View
212
Download
0
Category
Preview:
Citation preview
Also available in three phase with Motor Control Center (MCC). Separate spec sheets are available for these configurations.
The three phase P series quarter turn actuators have been designed for dependable performance in rugged industrial applications such as clean water and wastewater treatment, mining, process control, power and damper control. ProMation Engineering has an extensive stock of electric actuators and can ship product very rapidly, worldwide.The XMCC Series is a 3 Phase electric actuator with the same rugged industrial features ProMation is known for:
• Clutchless Manual Override • Easy to see raised position indicator • Ruggedboard internal soldered connections • NEMA 4X enclosures
The XMCC Series features a polyphase motor and is designed for use with your existing 3 phase motor control center (phase monitoring and motor control must be provided in any 3 phase installation).
Product Notes:1. The 3 Phase P Series can be ordered as an on/off (two position) model that can also be used in bump/jog applications.2. It can also be ordered with a premium internal proportional control card that accepts a wide range of control
signals, generates multiple feedback signals, and has look-ahead fault prevention. 3. Care must be taken during installation to make sure local phasing is correct for this actuator.
SD
15_P213_X
MC
C Ver D
_050515
Page 1 of 4 P2/3 XMCC Series
Product is shipped at MID-STROKE position to allow up to 6 seconds run time after power up to determine if the actuator is running in the correct direction. If it is not, immediately remove power to avoid possible damage to the actuator end stops.
P2/3 XMCC N4
Wire Sizing Chart
ActuatorSpecifications P2 P3Torque “lb/Nm 800”lbs/90Nm 1335“lbs/150NmSupply Voltage 230/3/60 380/3/60 440/3/60 480/3/60 230/3/60 380/3/60 440/3/60 480/3/60Max Inrush Current 1.4A 0.7A 0.9A 0.9A 1.4A 0.7A 0.9A 0.9ARunning Current 0.8A 0.4A 0.4A 0.4A 0.8A 0.4A 0.4A 0.4AMotor PolyphaseRuntime (90°@60Hz/vdc) 15 sec 22 secRuntime (90°@50Hz) 17 sec 26 secDuty Cycle On/Off/Jog: 25%, Proportional: Managed (75% maximum)Motor Starts 1200 per hourWeight 26lbs/12kgMechanical Connections ISO5211 F07 8pt 22mmElectrical Entry (2) 3/4” NPT Electrical Terminations 12-16gaEnvironmental Rating NEMA 4/4X Manual Override 5” HandwheelControl On/Off/Jog / ProportionalActuator Case Material Aluminum Alloy, Powder coated
Motor Protection 230°F/110°C Thermal F* Class*Totally Enclosed Non-Ventilated Motors
Ambient Temperature Operating Range
-22°F to +125°F-30°C to +52°C
Data Sheet
P2/3 3 Phase XMCCOn/Off/Jog/Proportional
ISO5211 F07 8P22
P Series Exploded View
Easily distinguishable yellow/red position
indicator
Worm Drive
Heavy Duty Drive Motor
Easily accessible switch &
cam stacks
Modular ControlCards
Clutchless OverrideHandwheel
Aluminum Casting4X Protection
Mechanical Stop Screws (2)
Epicyclic Gearing
Aluminum Casting4X Protection
NEMA 4Cover Seal
(Typical)
Application Notes:1. These actuators are to be mounted ONLY between a horizontal and upright position.2. When installing conduit, use proper techniques for entry into the actuator. Use drip loops to prevent
conduit condensate from entering the actuator. 3. Both NPT conduit ports MUST use proper equipment to protect the NEMA 4X integrity of the housing. 4. The anti-condensate heater is to be used in ALL applications. 5. Do not install or store the actuator outdoors or in humid environments without power to the heater.6. Use proper wire size to prevent actuator failure (see wire sizing chart). 7. Mechanical travel stops exist to prevent over-rotation for manual override only. They are not intended
to stop motor driven rotation.8. Do not parallel wire multiple actuators together without utilizing isolation relays! If this is your
intention, please contact ProMation Engineering for a multiple actuator parallel wiring diagram.
