View
623
Download
107
Category
Preview:
DESCRIPTION
omnibas install
Citation preview
5/19/2018 OmniBAS IDU Installation Ed4.0 En
1/120
Edition 4.0
Indoor Installation
& Cabling Manual
C fid ti l
GDC-002/34
Next Generation Ethernet
Microwave Backhaul Solution
5/19/2018 OmniBAS IDU Installation Ed4.0 En
2/120
Confidential
INTRACOM TELECOM
19.7 km Markopoulou Ave., Peania, Athens, GR 19002T +30 210 667 1000, F +30 210 667 1001
http://www.intracom-telecom.com
email (product support): omnibas_support@intracom.com
The information contained in this document is subject to change without prior notice.
INTRACOM S.A. TELECOM SOLUTIONS, 2013. All rights reserved.
All copyright, intellectual and industrial rights in this document and in the technical knowledge it containsare owned by INTRACOM S.A. TELECOM SOLUTIONS and/or their respective owners.
This document is made available to the end users only for their internal use.No part of this document nor any data herein may be published, disclosed, copied, reproduced,
redistributed by any form or means, electronically or mechanically, or used for any other purposewhatsoever without the prior written approval of INTRACOM S.A. TELECOM SOLUTIONS.Information as well as drawings and specifications contained in this document are subject to changewithout prior notice.
All trademarks and copyrights mentioned herein are the property of INTRACOM S.A. TELECOMSOLUTIONS and/or their respective owners.Any rights not expressly granted herein are reserved.
Printed in Greece.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
3/120
Document Revision History OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
-I-
Document Revision History
Revisions This page shows the main changes effected in relation to the previous
edition of the OmniBAS IDU Installation.Revisions
Previous: 3.0
Current: 4.0
Reasons ofchange
The table below shows the reasons for the document change effected in relation tothe previous document edition.
The main reasons of change are because of the following:
Addition of OmniBASTM
- 8W Indoor Unit
General Editing (whole document)
ParagraphM (Modified) /
A (Added)
Chapter 1 - Introduction
OmniBAS IDUs(page 6). A
Chapter 3 - Installation Materials
OmniBAS-8W(page18). A
Chapter 4 - Installation Prerequisites
Rack space requirements(page 24). A
Cabling Overview (page29). A
Chapter 5, Mechanical Installation
OmniBAS-8W(page 35). A
Chapter 6, Cabling Installation
Power Supply Cables(page 39). A/M
OmniBASTM-8W(page 48). A
IF Tails(page 50). A/M
E1 Terminations(page 53). A/M
I/O Cables(page 65). A/M
Ethernet Cables(page 69). M
High Speed Interconnection Cable (for OmniBASTM-8W)(page 70) A/M
Chapter 7, Cable Characteristics
OmniBAS-8W(page 74). A
OmniBAS-8W(page 77). A
OmniBAS-8W(page 78). A
5/19/2018 OmniBAS IDU Installation Ed4.0 En
4/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
Document Revision History
-II-
(Page intentionally left blank)
5/19/2018 OmniBAS IDU Installation Ed4.0 En
5/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
1
Table of Contents
1 Introduction ................................................................................................................... 3
About this Document....................................................................................................... 3Equipment Disposal ........................................................................................................ 5
Overview of OmniBAS Product Family ............................................................................ 6
Safety Precautions .......................................................................................................... 8
2 Installation Tools........................................................................................................... 9
3 Installation Material..................................................................................................... 10
OmniBAS-2W................................................................................................................ 10
OmniBAS-4W................................................................................................................ 14
OmniBAS-8W................................................................................................................ 18
4 Before Starting the Installation .................................................................................. 22
4.1 Installation Prerequisites ............................................................................................... 22
4.2 Cabling Overview.......................................................................................................... 25
5 Mechanical Installation ............................................................................................... 30
5.1 OmniBAS-2W................................................................................................................ 30
Chassis Overview ......................................................................................................... 30
IDU Installation.............................................................................................................. 32
5.2 OmniBAS-4W................................................................................................................ 33
Chassis Overview ......................................................................................................... 33
IDU Installation.............................................................................................................. 34
5.3 OmniBAS-8W................................................................................................................ 35
Chassis Overview ......................................................................................................... 35
IDU Installation.............................................................................................................. 36
6 Cabling Installation..................................................................................................... 38
6.1 Power Supply Cables .................................................................................................... 39
Preparation ................................................................................................................... 40
Installation..................................................................................................................... 44
6.2 IF Tails .......................................................................................................................... 50
6.3 E1 Terminations............................................................................................................ 53
Open End Cables (Balanced 120 ) ............................................................................. 54
BNC Terminations (Unbalanced 75 ) .......................................................................... 58
RJ-45 Terminations (Balanced 120 ) .......................................................................... 62
6.4 I/O Cables ..................................................................................................................... 65
6.5 Ethernet Cables ............................................................................................................ 69
6.6 High Speed Interconnection Cable (for OmniBASTM-8W) .............................................. 70
7 Cable Characteristics.................................................................................................. 71
7.1 GbE Cable Characteristics ............................................................................................ 71OmniBAS-2W................................................................................................................ 71
5/19/2018 OmniBAS IDU Installation Ed4.0 En
6/120
Table of Contents
2
OmniBAS-4W................................................................................................................ 73
OmniBAS-8W................................................................................................................ 74
7.2 Fast Ethernet Cable Characteristics.............................................................................. 75
OmniBAS-2W................................................................................................................ 75
OmniBAS-4W................................................................................................................ 76OmniBAS-8W................................................................................................................ 77
7.3 STM-1 Cable Characteristics......................................................................................... 78
OmniBAS-8W................................................................................................................ 78
Appendix-A: Modem Card Installation / Removal ................................................................ 79
Appendix-B: I/O Connections................................................................................................ 83
Appendix-D: Receptacles Pin Out......................................................................................... 87
OmniBAS-2W................................................................................................................ 87
OmniBAS-4W................................................................................................................ 96
OmniBAS-8W.............................................................................................................. 104
Appendix-E: Open End Cables Color Codes...................................................................... 111
5/19/2018 OmniBAS IDU Installation Ed4.0 En
7/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
3
1 Introduction
About this Document
Scope ofdocument
This document provides information concerning the installation and cablingof the following units:
OmniBASTM-2W
OmniBASTM-4W
OmniBASTM-8W
TargetAudience
This document is addressed to certified technicians with wireless equipmentknowledge and skills concerning the following:
Indoor Unit Installation (IDU).
Addition / Removal of IDU Cards.
Laying and Installation of Cables.
Preparation & Termination of: Ethernet, E1, Power cables e.t.c
Test & Measurement of cables (Ethernet, Optical, Power).
Equipment Grounding to the Main Grounding System.
RelatedManuals The following document for OmniBAS
TM
IDU Installation can be used foradditional product information:
# Document Name
1 OmniBAS_System_Ed_5.1_en.pdf
2 OmniBAS_IDU_Product Catalog_en_ed1.pdf
Conventions This document applies the following conventions:
This symbol means DANGER. The purpose of this symbol is towarn you that any wrong action can cause bodily injury or evendeath.
This symbol means CAUTION. The purpose of this symbol is toprevent you from performing an action that might result in damageof the equipment.
NOTE A note calls your attention to important supplementary information.
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
8/120
Chapter 1. Introduction
4
About this Document, Continued
ContactInformation
INTRACOM S.A. TELECOM SOLUTIONS
19.7 km Markopoulou Ave., Peania, Athens, GR-19002Tel. (+30) 210 667 1000, Fax: (+30) 210 667 1001
http://www.intracom-telecom.com
http://www.intracom-telecom.com/http://www.intracom-telecom.com/5/19/2018 OmniBAS IDU Installation Ed4.0 En
9/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
5
Equipment Disposal
Disposal of old electrical and electronic equipment (applicable through theEuropean Union and other European countries with separate waste collectionsystems).
This symbol, found on this product and any of its parts or on its operatinginstructions or on its packaging, indicates that electrical and electronic equipmentmay not be disposed of as unsorted municipal waste. Instead, this product shouldbe handed over to applicable collection points for the recycling of electrical andelectronic equipment.
By ensuring the correct disposal of this product, you will help prevent potentialnegative consequences to the environment and human health, which couldotherwise be caused by inappropriate disposal of this product.
By recycling, reusing and other forms of recovery of old electrical and electronicequipment you are making an important contribution to the conservation of natural
resources and to the protection of the environment.For more information about the recycling of this product, please contact your localmunicipal authorities, municipal waste disposal service or the store where youpurchased this product.
( ).
, ,
, , . .
, , .
, .
,
, .
, ..(www.electrocycle.gr
).
http://www.electrocycle.gr/http://www.electrocycle.gr/5/19/2018 OmniBAS IDU Installation Ed4.0 En
10/120
Chapter 1. Introduction
6
Overview of OmniBAS Product Family
Introduction The OmniBAS family of Intracom Telecom IP MW PtP portfolio comprises:
Split-mount systems:-OmniBAS Indoor Units (IDUs), 1RU / 2RU high and 19wide.
-OmniBAS Outdoor Units (ODUs) & antenna systems.
