Protecting life, environment and property…
AutroSafe Panel
To ProcessControlSystem
AutroLON
PowerLoop
AutroFieldBus
Video
BSD-340
BSD-321
AutroSafe Panel
ModBusProfiBus
ProfiSafeEthernet
Standard AutroSafeloop units
AutroFlame
AutroSafeIS loop units
BN-342(4-20mA)
AutroFlame CCTV
AutroSafe Controller
AutroLON
Information/repeaterpanel
Third-partydetector
Al_Comloop
IS Isolator unit
AutroOS
ID: IFG_PowerLoopDevices, 2004-05-28
Protecting life, environment and property…
PowerLoop driver BSD-340PowerLoop driver BSD-340
• Loop driver for –AutroFlame X33/1 PL–AutroPoint HC300 PL–4 – 20mA converter BN-342
• Up to 15 detectors on PowerLoop• 30W power dissipation at 100W
output• Automatic shutdown on overheat• Response time ≤2 seconds
Protecting life, environment and property…
PowerLoop driver BSD-340PowerLoop driver BSD-340
• Versions:– BSD-340/1 Rack mount– BSD-340/2 Din rail mount– BSD-340/EX Exd version
• Input:– AutroFieldBus and 24Vdc
• Output:– PowerLoop
• 30Vdc/100W Power supply• Communications protocol• Ring loop topology• Short circuit protected
Protecting life, environment and property…
PowerLoop driver BSD-340PowerLoop driver BSD-340
Service port(AS 2000?)Firmware update
Address switches
Connection Terminals (2.5mm)1 +24V DC input2 0V input3 PE ground4 PE ground5 IE ground6 PowerLoop A out plus7 PowerLoop A out minus8 IE ground9 PowerLoop B out plus10 PowerLoop B out minus11 AutroFieldBus A112 AutroFieldBus A213 AutroFieldBus A Shield14 AutroFieldBus A115 AutroFieldBus A216 AutroFieldBus A Shield
IndicatorsGreen: Power indicatorRed: Fault indicatorYellow: AutroField TXRed: AutroField RX
Protecting life, environment and property…
PowerLoop driver BSD-340/1PowerLoop driver BSD-340/1
• Rack-mount version– 19” 3U rack mounting
Protecting life, environment and property…
• DIN-rail-mount version– Identical to rack-mount
version, except for front and additional rail fixing clamps.
PowerLoop driver BSD-340/2PowerLoop driver BSD-340/2
Protecting life, environment and property…
General properties• Exd version for field mount in
hazardous areas• Based on a DIN-rail-mount version
fitted inside an Exd stainless steel housing
• Number of devices on thePowerLoop may be limited,depending on ambient temperature– 100W at 20ºC– 70W at 40ºC– 50W at 50ºC– 26W at 70ºC(PowerLoop Loop Calculator)
PowerLoop driver BSD-340/EXPowerLoop driver BSD-340/EX
Protecting life, environment and property…
AutroFieldBus to RS485 interface BSD-321
AutroFieldBus to RS485 interface BSD-321
• General properties– RS485 multidrop communication
• Max. 1200m cable length• Max. 28 AutroFlame CCTV• Max. 16 detectors• Galvanically isolated
– RS232 service port• for firmware upgrade
• Versions:– BSD-321/1 Din rail mount– BSD-321/EX Field mount unit
• (Same housing as BSD-340)
Protecting life, environment and property…
AutroFieldBus to RS485 interface BSD-321
AutroFieldBus to RS485 interface BSD-321
• Response time for alarm, ≤2 seconds
• Available protocols:– AutroPath Pulsar OPGD– AutroFlame CCTV – Kidde Fenwal Analaser II– Spectrex OPGD
Protecting life, environment and property…
AutroFieldBus to RS485 interface BSD-321
AutroFieldBus to RS485 interface BSD-321
• AutroPath Pulsar OPGD:– Alarms:
• Low alarm• High alarm
– Faults:• Beam block• TX Flash warning• TX Misalignment warning• RX Misalignment warning (or
particular obstruction)• Dirty optics
– Analogue values transmitted• Gas concentration
Protecting life, environment and property…
AutroFieldBus to RS485 interface BSD-321
AutroFieldBus to RS485 interface BSD-321
• AutroFlame CCTV:– Alarms:
• Alarm– Faults:
• General fault– Live video images
Protecting life, environment and property…
AutroFieldBus to RS485 interface BSD-321
AutroFieldBus to RS485 interface BSD-321
• Spectrex OPGD:– Alarms:
• Low alarm• High alarm
– Faults:• High noise• Obscuration (Beam block)• Partial misalignment
Protecting life, environment and property…
AutroFieldBus to RS485 interface BSD-321
AutroFieldBus to RS485 interface BSD-321
• Kidde Fenwal Analaser II:– Alarms:
• Alarm• Prealarm• Early warning
– Faults:• Detector trouble• Low air flow• High air flow
– Analog values transmitted:• Smoke level• Air Flow
Protecting life, environment and property…
PowerLoop 4-20mA input unit BN-342
PowerLoop 4-20mA input unit BN-342
• General purpose input unit for detectors with 4-20mA signal output.
