DEPARTMENT OF ELECTRICAL ENGINEERING
BABU BANARASI DAS NORTHERN INDIA INSTITUTE OF TECHNOLOGY,
LUCKNOW.
SUMMER TRAINING REPORT
TRANSMISSION AND PROTECTION OF POWER AT
POWERGRID CORPORATION OF INDIA LTD.
LUCKNOW
Submitted By:-
Name: Saurabh Pal
Roll No: 1005620088
(10.06.2013 22.07.2013)
7/28/2019 Power Grid, Lucknow
2/27
Acknowledgement
It is a pleasure to present this report which I had compiled during my training at
POWER GRID, Lucknow. There are many persons whom I would like to thank. Following in
the list are who provided me with valuable knowledge during my training period.
1). Devashish shukla.
2).Irfan sir.
I am also thankful to Mr. Irfan sir, our training in charge for his co-operationthroughout my presence in the organisation. He was very helpful and supportive throughout
my training and also helped me in preparing this report.
Without the help of these people I would have never been able to complete this report
successfully.
SAURABH PAL
B.Tech 3rd year
(Electrical Engg.)
BBDNIIT,
Lucknow.
7/28/2019 Power Grid, Lucknow
3/27
TABLE OF CONTENT
1). Electrical Circuit Breaker. 01
2). Electrical Isolator or Electrical Isolation Switch. 14
3). Wave trap. 17
4). Current transformer. 18
5). Capacitor voltage transformer. 21
6). Lightning arrester. 22
7/28/2019 Power Grid, Lucknow
4/27
1 | P a g e
Electrical Circuit Breaker
What is Circuit Breaker ?
Definition of Circuit Breaker : Electrical Circuit Breaker is a switching device which canbe operated manually as well as automatically for controlling and protection of electrical power
system respectively. As the modern power system deals with huge currents, the spacial attention
should be given during designing ofcircuit breaker to safe interruption of arc produced during
the operation of circuit breaker. This was the basic definition of circuit breaker.
Introduction to Circuit Breaker
The modern power system deals with huge power network and huge numbers of associated
electrical equipment. During short circuit fault or any other types of electrical fault these
equipment as well as the power network suffer a high stress of fault current in them which may
damage the equipment and networks permanently. For saving these equipments and the power
networks the fault current should be cleared from the system as quickly as possible. Again after
the fault is cleared, the system must come to its normal working condition as soon as possible for
supplying reliable quality power to the receiving ends. In addition to that for proper controlling
of power system, different switching operations are required to be performed. So for timely
disconnecting and reconnecting different parts of power system network for protection and
control, there must be some special type of switching devices which can be operated safely under
huge current carrying condition. During interruption of huge current, there would be large arcing
in between switching contacts, so care should be taken to quench these arcs in safe manner. Thecircuit breaker is the special device which does all the required switching operations during
current carrying condition. This was the basic introduction to circuit breaker
Working Principle of Circuit Breaker
The circuit breaker mainly consists of fixed contacts and moving contacts. In normal on
condition of circuit breaker, these two contacts are physically connected to each other due to
applied mechanical pressure on the moving contacts. There is an arrangement stored potential
energy in the operating mechanism of circuit breaker which is realized if switching signal given
to the breaker. The potential energy can be stored in the circuit breaker by different ways like bydeforming metal spring, by compressed air, or by hydraulic pressure. But whatever the source of
potential energy, it must be released during operation. Release of potential energy makes sliding
of the moving contact at extremely fast manner. All circuit breaker have operating coils (tripping
coils and close coil), whenever these coils are energized by switching pulse, the plunger inside
them displaced. This operating coil plunger is typically attached to the operating mechanism of
circuit breaker, as a result the mechanically stored potential energy in the breaker mechanism is
7/28/2019 Power Grid, Lucknow
5/27
2 | P a g e
released in forms of kinetic energy, which makes the moving contact to move as these moving
contacts mechanically attached through a gear lever arrangement with the operating mechanism.
After a cycle ofoperation of circuit breaker the total stored energy is released and hence the
potential energy again stored in the operating mechanism of circuit breaker by means of spring
charging motor or air compressor or by any other means. Till now we have discussed about
mechanical working principle of circuit breaker. But there are electrical characteristics of a
circuit breaker which also should be consider in this discussion of operation of circuit breaker.