The OmniBAS-XR all-outdoor system integrating everything(baseband / controller / modem / radio) into a robust enclosure. Thisproduct belongs to all outdoor family. Therefore, for the installation &cabling manual please refer to OmniBAS-XR_Installation_Ed2.0_en.pdf
document.
OmniBASIDUs
The OmniBAS Indoor Units (IDUs) are shown below:
Indoor Unit (IDU) Description
OmniBAS-2W - Ethernet only
OmniBAS-2W - 8E1
OmniBAS-2W-16E1
Native-IP, highly-flexible unit 1RUaccommodating two modems. It can bepositioned at the edge of the network, orcan be used as a repeater and even as aring node. OmniBAS-2W is available inthree versions.
Interfaces
OmniBAS-2W Ethernet-only:1xGbE & 4xFE
OmniBAS-2W Ethernet & 8xE1:1xGbE, 4xFE & 8xE1
OmniBAS-2W Ethernet & 16xE1:
4xGbE & 16xE1
OmniBAS-4W
Native-IP, highly-modular unit 1RUaccommodating up to four modems (withor without XPIC functionality). High airthroughput (1.6 Gbit/s) and 16 x E1 add /drop capabilities to fit demanding nodalapplications.
Interfaces
2xGbE, 2xFE & 16xE1
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
11/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
7
Overview of OmniBAS Product Family, Continued
OmniBASIDUs, continued
Indoor Unit (IDU) Description
OmniBAS-8W
OmniBAS-8W is the newestmember of the OmniBASfamilyfeaturing a leading ConvergedBackhaul and Aggregation Node(CBAN).
It is a highly-modular indoor unit 2RUcapable to simultaneouslyaccommodate eight radio modems,two interface cards and two controllercards in the same chassis.
Modems can be flexibly chosen
based on the connection to an ODU(through coaxial IF cabling) or to an
all-outdoor OmniBAS-XR system(through Ethernet cabling).
Interfaces
2 x GbE (electrical) & 4 x GbE(SFP), per Control Card
32 x E1, per Interface Card
4 x STM-1, per Interface Card
5/19/2018 OmniBAS IDU Installation Ed4.0 En
12/120
Chapter 1. Introduction
8
Safety Precautions
PROPER GROUNDING
Never power up the indoor equipment not yet connected to a propergrounding system.
There is risk of equipment failure and/or electrical shock.
Ensure that the indoor grounding system measures a path resistance lessthan 4 .
INDOOR EQUIPMENT PROPER SWITCHING ON / OFF
Never connect or disconnect the power supply cable(s) to or from theindoor equipment when the local dc power supply source is on.
There is risk of equipment failure.
Ensure the local dc power supply source is off and then connect ordisconnect the power supply cable(s) to or from the indoor equipment.
PROTECTION FROM LIGHTNING
Never leave the IF cable coming from the Outdoor Unit withoutadequate lightning protection.
There is risk of equipment failure and/or electrical shock.
Ensure that the IF cable coming from the Outdoor Unit is properly groundedas described in the Outdoor Radio Equipment Installation Manual (GDC-
001/81 manual code).
ESD PROTECTION
Always use proper antistatic protection (i.e. grounding bracelet,
antistatic bags, etc.) when handling the system cards.
Parts bearing the ESD sign (see left) have ESD sensitive exposed
components.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
13/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
9
2 Installation Tools
Tools List This chapter describes the tools requirements for the proper equipment
installation
(1)
:
Item Photo Description
1
Cros screw drivers:
(A): PH-1
(B): PH-3
2 Blade
3 Wire Stripper
4 Cable Jacket Stripper
5
Crimping tool for 1,5 /2,5 & 4 mm2cablecontact with theappropriate die
6Torque wrench 0,8 1,13 Nm, 8 mm
7 Hot-air blower
(1)The tools supply is installer responsibility.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
14/120
Chapter 3. Installation Material
10
3 Installation Material
OmniBAS-2W
PackageContents
The following table depicts the IDU contents for installation:
No Description
1 IDU Factory Test Results Paper.
2 IDU Standard Installation Material.
3 OmniBASTM-IDU.
NOTE
The package contents is the same for all types ofOmniBASTM-2W IDUs.
NOTE Keep the packaging of the equipment in good condition forlater use (i.e. safe transportation during relocation, return for
repair, etc.).
In case of disposal of the packaging material, it isrecommended to follow the safe disposal procedureaccording to local law.
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
15/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
11
OmniBAS-2W, Continued
Mounting kit
No Description Qty
1 Screw, M6 x 12
2 Washer, od = 15, id = 6,43 Caged nut, M6
4 per
idu
IF Tail
No Description Qty
1IF Tail 1,5m, RG223 SMA-type male, R/A to N-typefemale connector.
2
(A): O-ring
(B): Toothed lock washer
(C): Nut
1 setper
modemunit
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
16/120
Chapter 3. Installation Material
12
OmniBAS-2W, Continued
Powerconnector
No Description Qty
1 2-pole power connector.2 peridu
2 Heat Shrinkable Tube, 10cm. 1 peridu
3 Metallic pins for power connector for cable up to 1.5 mm2.4 peridu
4 Metallic pins for power connector for cable up to 2.5 mm24 peridu
Tie-wraps
No Description Qty
1 Tie-wraps 45cm, for indoor cables fastening.20 per
idu
2The screw and nut included are for connection ofOmniBASTM-4W grounding cable to the rack groundingterminal.
1 setper idu
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
17/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
13
OmniBAS-2W, Continued
Serial Cable forexternal alarms
Description Qty
External Alarm Cable 2m, Y-Type, DB9(Female), DB15(VGA),open end.
1 peridu
5/19/2018 OmniBAS IDU Installation Ed4.0 En
18/120
Chapter 3. Installation Material
14
OmniBAS-4W
PackageContents
The following table depicts the IDU contents for installation:
No Description
1 IDU Factory Test Results Paper.
2 IDU Standard Installation Material.
3 OmniBASTM-IDU.
NOTE Keep the packaging of the equipment in good condition forlater use (i.e. safe transportation during relocation, return forrepair, etc.).
In case of disposal of the packaging material, it isrecommended to follow the safe disposal procedureaccording to local law.
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
19/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
15
OmniBAS-4W, Continued
Mounting kit
No Description Qty
1 Screw, M6 x 12
2 Washer, od = 15, id = 6,43 Caged nut, M6
4 per
idu
IDU brackets
No Description Qty
1 Set of metallic bracket for chassis mounting.2 peridu
2 & 3Set of screws & washers for fixing metallic brackets forchassis mounting.
4 & 4per idu
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
20/120
Chapter 3. Installation Material
16
OmniBAS-4W, Continued
IF Tail
No Description Qty
1IF Tail 1,5m, RG223 SMA-type male, R/A to N-typefemale connector.
2
(A): O-ring
(B): Toothed lock washer
(C): Nut
1 permodemunit
Powerconnector
No Description Qty
1 2-pole power connector.2 peridu
2 Heat Shrinkable Tube, 10cm.1 peridu
3 Metallic pins for power connector for cable up to 1.5 mm2.4 peridu
4 Metallic pins for power connector for cable up to 2.5 mm24 peridu
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
21/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
17
OmniBAS-4W, Continued
Tie-wraps
No Description Qty
1 Tie-wraps 45cm, for indoor cables fastening.20 per
idu
2
The screw and nut included are for connection of
OmniBASTM
-4W grounding cable to the rack groundingterminal.
1 set
per idu
Screws formodules
Description Qty
Set of Screws for Modules Mounting 10 peridu
Serial Cable forexternal alarms
Description Qty
External alarm cable 2m, Y-Type, DB9(female), Mini DIN(7),open end
1 peridu
5/19/2018 OmniBAS IDU Installation Ed4.0 En
22/120
Chapter 3. Installation Material
18
OmniBAS-8W
PackageContents
The following table depicts the IDU contents for installation:
No Description
1 IDU Factory Test Results Paper.
2 IDU Standard Installation Material.
3 OmniBASTM-IDU.
NOTE Keep the packaging of the equipment in good condition forlater use (i.e. safe transportation during relocation, return forrepair, etc.).
In case of disposal of the packaging material, it isrecommended to follow the safe disposal procedureaccording to local law.
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
23/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
19
OmniBAS-8W, Continued
Mounting kit
No Description Qty
1 Screw, M6 x 12
2 Washer, od = 15, id = 6,43 Caged nut, M6
4 per
idu
IF Tail
No Description Qty
1IF Tail 1,5m, RG223 SMA-type male, R/A to N-typefemale connector.
2
(A): O-ring
(B): Toothed lock washer
(C): Nut
1 permodem
unit
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
24/120
Chapter 3. Installation Material
20
OmniBAS-8W, Continued
Groundingcable for idu
Description Qty
Grounding cable already terminated at both ends, 1m.Cross-head screw & grover already screwed on thegrounding point of the indoor unit.
1 per unit
Powerconnector
No Description Qty
1 2-pole power connector.2 peridu
2 Heat Shrinkable Tube, 10cm.1 peridu
3 Metallic pins for power connector for cable up to 4 mm2.4 peridu
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
25/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
21
OmniBAS-8W, Continued
Tie-wraps
No Description Qty
1 Tie-wraps 45cm, for indoor cables fastening.20 per
idu
2
The screw and nut included are for connection of
OmniBASTM
-8W grounding cable to the rack groundingterminal.