• 7 Configurable current windows to match any 3rd party detector:– Alarm levels
• Early warning• Prealarm (low)• Alarm (high)
– Faults• User definable
– Normal
Protecting life, environment and property…
PowerLoop 4-20mA input unit BN-342
PowerLoop 4-20mA input unit BN-342
• Pre-configured for:– Simrad GD-10P– Sieger Excel OPGD– Sieger Excel Duct– Draeger XP Tox
• Versions:– BN-342/1 Rack mount– BN-342/2 DIN Rail mount– BN-342/EX Eexme version
Protecting life, environment and property…
PowerLoop 4-20mA input unit BN-342
PowerLoop 4-20mA input unit BN-342
IndicatorsGreen: Power indicatorRed: Alarm (any alarmlevel)Yellow: FaultGreen: PowerLoop comms
Connection terminals (2.5mm)1 PowerLoop+ in2 PowerLoop- in3 PowerLoop+ out4 PowerLoop- out5 4-20mA input +6 4-20mA input –7 24V out (EX version)8 0V out (EX version)
Protecting life, environment and property…
PowerLoop 4-20mA input unit BN-342/1
PowerLoop 4-20mA input unit BN-342/1
• Rack mount unit– 19” 3U rack mounting
Protecting life, environment and property…
PowerLoop 4-20mA input unit BN-342/2
PowerLoop 4-20mA input unit BN-342/2
• DIN Rail mount version– For mounting in cabinets
Protecting life, environment and property…
PowerLoop 4-20mA input unit BN-342/EX
PowerLoop 4-20mA input unit BN-342/EX
• Eex me version – GRP housing for field mounting in hazardous area– IP66– 9.5W DC/DC Power supply for detectors
Protecting life, environment and property…
AutroFlame X33AF SS Exde PLAutroFlame X33AF SS Exde PL
• Power and communication on the same pair of wires– Ring-loop topology with short-circuit
isolators in the detector• Up to 8 detectors on one PowerLoop
– Max 12W consumption. (Heater 7W)• Connections (Exe terminals 2.5mm)
– 1 PowerLoop + In – 3 PowerLoop - In – 15 PowerLoop - Out – 18 PowerLoop + Out
• Housing:– SS 316– IP 66– Exde
Protecting life, environment and property…
AutroFlame X33AF SS Exde PLAutroFlame X33AF SS Exde PL
• Alarms– Fire alarm
• Faults:– The various fault messages
generated by the detector aremapped into the AutroSafe“Class-Reason” system
• Selftest – Runs “manual” OI test
• Complete test of alarm path
Protecting life, environment and property…
AutroFlame X33AF SS Exde PLAutroFlame X33AF SS Exde PL
• Firmware upgrade:– Via PowerLoop
Protecting life, environment and property…
AutroPoint HC 300 PLAutroPoint HC 300 PL
• Power and communication on the same pair of wires– Ring-loop topology with short-circuit
isolators in the detector• Up to 10 detectors on one Loop
– Max. 10 W consumption• Connections (Exe terminals 2.5mm)
1 PowerLoop - In 2 PowerLoop + In 3 Cal4 PowerLoop –5 PowerLoop +12 PowerLoop – Out13 PowerLoop + Out
• Changing of gas type (performance class) by Hart communicator via Exia port (PL-support is under development)
Protecting life, environment and property…
AutroPoint HC 300 PLAutroPoint HC 300 PL
• Alarms– Low alarm 5-60% LEL – High alarm 5-60%LEL
• Alarm limits set via PL• Faults:
– Various fault messages • Calibration fault• Zero Drift• Dirty Optics• Open Lamp• General fault PowerLoop
interface• General fault detector
• Analog values:– Gas concentration
Protecting life, environment and property…
AutroPoint HC 300 PLAutroPoint HC 300 PL
• Response time for alarm ≤ 2 seconds
• Firmware upgrade:– Remote upgrade via
PowerLoop• Housing:
– CF8M stainless steel– IP 66– Exde
Recommended