM3/H HI 10/22/2010 2:36:51 PM 2FIC1203.LO 2FIC1203 Flow Lower LineB UnitE PV = 68.9 KM3/H LO Recover
Date Source Message
F030210E.ai
Shelves Pane
Filters Pane
Dynamic Filters Pane
Detail Pane
Alarm & EventMessage Pane
Alarm & EventBrowser Pane
Figure CAMS for HIS Message Monitor
Consolidation of Alarms and EventsThe CAMS for HIS message monitor displays consolidated CENTUM VP process alarms, system alarms, and operator guide messages on one screen. In addition, Safety Instrumented System ProSafe-RS, Network-based Control Systems STARDOM, and Field Device Management Package (PRM) alarms and events are also consolidated and displayed.
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-14
TI 33K01A11-50E
Displaying Only Alarms and Events RequiredCAMS for HIS provides many functions to deliver the necessary alarms and events to the right person at the right time.
• Filtering/Sorting Alarm messages can be filtered and sorted using basic filters and user-defined filters. Basic filters such as a process alarm filter or a plant-hierarchy filter can be used without configuration. Filters unique to individual users can be defined, and temporary filters can also be created flexibly.
• Eclipsing Alarms and events that are activated repeatedly by the same tag can be integrated and displayed on a single line. Reducing the number of alarm messages displayed on the window will allow operators to reach the critical alarms more quickly and easily.
• Shelving Unnecessary or nuisance alarms can be moved to a temporary area called a shelf in order to “hide” alarms due to special circumstances. Individual unnecessary alarms can be manually moved to the shelf. Chattering alarms or alarms that match user-defined conditions can be automatically moved to the shelf.
• Load Shedding If too many alarms are generated in a short period of time due to an unexpected event, predefined filters can be automatically activated to reduce the operators’ monitoring load.
Sorting out Alarms and Adding Value-added InformationVarious identifiers for sorting alarms can be defined. In addition, various types of value-added information can be defined for alarms to help users take role-based action for alarms quickly and accurately.
• Examples of identifiers for providing only necessary alarms Purpose of monitoring (safety, environmental protection, economic efficiency)
• Examples of identifiers for providing an alarm only to the persons who need it Target user or user group
• Examples of identifiers for providing an alarm at the right time Allowed response time (urgent, quick, routine), desired degree of consequence (very large, large, medium, small), alarm priority (critical, high, medium, low, logging, reference)
• Examples of value-added information Root cause of alarm occurrence, role-based action to be taken, previous action procedures
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-15
TI 33K01A11-50E
Alarm Setpoint Management FunctionAn alarm setpoint is a threshold value for triggering an alarm. For an instance, the HH or PH is a setting item of alarm setpoint in a function block. When a plant is running, if the alarm setpoints are not proper, the process alarms may become either excessive or insufficient that the important abnormality may be ignored or delayed, or even resulted into a serious consequence. For safely operating a plant, the alarm setpoints must be properly defined and managed.
CAMS for HIS provides an alarm setpoint management function which consists of the following features:
• Values of the alarm setpoint that engineers set during the system engineering stage are saved as the master setpoints.
• The alarm setpoint management function compares the setpoint values between the master and the current ones, and displays the discrepancies.
• A current setpoint can be overwritten by the master setpoint, if necessary.
• A current setpoint values can be used to set the master setpoint value, if necessary.
CAMS for HIS Alarm builder
Alarm setpoint difference window
Downloading
Define master alarm setpoint values
Get master alarm setpoint values
Get current alarm setpoint values
Master alarm setpoint values
Master alarm setpoint values
Save discrepant alarm setpoints
Transfer current alarm setpoint values to overwrite the master alarm setpoint values
Transfer master alarm setpoint values to overwrite the current alarm setpoint values
HISENG FCS
Compare master and current alarm setpoint values and display discrepancies
Result of comparingthe alarm setpoints
Current alarm setpoint values
F030211E.ai
Figure Alarm Setpoint Management of CAMS for HIS
The alarm master setpoint values are defined on the CAMS for HIS alarm builder. Once the defined master setpoint values are downloaded to the HIS, the differences between the master and the current setpoint values are displayed.
