Power Quality Product Overview. GE Consumer & Industrial. Content. Introduction UPS Products Static Transfer Switches GE’s unique technologies. Energy is the Key. The actual power grid was built to supply the 3 main inventions of the last Century: the light bulb the electric motor - PowerPoint PPT Presentation
Citation preview
1 /GE /E. Timm
July 2006
Power QualityProduct OverviewGE Consumer & Industrial
2 /GE /
July 2006
• Introduction
• UPS Products
• Static Transfer Switches
• GE’s unique technologies
Content
3 /GE /
July 2006
To produce, store, transfer and restore 4 MB of datawe „burn“ the energy equivalent of 1 Kilo of coal
The actual power grid was built to supply the 3 main inventions of the last Century:
the light bulbthe electric motorthe refrigerator
Utilities provide a reliability of 99,9% = 8 hours out of tolerance/year
„good enough“ for this type of application
Energy is the Key
4 /GE /
July 2006
„DIGITAL WORLD“ELECTRICAL POWER
CRITICAL RAW MATERIAL OF THE 21ST CENTURY:QUANTITY & QUALITY & RELIABILITY OF ELECTRONS
Need: 99,9999999..%Fact: 99.9%
=
Utility not meeting business requirements
Process
5 /GE /
July 2006
UtilityFeed/Sub
station
TVSS
ATS
ProtectiveRelays
STS
SwitchGear
PDU
PLC Drives
BatteryMonitoring
Flywheel
SuperCap
Battery
Ride-throughEnergy Storage
DieselGenset
TurbineFuelCell
Local Generation
EnergyRental
customized premium power solutions
UPS
DC48 /120 V
LineCond.
ActiveFilter
Quality &Reliability
Quantity &Availability
Power Quality Cluster
6 /GE /
July 2006
Key Products – GE C&I
UPS Uninterruptible Power Supply
Active Filters
Static Transfer Switches
Protecting equipment and processes against disturbances in the utility
Eliminating higher harmonic currents, mains cleaning
Automatic switches to increase reliability of supplyto loads
7 /GE /
July 2006
Medium Enterprise – Data CentreLarge Enterprise – Data Centre
External Data CentreSemiconductor Fab
Process IndustryBioTech, Pharmaceuticals, Hospitals
Small Enterprise – Data Centre
Telecom - WirelessTelecom - Wireline
Commercial
UPS – Product Range
0.35 – 3 KVA 3 to 30 KVA Single or Redundant
20 – 120 KVASingle or Redundant
– 4’000 KVARedundant
8 /GE /
July 2006
350 - 1000VA (Sourced)
• Entry level product range
• Line interactive pluggable
500 - 3000VA
• Mid level line interactive pluggable
• High reliability and performance
600 - 4000VA
• Double conversion pluggable
• Mature technology, replacement 2006
• Single PC• EPOS • CCTV cameras
ML Series
Match
NetPro
Single Phase output UPS Typical Application
LP Series3 - 10kVA LP11/31T8 - 20kVA LP31
• Double conversion installable
• Unique RPA
• Small server• Hubs, routers
• Servers and PCs• Small IT networks• Telecom networks• Process control
• Mid-range IT networks• Healthcare equipment• Process control• Large telecom networks
9 /GE /
July 2006
LP33 Series
SitePro
Three Phase output UPS
SG Series
80 - 200kVA
•Best in class in output performance
•EMC solution for critical applications
10 - 60kVA ; 250 - 500kVA
•Transformer base design
•Configurable according to installation requirements
10 - 120kVA
•Transformerless; Clean Input Tech
•Small footprint, front access
• Healthcare equipment• IT infrastructure• Telecom networks
• Process control• Transportation infrastructure• Telecom networks• Healthcare equipment
• IT networks• Industrial applications• Broadcasting systems
Typical Application
10 /GE /
July 2006
K1normally OFF
U1
CT1
O2
K2normally OFF
K5normally ON
O3
K4normally ON
PRIMARY
SOURCE
L1 L2
U2
O1
K3normally ON
SECONDARYSOURCE
STSOUTPUT
Static Transfer Switches
STS Static Transfer Switch
• Electronic switch that ensures uninterruptible switching between a preferred source and an alternate source. (primary or secondary)
• Automatic operation – in case the preferred source is out of limits (fails) the load is automatically transferred to the healthy alternate source.