Lets have a discussion on electrical principle of circuit breaker
The circuit breaker has to carry large rated or fault power. Due to this large power there is
always dangerously high arcing between moving contacts and fixed contact during operation of
circuit breaker. Again as we discussed earlier the arc in circuit breaker can be quenching safely if
the dielectric strength between the current carrying contacts of circuit breaker increases rapidly
during every current zero crossing of the alternating current. The dielectric strength of the media
in between contacts can be increased in numbers of ways, like by compressing the ionized arcing
media since compressing accelerates the deionization process of the media, by cooling the arcing
media since cooling increase the resistance of arcing path or by replacing the ionized arcing
media by fresh gasses. Hence a numbers of arc quenching processes should be involved in
operation of circuit breaker.
Types of Circuit Breaker
According different criteria there are different types of circuit breaker
According to their arc quenching media the circuit breaker can be divided as
1). Air circuit breaker.
2). Oil circuit breaker.
3) SF6 Circuit Breaker.
4) Vacuum Circuit Breaker.
According to their services the circuit breaker can be divided as
1) Outdoor Circuit Breaker
2) Indoor Breaker
According to the operating mechanism of circuit breaker they can be divided as
7/28/2019 Power Grid, Lucknow
6/27
3 | P a g e
1) Spring operated Circuit Breaker
2) Pneumatic Circuit Breaker
3) Hydrolic Circuit Breaker
According to the voltage level of installation types of circuit breaker are referred as
1) High Voltage Circuit Breaker
2) Medium Voltage Circuit Breaker
3) Low Voltage Circuit Breaker
7/28/2019 Power Grid, Lucknow
7/27
4 | P a g e
Air Circuit Breaker Air Blast Circuit Breaker
This type of circuit breakers, is those kind of circuit breaker which operates in air at atmosphericpressure. After development of oil breaker, the medium voltage air circuit breaker (ACB) is
replaced completely by oil circuit breaker in different countries. But in countries like France and
Italy, ACBs are still preferable choice up to voltage 15 KV. It is also good choice to avoid the
risk of oil fire, in case of oil circuit breaker. In America ACBs were exclusively used for the
system up to 15 KV until the development of new vacuum and SF6 circuit breakers.
Working principle of Air Circuit Breaker
The working principle of this breaker is rather different from those in any other types of circuit
breakers. The main aim of all kind of circuit breaker is to prevent the reestablishment of arcingafter current zero by creating a situation where in the contact gap will withstand the system
recovery voltage. The air circuit breaker does the same but in different manner. For
interrupting arc it creates an arc voltage in excess of the supply voltage. Arc voltage is defined as
the minimum voltage required maintaining the arc. This circuit breaker increases the arc voltage
by mainly three different ways,
It may increase the arc voltage by cooling the arc plasma. As the temperature of arc plasma is
decreased, the mobility of the particle in arc plasma is reduced; hence more voltage gradient is
required to maintain the arc.
It may increase the arc voltage by lengthening the arc path. As the length of arc path is increased,
the resistance of the path is increased, and hence to maintain the same arc current more voltage is
required to be applied across the arc path. That means arc voltage is increased.
Splitting up the arc into a number of series arcs also increases the arc voltage.
Types of ACB
There are mainly two types of ACB are available.
1) Plain air circuit breaker
2) Air blast Circuit Breaker.
7/28/2019 Power Grid, Lucknow
8/27
5 | P a g e
Operation of ACB
The first objective is usually achieved by forcing the arc into contact with as large an area as
possible of insulating material. Every air circuit breaker is fitted with a chamber surrounding the
contact. This chamber is called arc chute. The arc is driven into it. If inside of the arc chute is
suitably shaped, and if the arc can be made conform to the shape, the arc chute wall will help to
achieve cooling. This type of arc chute should be made from some kind of refractory material.
High temperature plastics reinforced with glass fiber and ceramics are preferable materials for
making arc chute.
The second objective that is lengthening the arc path, is achieved concurrently with fist
objective. If the inner walls of the arc chute is shaped in such a way that the arc is not only
forced into close proximity with it but also driven into a serpentine channel projected on the arc
chute wall. The lengthening of the arc path increases the arc resistance.
The third technique is achieved by using metal arc slitter inside the arc chute. The main arc chute
is divided into numbers of small compartments by using metallic separation plates. These
metallic separation plates are actually the arc splitters and each of the small compartments
behaves as individual mini arc chute. In this system the initial arc is split into a number of series
arcs, each of which will have its won mini arc chute. So each of the split arcs has its won cooling
and lengthening effect due to its won mini arc chute and hence individual split arc voltage
becomes high. These collectively, make the over all arc voltage, much higher than the system
voltage. This was working principle of air circuit breaker now we will discuss in details the
operation of ACB in practice.
