Product BrochureCommercial Package Units | VFD Technology
Air | Commercial Package Units | VFD TechnologyINTEGRATED HOME COMFORT
Rheem Commercial Series™ Package Units, featuring VFD Technology integrate variable frequency drive operation for substantial energy savings and improved comfort.
• Reduces cost of meeting building ventilation requirements by up to 85%
• Improves part load efficiency (IEER) up to 51%
• Removes twice as much moisture than standard package units for lower relative humidity and increased comfort
• Meets ASHRAE 90.1-2010 and California Title 24 requirements
• Available on 71/2 - 25 ton package gas electric units and package air conditioners
15 - 25 Ton
7 1/2 - 12 1/2 Ton
Reduce Your Building's VentilationCost by up to 85% Over StandardRooftop Units.
Engineered for a new level of savings and comfort, the Rheem Commercial Series™ package unit with VFD Technology will reduce ventilation operating cost while maximizing comfort.
Rooftops with VFD BenefitAll Commercial Applications
ASHRAE 62 specifies ventilation rate for different types of commercial buildings. In each commercial building, there is a ventilation requirement for occupancy, building size and building type. Furthermore, per ASHRAE 62 and other building codes, ventilation is required when the building is occupied. Depending on occupancy, building size and building type, ventilation requirements during occupied mode generally vary from 10% to 40% of the package unit airflow. Supply fans in standard package units use constant volume, which means they have a single high speed airflow. Ventilation (fresh air) is supplied by the supply fans at maximum airflow resulting in maximum energy usage.
A Rheem Package Unit with VFD Technology, operates the supply fan at two speeds instead of only one. During the fan only mode and 1st stage cooling demand, it operates at 50% of high speed. During 2nd stage cooling and heating demand, it operates at 100%.
The indoor fan speed difference between a standard package unit and a Rheem Package Unit with VFD Technology is what enables dramatically reduced operation costs and improved comfort.
Schools
Health ClubsRestaurants
Commercial Package Units | VFD TechnologyINTEGRATED HOME COMFORT
The Fan Laws simply state power goes down eight times faster than airflow.
Low speed watts = high speed watts
Using VFD is strong science and reduces your monthly utility bills.
VFD Technology allows our units to work smarter to bring greater energy savings.
The Science Behind VFD Technology
( Low speed cfm )3High speed cfm
INDOOR FAN AIRFLOW VS. POWER
0
500
1000
1500
2000
2500
3000
0 1000 2000 3000 4000 5000 6000 7000 8000
Ind
oo
r Fa
n P
ow
er (W
atts
)
Airflow (CFM)Typical 20 tonTypical 10 ton
Constant fan/1st stage cooling operation of Standard RTU7550 cfm; 2729 watts
Constant fan/1st stage cooling operation of Standard RTU w/ VFD3803 cfm; 349 watts
Constant fan/1st stage cooling of Standard RTU3600 cfm; 1388 watts
Constant fan/1st stage cooling of Standard RTU w/ VFD1784 cfm; 169 watts
Rheem.com
Building codes require fan operation to supply fresh air during occupied modes. Current rooftops supply fresh air using high speed which is wasteful and uses a lot of energy. A Rheem Package Unit with VFD Technology reduces the supply fan speed by 50% while still meeting fresh air requirements and saving up to 85% of overall supply fan operating cost.
Ventilation Energy Savings
ANNUAL FAN COST COMPARISON
Without VFD With VFD
7.5 8.5 10.0 12.5 15.0 17.5 20.0 25.0
$324 $386
$79 $92
$532
$122
$873
$188
$534
$108
$762
$144
$879
$155
$1,540
$230
IEER INCREASE
Without VFD With VFD
7.5 8.5 10.0 12.5 15.0 17.5 20.0 25.0
11.9 12
14.5 14.411.9
10.8
13.512.4
14.612.6
14.5
11.4
14.8
10.1
14.114.4
LANTENT/SENSIBLE RATIO
Without VFD With VFD
7.5 8.5 10.0 12.5 15.0 17.5 20.0 25.0
0.31 0.3
0.680.62
0.34 0.31
0.64
0.3
0.62
0.32
0.64
0.27
0.61
0.31
0.680.63
Commercial equipment is sized for full load operation which only occurs with maximum outdoor load and indoor load. These conditions occurs only 10% to 30% of the time. Therefore 70% to 90% of cooling operation is on 1st stage. A Rheem Package Unit with VFD Technology increases IEER by up to 51% when operating on 1st stage cooling.
A standard package unit in 1st stage cooling operates the supply fan at 100% airflow. Operating in 1st stage cooling at 50% airflow can remove more than twice as much moisture than a standard package unit. A Rheem Package Unit with VFD Technology improves thecomfort level by reducing the relative humidity in the condition space.
