Indicating and adjustment
PLICSCOM
VEGADIS 81
VEGADIS 82
VEGADIS 175
Product Information
Contents
2 Indicating and adjustment –
Contents
1 Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Type overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Take note of safety instructions for Ex applications
Please note theEx specific safety informationwhich you can find on our homepagewww.vega.com/downloads under "Approvals" andwhich
comes with every instrument. In hazardous areas you should take note of the corresponding regulations, conformity and type approval
certificates of the sensors and power supply units. The sensors must only be operated on intrinsically safe circuits. The permissible electrical
values are stated in the certificate.
30143-EN-140402
1 Product description
In continuous level measurement, the level in a vessel is detected. The
measured value is further processed e.g. as 4 … 20 mA in a PLC or a
control system.
On-site indication of the measured value is often desired. To fulfill this
need, a wide range of display instruments is available. Indication, power
supply and mounting differ depending on the model. This product infor-
mation manual provides an overview and helps you select a suitable
instrument.
PLICSCOM
The display and adjustment module PLICSCOM is used for measured
value indication, adjustment and diagnosis of VEGA plics® sensors. It is
integrated in the respective sensor housing.Aftermounting, the sensor as
well as PLICSCOM are splash-proof even without housing cover.
An integratedbacklight enables reading even under unfavourable lighting
conditions. As an option, the display can also be equipped with heating
that ensures good readability at low temperatures down to -40 °C (-40 °F).
Your benefit
l Minimum time expenditure through reliable function and clear,
graphic-capable LC display with 4-key operation as well as integrated
lighting.
l Simple and reliable adjustmentof theplics® sensors throughclear text
indication and graphic support
l Since it is easy to detach, it can also be used on other sensors
VEGADIS 81
The VEGADIS 81 is an external measured value display for VEGA plics®
sensors that can also be used for sensor adjustment. It canbemounted at
a distance of up to 50 m from the sensor and is powered directly by the
sensor.Separate external energy is not required. If thesensor is difficult to
access, the VEGADIS 81 can be mounted at an optimised location.
Your benefit
l Good readability through clear DOT matrix display with easy 4-key
adjustment as well as integrated display lighting
l Simple, clearly structured adjustment of the plics® sensors through
clear text indication and graphic support
l Readability andoperability facilitated on site by thedisplay andadjust-
ment module which can be plugged in in 90° rotational steps
VEGADIS 82
VEGADIS 82 is suitable for measured value indication and adjustment of
standard sensors with HART protocol. The instrument is looped directly
into the 4… 20mA signal line at any location. A separate external power
supply is not required. VEGADIS 82 also operates exclusively as an in-
dicating instrument in a 4 … 20 mA current loop.
It is particularly suitable for hydrostatic pressure transmittersVEGAWELL
52 and radar sensorsVEGAPULSWL 61 4… 20mA/HART. It contains a
breather facility for ventilation of the sensors via the capillary line in the
special cable.
Your benefit
l Minimum time and cost expenditure for on-site parameter adjustment
via clearly arranged display with simple 4-key adjustment
l Reliable and easy adjustment of theHART sensors through clear text
indication with graphic support
VEGADIS 175
The VEGADIS 175 is a digital indicating instrument without additional
external energy. It is used for separate measured value indication on all
standardized 4… 20mA circuits.Due to the standardized dimensions of
the display, it is generally used as a front panel instrument.
The VEGADIS 175 is looped into the 4 … 20 mA signal cable at any
position and is suitable for active (four-wire) as well as passive (two-wire)
sensors.
Your benefit
l Universal use through 5-digit, scalable display
l Individually adjustable decimal point provides high flexibility when ad-
justing the instrument
l Reliable function and wide range of application thanks to compact,
rugged housing with high protection rating
Product description
Indicating and adjustment – 3
30143-EN-140402
2 Type overview
PLICSCOM VEGADIS 81
Function Pluggable display and adjustment module for plics®
sensors
External display and adjustment unit for plics® sensors
Signal input I2 bus I
2 bus
Sensors plics® sensors plics® sensors
Display on the instru-
ment
Graphics-capable clear text display with background
lighting
Graphics-capable clear text display with background
lighting
Mounting In the sensor or in VEGADIS 81 Wall, rail, tube mounting
Ambient temperature -15 … +70 °C (+5 … +158 °F) -15 … +70 °C (+5 … +158 °F)
-40 … +70 °C (-40 … +158 °F)
Protection rating IP 20 (unassembled), IP 40 (assembled) IP 66/IP 67, IP 66/IP 68 (0.2 bar)
Approvals According to the sensor or VEGADIS 81 ATEX, IEC, FM, CSA, GOST, UKR
VEGADIS 82 VEGADIS 175
Function Display and adjustment unit without additional external
energy
Digital indicating instrument without additional external
energy
Signal input 4 … 20 mA, 4 … 20 mA/HART 4 … 20 mA, 4 … 20 mA/HART
Sensors 4 … 20 mA active or passive 4 … 20 mA active or passive
Display on the instru-
ment
Graphics-capable clear text display with background
lighting
Large digital indication
Mounting Wall, rail, tube mounting Front panel mounting
Ambient temperature -15 … +70 °C (+5 … +158 °F) -10 … +60 °C (14 … +140 °F)
Protection rating IP 66/IP 67, IP 66/IP 68 (0.2 bar) IP 65
Approvals ATEX, IEC, FM, CSA, GOST, UKR ATEX
Type overview
4 Indicating and adjustment –
30143-EN-140402
3 Mounting
3.1 PLICSCOM
The display and adjustment module PLICSCOM offers the following in-
stallation possibilities:
l In the sensor
l In VEGADIS 81
3.2 VEGADIS 81 and 82
The instruments can be mounted in the following ways:
l Carrier rail 35 x 7.5 according to EN 50022
l Wall mounting
l Tube mounting
Wall mounting
The VEGADIS 81 and 82 are suitable for wall mounting in all available
housing materials.