The air circuit breaker, operated within the voltage level 1KV, does not require any arc control
device. Mainly for heavy fault current on low voltages (low voltage level above 1 KV) ABCs
with appropriate arc control device, are good choice. These breakers normally have two pairs of
contacts. The main pair of contacts carries the current at normal load and these contacts are made
of copper. The additional pair is the arcing contact and is made of carbon. When circuit breaker
is being opened, the main contacts open first and during opening of main contacts the arcing
contacts are still in touch with each other. As the current gets, a parallel low resistive path
through the arcing contact during opening of main contacts, there will not be any arcing in the
main contact. The arcing is only initiated when finally the arcing contacts are separated. The
each of the arc contacts is fitted with an arc runner which helps, the arc discharge to move
upward due to both thermal and electromagnetic effects as shown in the figure. As the arc is
driven upward it enters in the arc chute, consisting of splitters. The arc in chute will become
colder, lengthen and split hence arc voltage becomes much larger than system voltage at the time
ofoperation of air circuit breaker, and therefore the arc is quenched finally during the current
zero.
7/28/2019 Power Grid, Lucknow
9/27
6 | P a g e
SF6 Circuit Breaker
A circuit breaker in which the current carrying contacts operate in Sulphur Hexafluoride or SF6
gas is known as an SF6 Circuit Breaker.
SF6 has excellent insulating property. SF6 has high electro-negativity. That means it has high
affinity of absorbing free electron. Whenever a free electron collides with the SF6 gas molecule,
it is absorbed by that gas molecule and forms a negative ion.
The attachment of electron with SF6 gas molecules may occur in tow different ways,
1) SF6 + e = SF6
2) SF6 + e = SF5
+ F
These negative ions obviously much heavier than a free electron and therefore over all mobility
of the charged particle in the SF6 gas is much less as compared other common gases. We know
that mobility of charged particle is majorly responsible for conducting current through a gas.
Hence, for heavier and less mobile charged particles in SF6 gas, it acquires very high
dielectric strength. Not only the gas has a good dielectric strength but also it has the unique
property of fast recombination after the source energizing the spark is removed. The gas has also
very good heat transfer property. Due to its low gaseous viscosity (because of less molecular
mobility) SF6 gas can efficiently transfer heat by convection. So due to its high dielectric
strength and high cooling effect SF6 gas is approximately 100 times more effective arc
7/28/2019 Power Grid, Lucknow
10/27
7 | P a g e
quenching media than air. Due to these unique properties of this gas SF6 Circuit Breaker is
used in complete range of medium voltage and high voltage electrical power system. These
circuit breakers are available for the voltage ranges from 33KV to 800KV and even more.
Disadvantages of SF6 CB
The SF6 gas is identified as a greenhouse gas, safety regulation are being introduced in
many countries in order to prevent its release into atmosphere.Puffer type design of SF6 CB
needs a high mechanical energy which is almost five times greater than that of oil circuit breaker.
Types of SF6 Circuit Breaker
There are mainly three types of SF6 CB depending upon the voltage level of application
1) Single Interrupter SF6 CB applied for up to 245KV(220KV) system
2) Two Interrupter SF6 CB applied for up to 420KV(400KV) system
3) Four Interrupter SF6 CB applied for up to 800KV(715KV) system
7/28/2019 Power Grid, Lucknow
11/27
8 | P a g e
Working of SF6 Circuit Breaker
The working of SF6 CB of first generation was quite simple it is some extent similar to air blast
circuit breaker. Here SF6 gas was compressed and stored in a high pressure reservoir. During
operation of SF6 circuit breaker this highly compressed gas is released through the arc and
collected to relatively low pressure reservoir and then it pumped back to the high pressure
reservoir for reutilize.
The working of SF6 circuit breaker is little bit different in moder time. Innovation of puffer
type design makes operation of SF6 CB much easier. In buffer type design, the arc energy is
utilized to develop pressure in the arcing chamber for arc quenching.
7/28/2019 Power Grid, Lucknow
12/27
9 | P a g e
Here the breaker is filled with SF6 gas at rated pressure. There are two fixed contact fitted with a
specific contact gap. A sliding cylinder bridges these to fixed contacts. The cylinder can axially
slide upward and downward along the contacts. There is one stationary piston inside the cylinder
which is fixed with other stationary parts of the SF6 circuit breaker, in such a way that it can not
change its position during the movement of the cylinder. As the piston is fixed and cylinder is
movable or sliding, the internal volume of the cylinder changes when the cylinder slides.