1 set
per idu
Screws formodules
Description Qty
Set of Screws for Modules Mounting 18 peridu
Serial Cable forexternal alarms
Description Qty
External alarm cable, 2m, Y-Type, DB9(female), Micro-D 15C,open end
1 peridu
5/19/2018 OmniBAS IDU Installation Ed4.0 En
26/120
Chapter 4. Before Starting the Installation
22
4 Before Starting the Installation
4.1 Installation Prerequisites
Introduction This section describes the main actions that must be taken in considerationprior to the equipment installation.
Site survey Site survey should take place before starting the installation, taking into account thefollowing:
Location of appropriate grounding points.
Location of appropriate power supply distribution points.
Location of cable conduits available for routing the coaxial cables(interconnecting the indoor with the outdoor equipment)
Location of the network port distributors.
Thermal considerations and cooling requirements for the rack-mountedequipment.
Equipment rack occupation details.
Network portdistributors
Regarding the network ports (inclusive of STM-1, Ethernet, E1) provided bythe indoor equipment, suitable optical (or electrical) network port distributorsshould be available.
The exact location of the network port distributors, as well as the networkports to reserve, should be known prior to installing the indoor equipment.
Also, all the reserved ports on the network port distributors should bequalified and tested before realizing the network connections with the indoor
equipment.
Indoorpremisesconditions
The operating conditions (temperature, humidity) at the indoor premisesshould meet the specifications given by the manufacturer of the indoorequipment.
Indoorgroundingsystem
All racks within the installation premises should be connected to a low-resistance grounding system. The metal body of the rack, into which thesubracks are to be mounted, should be connected to this grounding system.
The enclosure of each subrack must be electrically connected to the racksmetal body (via a short grounding cable) to provide protection againstharmful discharge conditions.
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
27/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
23
Installation Prerequisites, Continued
Cable conduits Appropriate cable conduits should exist for the routing of installed cables,
inclusive of the coaxial IF cable(s) connecting the indoor equipment with theoutdoor transceiver boxes on the buildings roof.
Power supplyrequirements
The OmniBASTM- 2W /4Wsubracks require connection to a DC distributionboard accommodating either one or two Magnetic Circuit Breakers (MCB,
single-pole, 7 A, 80 V dc, B-curve for Telecom Applications).
The OmniBASTM- 8Wsubracks require connection to a DC distributionboard accommodating either one or two Magnetic Circuit Breakers (MCB,single-pole, 25 A, 80 V dc, B-curve for Telecom Applications).
Power consumption and input DC voltage range are as specified by themanufacturer of the equipment.
Lightningprotection
The network port distributors (optical distributors excluded) and the powersupply distributors should be equipped with the appropriate gas arresters, toprovide protection against lightning conditions.
Such conditions may induce voltage peaks on the cables, and thus disturbthe operation of the indoor equipment. For this purpose, all electricaldistributors should be connected to the local grounding system to allow the
installed gas arresters to operate.
Safety The indoor equipment premises should be of restricted access.
Only trained, authorized personnel should have access to the installedequipment.
Appropriate labeling should exist at points with high risk of contact withhazardous voltage.
A list with emergency phone numbers (e.g. medical assistance numbers)should be hung at easy-to-view positions.
Also, recommended are for safety purposes, a fire detection system and fire
extinguishers (installed at easy-to-access points) inside the installationpremises.
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
28/120
Chapter 4. Before Starting the Installation
24
Installation Prerequisites, Continued
Rack spacerequirements
The indoor equipment will be installed in an ETSI equipment rack.
IDURackSpace
Air-flowDirection
2W 1RU
4W 1RU
8W 2RU
NOTENo extra space is required for cooling.
Furthermore, sufficient free space should be left around therack position to allow for easy access, handling,maintenance and inspection of the installed equipment.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
29/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
25
4.2 Cabling Overview
OmniBASTM
-2W (8xE1)
No. Description
1 IF Tails (from radio outdoor unit)
2 8 x E1 Tributaries
3a 1 x Gigabit Ethernet Cable (Electrical Interface)
3b 1 x Fiber Cable (Gigabit Ethernet SFP Optical)
4 4 x Fast Ethernet Cables (Traffic / Inband)5 2 x Fast Ethernet Cables (Outband)
6 Serial Cable for External Alarms (AUX)
7 Engineering Order Wire Cable (EOW)
8 2 MHz External Synchronization Cable (IN/OUT)
9 DC Power Supply Cable
NOTE Either 3a or 3b port can be used for traffic (not simultaneously)
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
30/120
Chapter 4. Before Starting the Installation
26
Cabling Overview, Continued
OmniBASTM
-2W (ETH Only)
No. Description
1 IF Tails (from radio outdoor unit)
2a 1 x Gigabit Ethernet Cable (Electrical Interface)
2b 1 x Fiber Cable (Gigabit Ethernet SFP Optical)
3 4 x Fast Ethernet Cables (Traffic / Inband)
4 2 x Fast Ethernet Cables (Outband)
5 Serial Cable for External Alarms (AUX)
6 Engineering Order Wire Cable (EOW)
7 2 MHz External Synchronization Cable (IN/OUT)
8 DC Power Supply Cable
NOTE Either 2a or 2b port can be used for traffic (not simultaneously)
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
31/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
27
Cabling Overview, Continued
OmniBASTM
-2W (16xE1)
No. Description
1 IF Tails (from radio outdoor unit)
2 1 x 16 E1 Tributaries (with add/drop capabilities)
3a 1 x Gigabit Ethernet Cable
3b 1 x Fiber Cable (Gigabit Ethernet SFP Optical)
4 2 x Gigabit Ethernet Cables (Traffic / Inband)
5 2 x Fast Ethernet Cables (Outband)
6 Serial Cable for External Alarms (AUX)
7 2 MHz External Synchronization Cable (IN/OUT)
8-9 DC Power Supply Cables(1)
NOTE Either 3a or 3b port can be used for traffic (not simultaneously).
NOTE Combination of 1 x 3a & 1 x 3b interfaces is also available.
(1)The second power supply cable is optional
5/19/2018 OmniBAS IDU Installation Ed4.0 En
32/120
Chapter 4. Before Starting the Installation
28
Cabling Overview, Continued
OmniBASTM
-4W (2xGbE &2xFE)
No. Description
1 IF Tails (from radio outdoor unit)
2 1 x 16 E1 Tributaries (with add/drop capabilities)
3 DC Power Supply Cables(1)
4 2 x Gigabit Ethernet (Optical or Electical SFP)
5 2 x Fast Ethernet Cables (Traffic / Inband)
6 2 x Fast Ethernet Cables (Outband)
7 Serial Cable for External Alarms (AUX)
8 2 MHz External Synchronization Cable (IN/OUT)
Continued on next page
(1)The second power supply cable is optional
5/19/2018 OmniBAS IDU Installation Ed4.0 En
33/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
29
Cabling Overview, Continued
OmniBASTM
-8W
No. Description
1 IF Tails (from radio outdoor unit)
2 4 x Fiber Cables (4 x STM 1 / VC-12 (with add/drop capabilities)
3 2 x 16 E1 Tributary Cables (with add/drop capabilities)
4 2 MHz External Synchronization Cable (IN/OUT)5 PPS Synchronization Cable (IN/OUT)
6 High Speed Cable for OmniBASTM-8W indoor units interconnection.
74 x Gigabit Ethernet Cables to SFPs (Optical or Electrical) (Traffic/ Inband)
8 2 x Gigabit Ethernet Electrical Cables (Traffic / Inband)
9 1 x Fast Ethernet Cables (Outband)
10 Serial Cable AUX and External Alarms
11 DC Power Supply Cable
5/19/2018 OmniBAS IDU Installation Ed4.0 En
34/120
Chapter 5. Mechanical Installation
30
5 Mechanical Installation
5.1 OmniBAS-2W
Chassis Overview
Indoor UnitSlots
The cards of OmniBASTM-2W are already installed according to thecustomer ordered codes.
The following pictures and diagrams show the composition of all available2W indoor units.
OmniBASTM-2W is available in three variants, as below:
8E1 OmniBASTM-2W 8E1
Ethernet Only OmniBASTM-2W Ethernet Only
16E1 OmniBASTM-2W 16E1
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
35/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
31
Chassis Overview, Continued
OmniBAS-2WTM
8E1 & EthernetOnly IDU Slots
SlotID
Photo Card
M1M2
Point-to-Point MODEM.
OmniBASTM-2W, 1xGig-ETH, 4 x FE, 8 x E1Interfaces.
C
OmniBASTM-2W, 1 xGig-ETH, 4 x FEInterfaces.
OmniBAS-2WTM
16E1 IDU Slots
SlotID
Photo Card
D Dummy Panel(1).
M1M2
Point-to-Point MODEM.
C OmniBAS
TM
-2W, 4 xGig-ETH, 16 x E1Interfaces.
(1)Reserved for future use (Fan Tray). Currently applicable only in OmniBAS
TM-2W 16E1 Subrack.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
36/120
Chapter 5. Mechanical Installation
32
IDU Installation
Prerequisites Ensure that the installation premises are equipped with a reliable, low-
impedance ground connection system.