Long-Term Data ArchiveFrom CENTUM VP release 5, CAMS for HIS historical data can be saved to the long-term data archive which can be referred to by the CAMS for HIS historical viewer.
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-16
TI 33K01A11-50E
3.3 Operation and Monitoring Support Functions
This section describes the following functions supporting operation and monitoring.• Report function
• Remote operation and monitoring server function
• CENTUM desktop
• Security
3.3.1 Report FunctionDaily and monthly reports can be created using the report function. Microsoft Excel is used as the application tool. A report form of daily and monthly reports can be used for report templates. Users can also create new template from scratch. Data that can be read to the report are shown below.
• Closing data (average values, totals, maximums, minimums, etc.)
• Trend data
• Historical message
• Tag information
• Process data (instantaneous value)
• Batch data
The following shows an example of a daily report. The daily report can be created by setting the necessary tag names and process data.
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-17
TI 33K01A11-50E
XXXXXX Daily Report
Flow1 Flow2 Flow3 Total Total
FIC100 FIC200 FIC300 FIC400 FIC500
PV PV PV SUM SUM
m3/h m3/h m3/h m3 m3
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
000.0 000.0 000.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
00.0 00.0 00.0 00000.0 00000.0
Temp.1
TIC100
PV
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
Temp.2
TIC200
PV
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
Temp.3
DEGC DEGC DEGC
TIC300
PV
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
00.0
F030301E.ai
Date : yyyy/mm /dd
00:00
01:00
02:00
03:00
04:00
05:00
06:00
07:00
08:00
09:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
Ave.
Total
Max.
Min.
00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00Time for Max.
00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00Time for Min.
Figure Example of Daily Report Form
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-18
TI 33K01A11-50E
Printout StartPrintout start methods are shown:
• Automatic printout of pre-selected intervals/specific time
• Automatic printout when sequence messages are received
• Manual printout when a function key (on the operation keyboard) is pressed
• Manual printout when a button on the graphic view is clicked
• Manual printout from Microsoft Excel
• Printout started from the application program (using Visual Basic)
Report Printout from Another PCA report printout is possible using Microsoft Excel on another PC connected to the network.
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-19
TI 33K01A11-50E
3.3.2 Server for Remote Operation and Monitoring FunctionThe server for remote operation and monitoring function allows plant operation and monitoring as well as engineering from a remote PC. Plant operation and monitoring can be made from a remote PC far away from the central control room using the same windows as in HIS, except for some functions.
Client PCSite
CENTUM VP
Control Network
Central control room
Office building
Client PC
Intranet
Server for Remote Operationand Monitoring
F030302E.ai
Ethernet
03/31/2008 19:06
?Copy
2008/03/03 14:35
TESTUSER
FCS0101 Batch Manager Ready FCS0101 RIGHT Control FCS0101 RIGHT Manual Reset Start17 00
NAME
Name Input
OverviewTrend Plant
Search
TG0701TG0801GR0003GR0004GR0005TG0901GR0006GR0007
?
Window Name Input
Call
Default Station Information
View
CommentAddress /SYSTEM/.AL
Process Alarm
PP
SYSTEM
PRODUCT
.AL
.OG
.SO
.SH
.SA
.SF FCS0101
.SF FCS0102.PR
Favoritefavorite-1
MYPJT1
Tank B trame Procese A trame Geaotine trame
Ready
Tank A trame
FI4002 FI4002
XXXXXX XXXXXX
IM500CW RE 11RM
102030405060708090100
ME IFRMGPUMP
ME IFRMGPUMP
FM001
AC1400
TI1501
PM2000
FM002
AM401
A
B
CPELMPS
LICA48.9
FIC45.7 %
FIC25.4 %
LICA38.9 ?
TRC49.2 °C
FIC41.4 %
TDT53.8 °C
TDA37.5 °C 51.3 °C
PAC
Distillation column
100.0
0.0
20.0
40.0
60.0
80.0
Reactorflow
AUTNRPV
SV
MV
FIC200
FIC001
GR001 Distilation Column .AL Process Alarm
?Copy
2008/03/03 14:35
TESTUSER
FCS0101 Batch Manager Ready FCS0101 RIGHT Control FCS0101 RIGHT Manual Reset Start17 00
NAME
Name Input
OverviewTrend Plant
Search
TG0701TG0801GR0003GR0004GR0005TG0901GR0006GR0007
?
