JB
LS1
LS3
LS6
LS5
LS4
2
2
2
1
1
3 #8AWG + GRD
-53mmC
3 #8AWG + GRD
-53mmC
APPROXIMATE LOCATION
OF ELECTRICAL ROOM
JB
3 #8AWG + GRD
-53mmC
3 #8AWG + GRD
-53mmC
APPROXIMATE LOCATION
OF EXISTING JUNCTION BOX
2x (3 8AWG) + GRD
2 #8AWG + GRD
OVERBROOK PARK - SITE LAYOUT
1:200
1
E1
NEW LED LIGHT STANDARD AND POLE
NEW LIGHT STANDARD AND CIRCUIT
NUMBER IDENTIFICATION
NEW UNDERGROUND CONDUIT
LS#
1
(TYPICAL)
ELECTRICAL NOTES:
PROVIDE AND INSTALL NEW 240V LED TYPE 'A' LIGHT STANDARD c/w CONCRETE
POLE ASSEMBLY.
PROVIDE AND INSTALL A NEW 'ON' PUSHBUTTON ON LS2 POLE. NEW PUSHBUTTON
TO BE ENCLOSED IN WEATHERPROOF/WATERTIGHT ENCLOSURE.COORDINATE
PUSHBUTTON ENCLOSURE MOUNTING WITH POLE MANUFACTURER.
APPROXIMATE LOCATION OF ELECTRICAL ROOM. CONTRACTOR TO PROVIDE NEW
CONTACTOR AND CONNECT TO EXISTING TIMECLOCK/NEW PUSHBUTTON FOR
LIGHTING CONTROL. CONNECT NEW RINK LIGHTING TO x2 NEW 20A-2P BREAKERS.
ALSO PROVIDE NEW BREAKER/WIRING FOR PUSHBUTTON CONTROL.
PROVIDE NEW 53mmC FROM NEW JUNCTION BOX (LOCATED NEAR EXISTING
JUNCTION BOX) TO BE RUN DOWN OUTSIDE WALL TO EXTERIOR.
PROVIDE TRENCHING/SAWCUT TO ALLOW FOR NEW CONDUIT RUN.
CONTRACTOR TO COORDINATE USE OF LIFT DEVICE WITH CLIENT. EXISTING
GYMNASIUM FLOOR SHALL BE PROTECTED AND MAINTAINED TO EXISTING
CONDITION. TYPE OF LIFT USED SHALL BE DESIGNED FOR SUCH USE AND PRIOR
APPROVED BY CLIENT.
1
2
3
4
2
5
3
cct#
5
4
6
6
LIGHTING CONTROL DESCRIPTION:
1. THE NEW RINK LIGHTING IS TO BE CONTROLLED BY A DIGITAL TIME
CLOCK, PUSH-BUTTON AND CONTACTORS AS INDICATED TO PRESET A
SHUTDOWN TIME (11:00P.M.)
2. THE RINK LIGHTING WILL BE ENERGIZED BY A PUSH-BUTTON
MOUNTED ON THE EXTERIOR OF THE BUILDING. THE DIGITAL
TIMECLOCK WILL NOT ALLOW LIGHTS TO BE ENERGIZED BY
PUSHBUTTON UNLESS THE PRESET TIME IS REACHED. THE LIGHTING
WILL TURN OFF BY TIMECLOCK WHEN THE PRESET OFF TIME IS
REACHED.
3. THE RINK LIGHTING CONTACTOR - H.O.A. SWITCH LOCATED IN THE
ELECTRICAL ROOM WILL ALLOW THE USER TO BYPASS THE
PUSH-BUTTON AND DIGITAL TIMECLOCK, THEREFORE ALLOWING THE
RINK LIGHTING TO TURN ON WHEN REQUIRED.
4. CONTACT TR1A N.O. PREVENTS THE START BUTTON FROM
ENERGIZING THE RINK LIGHTING CONTACTOR.
5. START PUSH-BUTTON ENERGIZES CONTACTOR C1 IF TR1 PERMITS
AND CONTACT C1 N.O. CLOSES AND MAINTAINS THE CONTACTOR.