Required Tools& Accessories
The following tools will be needed:
Item 1-B (refer to Installation Toolson page 9)
The following accessories will be needed:
Product Description
OmniBASTM-2W Mounting kit(refer on page 11)
OmniBAS
TM
-4W -OmniBASTM-8W -
Procedure To perform the mechanical installation of the unit, follow the steps below:
Step Action
1 Use the mounting kit to install the chassis into the rack, as shown below.
(A) First install the cage nut (item 1) on the desired rear side of therack.
(B) Lift the idu on the corresponding position.
(C) Mount the idu using the screw (item 2) on the front side of therack.
2 To ground OmniBASTM
-2W, connect the loose end of the grounding
cable to the rack grounding terminal.
End of procedure
5/19/2018 OmniBAS IDU Installation Ed4.0 En
37/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
33
5.2 OmniBAS-4W
Chassis Overview
Introduction The cards of OmniBASTM
-4W are already installed according to the customerordered codes. The following picture and diagram shows the exact position of eachslot that consist an OmniBAS
TM-4W indoor unit:
Slot ID Photo Modules
F FAN TRAY.
POWER SUPPLY UNIT.
PS1, PS2
DUMMY PLATE, POWER UNIT.
Point-to-Point XPIC MODEM.
Point-to-Point MODEM.
M1, M2, M3,M4
DUMMY PLATE, MODEM.
16 E1 INTERFACE UNIT.
E1
DUMMY PLATE, USER MODULE.
(electrical)
CONTROL ELECTRICAL.
C
(optical)CONTROL OPTICAL.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
38/120
Chapter 5. Mechanical Installation
34
IDU Installation
Prerequisites Ensure that the installation premises are equipped with a reliable, low-
impedance ground connection system.
Required Tools& Accessories
The following tools will be needed:
Item 1-B (refer to Installation Toolson page 9)
The following accessories will be needed:
Product Description
OmniBASTM-2W -
OmniBAS
TM
-4W Mounting kit(refer on page 15)OmniBASTM-8W -
Procedure To perform the mechanical installation of the unit, follow the steps below:
Step Action
1 Use the mounting kit to install the chassis into the rack, as shown below.
(A) First install the cage nut (item 1) on the desired rear side of therack.
(B) Lift the idu on the corresponding position.
(C) Mount the idu using the screw (item 2) on the front side of therack.
2 To ground OmniBASTM-4W, connect the loose end of thegrounding cable to the rack grounding terminal.
End of procedure
5/19/2018 OmniBAS IDU Installation Ed4.0 En
39/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
35
5.3 OmniBAS-8W
Chassis Overview
Introduction The cards of OmniBASTM
-8W are already installed according to the customerordered codes. The following picture and diagram shows the exact position of eachslot that consist an OmniBAS
TM-8W indoor unit:
Slot ID Photo Modules
F FAN TRAY.
Point to Point XPIC MODEM .
Point to Point MODEM.
Point to Point MODEM Wireline SingleElectrical Optical.
M1 up
to M8
MODEM DUMMY PLATE.
SDH (4 x STM1) INTERFACE UNIT.
32E1 (2 x 16) INTERFACE UNIT.I1,I2
INTERFACE DUMMY PLATE.
CONTROL Combo(OPTICAL/ELECTRICAL).
POWER SUPPLY UNIT.C1
(1),C2
CONTROL DUMMY PLATE.
(1)C1 slot is available for additional card installation of Power Supply Unit (PSU) or secondControl Card (with PSU).
5/19/2018 OmniBAS IDU Installation Ed4.0 En
40/120
Chapter 5. Mechanical Installation
36
IDU Installation
Prerequisites Ensure that the installation premises are equipped with a reliable, low-
impedance ground connection system.
Required Tools& Accessories
The following tools will be needed:
Item 1-B (refer to Installation Toolson page 9)
The following accessories will be needed:
Product Description
OmniBASTM-2W -
OmniBAS
TM
-4W -OmniBASTM-8W Mounting kit(refer on page 19)
Procedure To perform the mechanical installation of the unit, follow the steps below:
Step Action
1 Use the mounting kit to install the chassis into the rack, as shown below.
(A) First install the cage nut (item 1) on the desired rear side of therack
(B) Lift the idu on the corresponding position
(C) Mount the idu using the screw (item 2) on the front side of therack
2 Choose one of the two available grounding points for idugrounding, as highlighted below:
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
41/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
37
IDU Installation, Continued
Procedure (continued)
Step Action
3 First install the grounding cable as shown below:
Then, connect the loose end of the grounding cable to the rackgrounding terminal.
End of procedure
5/19/2018 OmniBAS IDU Installation Ed4.0 En
42/120
Chapter 6. Cabling Installation
38
6 Cabling Installation
Overview This chapter describes how to install the following type of cables for all
OmniBAS
TM
Products Family.
Mainly the cables categorized as follows:
Power Supply Cables
IF Tails
E1 Terminations
I/O Cable
Ethernet Cable
High Speed Interconnection Cable (for OmniBASTM-8W)
5/19/2018 OmniBAS IDU Installation Ed4.0 En
43/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
39
6.1 Power Supply Cables
Introduction The following table provides all the available power cables with the following
characteristics:
The cable length is defined based on customer request:
Order Code Description Product
ACC-KO-PW-VV-15Black Color, stranded, PVC, 300 V,2 x 1,5 mm2
2W
4W
ACC-KO-PW-VV-25Black Color, stranded, PVC, 300 V,
2 x 2,5 mm2
2W
4W
8W
ACC-KO-PW-VV-40Black Color, stranded, PVC, 300 V,
2 x 4 mm2 8W
For OmniBASTM-2W/4W it is recommended to use 2 x 2,5 mm2,
stranded, PVC, black, 300 V power cable.
For OmniBASTM-8W it is recommended to use 2 x 4 mm2,stranded, PVC, black, 300 V power cable.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
44/120
Chapter 6. Cabling Installation
40
Preparation
Introduction The power cable preparation is common for all OmniBASTM Products
Family.
Required Tools& Accessories
The following tools will be needed:
Items 2, 3, 4, 5 & 7 (refer to Installation Toolson page 9)
The following accessories will be needed:
Product Description
OmniBASTM-2W
Power connector(refer on page 12)
Power Supply Cable ACC-KO-PW-VV-25 (refer on
page 39)
OmniBASTM-4W
Power connector(refer on page 16)
Power Supply Cable ACC-KO-PW-VV-25 (refer onpage 39)
OmniBASTM-8W
Power connector(refer on page 20)
Power Supply Cable ACC-KO-PW-VV-40 (refer onpage 39)
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
45/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
41
Preparation, Continued
Procedure For power supply cable preparation and termination to power connector,
proceed as follows:
Step Action
1 Strip the wires of the cable as shown below:
2 Cut 50 mm of heat shrink tube and pass it through:
3 Place the stranded wire into the connector contact. If you havestripped the stranded wire properly, the jacket should stop at point(1) and the stranded wire at point (2):
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
46/120
Chapter 6. Cabling Installation
42
Preparation, Continued
Procedure (continued)
Step Action
4 Take care to place the appropriate die (1,5 /2,5 / 4
mm2connector contact) in the crimping tool toavoid damage of the connector contact.
Crimp with the crimping tool. Different views ofcrimping are shown below:
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
47/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
43
Preparation, Continued
Procedure (continued)
Step Action
5 Repeat steps 3 and 4 for the other stranded wire. When youfinish, the cable should resemble to the photo below:
6 Insert the stranded wires into the connector(blue to pin 1, brownto pin 2). You must hear the clicking sound.
7 Heat the heat shrinkable tube with a hot-air blower. When youfinish, the cable should resemble to the photo below:
End of procedure
5/19/2018 OmniBAS IDU Installation Ed4.0 En
48/120
Chapter 6. Cabling Installation
44
Installation
OmniBASTM
-2W
prerequisites
The following are recommended:
The powerat the inputof OmniBAS
TM
-2W must be in the range40 V dc to 60 V dc.
The positive pole of the power supply source at OmniBASTM-2W
station must be grounded.
Powerconnectionoverview
Safety requirements require a single pole circuit-breaker to beemployed between the local dc power supply source and eachpower supply of OmniBASTM-2W. The circuit-breaker mustdisconnect the V pole of the power supply.
Before plugging or unplugging any power cable intoOmniBASTM-2W, you must set the circuit breaker(s) to OFF!
No Description
1 Power Cable
2 Single pole Circuit Breaker (MCB), 7 A, 80 V dc, B-curve for Telecom
Applications3 Local DC Power Distributor
NOTETwo power connectors apply to OmniBAS
TM-2W 16E1, using both of them
is optional.
NOTETwo power connectors apply to OmniBAS
TM-2W 16E1, using both of them
is optional.
NOTEAll OmniBAS
TM-2W IDU with 8E1s & Ethernet Only supports one power
contact.
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
49/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
45
Installation, Continued
Procedure To connect the power supply, proceed as follows:
Step Action
1 Switch-off the circuit breaker connected between the OmniBASTM-2W and the local dc power supply source.
2 Plug the power supply cable(s) into the power supplyreceptacle(s) on the front panel of the OmniBASTM-2W withoutapplying excessive force.
Applying pressure while the connector is inserted incorrectlyit might cause damage.