7 m
m(0
.28
")
82 mm (3.23")
10 mm(0.39")
Fig. 1: Drilling dimensions for VEGADIS for wall mounting
Carrier rail mounting
TheVEGADIS81 and82withplastic housingare suitable for direct carrier
rail mounting.
1 2
Fig. 3: VEGADIS 81 and 82 with plastic housing for carrier rail mounting
1 Base
2 Carrier rail
The versions with aluminium or stainless steel housing are supplied with
unassembled mounting accessories. The kit consists of an adapter plate
and four mounting screwsM5 x 12.
The adapter plate is screwed by the user to the socket of VEGADIS 81 or
82.
321
Fig.4: VEGADIS81and82withaluminiumandstainlesssteel housingfor carrier rail
mounting
1 Base
2 Adapter plate with screwsM5 x 12
3 Carrier rail
Tube mounting
The VEGADIS 81 and 82 for tube mounting are supplied with unas-
sembledmountingaccessories. It consistsof twopairsofmountingbrack-
ets and four mounting screwsM5 x 12.
The mounting brackets are screwed by the user to the socket of VEGA-
DIS.
21 3
Fig. 5: VEGADIS for tube mounting
1 4 screwsM5 x 12
2 Mounting brackets
3 Tube (diameter 1" to 2")
Front panel mounting
TheVEGADIS 82 is also available with a plastic housing for panel mount-
ing. The housing is fastened through the supplied screw clamps on the
rear of the panel.
4
5
1 2 3
Fig. 7: VEGADIS for panel mounting
1 Inspection window
2 Front panel
3 Screw clamp
4 Housing
5 Plug connector
3.3 VEGADIS 175
The VEGADIS 175 is designed for panel mounting. The housing is fas-
tened via the supplied screw clamps to the rear of the panel.
92mm (3 5/8")
45
mm
(1 4
9/ 6
4")
4
1 2 3
Fig. 9: VEGADIS 175 for panel mounting
1 Front panel
2 Bracket
3 Screw
Mounting
Indicating and adjustment – 5
30143-EN-140402
4 Electrical connection
4.1 Connection VEGADIS 81
Wiring plan
5 6 7 8 4
2
1
Fig. 10: Wiring plan VEGADIS for 4… 20mA/HART sensors
1 To the sensor
2 Ground terminal for connection of the cable screen1)
4.2 Connection VEGADIS 82
1 3
2Sensor
1 2+( ) (-)
power supply
3 4+( ) (-)
Fig. 12: Wiring plan VEGADIS 4… 20mA
1 To the sensor
2 Ground terminal for connection of the cable screen2)
3 For power supply
Sensor
1 2+( ) (-)
power supply
3 4+( ) (-)
R
off on
HART
1 4
2
3
Fig. 14: Wiring plan VEGADIS 4… 20mA/HART
1 To the sensor
2 Switch for communication resistor (on = activated, off = deactivated)
3 Ground terminal for connection of the cable screen3)
4 For power supply
4.3 Connection VEGADIS 175
Passive sensors
1 2 3 4
+
–
–
+
3
1
2
Fig. 16: Wiring plan, VEGADIS 175 for passive sensors
1 Sensor (passive)
2 Bridged internally
3 Voltage supply/Signal output
4 Ex area
5 Non-Ex area
Active sensors
1 2 3 4
+
– 1
2
Fig. 17: Wiring plan, VEGADIS 175 for active sensors
1 Sensor (active)
2 Bridged internally
Electrical connection
6 Indicating and adjustment –
1)Connect screen here. Connect ground terminal on the outside of the housing to ground as prescribed. The two terminals are galvanically connected.
2)Connect screen here. Connect ground terminal on the outside of the housing to ground as prescribed. The two terminals are galvanically connected.
