Presentation to KIB-TEK Northern Cyprus (16/11/2005)

Preview:

DESCRIPTION

Presentation to KIB-TEK Northern Cyprus (16/11/2005). Introductions. Graham Pryce – International Sales Manager Lucy Switchgear, UK Bill Carlyle – Business Development Manager Lucy Switchgear, UK. Company Background. Established in 1760 as an iron foundry - PowerPoint PPT Presentation

Citation preview

1

2

Presentation to KIB-TEK Northern Cyprus(16/11/2005)

3

Introductions

• Graham Pryce – International Sales Manager Lucy Switchgear, UK

• Bill Carlyle – Business Development Manager Lucy Switchgear, UK

4

Company Background

• Established in 1760 as an iron foundry• Over £50m capital employed supporting the business

-- Lucy Electric Lucy Electric - Lucy Castings- Lucy Castings - Lucy Properties- Lucy Properties

• 100 shareholders both individual and institutional

5

Company Structure

W Lucy & Co Ltd

Lucy Electric Group

Lucy Switchgear Lucy Lighting

Lucy Switchgear HQ – Thame, UK

Lucy Switchgear – BanburyPower Isolators Ltd

Lucy Switchgear - Dubai

Saudi Lucy – Saudi Arabia

Crompton Greaves Lucy - India

Lucy Switchgear FZE – Oil

Lucy Switchgear FZE – SF6

Lucy Switchgear – Commercial Office

Lucy Castings

Lucy Properties

6

Lucy Switchgear - UK

7

Company HQ - Thame

• New in 2005 - £6 million purpose built site in Thame, Oxfordshire.

• Modern Single Floor Manufacturing

• 200 employees

8

Thame Activities

• Assembly, configuration, testing of Ring Main Units (RMU)

• Customisation of Low Voltage (LV) panels• Assembly of cast iron pillars• Steel shell configuration• Isolators assembly• Connectors assembly

9

Lucy Switchgear - Banbury

– R&D for ground and pole mounted switchgear

– Automation– Manufacturing of pole mounted switchgear –

Rapier RX, Rapier DSB

10

Lucy Switchgear FZE

11

Lucy Switchgear FZE

• Manufacturing in Dubai since 1997

• Two Lucy Switchgear factories

• Over 200 employees

• Investment in the latest technologies, cutting-edge machinary and CAD software

12

Lucy Switchgear FZE - Activities

• Manufacturing

– Medium voltage ring main units– Low voltage distribution equipment– Medium voltage overhead line equipment

13

Global Presence

14

Global Presence

15

Global Network

• Lucy Switchgear has established a global network operating in over 50 countries

• Agents, joint venture associates and trading partners represent Lucy Switchgear products in key areas including the Middle East, the Far East, Europe, Africa, Australasia and South America.

16

New SABRE VRN2a

17

Sabre VRN2aProduct Description

Outdoor non-extensible ring main unit with 2 ring switches and tee-off vacuum circuit breaker in an SF6 filled enclosure with pressure relief facility

18

SABRE VRN2a

19

SABRE Comparison

Improved Features• Smaller and lighter• Easier to use• Improved test access

20

SABRE VRN2a Main Features

• Vacuum tee off circuit breaker

• Common switching chamber with

sealed SF6 environment

• 12/15.5k/24V versions

• Indoor and Outdoor

• Enhanced electrical performance

• Interlocked for safe operation

21

SABRE VRN2a Main Features

• Integral ring cable testing

• Internal arc tested cable boxes

• Side and rear cable access for maximum

operator safety

• Fault passage indicators

• IP54 rated sheet steel housing

• Pre-wired for motor actuation

• Variety of protection options including relay and

TLF

22

SABRE VRN2a Options

• Remote operation of ring switches/ CB

• Fault passage indicators

• Intertripping

• Neon indication

• Top entry cable boxes

• Castell interlocks

23

SABRE Protection Systems

• Time lag fuse protection (TLF)

• Relay protection

• Live parts are contained within

earthed stainless steel enclosures

• Positive safety interlocks on all

switch positions

• Padlocking facilities for all switch

and selector positions

• Internal ARC tests are carried out in

accordance with IEC and ENA

specifications.

All Sabre units offer a high degree of safety, with customers benefiting from our experience in independent protection systems.

24

Environment and Quality

• We are committed to providing products that minimise adverse

environmental impacts and contribute positively to customers’ own

environmental objectives

• We operate a quality management system, which conforms to and exceeds

international requirements of BSEN and ISO 9001:2000

25

Sabre VRN2aGeneral Arrangement

NB T-off height 1320mm

26

Sabre VRN2a – Technical Specification

• Rated voltage - 15.5kV

• Rated insulation level - 95kV/110kV lightning impulse

• Rated insulation level – 38kV/45kV power frequency

• Rated short time withstand current - 20kA/ 3 sec

• Rated peak withstand current – 50kA

• Internal Arc Relief - gas enclosure, 20kA for 1 sec, in enclosed secondary

substation housing, to fig 4, ENATS 41-36, no additional trunking

27

Sabre VRN2a –Technical Specification

• Ring Main Switches Normal Current 630A

• Circuit Breaker Tee-Off Normal Current 250A

• Degree of protection - Outdoor to IP54 (door closed)