DIGITAL TIMECLOCK CONTACT DESCRIPTION
LED
SOD
LED LIGHT STANDARD. (TYP. OF 6)
NEW RINK LIGHTING TO MEET CITY OF OTTAWA RINK LIGHTING CRITERIA FOR
AVERAGE AND UNIFORMITY ILLUMINATION LEVELS. CONTRACTOR TO SUBMIT A
HARD COPY COMPUTER SIMULATION DEPICTING PROPOSED LIGHTING LEVELS FOR
APPROVAL.
CABLE/DUCT TRENCH DETAIL (TYP.)
NTS
A
E2
LIGHTING CONTROL SCHEMATIC
NTS
B
E2
DIRECT BURIED POLE DETAIL
NTS
C
E2
1. INSTALLATION SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES AND BY-LAWS AND BE INSTALLED BY
WORKMEN SKILLED IN THAT PARTICULAR PORTION OF THE CONTRACT. DO COMPLETE INSTALLATION IN
ACCORDANCE WITH CSA C22.1-2012.
2. EXAMINE SITE AND LOCAL CONDITIONS AFFECTING WORK UNDER THIS DIVISION TO ENSURE THAT ALL WORK
CAN BE SATISFACTORILY CARRIED OUT WITHOUT CHANGES TO DRAWINGS. NO ALLOWANCES WILL BE MADE
LATER FOR ANY EXPENSE INCURRED THROUGH FAILURE TO MAKE THIS EXAMINATION. START OF WORK WILL BE
DEEMED EVIDENCE OF ACCEPTANCE OF, AND SATISFACTION WITH, EXISTING CONDITIONS.
3. PERMITS, FEES AND INSPECTION:
SUBMIT TO ELECTRICAL INSPECTION DEPARTMENT AND SUPPLY AUTHORITY NECESSARY NUMBER OF
DRAWINGS AND SPECIFICATIONS FOR EXAMINATION AND APPROVAL PRIOR TO COMMENCEMENT OF WORK. PAY
ASSOCIATED FEES. NOTIFY ENGINEER OF CHANGES REQUIRED BY ELECTRICAL INSPECTION DEPARTMENT
PRIOR TO MAKING CHANGES. FURNISH TO ENGINEER CERTIFICATES OF ACCEPTANCE FROM ELECTRICAL
INSPECTION DEPARTMENT ON COMPLETION OF WORK.
4. GUARANTEE ALL WORK FOR 12 MONTHS FROM DATE OF ACCEPTANCE.
5. COORDINATE ALL WORK WITH OTHER CONTRACTORS WORKING ON THIS PROJECT.
6. PERSONNEL PROTECTION / EQUIPMENT PROTECTION:
ENSURE THAT ALL PRECAUTIONS ARE TAKEN TO PROTECT ALL PERSONNEL FROM HAZARDS DURING THE
WORK. PROTECT ALL EQUIPMENT FROM DAMAGE FROM ANY CAUSE.
7. SCOPE OF WORK:
PERFORM ALL WORK SHOWN ON CONTRACT DRAWINGS AND AS COVERED IN THESE SPECIFICATIONS.
8. CLEAN UP:
DURING THE COURSE OF CONSTRUCTION AND UPON COMPLETION, REMOVE ALL RUBBISH AND WASTE
RESULTING FROM THIS WORK. CHECK, CLEAN AND REPAINT WHERE NECESSARY ALL ELECTRICAL EQUIPMENT
AND LEAVE IN A FIRST-CLASS CONDITION. PROVIDE FOR THE DAILY REMOVAL OF ELECTRICAL WASTE AND
DEBRIS FROM THE SITE.
9. MAINTAINING SERVICES:
REINSTATE, AS SOON AS POSSIBLE, ANY EXISTING CIRCUITS DISRUPTED DURING DEMOLITION OR
CONSTRUCTION NOT INTENDED TO BE REMOVED AS PART OF THIS CONTRACT. ANY EXISTING SERVICE THAT IS
TO REMAIN AND IS UNAVOIDABLY DISRUPTED DURING RENOVATION SHALL BE RESTORED TO ITS ORIGINALLY
FUNCTIONING STATE.