Switch Logic Map and Switch/Cam Arrangement
Term
inal
ID#
12
11
10
9
8
7
-5° 0°CW CCW
85°5° 90° 95°
SW3 CCW AUX(Factory Set - Adj)
SW4 CW AUX(Factory Set - Adj)}
}Closed Common
Open Common
}Used by Controller
Open
Not Closed
Closed
Not Open
Switch sequencing data is provided in the table below to show the change-of-state points during the rotation of the actuator from OPEN to CLOSED and back again. The red bar indicates when that terminal makes with it’s respective common.
SW1 and SW2 are set at the factory and should NOT be changed. The INCLUDED auxiliary switches SW3 & SW4 are forterminals7thru12andthosesetpointsmaybemodifiedifneed be. When so optioned, SW5 & SW6 auxiliary switches are initially set to function the same as auxiliary switches SW3 & SW4.
On/Off Switch/Cam arrangement shown
SD
15_P
213_
XM
CC
Ver
D_0
5051
5
Page 2 of 4 P2/3 XMCC Series
P2/3 Series Dimensional Data1
1
2
2
A A
B B
Drawn By
Finish
Promation Engineering Inc.16138 Flight Path Drive
Brooksville, Fl 34604Phone: 352-544-8436Fax: 352-544-8439
This Document is the property of ProMation Engineering,Inc. Distribution of this document without the written
consent of the owner is Strictly forbidden. Failure to comply will incur a liability for Damages.
Checked By4/8/2015
P2~P3 Dim Data Rev.
G
NO SCALE Sheet Number: 1
Material
ProMation Engineering, Inc.KHL
KHL
4/25/2013
P2_3 F07 8P22 DimData.idw
Created:
Last Checked:
Part No.
Dwg. Name
Dimensional Data for P2~P3 Actuators
Engineering Change NoticeChange Date Description Name
04.25.13 Document transferred to Inventor format KHL
11.12.13 Added rounded edges on Drive Coupling Data KHL
04.15.2014 Added tolerance on drive coupling data KHL
10.07.2014 Pushed square dimension to three decimal places KHL
REV
A
B
C
D
E
F
Dimensional Tolerances (Unless Otherwise Noted):X ± 2.5mm [X.X ± .1]
X.X ± .3mm [X.XX ± .01"]X.XX ± .13mm [X.XXX ± .005"]
ALL TOLERANCE FEATURES IN mm
G 04.08.2015 Added Isometric view of Drive Coupling and "Depth" tag for clarity KHL
H
Drive Coupling Fabrication Data
22.00 - .13.00+ mm
0.866 - 0.0050.000+ in
22.00 - .13.00+ mm
0.866 - 0.0050.000+ in
30.00 mm1.181 inDepth
30.00 mm1.181 in
229 mm9.0 in
324 mm12.8 in
211 mm8.3 in
123 mm4.8 in
180 mm7.1 in
90 mm3.5 in
287 mm11.3 in
Add 257mm
[10.1"] to allowfor coverremoval
70 mm2.8 inBHC
22 mm0.9 in
(4) M8x1.25
20mm0.8"
F07 ISO Flange
(2) 3/4" NPTEMT Entry
125 mm4.9 in
86 mm3.4 in
Existing Switchgear
Existing Switchgear
Wire sizing data is provided in the table below to assist in the selection of the proper wire size for these actuators using various wire sizes over distance.
Please make sure to reference the correct voltage and do not exceed the indicated length of the wire run for each model.
• Field Control Device may be relay contact, Switch or Triac type.
• Pilot device 10A MAX. Auxiliary switches are rated 10A @ 250vac MAX.
• Terminals 7-12 are dry type Form C.
• Terminals accept 12-16ga solid/stranded wire.
SAMPLE DIAGRAMSRefer to the proper IOM for your actuator for the correct wiring diagram or visit www.promationei.com.
On/Off/Jog Control
Proportional Control
• See page 4 for Control Input/Outputs
• Pilot device 10A MAX. Auxiliary switches are rated 10A @ 250vac MAX.
• Terminals 7-12 are dry type Form C.
• Terminals accept 12-16ga solid/stranded wire.
Product is shipped at MID-STROKE position to allow up to 6 seconds run time after power up to determine if the actuator is running in the correct direction. If it is not, immediately remove power to avoid possible damage to the actuator end stops.