During opening of the breaker the cylinder moves downwards against position of the fixed piston
hence the volume inside the cylinder is reduced which produces compressed SF6 gas inside the
cylinder. The cylinder has numbers of side vents which were blocked by upper fixed contact
body during closed position. As the cylinder move further downwards, these vent openings cross
the upper fixed contact, and become unblocked and then compressed SF6 gas inside the cylinder
will come out through this vents in high speed towards the arc and passes through the axial hole
of the both fixed contacts. The arc is quenched during this flow of SF6 gas.
During closing of the SF6 circuit breaker, the sliding cylinder moves upwards and as the position
of piston remains at fixed height, the volume of the cylinder increases which introduces low
pressure inside the cylinder compared to the surrounding. Due to this pressure difference SF6 gas
from surrounding will try to enter in the cylinder. The higher pressure gas will come through the
axial hole of both fixed contact and enters into cylinder via vent and during this flow; the gas
will quench the arc.
7/28/2019 Power Grid, Lucknow
13/27
10 | P a g e
Oil Circuit Breaker Bulk and Minimum Oil
Circuit Breaker
Mineral oil has better insulating property than air. In oil circuit breaker the fixed contact and
moving contact are immerged inside the insulating oil. Whenever there is a separation of current
carrying contacts in the oil, the arc is initialized at the moment of separation of contacts, and due
to this arc the oil is vaporized and decomposed in mostly hydrogen gas and ultimately creates a
hydrogen bubble around the arc. This highly compressed gas bubble around the arc prevents re-
striking of the arc after current reaches zero crossing of the cycle. The Oil Circuit Breaker is
the one of the oldest type of circuit breakers.
Operation of Oil Circuit Breaker
The operation of oil circuit breaker is quite simple lets have a discussion. When the current
carrying contacts in the oil are separated an arc is established in between the separated contacts.
Actually, when separation of contacts has just started, distance between the current contacts is
small as a result the voltage gradient between contacts becomes high. This high voltage gradient
between the contacts ionized the oil and consequently initiates arcing between the contacts. This
arc will produce a large amount of heat in surrounding oil and vaporizes the oil and decomposes
the oil in mostly hydrogen and a small amount of methane, ethylene and acetylene. The
hydrogen gas can not remain in molecular form and its is broken into its atomic form releasing
lot of heat. The arc temperature may reach up to 5000oK. Due to this high temperature the gas is
liberated surround the arc very rapidly and forms an excessively fast growing gas bubble aroundthe arc. It is found that the mixture of gases occupies a volume about one thousand times that of
the oil decomposed. From this figure we can assume how fast the gas bubble around the arc will
grow in size. If this growing gas bubble around the arc is compressed by any means then rate of
de ionization process of ionized gaseous media in between the contacts will accelerate which
rapidly increase the dielectric strength between the contacts and consequently the arc will be
quenched at zero crossing of the current cycle. This is the basic operation of oil circuit breaker.
In addition to that cooling effect of hydrogen gas surround the arc path also helps, the quick arc
quenching in oil circuit breaker.
Types of oil circuit breakers
There are mainly two types of oil circuit breakers available
7/28/2019 Power Grid, Lucknow
14/27
11 | P a g e
Bulk Oil Circuit Breaker or BOCB
Bulk Oil Circuit Breaker orBOCB is such types of circuit breakers where oil is used as arc
quenching media as well as insulating media between current carrying contacts and earthed parts
of the breaker. The oil used here is same as transformer insulating oil.
Minimum Oil Circuit Breaker or MOCB
These types of circuit breakers utilize oil as the interrupting media. However, unlike bulk oil
circuit breaker, a minimum oil circuit breaker places the interrupting unit in insulating
chamber at live potential. The insulating oil is available only in interrupting chamber. The
features of designing MOCB is to reduce requirement of oil, and hence these breaker are called
minimum oil circuit breaker.
Arc quenching in bulk oil circuit breaker
When the current carrying contacts in the oil are separated an arc is established in between the
separated contacts.
This arc will produce rapidly growing gas bubble around the arc. As the moving contact move
away from fixed contact the length of arc is increased as a result the resistance of the arc
increases. The increased resistance causes lowering the temperature and hence reducing the
formation of gasses surround the arc. The arc quenching in bulk oil circuit breaker takes place
when current passes through zero crossing. If we go through the arc quenching phenomenon
more thoroughly we will find many other factors effects the arc quenching in bulk oil circuitbreaker.