10. RESTORATION OF MATERIAL DAMAGE, CUTTING PATCHING AND MAKING GOOD:
COORDINATE, WITH OWNER, THE RESTORATION OF ANY BUILDING SURFACE OR INFRASTRUCTURE COMPONENT
THAT IS TO REMAIN AND IS DAMAGED AS A RESULT OF DEMOLITION (OR INSTALLATION) UNDER THIS DIVISION, IN
THIS PROJECT. THESE ITEMS SHALL BE RESTORED TO PRE-EXISTING CONDITION, THIS WORK INCLUDES
SURFACE FINISHES.
11. CLIENT COORDINATION:
COORDINATE JOB START-DATE AND WORKING HOURS WITH CLIENT OR CLIENTS REPRESENTATIVE. CO-
ORDINATE ANY ANTICIPATED ELECTRICAL SERVICE(S) DOWNTIME IN ADVANCE, WITH CLIENT, OR CLIENTS
REPRESENTATIVE.
12. MATERIALS AND EQUIPMENT:
NEW EQUIPMENT AND MATERIALS TO BE CSA CERTIFIED. WHERE THERE IS NO ALTERNATIVE TO SUPPLYING
EQUIPMENT WHICH IS NOT CSA CERTIFIED, OBTAIN SPECIAL APPROVAL FROM ELECTRICAL INSPECTION
DEPARTMENT.
13. EQUIPMENT SUBSTITUTION:
ALL EQUIPMENT SUPPLIED SHALL BE EXACTLY AS SPECIFIED HEREIN. SUBSTITUTIONS OR ALTERNATIVES TO
WHAT IS SPECIFIED WILL NOT BE ACCEPTED AFTER THE CLOSING OF TENDERS. SUBSTITUTION OR
ALTERNATIVES MUST BE SUBMITTED PRIOR TO TENDER CLOSING AND MUST BE APPROVED BY ENGINEER AND
OWNER. SUBSTITUTE OR EQUIVALENT EQUIPMENT MAY BE SUBMITTED FOR APPROVAL BUT ONLY DURING THE
TENDER PERIOD. AFTER TENDER CLOSES, NO SUBSTITUTE OR EQUIVALENT EQUIPMENT WILL BE APPROVED.
ALL EQUIVALENCY DECISIONS MADE BY THE ENGINEER WILL BE FINAL. THE BURDEN OF PROOF OF
EQUIVALENT PRODUCTS BOTH IN TERMS OF PERFORMANCE AND QUALITY SHALL BE ON THE CONTRACTOR.
14. EQUIPMENT IDENTIFICATION - LAMICOID NAMEPLATES:
ALL PULL-BOXES, PANELBOARDS, CONTACTORS OR OTHER SIMILAR EQUIPMENT FURNISHED IN THIS
SPECIFICATION, SHALL BE PROVIDED WITH ENGRAVED LAMICOID NAMEPLATES IDENTIFYING THE FUNCTION OF
EACH DEVICE. ALL LABELS LAMICOID 3mm THICK PLASTIC ENGRAVING SHEET WHITE FACE WITH BLACK CORE,
MECHANICALLY ATTACHED WITH SELF-TAPPING SCREWS: NAMEPLATES TO MATCH CITY OF OTTAWA
STANDARDS. NAMEPLATES FOR JUNCTION BOXES SHALL INDICATE SYSTEM AND VOLTAGE CHARACTERISTICS
TIMERS, CONTACTORS: INDICATE DEVICE NAME, EQUIPMENT BEING CONTROLLED AND VOLTAGE PULL BOXES:
INDICATE TYPE OF SYSTEM AND VOLTAGE
15. CSA AND MANUFACTURERS LABELS:
TO BE VISIBLE, ACCESSIBLE AND LEGIBLE AFTER EQUIPMENT IS INSTALLED.