Window Name InputCall
Default Station Information
View
CommentAddress /SYSTEM/.AL
Process Alarm
Favorite
PP
SYSTEM
PRODUCT
.AL
.OG
.SO
.SH
.SA
.SF FCS0101
.SF FCS0102.PR
03/31/2008 19:06
Ready
M3/H55.3
M3/H50.0
%65.1
favorite-1MYPJT1
Figure Example of Remote Operation and Monitoring
3.3.3 CENTUM DesktopThe CENTUM desktop is dedicated to HIS operation of CENTUM VP. It provides an optimum operation and monitoring environment by restraining standard Windows functions unnecessary for operation and monitoring.
Restrained Items• All icons (My Computer, Recycle Bin, etc.) on the desktop are hidden.
• Unnecessary items (Explorer, shutdown, etc.) in the Start menu are hidden.
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-20
TI 33K01A11-50E
3.3.4 SecurityThe security settings of CENTUM VP can be categorized into two functions: one is the CENTUM specific security function; and the other is the IT security function based on Windows security feature.
CENTUM Specific Security FunctionThe security function help prevent illegal operations and other problems and ensure the safety of the system. The security function restricts the scope of operation and monitoring permitted for an operator, and masks certain alarms of which the operator need not be notified.
Overview of Security FunctionsWhen the operator log on, the scope of operation and monitoring and the permission are specified. In addition, security can be defined for each function block and each window. Moreover, advanced security functions, such as an automatic user-out, can be set. In the operation and monitoring functions, operators have three attributes, including:
• User name The attribute to identify the user
• User group The attribute to decide the scope of operation and monitoring
• User Permission The attribute to decide the authority for operation and monitoring
The following shows the flow of security functions.
Check operation and monitoring
scope
Check user name
Check operation and monitoring
permission
Invalid operation
Operation history
• Function block operation and monitoring• Window operation and monitoring• Operation and monitoring of received messages
F030303E.ai
Operator
User inUser group
Invalid operation Invalid operation
OK OK OK
NG NG NG
User permission
Figure Flow of Security Functions
User nameThis is a user-specific user name which uniquely determines who the operator is. Historical (operation) logging and the like will include this user name. A password is associated with each user name.
User GroupThe user group which the user belongs to determines the scope of operation and monitoring functions that can be performed. The user group determines which FCS can be monitored, which FCS can be operated, and which windows can be displayed. You can restrict the items which can be monitored and operated by specifying the corresponding station name and drawing name, for example. You can specify certain groups in certain plants, for example.
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-21
TI 33K01A11-50E
User PermissionYou can subdivide a user group into several levels of user permission (restriction): ordinary operator, senior operator, engineering personal, etc. The default is three such levels – S1, S2, and S3 – per user group. The default user permissions for these three levels are as shown below. User-defined user permissions U1 to U7 are also possible.
Table Standard User Permissions
Permission level Monitoring Operation EngineeringS1 Yes No No
S2 Yes Yes No
S3 Yes Yes Yes
U1 to U7 Set by user
Yes: enabledNo: disabled
Security on a Per-Function-Block BasisYou can require confirmation when setting data in important function blocks, to prevent inadvertent data entry. Using operation marks, you can also change temporarily the operations are available or not.For each individual function block, you can specify:
• User restrictions User restrictions on changing settings such as SV, MV or alarms
• Confirmation of settings The need for confirmation of settings (to help prevent errors)
• Alarm processing The type of alarm (blinking, need for acknowledgment, repeat alarms)
• Tag mark The tag mark corresponding to an individual function block can also be specified by the user, to indicate tag importance (priority).
Table Tag Mark
Tag priority Tag mark
Important tag
Ordinary tag
Auxiliary tag 1
Auxiliary tag 2
Window-based SecurityThe operation and monitoring authority can be set for each window/view. By setting the operation and monitoring authority on graphic views, changing the instrument faceplate assignment or acknowledging of alarm blinking can be prohibited. On the trend view, the change of trend pens assignment and the start/stop of batch trends can be prohibited. On the HIS setup window, the change of function key assignment definition can also be prohibited.
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-22
TI 33K01A11-50E
Advanced SecurityAdvanced security is provided to block password leaks and to prevent illegal access and other problems.