If you want to disconnect the power supply cable, push
downwards the metallic secure lock on the upper part of theconnector (1) and pull outwards to disconnect (2).
End of procedure
NOTEThe above procedure is related to OmniBAS
TM-2W IDU with 8E1s &
Ethernet Only that supports one power connection.
The OmniBASTM
-2W IDU with 16E1 supports two power cableconnections and the procedure is the same as above for both powercables.
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
50/120
Chapter 6. Cabling Installation
46
Installation, Continued
OmniBASTM
-4W
prerequisites
The following are recommended:
The powerat the inputof OmniBAS
TM
-4W must be in the range40 V dc to 60 V dc.
The positive pole of the power supply source at OmniBASTM-4W
station must be grounded.
Powerconnectionoverview
Safety requirements require a single pole circuit-breaker to beemployed between the local dc power supply source and eachpower supply of OmniBASTM-4W. The circuit-breaker mustdisconnect the V pole of the power supply.
Before plugging or unplugging any power cable intoOmniBASTM-4W, you must set the circuit breaker(s) to OFF!
No Description
1 Power Cable
2 Single pole Circuit Breaker (MCB), 7 A, 80 V dc, B-curve for TelecomApplications
3 Local DC Power Distributor
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
51/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
47
Installation, Continued
Procedure To connect the power supply, proceed as follows:
Step Action
1 Switch-off the circuit breaker connected between the OmniBASTM-4W and the local dc power supply source.
2 Plug the power supply cable(s) into the power supplyreceptacle(s) on the front panel of the OmniBASTM-4W withoutapplying excessive force.
Applying pressure while the connector is inserted incorrectlyit might cause damage.
If you want to disconnect the power supply cable, pushdownwards the metallic secure lock on the upper part of theconnector (1) and pull outwards to disconnect (2).
End of procedure
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
52/120
Chapter 6. Cabling Installation
48
Installation, Continued
OmniBASTM
-8W
prerequisites
The following are recommended:
The powerat the inputof OmniBAS
TM
-8W must be in the range40 V dc to 60 V dc.
The positive pole of the power supply source at OmniBASTM-8W
station must be grounded.
Powerconnectionoverview
Safety requirements require a single pole circuit-breaker to beemployed between the local dc power supply source and eachpower supply of OmniBASTM-8W. The circuit-breaker mustdisconnect the V pole of the power supply.
Before plugging or unplugging any power cable intoOmniBASTM-8W, you must set the circuit breaker(s) to OFF!
No Description1 Power Cable
2 Single pole Circuit Breaker (MCB), 25 A, 80 V dc, B-curve forTelecom Applications
3 Local DC Power Distributor
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
53/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
49
Installation, Continued
Procedure To connect the power supply, proceed as follows:
Step Action
1 Switch-off the circuit breaker(s) connected between theOmniBASTM-8W and the local dc power supply source.
2 Plug the power supply cable(s) into the power supplyreceptacle(s) on the front panel of the OmniBASTM-8W withoutapplying excessive force.
Applying pressure while the connector is inserted incorrectly
it might cause damage.
If you want to disconnect the power supply cable, pushdownwards the metallic secure lock on the upper part of theconnector (1) and pull outwards to disconnect (2).
End of procedure
5/19/2018 OmniBAS IDU Installation Ed4.0 En
54/120
Chapter 6. Cabling Installation
50
6.2 IF Tails
IF Tail purpose You should connect the IF cable coming from the Outdoor Unit to the IF tail
to protect the ODU receptacle on the front panel of OmniBAS
TM
indoor unitsagainst mechanical damage, which might occur in case of direct connectionof the heavy IF cable.
Use the requirement tool to tighten the SMA connector.
Required Tools& Accessories
The following tools will be needed:
Item 6 (refer to Installation Toolson page 9)
The following accessories will be needed:
Product Description
OmniBASTM-2W IF Tail(refer on page 11)
Tie-wraps(refer on page 12)
OmniBASTM-4W IF Tail(refer on page16)
Tie-wraps (refer on page17)
OmniBASTM-8W IF Tail19
Tie-wraps (refer on page 21)
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
55/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
51
IF Tails, Continued
Procedure To connect the IF tail(s), follow the steps below:
Step Action
1 Never connect or disconnect an IF tail whenOmniBAS
TM-ODU is ON and Operating! There is risk of
equipment failure.
2 Fix the both ends of the IF tail , as shown below:
3 Tight the N-type female connector onto the IF cable coming fromthe Outdoor Unit.
3 Use the tie-wraps for IF tail cable fastening.
4 Repeat for the remaining IF tails that may exist.
NOTEThe above procedure is applicable for all OmniBASTM-Products Family indoor units.
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
56/120
Chapter 6. Cabling Installation
52
IF Tails, Continued
Connectionusing O-ring
Optionally you can fix the N-type connector of the IF tail onto a metallic
surface through the nut and washer provided inside the IF tail packaging. Ifyou have such a metallic surface, follow the steps below:
Step Action
1 Open a mounting hole on the metallic surface as in the figurebelow (dimensions in mm).
2 Put the -ring onto the N-type connector of the IF tail and passthe N-type connector through the metallic surface you have.
3 Put the toothed lock washer and nut onto the N-type connector asprotruding from the metallic surface.
Item Description
1 O-ring2 Toothed lock washer
3 Nut
4 N-type connector
5 Metallic surface
4 Hand tight the IF cable coming from the Outdoor Unit into the N-type connector protruding from the metallic surface.
End of procedure
5/19/2018 OmniBAS IDU Installation Ed4.0 En
57/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
53
6.3 E1 Terminations
Overview This section provides all the available installations of the E1 cables &
accessories for OmniBAS
TM
Products Family.
Mainly the type of the E1 terminations are categorized as follows:
Open End Cables (Balanced 120)
BNC Terminations (Unbalanced 75)
RJ-45 Terminations (Balanced 120)
5/19/2018 OmniBAS IDU Installation Ed4.0 En
58/120
Chapter 6. Cabling Installation
54
Open End Cables (Balanced 120 )
Overview This paragraph describes the E1 Open End Cables (Balanced 120 )
installation for the following models:
OmniBASTM-2W 8E1
OmniBASTM-2W 16E1 /4W
OmniBASTM-8W
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
59/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
55
Open End Cables (Balanced 120 ), Continued
OmniBASTM
-2W8E1
The cable characteristics are given below:
Order Code Description
ACC-IT-01-RO-081xE1 Cable, Balanced (120 ), Shielded, RJ-45 Jack toOpen End, 8 m.
Procedure To connect the cable, follow the steps below:
Step Action
1 Arrange the cable appropriately so that the E1 cables can beeasily inserted / extracted.
Plug the cable into the receptacle shown in the figure below andthen terminate the open ends of the cables onto the DistributionFrame according to the tables that follow.
2
Quad Color Signal Wire Marking
Tx+ T+White / OrangeOrange Tx- T-
Rx+ R+BlueWhite / Blue Rx- R-
End of procedure
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
60/120
Chapter 6. Cabling Installation
56
Open End Cables (Balanced 120 ), Continued
OmniBASTM
-2W16E1 /4W
The cable characteristics are given below:
Order Code Description
ACC-LT-16-IO-1016xE1 Cable, Balanced (120 ), 68 Pins HighDensity Connector to Open End, 10 m
ACC-KT-16-3O-03
ACC-KT-16-3O-07
ACC-KT-16-3O-10
16xE1 Cable, Balanced (120 ), 68 Pins HighDensity Connector to Open End,3 m
16xE1 Cable, Balanced (120 ), 68 Pins HighDensity Connector to Open End,7 m
16xE1 Cable, Balanced (120 ), 68 Pins HighDensity Connector to Open End,10 m
Procedure To connect the cable, follow the steps below:
Step Action
1 Arrange the cable appropriately so that the Interface Card can beeasily inserted / extracted.
2 Plug the cable into the receptacle shown in the figure below andthen terminate the open ends of the cable onto the DistributionFrame according to the color cable table (see appendixAppendix-
E: Open End Cables Color Codes)
OmniBASTM-2W 16E1 OmniBASTM-4W
End of procedure
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
61/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
57
Open End Cables (Balanced 120 ), Continued
OmniBASTM
-8W The cable characteristics are given below:
Order Code Description
ACC-WT-U1-VO-3
ACC-WT-U1-VO-10
16xE1 Cable, Balanced (120 ), 64 Pins Connectorto Open End, 3 m
16xE1 Cable, Balanced (120 ), 64 Pins Connectorto Open End, 10 m
Procedure To connect the cable, follow the steps below:
Step Action1 Arrange the cable appropriately so that the Interface Card can be
easily inserted / extracted.