16. CONDUITS, CONDUIT FITTINGS:
DRAWINGS DO NOT INDICATE ALL CONDUIT RUNS. THOSE INDICATED ARE IN DIAGRAMMATIC FORM ONLY.
EXTERIOR CONDUITS: RIGID PVC CONDUIT: SIZE AS INDICATED. INTERIOR CONDUITS: ELECTRICAL METALLIC
TUBING (EMT): WITH COUPLINGS, SIZE AS INDICATED. CONDUIT FASTENINGS: ONE HOLE STEEL STRAPS TO
SECURE SURFACE CONDUITS 50 MM AND SMALLER. TWO HOLE STEEL STRAPS FOR CONDUITS LARGER THAN
50mm. CONDUIT FITTINGS: FITTINGS: MANUFACTURED FOR USE WITH CONDUIT SPECIFIED. COATING: SAME AS
CONDUIT. FACTORY "ELLS" WHERE 90 DEGREE BENDS ARE REQUIRED FOR 25mm AND LARGER CONDUITS.
WATERTIGHT CONNECTORS AND COUPLINGS FOR EMT. SET-SCREWS ARE NOT ACCEPTABLE. EXPANSION
FITTINGS FOR RIGID CONDUIT: WEATHERPROOF EXPANSION FITTINGS WITH INTERNAL BONDING ASSEMBLY
SUITABLE FOR 200mm LINEAR EXPANSION. WATERTIGHT EXPANSION FITTINGS WITH INTEGRAL BONDING
JUMPER SUITABLE FOR LINEAR EXPANSION AND 19mm DEFLECTION IN ALL DIRECTIONS. WEATHERPROOF
EXPANSION FITTINGS FOR LINEAR EXPANSION AT ENTRY TO PANEL.
CONDUIT INSTALLATION:
INSTALL CONDUITS TO CONSERVE HEADROOM IN EXPOSED LOCATIONS AND CAUSE MINIMUM INTERFERENCE IN
SPACES THROUGH WHICH THEY PASS. USE ELECTRICAL METALLIC TUBING (EMT) FOR GENERAL USE, EXCEPT IN
CAST CONCRETE. BEND CONDUIT COLD. REPLACE CONDUIT IF KINKED OR FLATTENED MORE THAN 1/10TH OF
ITS ORIGINAL DIAMETER. MECHANICALLY BEND STEEL CONDUIT OVER 19mm DIA. FIELD THREADS ON RIGID
CONDUIT MUST BE OF SUFFICIENT LENGTH TO DRAW CONDUITS UP TIGHT. INSTALL FISH CORD IN EMPTY
CONDUITS. WHERE CONDUITS BECOME BLOCKED, REMOVE AND REPLACE BLOCKED SECTION. DO NOT USE
LIQUIDS TO CLEAN OUT CONDUITS. DRY CONDUITS OUT BEFORE INSTALLING WIRE. PROVIDE PULL (FISH) CORD:
IN EMPTY CONDUITS.
17. WIRE AND CABLES:
LL WIRING SHALL BE COPPER. MINIMUM SIZE OF 12 AWG. COPPER CONDUCTORS STRANDED FOR 10 AWG AND
LARGER. CONDUCTORS SIZED AS INDICATED ON PROJECT DRAWINGS WITH 600V INSULATION OF CHEMICALLY
CROSS-LINKED THERMOSETTING POLYETHYLENE MATERIAL RATED. INTERIOR CONDUCTORS TO BE RW90.
EXTERIOR CONDUCTORS TO BE RWU90. WIRING IDENTIFICATION: IDENTIFY WIRING WITH PERMANENT INDELIBLE
IDENTIFYING MARKINGS, EITHER NUMBERED OR COLOURED PLASTIC TAPES, ON BOTH ENDS OF PHASE
CONDUCTORS OF FEEDERS AND BRANCH CIRCUIT WIRING. MAINTAIN PHASE SEQUENCE AND COLOUR CODING
THROUGHOUT. USE COLOUR CODED WIRES IN COMMUNICATIONS SYSTEMS CABLES, MATCHED THROUGHOUT
THE SYSTEM. COLOUR CODE TO CSA C22.1
18. JUNCTION BOXES:
ALL JUNCTION BOXES SHALL BE COMPLETE WITH BLANK COVER PLATES. EXTERIOR PULL BOXES: SHALL BE PVC
CONSTRUCTED AND WEATHERPROOF/WATERTIGHT.