SD
15_P213_X
MC
C Ver D
_050515
Page 3 of 4 P2/3 XMCC Series
NOT OPEN*
OPEN COM*
OPEN*
NOT CLOSED*
CLOSED COM*
CLOSED*
C
B
12
11
10
9
8
7
LINE IN
480/3Ø
* CONNECTIONSOPTIONAL
GND Screw
GND
6
5
4
3
2
1
GRN
SW3
SW4
AUXILIARYSWITCH
(STANDARD)
ALL SWITCHESSHOWN WITHACTUATOR IN
FULL OPENPOSITION
AUXILIARYSWITCH
(STANDARD)
E1E2
Actuator ships in Mid-Stroke position!
J1
HEATER
SW2
SW1
J2
E1E2J3
112
43
Items within dotted line locatedinside actuator housing
430-10100 Switch Card
SW1
SW2
SW3
SW4
Switch StackDetail
A
5 6
21 22
3 4
1 2
A1 A2MC1
MC2
ØA
ØB
ØC NO
C
NC
REV Ø RELAY
120VAC COIL
120VAC COIL
5 6
21 22
3 4
1 2
A1 A2
ABCDEF WHT
BLU
RED
Correct Phase errors within 6 sec after power-up.
Supplied by others
410-50100TL25-1800
Heater is 25W120V
120vac Control ONLY
M410-92383380V/3Ø
WHT
WHT
WHT
120VAC
380VAC
T1 380/120
FB OUT
INSignal OUT+
Signal IN+
430-10102Controller
Signal COMCOM
A
P2/3-483PN4-XMCCUse For:
WD
-85
0-2
82
42
P2/3 XMCC N4
MAX distance between Actuator and Supply (feet)
Actuator P2 P3Voltage 230/3/60 380/3/60 440/3/60 480/3/60 230/3/60 380/3/60 440/3/60 480/3/60
1.4A 0.7A 0.9A 0.9A 1.4A 0.7A 0.9A 0.9A
16 1701 3401 5291 5772 1701 3401 5291 577214 2747 5495 8547 9324 2747 5495 8547 932412 4202 8403 13072 14260 4202 8403 13072 1426010 7143 14286 22222 24242 7143 14286 22222 242428 10661 21322 33167 36183 10661 21322 33167 36183
WireGage
Amps
Wire Sizing Chart
ActuatorSpecifications P2 P3Torque “lb/Nm 800”lbs/90Nm 1335“lbs/150NmSupply Voltage 230/3/60 380/3/60 440/3/60 480/3/60 230/3/60 380/3/60 440/3/60 480/3/60Max Inrush Current 1.4A 0.7A 0.9A 0.9A 1.4A 0.7A 0.9A 0.9ARunning Current 0.8A 0.4A 0.4A 0.4A 0.8A 0.4A 0.4A 0.4AMotor PolyphaseRuntime (90°@60Hz/vdc) 15 sec 22 secRuntime (90°@50Hz) 17 sec 26 secDuty Cycle 25%Motor Starts 1200 per hourWeight 26lbs/12kgMechanical Connections ISO5211 F07 8pt 22mmElectrical Entry (2) 3/4” NPT Electrical Terminations 12-16gaEnvironmental Rating NEMA 4/4X Manual Override 5” HandwheelControl On/Off/JogActuator Case Material Aluminum Alloy, Powder coated
Motor Protection 230°F/110°C Thermal F* Class*Totally Enclosed Non-Ventilated Motors
Ambient Temperature Operating Range
-22°F to +125°F-30°C to +52°C
Wiring Diagrams for P2/3 Series
NOT OPEN*
OPEN COM*
OPEN*
NOT CLOSED*
CLOSED COM*
CLOSED*
RUN CW
RUN CCW
C
B
12
11
10
9
8
7
LINE IN
230/3Ø
* CONNECTIONSOPTIONAL
FIELDCONTROL
DEVICE
GND Screw
GND
6
5
4
3
2
1
GRN
SW3
SW4
AUXILIARYSWITCH
(STANDARD)
ALL SWITCHESSHOWN WITHACTUATOR IN
FULL OPENPOSITION
AUXILIARYSWITCH
(STANDARD)
E1E2
Actuator ships in Mid-Stroke position!