7/28/2019 Power Grid, Lucknow
15/27
12 | P a g e
Vacuum Circuit Breaker or VCB and
Vacuum Interrupter
A vacuum circuit breaker is such kind of circuit breaker where the arc quenching takes place in
vacuum. The technology is suitable for mainly medium voltage application. For higher voltage
Vacuum technology has been developed but not commercially viable. The operation of opening
and closing of current carrying contacts and associated arc interruption take place in a vacuum
chamber in the breaker which is called vacuum interrupter. The vacuum interrupter consists of a
steel arc chamber in the centre symmetrically arranged ceramic insulators. The vacuum pressure
inside a vacuum interrupter is normally maintained at 10 6 bar.
The material used for current carrying contacts plays an important role in the performance of the
vacuum circuit breaker. CuCr is the most ideal material to make VCB contacts. Vacuum
interrupter technology was first introduced in the year of 1960. But still it is a developingtechnology. As time goes on, the size of the vacuum interrupter is being reducing from its early
1960s size due to different technical developments in this field of engineering. The contact
geometry is also improving with time, from butt contact of early days it gradually changes to
spiral shape, cup shape and axial magnetic field contact. The vacuum circuit breaker is today
recognized as most reliable current interruption technology for medium voltage system. It
requires minimum maintenance compared to other circuit breaker technologies.
Advantages of vacuum circuit breaker or VCB
Service life of Vacuum Circuit Breaker is much longer than other types of circuit breakers. Thereis no chance of fire hazard as oil circuit breaker. It is much environment friendly than SF6
Circuit breaker. Beside of that contraction of VCB is much user friendly. Replacement of
Vacuum Interrupter (VI) is much convenient.
Operation of Vacuum Circuit Breaker
The main aim of any circuit breaker is to quench arc during current zero crossing, by establishing
high dielectric strength in between the contacts so that reestablishment of arc after current zero
becomes impossible. The dielectric strength of vacuum is eight times greater than that of air and
four times greater than that of SF6 gas. This high dielectric strength makes it possible to quench
a vacuum arc within very small contact gap. For short contact gap, low contact mass and no
compression of medium the drive energy required in vacuum circuit breaker is minimum. When
two face to face contact areas are just being separated to each other, they do not be separated
instantly, contact area on the contact face is being reduced and ultimately comes to a point and
then they are finally de-touched. Although this happens in a fraction of micro second but it is the
fact. At this instant of de-touching of contacts in a vacuum, the current through the contacts
7/28/2019 Power Grid, Lucknow
16/27
13 | P a g e
concentrated on that last contact point on the contact surface and makes a hot spot. As it is
vacuum, the metal on the contact surface is easily vaporized due to that hot spot and create a
conducting media for arc path. Then the arc will be initiated and continued until the next current
zero. At current zero this vacuum arc is extinguished and the conducting metal vapour is re-
condensed on the contact surface. At this point, the contacts are already separated hence there is
no question of re-vaporization of contact surface, for next cycle of current. That means, the arc
cannot be reestablished again. In this way vacuum circuit breaker prevents the reestablishment of
arc by producing high dielectric strength in the contact gap after current zero.
There are two types of arc shapes. For interrupting current up to 10kA, the arc remains diffusedand the form of vapour discharge and cover the entire contact surface. Above 10kA the diffused
arc is constricted considerably by its own magnetic field and it contracts. The phenomenon gives
rise over heating of contact at its center. In order to prevent this, the design of the contacts should
be such that the arc does not remain stationary but keeps travelling by its own magnetic field.
Specially designed contact shape of vacuum circuit breaker make the constricted stationary arc
travel along the surface of the contacts, thereby causing minimum and uniform contact erosion.
7/28/2019 Power Grid, Lucknow
17/27
14 | P a g e
Electrical Isolator or Electrical Isolation
Switch
Definition of Isolator
Circuit breaker always trip the circuit but open contacts of breaker cannot be visible physically
from outside of the breaker and that is why it is recommended not to touch any electrical circuit
just by switching off the circuit breaker. So for better safety there must be some arrangement so
that one can see open condition of the section of the circuit before touching it. Isolator is a
mechanical switch which isolates a part of circuit from system as when required. Electrical
isolators separate a part of the system from rest for safe maintenance works.
So definition of isolator can be rewritten as Isolator is a manually operated mechanical switch
which separates a part of the electrical power system normally at off load condition.