• User Lockout The logon attempts with invalid password and user name are monitored. If the attempts are continued for number of times, a system alarm message is initiated to alert for the illegal access. It is possible to lock out the user who attempted logon as an illegal user.
• Password Expiration You can set the expiration period of password. 14 days before the expiration date of a password, a message notifying that the password will soon expire is displayed.
• Prohibiting Using Previously Used Passwords You can make settings so that a user cannot specify the same character string as a previously used password when the user changes the password.
• Automatic User-Out If the keyboard or the mouse has not been touched for a designated time period, the user is automatically user-out.
IT Security FunctionThe IT security function strengthens security for CENTUM VP. CENTUM VP IT environment is hardened by using Windows security functions. For example, by using the Windows access control for users and user groups, accesses to CENTUM VP tools and file folders can be managed. It can be used as a security countermeasure when a person logs in to the PC by Windows user for operator, he can access to the operator displays and tools but not for engineering tools. By Windows Firewall or DCOM setting, it restricts the communication types and communication ports.
IT Security SettingCENTUM VP supports the IT security setting using Windows security function. By defining the IT security setting, it hardens the computer and protects it from cyber threats. In Yokogawa system products, cyber threats are categorized as follows:
(1) Network attacks(2) Direct attacks by manipulating computer components (*1)(3) Theft of computer components (*1) or important data
*1: The computer component means a Microsoft Windows computer-based Yokogawa system product such as HIS, ENG, and etc.
Three different security models are available to handle these threats. These models flexibly support different system configurations and operations.
Table Security models
Model Feature
Legacy model The security is not strengthened. It prioritizes collaboration with legacy products and the products where IT security is not applied.
Standard model This model focuses on the operations of the relevant systems and collaboration with other systems. It complies with the threats described in the above (1) and (2).
Strengthened model This model counters all the three threats stated above. (*1)
The table below shows the relationship between the above security model and corresponding countermeasures.*1: For more information about setting the strengthened model, please contact Yokogawa sales department.
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-23
TI 33K01A11-50E Sep. 22, 2011-00
Table Security measures
Security type Security measureSecurity model
Legacy Standard StrengthenedAccess control Yes YesPersonal firewall tuning Yes YesStop unused Windows services Yes
Change IT environment settings
Change Administrator’s user name YesHide last logon user name Yes Yes YesApply software restriction policies Yes YesRestriction on AutoRun Yes Yes YesApply StorageDevicePolicies function Yes YesDisable USB storage devices Yes YesDisable NetBIOS over TCP/IP Yes YesChange LAN Manager authentication level Yes YesApply the password policy YesApply the audit policy YesApply the account lockout policy YesHDD password function by BIOS Yes (*1)
CENTUM VP provides a tool that configures the security settings automatically in accordance with the security models. Follow the guide and perform manual configuration for a product without the tool, or models that the tool do not support.*1: Manual setting is available as the tool is not applicable to set this function.
Windows Authentication ModeWindows authentication mode is made of collaborating the CENTUM specific security function and the IT security function. For previous CENTUM systems, users are defined within the CENTUM operation and monitoring functions independently from the Windows user accounts, and access limitations are applied to them. (CENTUM authentication mode)By using the Windows authentication mode, the Windows accounts and the operation and monitoring users can be integrated, and ensure a secure system within the Windows user management framework. The centralized user management enables the Windows domain configuration, which significantly improves the system usability.
Single Sign OnThe Windows authentication mode provides the following two methods for making HIS available by performing user authentication only once.
• Windows Type Single Sign On If a user logs in from the Windows logon dialog box, the user automatically proceeds to the state of user-in to HIS.
• HIS Type Single Sign On When a PC is started, the user is automatically logged onto Windows, HIS is started with least right (OFFUSER), and the user is placed in the user-out state.
3. Operation and Monitoring Functions 3-24
TI 33K01A11-50E Sep. 22, 2011-00
3.3.5 HIS UtilityThe HIS utility sets the HIS operational environment such as the users and securities to start the HIS. The text below explains the items that can be set on HIS Utility.
OK Cancel
User Environment Settings
You need to logoff and logon.