Part Load Energy Savings
Improved Comfort
*Assumptions: calculated based on 8:00 a.m. to 5:00 p.m. operation Monday thru Friday, 250 days per year. Electric rate11.5 /kWh)
**IEER per AHRI 340/360)
***82 outdoor DB; 80 DB/69.6 WB Indoor
Data Source: Rheem
**
*
***
¢
PACKAGE GAS ELECTRIC UNITCOOLING DATA HEAT INPUT PHYSICAL DATA
MODEL NOMINAL TONNAGE
GROSS CAPACITY
(BTUH)
AHRI RATED
NET CAPACITY
(BTUH)
NOMINAL CFM/ARI RATED (CFM)
EER IEER STANDARD: (BTUH)
HIGH: (BTUH)
DIMENSIONS H X W X L (INCHES)
SHIPPING WEIGHT
(LBS)
RKNL-H090 7.5 93,000 90,000 3,000/2,775 11.2 14.7 75,000/150,000 112,500/225,000 44 x 58.8 x 93.7 1,054
RKNL-H102 8.5 101,000 97,000 3,200/3,200 11.2 14.4 75,000/150,000 112,500/225,000 44 x 58.8 x 93.7 1,096
RKNL-H120 10 123,000 118,000 4,000/3,750 11.2 14.4 75,000/150,000 112,500/225,000 44 x 58.8 x 93.7 1,149
RKNL-H151 12.5 146,000 140,000 5,000/4,225 10.8 13.5 75,000/150,000 126,000/225,000 44 x 58.8 x 93.7 1,303
RKNL-H181 15 188,000 182,000 6,000/5,900 11.1 14.4 125,000/250,000 175,000/350,000 57 x 85.9 x 152 2,084
RKNL-H210 17.5 212,000 204,000 7,000/7,025 11.6 14.5 125,000/250,000 175,000/350,000 57 x 85.9 x 152 2,272
RKNL-H240 20 244,000 234,000 8,000/7,725 11.1 14.8 150,000/300,000 200,000/400,000 57 x 85.9 x 152 2,415
RKNL-H300 25 312,000 294,000 10,000/9,475 10.0 13.4 150,000/300,000 200,000/400,000 57 x 85.9 x 152 2,514
Commercial Package Units
VFD TechnologyINTEGRATED HOME COMFORT
Rheem.comPrinted in the U.S.A. 06/12 QG Form No. M11-1666
Rheem USA • P.O. Box 17010Fort Smith, Arkansas 72917
Rheem Canada Ltd./Ltée • 125 Edgeware Road, Unit 1 Brampton, Ontario L6Y 0P5
In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.
Air
Specifications
PACKAGE AIR CONDITIONERCOOLING DATA HEAT INPUT PHYSICAL DATA
MODEL NOMINAL TONNAGE
GROSS CAPACITY
(BTUH)
AHRI RATED
NET CAPACITY
(BTUH)
NOMINAL CFM/ARI RATED (CFM)
EER IEER STANDARD: (BTUH)
HIGH: (BTUH)
DIMENSIONS H X W X L (INCHES)
SHIPPING WEIGHT
(LBS)
RLNL-H090 7.5 93,000 90,000 3,000/2,775 11.2 14.7 10 20 44 x 58.8 x 93.7 1,054
RLNL-H102 8.5 101,000 97,000 3,200/3,200 11.2 14.4 10 20 44 x 58.8 x 93.7 1,096
RKNL-H120 10 123,000 118,000 4,000/3,750 11.2 14.4 10 20 44 x 58.8 x 93.7 1,149
RLNL-H151 12.5 146,000 140,000 5,000/4,225 11.0 13.5 10 20 44 x 58.8 x 93.7 1,303
RLNL-H181 15 188,000 182,000 6,000/5,900 11.1 14.4 20 75 57 x 85.9 x 152 2,084
RLNL-H210 17.5 212,000 204,000 7,000/7,025 11.6 14.5 20 75 57 x 85.9 x 152 2,272
RLNL-H240 20.0 244,000 234,000 8,000/7,725 11.1 14.8 20 75 57 x 85.9 x 152 2,415
RLNL-H300 25.0 312,000 294,000 10,000/9,475 10.0 13.4 20 75 57 x 85.9 x 152 2,514
Rheem Commercial HVAC Equipment Financing allows the full cost of HVAC
projects in commercial applications, to be bundled into one convenient,
affordable monthly payment. Administered by GreatAmerica™ Financial
Services, every aspect of the HVAC project; such as, equipment, installation,
labor and extended warranty, is eligible to be financed up to 60 months with
no down payment or security deposit! There is no application process, and all
contractors in good standing qualify to use the program. To learn more, visit
us online today at www.greatamerica.com/Rheem.
Convenient Commercial Financing is NOW AVAILABLE! PAYMENT CALCULATOR
12 months24 months36 months48 months60 months
$5,000 - $14,999
.09168
.04837
.03298
.02597
.02174
$15,000 - $49,999
.09073
.04778
.03238
.02536
.02120
$50,000 - $99,999
.09002
.04766
.03215
.02512
.02100
Example: $13,000 Invoice1. Select the invoice range in the top row ($5,000 - $14,999)
2. Select any term (for 36 months, it's .03298)
3. Multiply $13,000 x .03298 = $428.74/month for 36 months
Recommended