3)Connect screen here. Connect ground terminal on the outside of the housing to ground as prescribed. The two terminals are galvanically connected.
30143-EN-140402
5 Operation
5.1 Operation on PLICSCOM, VEGADIS 81,
VEGADIS 82
1
2
Fig. 18: Display and adjustment elements
1 LC display
2 Adjustment keys
Key functions
l [OK] key:
- Move to the menu overview
- Confirm selected menu
- Edit parameter
- Save value
l [->] key:
- Presentation, change measured value
- Select list entry
- Select editing position
l [+] key:
- Change value of the parameter
l [ESC] key:
- Interrupt input
- Jump to next higher menu
5.2 AdjustmentonVEGADIS81withPACTware
PACTware/DTM
The plics® sensors can be adjusted through VEGADIS 81 via PACTware
independent of the respective signal outout. For operation with
PACTware, an instrument driver (DTM) is required for the respective
sensor.
All currently available VEGA DTMs are provided as "DTMCollection and
PACTware" on a data carrier. They are available from the responsible
VEGA agency for a token fee. The standard version of the "DTM Collec-
tion and PACTware" is available as a free-of charge download from the
Internet. This standard version includes already the project documenta-
tion and storage.
For additional functions of the DTM such as multiviewer and tank calcu-
lation, the full version "DTM Collection and PACTware" is required. This
version can be bought from the VEGA agency serving you.
Connection of the PC to VEGADIS 81
1
3
2
6
454
4
Fig. 19: Connection of VEGADIS to the sensor and the PC
1 Voltage supply/Signal output sensor
2 Sensor
3 Connection cable VEGADIS - Sensor
4 VEGADIS
5 VEGACONNECT
6 PC with PACTware
For the adjustment with PACTware, a VEGACONNECT as well as a
power supplyunit are required inaddition to thePCand thesuitableVEGA
DTM.
5.3 Adjustment on VEGADIS 175
Indication and adjustment are carried out on the front via a clear LC dis-
play and three keys.
VEGADIS 175 OK
3 2
1
Fig. 21: Display and adjustment elements
1 Digital indication
2 Key (OK)
3 Adjustment keys +/-
Key functions
l [OK] key:
- Move to the menu overview
- Confirm selected menu
- Edit parameter
- Save value
l [+]/[-] keys:
- Change value of the parameter
Operation
Indicating and adjustment – 7
30143-EN-140402
6 Dimensions
PLICSCOM
27
,6m
m(1
.09
")
ø 6
6,3
mm
(2.6
1")
45,1mm (1.78")
9,7mm (0.38")
Fig. 22: Dimensions of display and adjustment module
VEGADIS 81
1
ø 79 mm (3.11") ~ 69 mm
(2.72")
85
mm
(3
.35
")8
2 m
m (
3.2
3")
97
mm
(3
.82
")
6,5
mm
(0
.26
")
97 mm (3.82")
Fig. 23: Dimensions, VEGADIS 81 with plastic housing
1 Cable gland with version with heated display and adjustment module
VEGADIS 82 - plastic housing
ø 79 mm
(3.11")
~ 69 mm
(2.72")
85
mm
(3.3
5")
82
mm
(3.2
3")
97
mm
(3.8
2")
6,5
mm
(0.2
6")
97 mm
(3.82")
Fig. 24: VEGADISwith plastic housing
VEGADIS 82 - Plastic housing - Panel mounting
72,5 mm
(2.85")
72
,5 m
m
(2.8
5")
78
,2 m
m
(3.0
8")
22,5 mm
(0.89")
70 mm
(2.76")
77
mm
(3.0
3")
67
mm
(2.6
4")
56 mm
(2.20")
76 mm
(2.99")
Fig. 26: VEGADISwith plastic housing for panel mounting
VEGADIS 175
1 2 3 4
- + OKVEGADIS 175
96 mm (3 25/32")
48
mm
(1 5
7/ 6
4")
91 mm (3 37/64")
91 mm (3 37/64")80 mm (3 5/32")9,5 mm
(3/8")
6 mm
(15/64")
43
mm
(1 1
1/ 1
6")
Fig. 28: Dimensions VEGADIS 175
Dimensions
8 Indicating and adjustment –
30143-EN-140402
Indicating and adjustment – 9
30143-EN-140402
10 Indicating and adjustment –
30143-EN-140402
Indicating and adjustment – 11
30143-EN-140402
VEGA Grieshaber KG
Am Hohenstein 113
77761 Schiltach
Germany
Phone +49 7836 50-0
Fax +49 7836 50-201
E-Mail: info.de@vega.com
www.vega.com
You can find at www.vega.com
l operating instructions manuals
l specification sheet
l Software
l drawings
l certificates
l approvals
and much, much more
Subject to change without prior notice 30143-EN-140402
Recommended