User Action Security CAMS for HIS OPC
Setting
HIS Utility
F030308E.ai
Figure HIS Utility - User Tab
In the HIS utility window, items for setting are listed by the tabs as described below.
User TabUsers are added or deleted from the user tab. user-specific setting can be defined as the following settings.
• Automatic Logon (*1)
• CENTUM Desktop
• HIS Start*1: Only when the CENTUM authentication mode is applied.
Action TabOperation keyboard, mouse operation and other settings can be performed.
• Configuration Operation Keyboard
• INC/DEC Operation Mode Using Mouse
• Trend Acquisition Pen Assignment
3. Operation and Monitoring Functions 3-25
TI 33K01A11-50E
Security TabThe HIS security polices can be set.
CAMS for HIS TabThe items specific to the Consolidated Alarm Management Software for HIS can be set.
HIS-TSE TabThe items specific to the Server for Remote Operation and Monitoring Function can be set. This tab is only displayed when the Server for Remote Operation and Monitoring Function package (LHS1150 or LHM1150) is activated in the computer.
OPC TabThis tab defines specific settings for the Exaopc OPC interface package (for HIS).
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-26
TI 33K01A11-50E Sep. 22, 2011-00
3.4 Windows for System AdministrationCENTUM VP has the windows for displaying the abnormalities of the running system and the windows for user’s convenience and customization. These windows are explained below.
3.4.1 System Status OverviewThe System Status Overview displays the statuses of all stations and the communication devices within the domain in a list (*1). The outline of the System Status Overview will be introduced below.
*1: A domain includes all the stations connected with one segment of control buses. The control bus here means V net or Vnet/IP. When connecting V net to one of our system with a control bus other than V net or Vnet/IP by using Bus Converter (BCV), a virtual V net domain can be defined.
.SO System Status Overview
Ready
FCS0101 FCS0103FCS0102 FCS0104 FCS0105 FCS0106
MYPJT Domain : 01 V net1 V net2
liaF
liaF
HIS0121 HIS0122 HIS0123 HIS0124
FCS
IOM FCS
ACG0109 BCVV0111ACG0110 BCVV0112
HIS0119 HIS0120
F030401E.ai
Figure System Status Overview
The System Status Overview displays the statuses of all stations and the communication devices within the domain in details by various icons. From here, the windows of system maintenance can be called up.
3. Operation and Monitoring Functions 3-27
TI 33K01A11-50E Sep. 22, 2011-00
3.4.2 System Alarm ViewThe System Alarm view (*1) is an overview that displays the system alarm messages to notify the user of system hardware errors (FCS fail, module error, etc.) and communication errors.*1: When the CAMS for HIS is valid, the system alarm view become the CAMS for HIS message monitor.
26/77Range: All
1 0823 01/14 03:20:01 Printer EPSON MJ-930C Offline 2 0502 01/14 02:31:02 DataBase Equalize Complete 3 0510 01/14 02:30:57 Data Base Download from YOKOGAWA File = ClsDef.odb 4 0510 01/14 02:30:57 Data Base Download from YOKOGAWA File = TrDspAssign.odb 5 0510 01/14 02:30:57 Data Base Download from YOKOGAWA File = TrAssign.odb 6 0502 01/14 02:29:33 DataBase Equalize Complete 7 0510 01/14 02:29:23 Data Base Download from YOKOGAWA File = ClsMng.odb 8 0510 01/14 02:29:23 Data Base Download from YOKOGAWA File = TrDef.odb 9 0823 01/12 09:50:03 Printer EPSON MJ-930C Offline 10 0502 01/12 09:28:46 DataBase Equalize Complete 11 0510 01/12 09:28:37 Data Base Download from YOKOGAWA File = OGAR010101.odb 12 0510 01/12 09:28:37 Data Base Download from YOKOGAWA File = SDAR010101.odb 13 0510 01/12 09:28:37 Data Base Download from YOKOGAWA File = Inst0357.odb 14 0510 01/12 09:28:37 Data Base Download from YOKOGAWA File = TFAR010101.odb 15 0510 01/12 09:28:37 Data Base Download from YOKOGAWA File = TFFCS0101.odb 16 0471 01/12 09:28:28 FCS0101 Online Download Complete 17 0502 01/09 06:29:46 DataBase Equalize Complete 18 0510 01/09 06:29:41 Data Base Download from YOKOGAWA File = OPSBL1.dsp 19 0510 01/09 06:29:41 Data Base Download from YOKOGAWA File = UTSW1.dsp 20 0510 01/09 06:29:41 Data Base Download from YOKOGAWA File = OPSFC1.dsp 21 0510 01/09 06:29:41 Data Base Download from YOKOGAWA File = SFCSW1.dsp 22 0510 01/09 06:29:41 Data Base Download from YOKOGAWA File = OGAR010101.odb 23 0510 01/09 06:29:41 Data Base Download from YOKOGAWA File = SDAR010101.odb 24 0510 01/09 06:29:41 Data Base Download from YOKOGAWA File = Inst0357.odb 25 0510 01/09 06:29:40 Data Base Download from YOKOGAWA File = TFAR010101.odb 26 0510 01/09 06:29:40 Data Base Download from YOKOGAWA File = TFFCS0101.odb
F030402E.ai
.SA System Alarm Message
Ready
HELP
Figure System Alarm View
The System Alarm view displays system alarm messages in the order with the most recent ones first. When an alarm occurs, the alarm starts to buzz, and at the same time the button in the System Message banner and the LED for the key on the operation keyboard begin to flash to notify the operator.