• Type tested to ENATS 41-36 issue 2, 2004

• Standard unit suitable for both direct transformer mounting and

freestanding cable connected applications

28

Sabre Test Certificate

• IEC 62271 – 103

• IEC 62271 – 100

• IEC 62271 – 102

• IEC 60056

• BS EN 60265 – 1

• BS EN 60129

• BS EN 60694

• BS EN 60298

• ENA TS 41-36

Sabre has been fully certified in accordance with IEC standards:

29

Package Substation

A selected Transformer supplier

LUCY RMU LV cabinets

30

Compact substation Indoor and Outdoor type

Outdoor

Brick building

Indoor

GRP enclosure

31

Automation Products & Systems

32

RMU Automation & Retrofit Actuator Solutions

33

Automated SABRE VRN2a

• Designed with automation in mind

• Wiring loom standard for both ring switches and indications

• Microprocessor controlled rotary actuator - same for both ring switches

• Simple plug-in installation to front of panel

34

Automated Sabre VRN2a

• Easy to remove actuator for manual operation

• CB actuator available as an option

• Fully integrated with Gemini-RTU for remote control & monitoring

35

Lucy Retrofit RMU Solutions

• Available on Lucy FRMU, EOS, SCRMU and the latest generation of RMU - the SABRE range

• Retrofit RMU kit also developed for Long & Crawford type T3/ T4GF3 & J3/ J4 (ring switches only)

• Non-intrusive

• Can be retrofitted with the RMU alive

36

Lucy Retrofit RMU Solutions

• Single or double actuator ring switch retrofit kits available, including tee-off CB actuator on Sabre RMU & SCRMU

• Standard 24V actuator supply voltage

• Motor control unit for interfacing with the Gemini-RTU or third party RTUs

• Equip RMU with Earth Fault Passage Indicator and core balanced CT

37

Automated FRMU

38

FRMU & Gemini-RTU

39

Automated L&C T3/ T4GF3 RMU

40

L&C J3/J4 Retrofit Actuator

41

RAPIER OverheadRange

42

Rapier Overhead Range

Rapier GX - based on SF6 technology

• GX-M (manual, hook-stick operation)

• GX-RC (local/ remote control via Gemini-RTU)

• GX-S or Sectionaliser (under development)

43

Rapier GX Load Break Switch - Features

• Ratings up to 38kV• SF6 gas utilised as both arc

quenching and insulating medium

• Equipped with 3 current transformers and 6 VCT’s in the bushings

• Stainless Steel enclosure sealed for life

• Motor actuator for DA• Overpressure membrane for

internal arc protection

44

Rapier GX Load Break Switch - Features (contd)

• Options available include: - Low gas pressure lockout device

- Gas pressure switch

- 3 additional CT’s for SEF

- Manual locking device

- Built-in VT for control cabinet supply

• GX LBS integrated with Gemini-RTU controller (described later)

45

Rapier GX Load Break Switch- Benefits

• Field proven LBS performance• Low capital and lifetime costs• Virtually maintenance free• Designed for maximum operator safety• Capable of live line installation• Integrated solution for distribution automation

46

Rapier Overhead Range

Rapier RX - based on air break technology

• RX-M (manual down pole or hook-stick operation)

• RX-RC (local/ remote control via Gemini-RTU)

• RX-FS or Fuse Switch

47

Problems Associated withOlder Air Break Designs

• Mechanisms would seize up over time due to stiff bearings and corroded main contacts

• Load Break Heads seized up due to complex design

• Braided flexes and joints suffered corrosion

• Significant maintenance over the switches’ lifecycle

48

New Features in RX Design

• Low friction, corrosion resistant bearing leading to low maintenance and improved reliability

• Laminated flexes with no corrosive effects. (Tested for 2,000 operations before single lamination broke)

• New simpler design of Arc Chute device for rapid arc extinction when load breaking

• New tungsten tipped contacts so that Fault Make Heads can be fitted as an option

• All key components now stainless steel for corrosion resistance

49

New Rapier RX Switch

Arc Chute

Fault Make Head

Laminated Flexes

Pin Bearing

Universal MainContacts

50

New RX switch design

51

Double Acting Spring Mechanism (DASM)

Closed orhook ends

Overtravel stops

Operatingarm

De-latchingarms

Verticaldrive rod

52

Modular Design Approach

Switches can be specified with:

• FMH, LBH or EB• Current ratings of 400, 630 or 800A• Short circuit ratings up to 25kA for 3 seconds• Choice of insulators - traditional ceramic or

polymeric options such as EPDM and Silicone Rubber

• Manual or motorised mechanism• Remotely controlled with RTU and integral

motorised actuator

53

Patented Fault Passage Indicator

FPI

54

Why consider an RX switch as part of your DA?