2 Plug the cable into the receptacle shown in the figure below andthen terminate the open ends of the cable onto the DistributionFrame according to the color cable table (see appendixAppendix-E: Open End Cables Color Codes)
End of procedure
5/19/2018 OmniBAS IDU Installation Ed4.0 En
62/120
Chapter 6. Cabling Installation
58
BNC Terminations (Unbalanced 75 )
Overview This paragraph describes the BNC terminations (Unbalanced 75 ) for the
following models:
OmniBASTM-2W 8E1
OmniBASTM-2W 16E1 /4W
OmniBASTM-8W
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
63/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
59
BNC Terminations (Unbalanced 75 ), Continued
OmniBASTM
-2W8E1
The cable / panel characteristics are given below:
Order Code Description
ACC-C-T-U1-IDC-J-01
ACC-LN-16-1N-VV
8xE1 Cable, Balanced (120 ), RJ-45 Jacks to 68Pins High Density Connector, 0.8 m
Conversion Panel with 68 Pins High DensityReceptacle and 16 Pairs(Tx-Rx) BNC (75 )
receptacles
Procedure To connect the cable, follow the steps below:
Step Action
1 Arrange the cable appropriately so that the cables can be easilyinserted / extracted.
2 Plug both ends of the cable into the relevant receptacles, asshown in the figure below:
End of procedure
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
64/120
Chapter 6. Cabling Installation
60
BNC Terminations (Unbalanced 75 ), Continued
OmniBASTM
-2W16E1 /4W
The cable / panel characteristics are given below:
Order Code Description
ACC-C-T-U1-IDC-IDC-00
ACC-LN-16-1N-VV
16xE1 Cable, Balanced (120 ), both Ends 68Pins High Density Connector, 0.5 m.
Conversion Panel with 68 Pins High DensityReceptacle and 16 Pairs(Tx-Rx) BNC (75 )
receptacles.
Procedure To connect the cable, follow the steps below:
Step Action
1 Arrange the cable appropriately so that the Cables & InterfaceCard can be easily inserted / extracted.
2 Plug both ends of the cable into the relevant receptacles, asshown in the figure below:
OmniBASTM-2W 16E1 OmniBASTM-4W
End of procedure
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
65/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
61
BNC Terminations (Unbalanced 75 ), Continued
OmniBASTM
-8W
The cable / panel characteristics are given below:
Order Code Description
ACC-WT-CP-IV-07
ACC-LN-16-1N-VV
16xE1 Cable, Balanced (120 ), 64 Pins Connector to 68 Pins HighDensity Connector, 0.7 m.
Conversion Panel with 68 Pins High Density Receptacle and 16Pairs(Tx-Rx) BNC (75 ) receptacles.
Procedure To connect the cable, follow the steps below:
Step Action
1 Arrange the cable appropriately so that the Interface Card can beeasily inserted / extracted.
2 Plug both ends of the cable into the relevant receptacles, asshown in the figure below:
End of procedure
5/19/2018 OmniBAS IDU Installation Ed4.0 En
66/120
Chapter 6. Cabling Installation
62
RJ-45 Terminations (Balanced 120 )
Overview This paragraph describes the RJ-45 terminations (Balanced 120 ) for the
following models:
OmniBASTM-2W 16E1 /4W
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
67/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
63
RJ-45 Terminations (Balanced 120 ), Continued
OmniBASTM
-2W16E1 /4W
The cable / panel characteristics are given below:
Order CodeDescription
Product
MOD-W-EC
MOD-O-MB
16xE1 Cable, Balanced (120 ), 68 Pins HighDensity Connector to RJ-45 Jacks, 0.8 m.
Mounting Bracket for 16 x RJ-45 E1Receptacles.
Procedure To connect the cable, follow the steps below:
Step Action
1 Arrange the cable appropriately so that the controller card &cables can be easily inserted / extracted.
2 Plug both ends of the cable into the relevant receptacles, asshown in the figure below. The E1 numbering is indicated throughspecial cable marking.
OmniBASTM-2W 16E1 OmniBASTM-4W
End of procedure
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
68/120
Chapter 6. Cabling Installation
64
RJ-45 Terminations (Balanced 120 ), Continued
Use of RJ-45MountingBracket
You can optionally install the RJ-45 mounting bracket for optimum
arrangement of E1 tributary cables, as shown below:
Detail
Detail
5/19/2018 OmniBAS IDU Installation Ed4.0 En
69/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
65
6.4 I/O Cables
RequiredAccessories
The following accessories will be needed:
Product Description
OmniBASTM-2W Serial Cable for external alarms(refer on page 13)
OmniBASTM-4W Serial Cable for external alarms(refer on page 17)
OmniBASTM-8W Serial Cable for external alarms(refer on page 21)
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
70/120
Chapter 6. Cabling Installation
66
I/O Cables, Continued
Procedure forOmniBAS
TM-2W
To connect the external alarm cable, follow the steps below:
Step Action
1 Arrange the cable appropriately so that the Controller Card can beeasily inserted / extracted.
2 Plug the cable into the AUX receptacle shown in the figure below:
3 Terminate the open end of the cable based on the chromatic codegiven inAppendix-D: Receptacles Pin OutAUXon page 90.
End of procedure
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
71/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
67
I/O Cables, Continued
Procedure forOmniBAS
TM-4W
To connect the external alarm cable, follow the steps below:
Step Action
1 Arrange the cable appropriately so that the Controller Card can beeasily inserted / extracted.
2 Plug the cable into the AUX receptacle shown in the figure below:
3 Terminate the open end of the cable based on the chromatic codegiven inAppendix-D: Receptacles Pin OutAUXon page 99.
End of procedure
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
72/120
Chapter 6. Cabling Installation
68
I/O Cables, Continued
Procedure forOmniBAS
TM-8W
To connect the external alarm cable, follow the steps below:
Step Action
1 Arrange the cable appropriately so that the Controller Card can beeasily inserted / extracted.
2 Plug the cable into the AUX 2 receptacle shown in the figure
below:
3 Terminate the open end of the cable based on the chromatic code
given inAppendix-D: Receptacles Pin OutAUX 2on page 107.
End of procedure
5/19/2018 OmniBAS IDU Installation Ed4.0 En
73/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
69
6.5 Ethernet Cables
OmniBASProductsFamily
The cable characteristics are given below:
Order CodeDescription
Product
ACC-IO-PA-JJ-01
ACC-IO-PA-JJ-05
ACC-IO-PA-JJ-10
Ethernet Straight Cable Prefabricated, CAT5e,Terminated both ends to RJ-45 Jack, 1 m
Ethernet Straight Cable Prefabricated, CAT5e,Terminated both ends to RJ-45 Jack, 5 m
Ethernet Straight Cable Prefabricated, CAT5e,Terminated both ends to RJ-45 Jack, 10 m
CableInstallation
Terminate each end of the cable to the corresponding RJ-45 jack.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
74/120
Chapter 6. Cabling Installation
70
6.6 High Speed Interconnection Cable (for OmniBASTM-8W)
OmniBASTM
-8W The cable characteristics are given below:
Order CodeDescription
Product
ACC-WT-GB-VV-1High Speed Cable, Prefabricated, for Interconnectionbetween two OmniBAS
TM-8W units, Latch, 1 m.
Procedure To connect the cable, follow the steps below:
Step Action
1 Arrange the cable appropriately so that the controller card can beeasily inserted / extracted.
2 Plug the cable into the relevant receptacle, as shown in the figurebelow:
End of procedure
5/19/2018 OmniBAS IDU Installation Ed4.0 En
75/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
71
7 Cable Characteristics
7.1 GbE Cable Characteristics
OmniBAS-2W
Electrical GbEcablecharacteristics
Type of cable CAT6 or higher, UTP,4 pairs x AWG26 / AWG24
Cable termination (module side) RJ-45 plug
Cable terminated on Receptacles on the module front panel, asfollowing:
GbE 1, 2, 3, 4 for OmniBASTM
-2W 16E1.
GbE for OmniBASTM
-2W 8E1.
GbE for OmniBAS
TM
-2W Ethernet Only.Cable maximum length 100 m
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
76/120
Chapter 7. Cable Characteristics
72
OmniBAS-2W, Continued
Optical GbEcablecharacteristics
Type of cable Fiber
Cable termination (module side) IEEE 802.3z, 1000Base-X (SFP MSAmechanics)
Cable terminated on Receptacles on the module front panel, asfollowing:
GbE 1, 2 for OmniBASTM
-2W 16E1.
GbE for OmniBASTM
-2W 8E1.
GbE for OmniBASTM
-2W Ethernet Only.
Cable maximum length Depends on SFP module.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
77/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
73
OmniBAS-4W
Electrical GbEcablecharacteristics
Type of cable CAT6 or higher, UTP,4 pairs x AWG26 / AWG24
Cable termination (module side) RJ-45 plug
Cable terminated on ETH 100/1000 1, 2 receptacles on the modulefront panel
Cable maximum length 100 m
Optical GbEcablecharacteristics
Type of cable Fiber
Cable termination (module side) IEEE 802.3z, 1000Base-X (SFP MSAmechanics)
Cable terminated on ETH 100/1000 1, 2 receptacles on the modulefront panel
Cable maximum length Depends on SFP module.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
78/120
Chapter 7. Cable Characteristics
74
OmniBAS-8W
Electrical GbEcablecharacteristics
Type of cable CAT6 or higher, UTP,4 pairs x AWG26 / AWG24
Cable termination (module side) RJ-45 plug
Cable terminated on GbE 100/1000 5, 6 receptacles on the modulefront panel
Cable maximum length 100 m
Optical GbEcablecharacteristics
Type of cable MULTIMODE Fiber Optic Cable.