3. Operation and Monitoring Functions 3-28
TI 33K01A11-50E Sep. 22, 2011-00
3.4.3 FCS Status Display ViewFCS Status Display view is for displaying the FCS hardware configurations and FCS running status.
01
PSU PSU
FCS0101Distillation column AStation No : 1 Type : AFV40D
Revision : R5.01.00Generation : 09/22/2011 8:30
CPU Idle Time : 58secComm Load Ave : 0%
Cur : 0%Test Mode : OFFControlStatus : RUN
Comm I/O : ON
TEMP CPU ( L, R ) FCU Battery ( L, R )Battery ( L, R )HKURDY ( L, R )
.SF FCS0101 Station Status Display
Ready
MAN
UPC
UPC
USP
USP
Not ReadyStand-ByControlHard ReadyMaintenance
MYPJT Domain : 01 Vnet/IP1 Vnet/IP2
FCS
IOM FCS
12
1 2
COM
PSU
COM
02COM
PSU PSU
COM
03COM
PSU PSU
COM
04COM
PSU PSU
COM
05COM
PSU PSU
COM
06COM
PSU PSU
COM
07COM
PSU PSU
COM
08
PSU
COM
09COM
PSU PSU
COM
10COM
PSU PSU
COM
11COM
PSU PSU
COM
12COM
PSU PSU
COM
13COM
PSU PSU
COM
14COM
PSU PSU
1 CPU_CB 2 NODE_CB 3 TB_CB 4 TB_CB 5 NODE_CB 6 TB_CB 7 TB_CB 8 CB0201 9 NODE_CB HKBusTEMPFANPSU RPSU LTB_PSU RTB_PSU L
HKBus TEMP FAN PSU R PSU LTB_PSU RTB_PSU L
HKBus TEMP FAN PSU R PSU L TB_PSU R TB_PSU L
HKBus TEMP FANPSU RPSU L TB_PSU R TB_PSU L
HKBusTEMPFANPSU RPSU LTB_PSU RTB_PSU L
HKBusTEMPFANPSU RPSU LTB_PSU RTB_PSU L
HKBusTEMPFANPSU RPSU LTB_PSU RTB_PSU L
HKBus TEMP FAN PSU R PSU LTB_PSU RTB_PSU L
HKBus TEMP FAN PSU R PSU LTB_PSU RTB_PSU L
F030403EE.ai
Figure FFCS-V Status Display View (With Cabinet)
The FCS Status Display view displays the FCS’ station information, hardware configuration and its status, and whether or not the communication bus status is normal in color, so that users can visually check the system status at a glance. Using the FCS Status Display view, users can start or shut down the control station.
3. Operation and Monitoring Functions 3-29
TI 33K01A11-50E
3.4.4 HIS Status Display ViewThe HIS Status Display view displays an overview of the operation status or each setting of the console type HIS. The HIS Status Display view can be called up on the console type HIS.