• Much improved design so that the RX can be relied upon to be remotely controlled

• Significant price differential with SF6 enclosed switches e.g. £1,000 - £1,500

• No monitoring of SF6 gas pressure

• RX switch considered as a Point of Isolation

• Environmentally friendly “AIR BREAK TECHNOLOGY”

55

GEMINI-RTU V2

56

Gemini-RTU

• Servo Control of actuator• RTU to manage

communications• DNP3 protocol as standard,

IEC 60870-5-101 and WISP+ optional

• Programmable e.g. Automation sequences

• Expandable digital I/O and current monitoring

• Voltage sensing derived from CVTs

57

Gemini-RTU

• 24V battery backup• Battery condition monitoring

- low battery voltage alarm

- deep discharge protection

- configurable on-load battery test

- loss of AC voltage alarm to DC charger unit• Local/ remote operation• Flexible communications media such as radio, Packet

Data, GSM/ GPRS, PSTN, leased lines and fibre optic• Common RTU platform for the pole and ground-mounted

switchgear - can control up to four switching functions

58

Gemini-RTU

59

Other GEMINI Systems

60

Gemini-SCADA Secondary Control System

• PC based SCADA package from CI Technologies

• Lucy Switchgear is a Citect Integration Partner

• Monitoring, data logging and report tasks

• Monitoring of alarm conditions

• User display/ HMI interface

61

Gemini-SCADA Secondary Control System

• Tasks can be installed on different machines

• Open and scaleable architecture

• I/O Communications - DNP3 provided as standard protocol

• Networking

• Password security

62

Gemini-DCData Concentrator

• Provides distributed processing of secondary nodes

• DNP3 protocol as standard to secondary nodes

• Communications adaptation to corporate networks e.g. low power radio or GSM links to high speed networks

1

63

Gemini-DCData Concentrator/ Bridge

• Product development close to completion (available Jan 2005)

• Provides distributed processing of secondary nodes

• DNP3 protocol as standard to secondary nodes with IEC 60870-5-101 or DNP3 on host port to master SCADA/ RTU

• Communications adaptation to corporate networks e.g. low power radio or GSM links to high speed networks

1

64

System Architectures

65

Existing SCADA Systems

Switchgear

Gemini-RTUs

Communications Media

Modems

Existing SCADA or NMS

Modem

66

Existing SCADA Systems

• Protocols

Gemini-RTU (host port) DNP3,IEC 60870-5-101

WISP+

Modbus

NB - DNP3 & IEC 60870-5-101 open world standards,

WISP+ Schneider proprietary and Modbus for

industrial applications• Communications

Radio, Packet Data (Paknet), GSM/ GPRS, pilot wire orleased lines, Bluetooth and fibre optic

67

Standalone Gemini-SCADA

Switchgear

Gemini-RTUs

Communications Media

Modems

Gemini-SCADA

Modem

68

Standalone Gemini-SCADA

• Protocols

Gemini-SCADA DNP3

Gemini-RTU (host port) DNP3

For this system architecture, DNP3 is our preferred

protocol. However, IEC 60870-5-101 is available as

an option.

• Communications

As specified for existing SCADA systems

69

Gemini-DC(Data Concentrator/ Bridge)

Gemini-DC

SCADA

NB - DNP3 links throughout

Gemini-RTUs

Repeater

70

Gemini-DCData Concentrator/ Bridge• Protocols

Gemini-DC to SCADA DNP3/ IEC 60870-5-101 (serial link)

Gemini-RTU (host port) DNP3• Communications

Low power radio or GSM predominately

NB• Gemini-DC will reside mainly in primary substations

adjacent to primary RTU• Intermediate node acts as a Store/ Forward of

messages to other RTUs. This provides greater transmission coverage

71

Automation Project References

72

Recent Experience

Eastern Electricity (24-7), UK: Contract for 50 Remote control RMUs - inc. RTU, PakNet Pad and PSU.

Discussing complete installation, commissioning and radio studies.

London Electricity (24-7), UK: 400 RMUs installed fitted with single and double actuators. Pluto units also fitted to some units with PSTN line connection.

S&SE, UK: 500 retrofit automation kits installed comprising actuator and interface control electronics.

Discussing supply and installation of RTU and communications along with actuator simultaneously.

Power Grid, Singapore: 500 remotely controlled RMUs, equipped with actuators and provision for Control Box and with LV control and monitoring terminations.

73

Recent Experience (contd)

EAC, Cyprus: 85 RMU retrofit actuators and 10 Rapier RX-RC24s for a remote control pilot project. Rapier RX-RC24 devices are embedded with DNP3 firmware and communications achieved via the GSM network.

Central Networks, UK: Trials of automated FRMUs for Auto-changeover at open point and Auto-open at midpoint. Equipped with Gemini-RTU and Paknet communications. 350 off Rapier RX-RC12’s installed on network.

Northern Ireland Electricity, UK: Trials of Rapier RX-RC12s being remotely controlled using the IEC 60870-5-101 protocol and high power radio communications. 120 off Gemini-RTUs supplied for autorecloser interfaces.

United Utilities, UK: Trial of two automated Rapier RX-RC’s at open points; equipped with Gemini-RTUs and GSM communications.

74

End of Presentation

Any questions?