J1
HEATER
SW2
SW1
J2
E1E2J3
112
43
Items within dotted line locatedinside actuator housing
430-10100 Switch Card
SW1
SW2
SW3
SW4
Switch StackDetail
A
5 6
21 22
3 4
1 2
A1 A2MC1
MC2
ØA
ØB
ØC NO
C
NC
120VAC
230VAC
REV Ø RELAY
T1 230/120
120VAC COIL
120VAC COIL
5 6
21 22
3 4
1 2
A1 A2
ABCDEF WHT
BLU
RED
Correct Phase errors within 6 sec after power-up.
Supplied by others
410-50100TL25-1800
Heater is 25W120V
120vac Control ONLY
M410-92233230V/3Ø
BRN
BLU
BLK
P2/3-233N4-XMCC
B
Use For:
WD
-85
0-2
61
42
Use your smart phone barcode scanner app here.
16138 Flight Path Drive Brooksville, FL 34604
Phone (352) 544-8436 Fax (352) 544-8439email: sales@promationei.com
ProMation Engineering follows a policy of continual product updates and enhancements. Our website is the best place to obtain the latest product documentation, including the wiring diagrams for these controllers. Visit us at www.promationei.com or use the QR code below to link to the site.
ProMation Product Line
PL SeriesLinear Drive
Up to 4400lbs down/up force.
P SeriesNon-Spring Return
55”lbs through 40,000”lbs.
PA~PD Series Spring Return
445”lbs through 2300”lbs.
PBU Battery Back-Up Systems
Provides battery power to drive open
The Premium controller offers a full array of features - such as various control and feedback signals, alphanumeric readout, several fault indicators for operational diagnostics,
Control Signal Inputs(selectable using program menu):0-10vdc, 1-5vdc, 2-10vdc, 4-20mA
Factory set with common isolated from ground. Ground reference is possible.
ProMation Premium Controller:
Signal Input Impedance Sensitivity
0-10vdc 140k ohms 50mV
1-5vdc 250k ohms 20mV
2-10vdc 140k ohms 40mV
4-20mA 250 ohms 80µA
Feedback Signal Output (Can be different than input): 0-10vdc, 1-5vdc, 2-10vdc, 4-20mA
Max Load: 250 ohms
extensive data logging that provides full proportional control for all industrial applications. ModBus communications are also an option on this controller.
Full Proportional Control Featuring:• Autocalibration• Programmable• High resolution• Alarm Outputs• Data logging• Simple User Interface• Field Selection Friendly• Thermal Management
Auxi l iary Signal Output (programmable):A larm Contacts a l low for signaling of 5 different fault conditions. 2 Position ControlContacts and capability for 2 position (only) override of the actuator.
Proportional Control
• Premium Proportional Controller Option. Converts 2 position to proportional control.• Mechanical Torque Switch Assembly• IP68 Protection, tested to 0.7kgf/cm2 for 72 hours. P2~P8 only.• 1k ohm position feedback potentiometer.• 5k ohm position feedback potentiometer.• 10k ohm position feedback potentiometer.• 4-20mA feedback generator for On/Off/Jog actuators.• Auxiliary Switch set. Provides 3rd and 4th auxiliary switches (Form C x 2).• Integral Thermostat for Heater Control - turns on at 32°F, turns off at 50°F.• Cold weather auxiliary heater option. Thermostatically controlled, On 32°F, Off
at 50°F, auto reset, hermetically sealed, 120/230vac On/Off/Jog type actuators. 175W Internal Heater, 2A power consumption.
• Chain wheel override for applications where an actuator is mounted some distancefromthefloor.(UsewithLCS).
• Epoxy coating for increased environmental protection.• Nylon coating for increased environmental protection.• Stainless Steel actuator enclosure. P2~P6 Only.
Cold Weather Heater Option keeps your actuator operational in cold weather applications. Automatically compensates internal temperatures in response to severe external conditions.
AVAILABLE OPTIONS (Factory Installed)
SD
15_P
213_
XM
CC
Ver
D_0
5051
5
Page 4 of 4 P2/3 XMCC Series
Recommended