• This transfer is seamless in case both sources are synchronized
11 /GE /
July 2006
Static Transfer Switches
• Redundant power supplies
• Redundant cooling
• Over voltage protection
• Front access for service
• Manual bypass
• Alarm contact interface
• User friendly control panel
• Neutral dimensioned for 200%
• Unique conductivity detection
3 phase STS: 25 – 630 A 400V 3&4 pole
1 phase STS: 25 – 400 A 230V 1&2 pole
12 /GE /
July 2006
RPA Redundant Parallel ArchitectureHigh reliability UPS cluster with no single point of failure
SEM Super ECO ModeSaving energy whilst maintaining high protection level
IEM Intelligent Energy Management Award winning concept for energy savings
GE‘s unique technologies
13 /GE /
July 2006
Redundant Parallel Architecture
• Up to 8 units in parallel• Any UPS able to be the logic
leader• Decentralized bypass• Redundant Communication Bus• Transparent failover and
recovery process • True redundancy with no single
point of failure
to critical load
utility supply
14 /GE /
July 2006
Super ECO Mode
AC
AC
DC
DC
2 Conversion Processes:
+ optimal protection for mission critical applications- increased energy losses
SS
Balance:
For less critical loads run UPS on bypass continuously
In case mains is out of limits transfer the load to inverterSuper ECO Mode: not only is the load supplied on
bypass, but the inverter is also switched off, increasing energy savings
VFI concept
15 /GE /
July 2006
Super ECO Mode
Super ECO mode• Efficiency : 98% • to Inverter in case Bypass is out of limits • Fast error detection• Extremely short transfer times (<2 ms)• User definable scheduling• Available for 10 – 500 kVA
Bypass on/off
Inverter current
Inverter control
Output voltage
Fast Transfer to Inverter
< 2ms
16 /GE /
July 2006
UPS: Cost of Ownership• Purchasing Cost & Installation Cost• Direct Operating Cost Efficiency = Energy Losses = Heat• Indirect Operating Cost
Heat = air conditioning / Ventilation
• Maintenance Cost
Intelligent Energy Management
17 /GE /
July 2006
Typical Load Situation
Load
Time
100%
20%20%
70% 30%
Intelligent Energy Management
Full load: 5 x 10 = 50 hoursPartial load: 5 x 14 + 2 x 24 = 188 hours
18 /GE /
July 2006
LOAD 300 kVA
75 %
Time
Load
8.00 18.00
LOAD = 100 %
Load%
Efficiency4 UPS
UPS 1 - 100 kVA
UPS 2 - 100 kVA
UPS 3 - 100 kVA
UPS 4 - 100 kVA
Full-Load Condition
75 %
75 %
75 %
Intelligent Energy Management
19 /GE /
July 2006
LOAD 60 kVA
8.00
Time
18.00
LOAD = 20 %
Load
Load%
Efficiency4 UPS
UPS 1 - 100 kVA
UPS 2 - 100 kVA
UPS 3 - 100 kVA
UPS 4 - 100 kVA
15 %
15 %
15 %
15 %
Intelligent Energy Management
Partial Load Condition
20 /GE /
July 2006
UPS 1 - 100 kVA
UPS 2 - 100 kVA
UPS 3 - 100 kVA
UPS 4 - 100 kVA
LOAD 60 kVA
Time18.00 8.00
LOAD = 20 %Load
Load%
Efficiency2 UPS
30 %
30 %
Intelligent Energy Management
Partial Load Condition with IEM (redundancy)
21 /GE /
July 2006
LOAD 60 kVA
LoadTime
18.00 8.00
LOAD = 20 %
Load%
UPS 1 - 100 kVA
UPS 2 - 100 kVA
UPS 3 - 100 kVA
UPS 4 - 100 kVA
Efficiency1 UPS
60 %
Intelligent Energy Management
Partial Load with IEM (mains redundancy)
22 /GE /
July 2006
Number of UPS : 4Full load condition : 75%Partial Load Condition : 10%Losses : efficiency of UPS*Cost per kWh : 0.11 $Hours at full load : 50h / weekHours at partial load : 118 / week
*: Load Efficiency
75% 94% 50% 93% 30% 87.5% 15% 79%
101520304060801001201602002503304005000
5000
10000
15000
20000
25000
30000
35000
UPS POWER (kVA)
IEM Savings with Utility redundancyIEM Savings with UPS redundancy
US$
Intelligent Energy Management
23 /GE /
July 2006