19. FOLLOW MANUFACTURERS' INSTRUCTIONS REGARDING THE HANDLING, INSTALLING AND TESTING OF THEIR
EQUIPMENT.
20. GROUNDING AND BONDING:
PROVIDE GROUNDING & BONDING TO CSA C22.2 No. 0.4-[M1982 (R1993)], BONDING AND GROUNDING OF
ELECTRICAL EQUIPMENT INSTALL COMPLETE PERMANENT, CONTINUOUS, SYSTEM AND CIRCUIT, EQUIPMENT,
GROUNDING SYSTEMS INCLUDING CONDUCTORS, CONNECTORS, ACCESSORIES, AS REQUIRED TO CONFORM TO
REQUIREMENTS OF LOCAL AUTHORITY HAVING JURISDICTION OVER INSTALLATION. WHERE EMT IS USED, RUN
GROUND WIRE IN CONDUIT.
21. TESTING AND INSPECTION:
TEST ALL WIRING AND EQUIPMENT AND CORRECT ANY FAILURE TO PERFORM. MAKE GOOD ANY DEFICIENCIES
NECESSARY TO OBTAIN THE ELECTRICAL INSPECTION CERTIFICATE AT NO COST TO THE OWNER.
22. LIGHTING FIXTURES (LUMINAIRES), COMPLETE WITH LAMPS AS FOLLOWS :
TYPE LAMP VOLTAGE DESCRIPTION
A LED 240V GLEON-AA-07-LED-E1-SL4 OR EQUIVALENT
(CONCRETE POLE USI HA-250-C-2PG-USI-20)
FIXTURE WIRING: MAKE CONNECTIONS OF WIRES TO TERMINALS OF LAMPHOLDER AND OTHER ACCESSORIES IN
A NEAT AND WORKMANLIKE MANNER AND WHICH ARE ELECTRICAL AND MECHANICALLY SECURE AND SAFE,
WITH NO LOOSE STRANDS PROTRUDING. PROVIDE WIRING CHANNELS AND WIREWAYS FREE FROM
PROJECTIONS AND ROUGH OR SHARP EDGES THROUGHOUT. AT POINT OR EDGES OVER WHICH THE
CONDUCTORS SHALL PASS AND MAY BE SUBJECT TO INJURY OR WEAR, ROUND EDGE TO MAKE A SMOOTH
CONTACT SURFACE WITH THE CONDUCTORS. INSTALL INSULATED BUSHINGS AT POINTS OF ENTRANCES AND
EXITS OF FLEXIBLE WIRING. PROTECT WIRING WITH GROMMET OR TUBING AT POINTS WHERE ABRASION MAY
OCCUR. CONCEAL WIRING WITHIN FIXTURE CONSTRUCTION EXCEPT WHERE THE FIXTURE DESIGN OR
MOUNTING DICTATES OTHERWISE.
23. CONCRETE POLE:
CONCRETE POLES TO NEMA SH5-1969 (R1974), DESIGNED FOR UNDERGROUND WIRING AND DIRECT BURIED
MOUNTING. STYLE: ROUND TAPERED (12" - 6" DIAMETER) ROUND FOR NUMBER OF LUMINAIRE MOUNTING
BRACKETS, AS INDICATED. THE POLES SHALL HAVE SUFFICIENT STRENGTH TO WITHSTAND STEADY WIND
SPEEDS OF 135 KM/H WITH A 1.3 GUST FACTOR. POLE TO BE C/W REQUIRED SUPPORTS AND ASSOCIATED
ACCESSORIES. CONCRETE POLE (MATERIAL) INFORMATION SHOWN FOR REFERENCE ONLY.