Cable termination (module side) IEEE 802.3z, 1000Base-X (SFP MSAmechanics)
Cable terminated on GbE 1000 1, 2, 3, 4 receptacles on the modulefront panel
Cable maximum length Depends on SFP module.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
79/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
75
7.2 Fast Ethernet Cable Characteristics
OmniBAS-2W
Fast Ethernet
cablecharacteristics
Type of cable CAT5 or higher, UTP, 4 pairs x AWG26
Cable termination (module side) RJ-45 plug
Cable terminated on Receptacles on the module front panel, asfollowing:
NMS 10/100 1, 2 for OmniBASTM
-2W 16E1.
ETH 10/100 1,2,3,4 & NMS 10/100 1,2 for
OmniBASTM
-2W 8E1.
ETH 10/100 1,2,3,4 & NMS 10/100 1,2 forOmniBAS
TM-2W Ethernet Only.
Cable maximum length 100 m
NOTEYou should connect the Network Management System (SNMP) either tothe NMS 10/100 1 or the NMS 10/100 2receptacle for outband
management connection.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
80/120
Chapter 7. Cable Characteristics
76
OmniBAS-4W
Fast Ethernet
cablecharacteristics
Type of cable CAT5 or higher, UTP, 4 pairs x AWG26
Cable termination (module side) RJ-45 plug
Cable terminated on ETH 10/100 1 or2 receptacles on the modulefront panel
NMS 10/100 1 or2 receptacles on the modulefront panel
Cable maximum length 100 m
NOTE
You should connect the Network Management System (SNMP) either to
the NMS 10/100 1 or the NMS 10/100 2receptacle for outbandmanagement connection.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
81/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
77
OmniBAS-8W
Fast Ethernet
cablecharacteristics
Type of cable CAT5 or higher, UTP, 4 pairs x AWG26
Cable termination (module side) RJ-45 plug
Cable terminated on NMG 10/100 receptacle on the module frontpanel
Cable maximum length 100 m
NOTEYou should connect the Network Management System (SNMP) to theNMG 10/100 receptacle for outband management connection.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
82/120
Chapter 7. Cable Characteristics
78
7.3 STM-1 Cable Characteristics
OmniBAS-8W
STM-1 cablecharacteristics
Type of cable Multimode/singlemode fiber optic cable LCtype connector
Cable termination (module side) SFP
Cable terminated on STM-1 1, 2, 3, 4 receptacles on the modulefront panel
Cable maximum length Various lengths of cables are available
5/19/2018 OmniBAS IDU Installation Ed4.0 En
83/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
79
Appendix-A: Modem Card Installation / Removal
Prerequisites The following prerequisites are common for any modem ofOmniBASTM-
Products Familyand must be taken in consideration before starting anyinsertion or extraction of the modem card.
NOTE The Modem Card is hot swappable.
It is recommended before proceeding to the card installation,to wear a grounding braceletand attach it to one of the two
appropriate receptacles on the chassis as given below:
Product Grounding Bracelet Receptacles
OmniBASTM-2W
OmniBASTM-4W
OmniBASTM-8W
Never connect or disconnect an IF tailwhen OmniBASTM-
ODU is ON and Operating! There is risk of equipment failure.
If modem IF tail is installed please refer to Procedureonpage 51for how to connect or disconnect the tail.
Modem insertion or extraction in a live network must be doneby authorized persons ONLY.
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
84/120
Appendix-A: Modem Card Installation / Removal
80
Appendix-A: Modem Card Installation / Removal, Continued
Procedure forOmniBAS
TM-2W
In order to insert a modem card to OmniBASTM-2W indoor unit, please follow
the procedure below:
Step Action
1 Remove the modem dummy plate and keep it for maintenancereasons.
NOTEThe Modem dummy plate is required in 1+0configuration for proper thermal management.
2 Slide the modem card into the appropriate pair of guides andpush it in until it connects to the backplane connector.
3 Hand-tight the two screws on the front panel of the modem cardto secure the card in place.
End of procedure
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
85/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
81
Appendix-A: Modem Card Installation / Removal, Continued
Procedure forOmniBAS
TM-4W
In order to insert a modem card to OmniBASTM-4W indoor unit, please follow
the procedure below:
Step Action
1 Remove the modem dummy plate and keep it for maintenancereasons.
2 Slide the modem card into the appropriate pair of guides and
push it in until it connects to the backplane connector.
3 Hand-tight the two screws on the front panel of the modem cardto secure the card in place.
End of procedure
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
86/120
Appendix-A: Modem Card Installation / Removal
82
Appendix-A: Modem Card Installation / Removal, Continued
Procedure forOmniBAS
TM-8W
In order to insert a modem card to OmniBASTM-8W indoor unit, please follow
the procedure below:
Step Action
1 Remove the modem dummy plate and keep it for maintenancereasons.
2 Slide the modem card into the appropriate pair of guides andpush it in until it connects to the backplane connector.
3 Hand-tight the two screws on the front panel of the modem card
to secure the card in place.
End of procedure
5/19/2018 OmniBAS IDU Installation Ed4.0 En
87/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
83
Appendix-B: I/O Connections
Introduction The I/O signals are provided by the following receptacles:
Product IN OUT Receptacle
OmniBASTM-2W 4 4 AUX
OmniBASTM-4W 2 2 AUX
OmniBASTM-8W 3 2 AUX 2
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
88/120
Appendix-B: I/O Connections
84
Appendix-B: I/O Connections, Continued
OmniBASTM
-2WInput alarmsconnectioncircuit
The dry-contact input alarms are internally pulled up to +3,3 V. When anexternal switch is closed, the corresponding signal is low (alarm condition).
OmniBASTM
-2WOutput alarmsconnectioncircuit
The alarms transmission circuit receives alarms in TTL form from the microprocessorand routes them as external alarms in dry-contact form. When a high signal entersthe relays driver, the relay is activated and current passes through the load of thecorresponding alarm output.
* The maximum ratings for the Voltage Source are:Max DC voltage: V=100 VDC and Max DC current: IL=200 mADC(polarity isinsignificant)The loads can be indicator lamps, relays coils, buzzers, etc.
NOTEApplicable for all types of OmniBASTM-2W IDUs.
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
89/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
85
Appendix-B: I/O Connections, Continued
OmniBASTM
-4WInput alarmsconnectioncircuit
The dry-contact input alarms are internally pulled up to +3,3V. When anexternal switch is closed, the corresponding signal is low (alarm condition).
EXIN1
EXIN2
TO
MICROPROCESSOR
(TTLLEVEL)
SYSTEM
GND
(Each resistor: 10K)
+3,3V
OmniBASTM
-4WOutput alarmsconnection
circuit
The alarms transmission circuit receives alarms in TTL form from themicroprocessor and routes them as external alarms in dry-contact form.When a low signal enters an optocoupler, current passes through the load
of the corresponding EXTOUT (alarm condition).
OPTOCOUPLERS
EXOUT1
EXOUT2
FROM
MICRO
PROCESSOR
(TTLL
EVEL)
SYSTEMLOADS
V*
VOLTAGE
SOURCE
GND FL
ALARM
SIGNALS
IL
* The maximum ratings for the Voltage Source are either:DC: V=100VDC / IL=80mADC(polarity is insignificant)
The loads can be indicator lamps, relays coils, buzzers, etc.
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
90/120
Appendix-B: I/O Connections
86
Appendix-B: I/O Connections, Continued
OmniBASTM
-8WInput alarmsconnectioncircuit
The dry-contact input alarms are internally pulled up to +3,3V. When anexternal switch is closed, the corresponding signal is low (alarm condition).
EXIN1
EXIN2
TO
MICROPROCESSOR
(TTLLEVEL)
SYSTEM
GND
(Each resistor: 10K)
+3,3V
OmniBASTM
-8WOutput alarmsconnection
circuit
The alarms transmission circuit receives alarms in TTL form from themicroprocessor and routes them as external alarms in dry-contact form.When a low signal enters an optocoupler, current passes through the loadof the corresponding EXTOUT (alarm condition).