Operation of Electrical Isolator
As no arc quenching technique is provided in isolator it must be operated when there is no
chance current flowing through the circuit. No live circuit should be closed or open by isolator
operation. A complete live closed circuit must not be opened by isolator operation and also a live
circuit must not be closed and completed by isolator operation to avoid huge arcing in between
isolator contacts. That is why isolators must be open after circuit breaker is open and these must
be closed before circuit breaker is closed. Isolator can be operated by hand locally as well as by
motorized mechanism from remote position. Motorized operation arrangement costs more
compared to hand operation; hence decision must be taken before choosing an isolator for system
whether hand operated or motor operated economically optimum for the system. For voltages up
to 145KV system hand operated isolators are used whereas for higher voltage systems like 245
KV or 420 KV and above motorized isolators are used.
Types of Electrical Isolators
There are different types of isolators available depending upon system requirement such as
1).Double Break Isolator
1).Single Break Isolator
3).Pantograph type Isolator
7/28/2019 Power Grid, Lucknow
18/27
15 | P a g e
Depending upon the position in power system, the isolators can be categorized as
Bus side isolator the isolator is directly connected with main bus
Line side isolator the isolator is situated at line side of any feeder
Transfer bus side isolator the isolator is directly connected with transfer bus
Constructional features of Double Break Isolators
Lets have a discussion on constructional features of Double Break Isolators. These have three
stacks of post insulators as shown in the figure. The central post insulator carries a tubular or flat
male contact which can be rotated horizontally with rotation of central post insulator. This rod
type contact is also called moving contact.
7/28/2019 Power Grid, Lucknow
19/27
16 | P a g e
The female type contacts are fixed on the top of the other post insulators which fitted at both
sides of the central post insulator. The female contacts are generally in the form of spring loaded
figure contacts. The rotational movement of male contact causes to come itself into female
contacts and isolators becomes closed. The rotation of male contact in opposite direction make to
it out from female contacts and isolators becomes open.
Rotation of the central post insulator is done by a driving lever mechanism at the base of the post
insulator and it connected to operating handle (in case of hand operation) or motor (in case of
motorized operation) of the isolator through a mechanical tie rod.
Constructional features of Single Break Isolators
The contact arm is divided into two parts one carries male contact and other female contact. The
contact arm moves due to rotation of the post insulator upon which the contact arms are fitted.
Rotation of both post insulators stacks in opposite to each other causes to close the isolator by
closing the contact arm. Counter rotation of both post insulators stacks open the contact arm and
isolator becomes in off condition. This motorized form of this type of isolators is generally used
but emergency hand driven mechanism is also provided.
Earthing Switches
Earthing switches are mounted on the base of mainly line side isolator. Earthing switches are
normally vertically break switches. Earthing arms (contact arm of earthing switch) are normally
aligned horizontally at off condition. during switching on operation, these earthing arms rotate
and move to vertical position and make contact with earth female contacts fitted at the top of the
post insulator stack of isolator at its outgoing side. The erarthing arms are so interlocked with
main isolator moving contacts that it can be closed only when the main contacts of isolator are in
open position. Similarly the main isolator contacts can be closed only when the earthing arms are
in open position.
7/28/2019 Power Grid, Lucknow
20/27
17 | P a g e
Wave trap
Line trap also is known as Wave trap. What it does is trapping the high frequency
communication signals sent on the line from the remote substation and diverting them to the
telecom/teleportation panel in the substation control room (through coupling capacitor andLMU).This is relevant in Power Line Carrier Communication (PLCC) systems for
communication among various substations without dependence on the telecom company
network. The signals are primarily teleportation signals and in addition, voice and data
communication.
Transmission line may carry some disturbance or noise signals having high frequency, it also
carries the high frequency signals from the PLCC. These high frequency signals should not be
coming on the buses as these may damage the equipment on the bays. The Wave trap offers high
impedance to the high frequency communication signals thus obstructs the flow of these signals
in to the substation bus bars. If wave trap were not to be there, then signal loss is more and
communication will be ineffective/probably impossible.
7/28/2019 Power Grid, Lucknow
21/27
18 | P a g e
Current transformer
A current transformer (CT) is used for measurement of alternating electric currents. Current
transformers, together with voltage transformers (VT) (potential transformers (PT)), are known
as instrument transformers. When current in a circuit is too high to directly apply to measuringinstruments, a current transformer produces a reduced current accurately proportional to the
current in the circuit, which can be conveniently connected to measuring and recording
instruments. A current transformer also isolates the measuring instruments from what may be
very high voltage in the monitored circuit. Current transformers are commonly used in metering
and protective relays in the electrical power industry.