24. POLE EXECUTION:
POLES SHALL BE HANDLED USING SUITABLE NON-ABRASIVE SLINGS AT THE POLE PICK-UP POINTS SPECIFIED BY
THE POLE MANUFACTURER. MOUNT POLES AS INDICATED AND IN ACCORDANCE WITH THE MANUFACTURER'S
INSTRUCTIONS.
25. LIGHTING CONTACTOR(S):
TO CSA C22.2 NO.14
INSTALLED IN A CSA TYPE 2, EEMAC GREY
COIL VOLTAGE: 120VAC/60HZ
CONTACT RATINGS: 240VAC, 2P, 30A INDUCTIVE
AUXILIARY CONTACTS: NORMALLY OPEN AND CLOSED RATED FOR 120VAC.
PILOT LIGHTS: 120VAC LED PUSH-TO-TEST
APPROVED MANUFACTURERS: EATON CUTLER-HAMMER, SCHNEIDER, SIEMENS
26. DIGITAL TIMECLOCKS:
INSTALLED IN A METAL INDOOR/OUTDOOR ENCLOSURE NEMA 3R
STANDARD: cUL LISTED
INPUT VOLTAGE: 120VAC/60HZ
TIMING ACCURACY: LINE FREQUENCY
DISPLAY: LCD
TYPE: 24HR PERMANENT SCHEDULE RETENTION
MANUAL OVERRIDE ON/OFF
CLOCK FORMAT: 12HR, AUTOMATIC DAYLIGHT SAVINGS TIME AND LEAP YEAR COMPENSATION
BACKUP POWER: CAPACITOR, 100HRS, W/ POWER FAILURE INDICATION
CONTACT RATINGS: 120VAC, SPDT, 30A INDUCTIVE
APPROVED MANUFACTURERS: TORK MODEL E103B
27. LUMINAIRE INSTALLATION:
LUMINAIRES SHALL BE KEPT FREE OF CONDITIONS WHERE MOISTURE OR DIRT COULD DAMAGE THE BALLASTS
OR REFLECTING SURFACES OF THE OPTICAL SYSTEM. LUMINAIRES SHALL BE CHECKED FOR THE CORRECT
OPTICAL SYSTEM SETTINGS TO GIVE THE DESIGNATED TYPE OF LIGHT DISTRIBUTION. IF REQUIRED, THE
CONTRACTOR SHALL RESET THE LAMPHOLDER IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS
TO GIVE THE PROPER TYPE OF DISTRIBUTION INDICATED IN THE CONTRACT DOCUMENTS. LUMINAIRES SHALL
BE MOUNTED ON POLES AND SHALL BE INSTALLED LEVEL ALONG BOTH THE LONGITUDINAL AND TRANSVERSE
AXIS. LUMINAIRE CLAMPING ASSEMBLIES SHALL BE SECURELY TIGHTENED, UPON COMPLETION OF LEVELING,
TO PREVENT SHIFTING BY WIND.
RISER WIRES IN POLES SHALL BE TERMINATED AT TOP OF POLE. CONNECTIONS SHALL BE MADE WITH
COMPRESSION CONNECTORS INSULATED WITH INSULATING COVERS.
28. SHOP DRAWINGS:
PROVIDE SIX (6) COPIES OF SHOP DRAWINGS FOR THE FOLLOWING EQUIPMENT: CONTACTOR, DIGITAL
TIMECLOCK, BREAKERS, LUMINAIRE, LAMP, BALLAST, CONCRETE POLE AND ACCESSORIES ANY ADDITIONAL
EQUIPMENT AS REQUIRED BY THE ENGINEER.
29. RECORD DRAWING:
SHOW ON THE RECORD DRAWINGS THE APPROXIMATE PATH OF RACEWAYS LINKING ALL OUTLETS, JUNCTION
AND PULL BOXES: THE LOCATION OF JUNCTION AND PULL BOXES, THE NUMBER AND SIZE OF CONDUCTORS IN
ALL RACEWAYS. SHOW ON THE RISER DIAGRAMS ALL JUNCTION BOXES AND PULL BOXES AND IDENTIFY THEM
WITH RESPECT TO LOCATION IN THE BUILDING. CROSS-REFERENCE THESE BOXES BETWEEN RISERS AND
FLOOR PLANS. TURN OVER TO THE ENGINEER TWO COMPLETE SETS OF `AS-BUILT' DRAWINGS UPON
COMPLETION OF THE PROJECT AND PRIOR TO FINAL PAYMENT.