OPTOCOUPLERS
EXOUT1
EXOUT2
FROM
MICROP
ROCESSOR
(TTLLE
VEL)
SYSTEMLOADS
V*
VOLTAGE
SOURCE
GND FL
ALARM
SIGNALS
IL
* The maximum ratings for the Voltage Source are either:DC: V=100VDC / IL=80mADC(polarity is insignificant)
The loads can be indicator lamps, relays coils, buzzers, etc.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
91/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
87
Appendix-C: Receptacles Pin Out
OmniBAS-2W
ElectricalGbE
(For AllOmniBAS
TM-2W
IDU Types)
Location Front Panelof Control Card
Scope For Ethernet traffic (100 / 1000Mbit/s) provisioning and connectionto the IP / MPLS network
Type RJ-45 Female
Pin out
Pin Signal Description
1 Transmit and Receive Data A+ Input / Output
2 Transmit and Receive Data A- Input / Output
3 Transmit and Receive Data B+ Input / Output
4 Transmit and Receive Data C+ Input / Output
5 Transmit and Receive Data C- Input / Output
6 Transmit and Receive Data B- Input / Output
7 Transmit and Receive Data D+ Input / Output
8 Transmit and Receive Data D- Input / Output
OpticalGbE
(For AllOmniBAS
TM-2W
IDU Types)
Location Front Panelof Control Card
Scope For Ethernet traffic (100 / 1000Mbit/s) provisioning and connectionto the IP / MPLS network
Type SFP cage
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
92/120
Appendix-D: Receptacles Pin Out
88
OmniBAS-2W, Continued
ETH 10/100 1-4
(ForOmniBASTM-2WIDU 8E1 ÐERNETOnly)
Location Front Panel of Control Card
Scope For Ethernet traffic (10 / 100 Mbit/s) provisioning andconnection to the IP / MPLS network
Type RJ-45 Female
Pin out
Pin Signal Description
1 TX+ Output+
2 TX- Output-
3 RX+ Input+
4 N/A N/A
5 N/A N/A
6 RX- Input-
7 N/A N/A
8 N/A N/A
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
93/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
89
OmniBAS-2W, Continued
NMS 10/1001 and 2
(For AllOmniBAS
TM-2W
IDU Types)
Location Front Panel of Control Card
NMS 10/100 1: For connection tothe NMS / GUI or forinterconnection (servingmanagement transfer) with anotherOmniBAS-2W
Scope
NMS 10/100 2: For connection tothe NMS / GUI or forinterconnection (servingmanagement transfer) with anotherOmniBAS-2W
Type RJ-45 FemalePin out
Pin Signal Description
1 TX+ Output+
2 TX- Output-
3 RX+ Input+
4 N/A N/A
5 N/A N/A
6 RX- Input-
7 N/A N/A
8 N/A N/A
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
94/120
Appendix-D: Receptacles Pin Out
90
OmniBAS-2W, Continued
AUX
(For AllOmniBASTM-2WIDU Types)
Location Front Panel of Control Card
Scope For Serial Console (RS-232Interface) and Internal / ExternalAlarms (Dry Contacts) connection
Type D-Sub HD 15 Pin Female
Pin out
Pin Signal DescriptionWire
Colour
1 ALM_OUT2_NC Alarm Output 2 Normally Closed Black
2 RS232_TX(1)
Transmit Data from OmniBAS -
3 RS232_RX(1)
Receive Data from PC -
4 ALM_OUT1_CM Alarm Output 1 Common Brown
5 RS232_GND(1)
RS232 Ground -
6 ALM_OUT2_NO Alarm Output 2 Normally Open Red
7 TTL_ALM_IN3_N(2)
Alarm Input 3 Negative Orange
8 TTL_ALM_IN4_N Alarm Input 4 Negative Yellow
9 ALM_OUT1_NC Alarm Output 1 Normally Closed Green
10 ALM_OUT1_NO Alarm Output 1 Normally Open Blue
11 ALM_OUT2_CM Alarm Output 2 Common Purple
12 TTL_ALM_IN3_P Alarm Input 3 Positive Gray
13 TTL_ALM_IN4_P Alarm Input 4 Positive White
14 TTL_ALM_IN1(3)
Alarm Input 1 Pink
15 TTL_ALM_IN2 Alarm Input 2 Light Green
Continued on next page
(1)These signals concern a Serial Console connection and are terminated onto the DB9 connector of the
cable.
(2)Negative return terminal of alarm input pair.(3)
Single inputs with respect to ground.
5/19/2018 OmniBAS IDU Installation Ed4.0 En
95/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
91
OmniBAS-2W, Continued
SYNC
(For AllOmniBASTM-2WIDU Types)
Location Front Panel of Control Card
Scope Clock Synchronization Interface(G.703 Clause 13)
Type 1.0 / 2.3 (Micro Siemens)
Pin out
Pin Signal Description
1 Sync In / Out Synchronization Input / Output(configurable)
EOW
(ForOmniBAS
TM-2W
IDU 8E1 ÐERNETOnly)
Location Front Panel of Control Card
Scope For headset connection and full-duplex communication with theremote station (Engineering OrderWire)
Type 6 Pin Modular Jack
Pin out
Pin Signal Description
1 GND Ground
2 GND Ground
3 SPKR Speaker
4 MIC Microphone
NOTE Not applicable for OmniBASTM-2W IDU 16E1.
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
96/120
Appendix-D: Receptacles Pin Out
92
OmniBAS-2W, Continued
ModemConnector
Location Front Panel of Modem Card
Scope For connection to the Outdoor Unit
The receptacle carries the followingsignals using frequency-divisionmultiplexing:
-48 V dc power to the OutdoorUnit
Bidirectional Service Channel(S.C.) data, enablingcommunication between Indoorand Outdoor Units. The Service
Channel carries an Rx signalcentred at 10,7 MHz and a Txsignal centred at 6 MHz, On/OffKeying modulated.
The 140 MHz Rx IF signal
The 350 MHz Tx IF signal
Type SMA Female
Pin out
Pin Signal Description
Centre -48 V DC / S.C. / RX IF / TX IF Input / Output
Shield Shield / Chassis GND N/A
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
97/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
93
OmniBAS-2W, Continued
E1 1-8
(ForOmniBASTM-2WIDU 8E1)
Location Front Panel of Control Card
Scope For provisioning of up to 8xE1 Tributaries (120 balanced)
TypeRJ-45 Female
Pin out
8 1 8 1 8 1 8 1 8 1 8 1 8 1 8 1
Pin Signal Description
1 RX- Input-2 RX+ Input+
3 N/A N/A
4 TX- Output-
5 TX+ Output+
6 N/A N/A
7 N/A N/A
8 N/A N/A
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
98/120
Appendix-D: Receptacles Pin Out
94
OmniBAS-2W, Continued
E1/T11-16
(ForOmniBAS
TM-2W
IDU 16 E1)
Location Front Panel of Interface Card
Scope For provisioning of up to 16xE1 Tributaries (120 balanced)
TypeMini D Ribbon (MDR) 68-pin Female
Pin out
E1 tributaries E1 1-16 Recept. E1 tributaries E1 1-16 Recept.
Tx1+ 68 Tx9+ 50Tx1- 67 Tx9- 49
Rx1+ 34 Rx9+ 16Rx1- 33 Rx9- 15
Tx2+ 66 Tx10+ 48
Tx2- 65 Tx10- 47Rx2+ 32 Rx10+ 14
Rx2- 31 Rx10- 13
Tx3+ 64 Tx11+ 46
Tx3- 63 Tx11- 45
Rx3+ 30 Rx11+ 12Rx3- 29 Rx11- 11
Tx4+ 62 Tx12+ 44
Tx4- 61 Tx12- 43
Rx4+ 28 Rx12+ 10
Rx4- 27 Rx12- 9Tx5+ 60 Tx13+ 42
Tx5- 59 Tx13- 41
Rx5+ 26 Rx13+ 8
Rx5- 25 Rx13- 7
Tx6+ 58 Tx14+ 40Tx6- 57 Tx14- 39
Rx6+ 24 Rx14+ 6
Rx6- 23 Rx14- 5
Tx7+ 56 Tx15+ 38
Tx7- 55 Tx15- 37Rx7+ 22 Rx15+ 4
Rx7- 21 Rx15- 3
Tx8+ 54 Tx16+ 36
Tx8- 53 Tx16- 35Rx8+ 20 Rx16+ 2Rx8- 19 Rx16- 1
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
99/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
95
Power Location Front Panel of Control Card
Scope For connection of 48 V dc power
supply voltageType Two poles Male power connector
Pin out
Pin Signal
(+) Power Supply Return (GND)
(-) -48 V dc, nominal(40 V dc to 60 V dc)
Power
(ForOmniBAS
TM-2W
IDU 16E1)
Location Front Panel of Control Card
Scope For connection of 48 V dc powersupply voltage
Type Two poles Male power connector
Pin out
Pin Signal
(+) Power Supply Return (GND)
(-) -48 V dc, nominal(40 V dc to 60 V dc)
5/19/2018 OmniBAS IDU Installation Ed4.0 En
100/120
Appendix-D: Receptacles Pin Out
96
OmniBAS-4W
ElectricalETH 100/10001 and 2
Location Front Panel of Control Card
Electrical ModelScope For Ethernet traffic provisioning and
connection to the IP / MPLSnetwork
Type RJ-45 Female
Pin out
Pin Signal Description
1 Transmit and Receive Data A+ Input / Output
2 Transmit and Receive Data A- Input / Output
3 Transmit and Receive Data B+ Input / Output
4 Transmit and Receive Data C+ Input / Output
5 Transmit and Receive Data C- Input / Output
6 Transmit and Receive Data B- Input / Output
7 Transmit and Receive Data D+ Input / Output
8 Transmit and Receive Data D- Input / Output
OpticalETH 100/10001 and 2
Location Front Panel of Control Card OpticalModel
Scope For Ethernet traffic provisioning andconnection to the IP / MPLSnetwork
Type SFP cage
Continued on next page
5/19/2018 OmniBAS IDU Installation Ed4.0 En
101/120
OmniBAS -2W -4W -8W
Installation and Cabling Manual - Edition 4.0
97
OmniBAS-4W, Continued
ETH 10/1001 and 2
Location Front Panel of Control Card
ETH 10/100 1: For connection tothe NMS / GUI or forinterconnection (servingmanagement transfer) with anotherOmniBAS-4W
Scope
ETH 10/100 2: For connection tothe NMS / GUI or forinterconnection (servingmanagement transfer) with anotherOmniBAS-4W
Type RJ-45 FemalePin out
Pin Signal
Recommended