Current transformers are used for protection, measurement and control in high voltage electrical
substations and the electrical grid. Current transformers may be installed inside switchgear or in
apparatus bushings, but very often free-standing outdoor current transformers are used. In a
switchyard, live tankcurrent transformers have a substantial part of their enclosure energized atthe line voltage and must be mounted on insulators. Dead tankcurrent transformers isolate the
measured circuit from the enclosure. Live tankCTs are useful because the primary conductor is
short, which gives better stability and a higher short-circuit current withstand rating. The primary
of the winding can be evenly distributed around the magnetic core, which gives better
performance for overloads and transients. Since the major insulation of a live-tank current
transformer is not exposed to the heat of the primary conductors, insulation life and thermal
stability is improved.
Design
Like any other transformer, a current transformer has a primary winding, a magnetic core, and a
secondary winding. The alternating current flowing in the primary produces an alternating
7/28/2019 Power Grid, Lucknow
22/27
19 | P a g e
magnetic field in the core, which then induces an alternating current in the secondary winding
circuit. An essential objective of current transformer design is to ensure that the primary and
secondary circuits are efficiently coupled, so that the secondary current bears an accurate
relationship to the primary current.
The most common design of CT consists of a length of wire wrapped many times around asilicon steel ring passed 'around' the circuit being measured. The CT's primary circuit therefore
consists of a single 'turn' of conductor, with a secondary of many tens or hundreds of turns. The
primary winding may be a permanent part of the current transformer, with a heavy copper bar to
carry current through the magnetic core. Window-type current transformers (aka zero sequence
current transformers, or ZSCT) are also common, which can have circuit cables run through the
middle of an opening in the core to provide a single-turn primary winding. When conductors
passing through a CT are not centered in the circular (or oval) opening, slight inaccuracies may
occur.
Shapes and sizes can vary depending on the end user or switchgear manufacturer. Typicalexamples of low voltage single ratio metering current transformers are either ring type or plastic
moulded case. High-voltage current transformers are mounted on porcelain bushings to insulate
them from ground. Some CT configurations slip around the bushing of a high-voltage
transformer or circuit breaker, which automatically centers the conductor inside the CT window.
The primary circuit is largely unaffected by the insertion of the CT. The rated secondary current
is commonly standardized at 1 or 5 amperes. For example, a 4000:5 CT would provide an output
current of 5 amperes when the primary was passing 4000 amperes. The secondary winding can
be single ratio or multi ratio, with five taps being common for multi ratio CTs. The load, or
burden, of the CT should be of low resistance. If the voltage time integral area is higher than thecore's design rating, the core goes into saturation towards the end of each cycle, distorting the
waveform and affecting accuracy.
Usage
Current transformers are used extensively for measuring current and monitoring the operation of
the power grid. Along with voltage leads, revenue-grade CTs drive the electrical utility's watt-
hour meter on virtually every building with three-phase service and single-phase services greater
than 200 amps.
The CT is typically described by its current ratio from primary to secondary. Often, multiple CTs
are installed as a "stack" for various uses. For example, protection devices and revenue metering
may use separate CTs to provide isolation between metering and protection circuits, and allows
current transformers and different characteristics (accuracy, overload performance) to be used for
the devices.
7/28/2019 Power Grid, Lucknow
23/27
20 | P a g e
Safety precautions
Care must be taken that the secondary of a current transformer is not disconnected from its load
while current is flowing in the primary, as the transformer secondary will attempt to continue
driving current across the effectively infinite impedance up to its core saturation voltage. This
may produce a high voltage across the open secondary into the range of several kilovolts,
causing arcing, compromising operator with equipment safety, or permanently affect the
accuracy of the transformer.
Burden
The secondary load of a current transformer is usually called the "burden" to distinguish it from
the load of the circuit whose current is being measured.
The burden, in a CT metering circuit is the (largely resistive) impedance presented to its
secondary winding. Typical burden ratings for IEC CTs are 1.5 VA, 3 VA, 5 VA, 10 VA, 15VA, 20 VA, 30 VA, 45 VA & 60 VA. As for ANSI/IEEE burden ratings are B-0.1, B-0.2, B-0.5,
B-1.0, B-2.0 and B-4.0. This means a CT with a burden rating of B-0.2 can tolerate up to 0.2
of impedance in the metering circuit before its secondary accuracy falls outside of an accuracy
specification. These specification diagrams show accuracy parallelograms on a grid
incorporating magnitude and phase angle error scales at the CT's rated burden. Items that
contribute to the burden of a current measurement circuit are switch-blocks, meters and
intermediate conductors. The most common source of excess burden is the conductor between
the meter and the CT. When substation meters are located far from the meter cabinets, the
excessive length of wire creates a large resistance. This problem can be reduced by using CTs
with 1 ampere secondaries, which will produce less voltage drop between a CT and its metering
devices.