30. LOAD BALANCE:
MEASURE PHASE CURRENT TO PANELBOARDS WITH NORMAL LOADS (LIGHTING) OPERATING AT TIME OF
ACCEPTANCE. ADJUST BRANCH CIRCUIT CONNECTIONS AS REQUIRED TO OBTAIN BEST BALANCE OF CURRENT
BETWEEN PHASES AND RECORD CHANGES. SUBMIT, AT COMPLETION OF WORK, REPORT LISTING PHASE AND
NEUTRAL CURRENTS ON PANELBOARDS, OPERATING UNDER NORMAL LOAD. STATE HOUR AND DATE ON WHICH
EACH LOAD WAS MEASURED, AND VOLTAGE AT TIME OF TEST.
31. FIELD QUALITY CONTROL:
INSULATION RESISTANCE TESTING: MEGGER CIRCUITS, FEEDERS AND EQUIPMENT UP TO 250 V WITH A 500V
INSTRUMENT. CHECK RESISTANCE TO GROUND BEFORE ENERGIZING. CARRY OUT TESTS IN PRESENCE OF
ENGINEER. PROVIDE INSTRUMENTS, METERS, EQUIPMENT AND PERSONNEL REQUIRED TO CONDUCT TESTS
DURING AND AT CONCLUSION OF PROJECT. SUBMIT TEST RESULTS FOR ENGINEER'S REVIEW.
32. COORDINATION OF PROTECTIVE DEVICES:
ENSURE CIRCUIT PROTECTIVE DEVICES SUCH AS OVERCURRENT TRIPS, RELAYS AND FUSES ARE INSTALLED TO
REQUIRED VALUES AND SETTINGS.
33. OPERATION AND MAINTENANCE MANUAL:
AT CLOSE OF CONTRACT, PRIOR TO COMMISSIONING, PROVIDE A THREE-RING BINDER CONTAINING A LISTING
OF ALL MAJOR ITEMS OF EQUIPMENT IN PROJECT (AND RELEVANT CATALOGUE NUMBERS). LIST ADDRESSES
AND TELEPHONE NUMBERS OF SUPPLIERS. WHERE APPLICABLE, INCLUDE MANUFACTURER DRAWINGS,
SPECIFICATIONS, MAINTENANCE AND OPERATING INSTRUCTIONS AND RECOMMENDATIONS. IDENTIFY NAME OF
PROJECT AND CITY OF OTTAWA PROJECT NUMBER, IN BOLD LETTERS, ON FRONT AND SPINE OF BINDER.
34. INSTRUCT, OR PROVIDE FOR INSTRUCTION OF CLIENT OR CLIENT DESIGNATED STAFF IN THE OPERATION OF
ANY SYSTEMS NEWLY INSTALLED IN THIS PROJECT.
35. DUCTBANK INSTALLATION:
TO REMOVE SAND, EARTH AND OTHER FOREIGN MATTER: PULL A STEEL MANDREL NOT LESS THAN 300mm LONG
AND 6mm LESS THAN THE INTERNAL DIAMETER OF DUCT THROUGH EACH INDIVIDUAL DUCT, FOLLOW THIS BY A
STIFF BRISTLE BRUSH. PULL A STIFF BRISTLE BRUSH THROUGH EACH DUCT IMMEDIATELY BEFORE PULLING IN
CABLES. IN EACH EMPTY DUCT INSTALL A POLYPROPYLENE PULL ROPE CONTINUOUS THROUGHOUT, WITH 3M
OF SPARE ROPE AT EACH END. INSTALL CABLE DUCT MARKERS AS REQUIRED ABOVE FINISHED DUCTS. END OF
SPECIFICATION