HIS0164 PlantA
Station No : 64 Type : LPCKITRevision : R5.01. 00
ID No : 0021C010031
TEMP Air in Air outFAN
Door ( D1 D2 D3 )DISK STATUS HDD1 HDD2
.SF HIS0164 HIS Status Display
Ready
MYPJT Domain : 01 V net1 V net2
FCS
IOM
PCI 1 IDE 2 USB 3 SM Bus 4 Audio 5 VGA 6 V net 7 RAS 8 RS232-C 9 VGA 10 Ethernet
COM 1 2 3 UPS 4 Opkb 5 Touch1 6 Touch2
Parallel 1 Printer1
FCS
F030404E.ai
Figure HIS Status Display View (An Example of Enclosed Display Style Console HIS)
The HIS Status Display view displays HIS information and hardware configuration, and indicates the hardware status by colors to facilitate the grasp of the HIS status at a glance. This view can also be used to switch the valid/invalid states of the control network (V net or Vnet/IP) and to maintain the touch panel.
Sep. 22, 2011-00
3. Operation and Monitoring Functions 3-30
TI 33K01A11-50E Sep. 22, 2011-00
3.4.5 HIS Setup WindowThe HIS Setup window is used for displaying the current station’s information or changing operation settings.
ApplyCancelOK E040304E.ai
.SH HIS Setup
Help
Emulate Function Key (HIS should be restarted.) 100000Number of Tags
(The computer should be restarted.)
Project : MYPJTStation Name : HIS0164 Type : PC (PC) Address : 01-64 Comment : OS : Windows Vista (6. 0. 6001: Service Pack 1)OPKB Revision : 0. 0 Port :
File
REPORT Process Management Multiple-MonitorFunction Keys Operation Mark Multimedia Browser Bar Long-TermTrend
External Recorder OPCWindow Swithcing AlarmBuzzer Display Preset Menu
Equalize
PrinterStation
Figure Station Tab in HIS Setup Window
The HIS Setup window can perform settings specific to the HIS such as the operation and monitoring window display size setting, printer setup and operation screen mode setting. The tabs for each setting item in the HIS Setup window are provided.
StationDisplays the project name, station information and OS information.
PrinterSets printing message and window messages output settings.
BuzzerSetting of the volume, tone, sound source of a buzzer.
DisplayDefines the settings regarding the operation and monitoring windows.
Window SwitchingThis tab is for the settings regarding the types and actions of the windows called from System Message Banner and the windows popped out by the occurred alarm or event messages.
AlarmThis tab is for the settings regarding the alarm display and acknowledgement actions.
Preset MenuThis tab is for the settings regarding the functions to be simply called by the preset menu.
3. Operation and Monitoring Functions 3-31
TI 33K01A11-50E Sep. 22, 2011-00
EqualizeRuns equalization or sets the equalization related settings.
Function KeysThis tab is for the settings regarding the functions assigned to the function keys.
Operation MarkThis tab is for the settings regarding the labels (character strings) and colors assigned to the operation marks.
MultimediaThis tab is for the settings regarding the multimedia usages.
Browser BarDefines the settings regarding the Browser Bar.
TrendDefines the settings regarding the trend display.
Long-TermThis tab is for the settings regarding the long-term trend. This tab can be displayed only when the Long-Term Data Archive Package (LHS6510) is activated.
External RecorderThis tab is for the settings regarding the external recorders connected to the CENTUM VP system. This tab can be displayed only when the Output to External Recorder Package (LHS4150) is activated.
OPCThis tab is for the settings regarding the Exaopc OPC Interface pckage (for HIS). This tab can be displayed only when the Exaopc OPC Interface Package (for HIS) (LHS2411) is activated.
REPORTThis tab is for the settings regarding the report package. This tab can be displayed only when the Report Package (LHS6530) is activated.
Process ManagementThis tab is for the settings of the process management. This tab can be displayed only when the VP Batch (Batch Management Package) is activated.
Multiple-MonitorThis tab is for the settings regarding the multiple monitors. This tab can be displayed only when the Multiple-Monitor Support Package (LHS4600) is activated.
i
TI 33K01A11-50E
Revision Information● Title : Integrated Production Control System CENTUM VP System Overview (HMI Overview)● Manual No. : TI 33K01A11-50E
Sep. 2011/1st EditionNewly published