...to complete your network
CONTEG SOLUTIONSfor the next decade!
1
CONTEG DATA SHEET
VENTILATION UNITS & FANS & ACTIVE DOOR
TARGETED COOLING
version: 16-04-2012
CONTEG, spol. s r.o.
Headquarters Czech Republic:Na Vítězné pláni 1719/4140 00 Prague 4
Tel.: +420 261 219 182 Fax: +420 261 219 192
conteg@conteg.comwww.conteg.com
Local Branches/Offices:Austria: +43 699 1819 7071Benelux: +32 477 957 126Eastern Europe / Nordics: +49 172 8484 346 France, Maghreb: +33 686 074 386Germany / Switzerland / Baltics / Denmark / Italy: +49 170 523 4958 Middle East: +971 555 08 32 41Russia, CIS: +7 495 967 3840Slovakia: +421 917 874 111
...to complete your networkwww.conteg.com
CONTEG SOLUTIONSfor the next decade!
2
DP-VEN-02
DP-VEN-03DP-VEC-03
DP-VEN-04
DP-VEN-05
DP-VEN-06DP-VEC-06
DP-VEN-07
DP-VEN-08
DP-VEN-09DP-VEC-09
19" mounting ventilation unitConnecting kit for installation in top or
bottom frame of free standing racks depth 1000mm
Connecting kit for installation in top orbottom frame of free standing racks
depth 600, 800 or 1200mm
DP-VER-03
DP-VER-03F
DP-VER-06
DP-VER-06F
DP-VER-031
DP-VER-031F
DP-VER-061
DP-VER-061F
DP-VER-091
DP-VER-091F
Used to force airflow through a rack to assist with cooling.
DESCRIpTION:• Twotoninefans• Possibletoinstall:
a) in 19" extrusions – horizontally b) intoporbottomframeoffree‑standingrack
• Connectingkitforventilationunitisneededwheninstallingintoporbottomframe
• Temperaturerange‑10°Cto55°C• Thermostatintherange0°C – 60°Cincluded;
optionally no thermostat• Voltagerange230V/50Hz(optionally48VDC)• ProtectioncategorytoEN60529IP20• ColorpowdercoatedRAL(standardRAL9005)• High‑endversionwiththemostefficientECfansDP‑VEC‑xx
• AllDP‑VENandDP‑VECunitsarecompatiblewith all Conteg products
VENTILATION UNITS
DP‑VEN‑06
Information on installation options (into top or bottom frame of ROR rack series) on request
EC TECHNOLOGY:Efficient,ecological,economical!New high quality fans feature electro‑nically commuted synchronic mo‑tors, well known as „EC motors“. The main advantage of this technology is a very low power consumption in compa‑risontothestandardACmotors.Forexample–powerconsumptionofournewDP‑VECventilationunitisseventimeslowerthenthestandardDP‑VENwithequalair‑flow.Onthetopofit,DP‑VECprovidesupto60%biggerair‑flowwithequalnum‑beroffansandrequiredairpressureincomparisonwiththestandardDP‑VEN.
Ventilation unit selection:Ifyouneedtoremoveheatfromacabinet,justmakeaneasycalculationtofindacorrecttypeoftheventilationunit.Followingtwoentriesareneededforthecalculation:(1)MaximumairtermperatureintheITroomand(2)amaximumtem‑peratureoftheairexhaustedfromthetechnologyinstalledinsidethecabinet.Thencalculatethetemperaturedifference(incaseitisunknownuse3or5°C)tousethisformula:
N = Q * A /ΔtN=numberoffansQ=exhaustedheatload(W)Δt=calculatedtemperaturediffeence(Kor°C)forDP‑VEN.....A=0,02626forDP‑VEC.....A=0,01634SelectventilationunitwiththesameasthecalculatedNorhighernumberoffans.Thiscalculationisonlyestimate.Contegcannotbearresponsibilityforincorrectselection.Remember! The heat exhausted from the cabinet increases the room temperature so the room ventilation has to besufficientorair‑conditionmustbeused.
...to complete your networkwww.conteg.com
CONTEG SOLUTIONSfor the next decade!
3
FRAME OF RACK
VENTILATION UNIT
CONNECTING FRAME
ANGLE FITTING
SCREW M5
SCREW M5
SCREW M5X15
DP-VEN-02 (03)DP-VEC-03
DP-VEN-04 (05, 06)DP-VEC-06
DP-VEN-07 (08, 09)DP-VEC-09
DP‑VE‑ROV2
DP‑VE‑ROV4
DP‑VE‑ROF4/100Side panel installation Special perforation VH or -TH
Used to force airflow through a rack where ventilation unit is not used.
DESCRIpTION:• Possibletoinstall: a)onsideortopofwall‑mountingrack–specialperforationneeded
(orderingcodeofthewallmountingracktobeextended:‑VHfor2xsideperforationor–THfor2xtopcoverperforation;bothforDP‑VE‑01only‑VCfor2xcentreorientedholesforDP‑VEN‑01)
b)intoporbottomframeofdistributionrack ‑requiresperforatedglandplateDP‑VE‑ROV2orDP‑VE‑ROV4
• Mountingkitincluded• Twoversions(ACtechnology):‑withthermostatatsteelbox‑DP‑VEN‑01‑withoutthermostat‑DP‑VE‑01(for‑VHor‑THopenings)
FANS
DP‑VEN‑01
Code Air flow (m3/h)
Rated current max. (A)
Power consumption (W)
Annual power consumption1)
(kWh/year)
Possible heat
removal 2)
(kW)
Standard AC fans
SpecificFanPower(SFP)=611W/(m3/s)
DP‑VEN‑02 224 0,180 38 333 0,38
DP‑VEN‑03 336 0,270 57 499 0,57
DP‑VEN‑04 448 0,360 76 666 0,76
DP‑VEN‑05 560 0,450 95 832 0,95
DP‑VEN‑06 672 0,540 114 999 1,14
DP‑VEN‑07 784 0,630 133 1165 1,33
DP‑VEN‑08 896 0,720 152 1332 1,52
DP‑VEN‑09 1008 0,810 171 1498 1,71
NEW PRODUCTS 2012
High-end EC fans
SpecificFanPower(SFP)=88W/(m3/s)
DP‑VEC‑03 540 0,057 13,2 116 0,92
DP‑VEC‑06 1080 0,114 26,4 231 1,84
DP‑VEC‑09 1620 0,171 39,6 347 2,751) in case of non-stop operation2) if temperature difference between intake and exhaust air from the rack is Δt=5K
...to complete your networkwww.conteg.com
CONTEG SOLUTIONSfor the next decade!
4
ACTIVE DOORThe active door is designed formounting of up to 3 ventilation units,
eachwith6fans(forracksof600mmwidth)and9fans(forracksof800mmwidth).Frontmountedactivedoorensureseffectiveairdelivery intotherack.Therearmountedactivedoorremovesheatedairfromtherack.Activedoors can be where higher density heat loads are required by augmenting thedeliveryorextractionofairforcoolingpurposes.
• Perforatedsheetmetalorventeddoor• Preparationformountingof3ventilationunits,eachwith6fans• Multipoint swivel handle lock• Universal keys• Colour design – powdered paint RAL 7035 or RAL 9005
Apply the appropriate codes in positions describing door type/door lock type in the rack ordering matrix:
• JWforsheetsteelperforateddoor,readyforupto3x6(3x9)‑positionventilation unit, multipoint swivel handle lock, universal key
• KWforventeddoor,readyforupto3x6(3x9)‑positionventilationunit,multipoint swivel handle lock, universal key
Recommended