Knee-point core-saturation voltage
The knee-point voltage of a current transformer is the magnitude of the secondary voltage after
which the output current ceases to linearly follow the input current within declared accuracy. In
testing, if a voltage is applied across the secondary terminals the magnetizing current will
increase in proportion to the applied voltage, up until the knee point.( The knee point is defined
as the voltage at which a 10% increase in applied voltage increases the magnetizing current by
50%). From the knee point upwards, the magnetizing current increases abruptly even with smallincrements in voltage across the secondary terminals. The knee-point voltage is less applicable
for metering current transformers as their accuracy is generally much tighter but constrained
within a very small bandwidth of the current transformer rating, typically 1.2 to 1.5 times rated
current. However, the concept of knee point voltage is very pertinent to protection current
transformers, since they are necessarily exposed to currents of 20 or 30 times rated current
during faults.
7/28/2019 Power Grid, Lucknow
24/27
21 | P a g e
Capacitor voltage transformer
A capacitor voltage transformer (CVT), or capacitance coupled voltage transformer (CCVT) is a
transformer used in power systems to step down extra high voltage signals and provide a low
voltage signal, for measurement or to operate a protective relay. In its most basic form the device
consists of three parts: two capacitors across which the transmission line signal is split, an
inductive element to tune the device to the line frequency, and a transformer to isolate and
further step down the voltage for the instrumentation or protective relay. The tuning of the
divider to the line frequency makes the overall division ratio less sensitive to changes in the
burden of the connected metering or protection devices. The device has at least four terminals: aterminal for connection to the high voltage signal, a ground terminal, and two secondary
terminals which connect to the instrumentation or protective relay. CVTs are typically single-
phase devices used for measuring voltages in excess of one hundred kilovolts where the use of
wound primary voltage transformers would be uneconomical. In practice, capacitor C1 is often
constructed as a stack of smaller capacitors connected in series. This provides a large voltage
drop across C1 and a relatively small voltage drop across C2.
7/28/2019 Power Grid, Lucknow
25/27
22 | P a g e
The CVT is also useful in communication systems. CVTs in combination with wave traps are
used for filtering high frequency communication signals from power frequency. This forms a
carrier communication network throughout the transmission network.
A capacitive voltage transformer works on the principle of voltage division, by using two
capacitances, one many times larger than the other. So for example, if the capacitances are C1and C2 (C2>C1), and we need to measure a voltage V, the voltage across the larger capacitance
C2 will be V2 = V*C1/(C1+C2) ~. Thus, we have effectively reduced the voltage level to a
fraction of the original without using step down transformers (which for larger voltages will be
bulky and expensive). CVTs on the other hand, are cheaper and smaller. This V2 can be further
isolated and stepped down using a step-down transformer.
Lightning arrester
A lightning arrester (in Europe: surge arrester) is a device used on electrical power systems andtelecommunications systems to protect the insulation and conductors of the system from the
damaging effects of lightning. The typical lightning arrester has a high-voltage terminal and a
ground terminal. When a lightning surge (or switching surge, which is very similar) travels along
the power line to the arrester, the current from the surge is diverted through the arrestor, in most
cases to earth.
In telegraphy and telephony, a lightning arrestor is placed where wires enter a structure,
preventing damage to electronic instruments within and ensuring the safety of individuals near
them. Smaller versions of lightning arresters, also called surge protectors, are devices that are
connected between each electrical conductor in power and communications systems and theEarth. These prevent the flow of the normal power or signal currents to ground, but provide a
path over which high-voltage lightning current flows, bypassing the connected equipment. Their
purpose is to limit the rise in voltage when a communications or power line is struck by lightning
or is near to a lightning strike.
If protection fails or is absent, lightning that strikes the electrical system introduces thousands of
kilovolts that may damage the transmission lines, and can also cause severe damage to
transformers and other electrical or electronic devices. Lightning-produced extreme voltage
spikes in incoming power lines can damage electrical home appliances.
7/28/2019 Power Grid, Lucknow
26/27
23 | P a g e
Working of lightning arrester
The lightning arrestor protects the structure from damage by intercepting flashes of lightning and
transmitting their current to the ground. Since lightning strikes tends to strike the highest objectin the vicinity, the rod is placed at the apex of a tall structure. It is connected to the ground by
low-resistance cables. In the case of a building, the soil is used as the ground, and on a ship,
water is used. A lightning rod provides a cone of protection, which has a ground radius
approximately, equal to its height above the ground.
7/28/2019 Power Grid, Lucknow
27/27
LA Characteristics
Recommended