NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Inspection Type Last EditedTime InInspectionId
P.S./I.S. 189 (@STEENWICK AVE)-X, 3441 STEENWICK AVENUE, BRONX, NY, 10475School:
4493 2020-03-20 08:07AM 2020-08-22 08:15PMARCHITECTURAL - SENIOR
4564 2020-03-20 08:21AM 2020-03-26 05:43PMARCHITECTURAL - ASSOCIATE
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? No
Locker Rooms (no key)Comments on Inaccessible Inspection
Principal(s) Information
Principal Name Edwardo Calderon
Principal Organization I.S. 462 - Bronx (Cornerstone Academy for Social Action Middle
School)
Meeting with Principal? No
Principal Feedback No Feedback from Principal
Principal Name James Bellon
Principal Organization P.S. / I.S. 189 - Bronx
Meeting with Principal? No
Principal Feedback No Feedback from Principal
Principal Name Shante Chunn
Principal Organization X723 SPED - Bronx
Meeting with Principal? No
Principal Feedback No Feedback from Principal
Custodian Peter Mascia
Fireman Anthony Vega
Building Square Footage 108,000
Comments on the Area (Square Feet) None
Comments on the Stories (Floors) plus Basements 4 (No Basement)
Comments on the Year Built 2007
Comments on the Student Population 709
Comments on the Staff Population 192
Comments on the Number of Classrooms 49
Weather Fair
Facade Photo
Corner of Steenwick Avenue and Reeds Mill Lane - West View
Page 1 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural InspectionMain Entrance Photo
Facade A - Steenwick Avenue
Roof Photo
Roof 1 from Bulkhead - North View
No System UpgradedHave any Systems/Major Building Components been upgraded?
Have there been any New Building Additions? No New Construction
Tandem No Tandem
Leased Space? No
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
Broken Glass Cracked Windows are
Potential Safety Hazard
Windows Facade G at
Corridor near
Room 241
shown, also
Corridor
Windows near
Rooms 201,
302/Stair 3A
and 310
Peter
Mascia
Yes Custodian
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Page 2 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Accessibility
Accessibility Status Question Response
Is the Primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are All floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,
Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Complies Required DeficiencyAudio
Induction
System
Fire
Alarm
Strobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
YesExterior Entrances & Exits
NoNoExterior H/C Lifts
YesYesExterior Ramps and Railings
Interior Routes
NoNoCorridor and Lobby H/C Lifts
YesYesInterior Corridor Doors And
Hardware
YesInterior Corridors & Lobbies
YesYesInterior Elevators
YesInterior Lobby Doors And Hardware
NoInterior Ramps
Rooms & Spaces
Art Rooms
Yes YesRoom 315
Auditorium
Yes Yes1st Floor Yes Yes
Cafeteria
Yes Yes1st Floor Yes Yes
Classrooms
Yes Yes1st to 4th Floors
Computer Rooms
Yes YesRoom 410
Gymnasium
Yes Yes1st Floor Yes Yes
Library
Yes YesRoom 324
Main Office
Yes YesRoom 108 (SPED 723 @
X189)
Yes YesRoom 122 (P.S. 189)
Yes YesRoom 422 (I.S. 462)
Multi-purpose Room
Yes YesRoom 438 Yes Yes
Nurse's Office
Yes YesRoom 127 (P.S. 189 and
I.S. 462)
Yes YesRoom 225 (SPED 723 @
189X)
Page 3 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Physical Breakdown Structure Exists Complies Required DeficiencyAudio
Induction
System
Fire
Alarm
Strobe
NoPool
Science Lab
Yes YesRooms 313, 413, 427
Toilet Rooms (boys)
Yes Yes1st to 4th Floors
Toilet Rooms (girls)
Yes Yes1st to 4th Floors
Toilet Rooms (staff)
Yes Yes1st to 4th Floors
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
Does not existAREAWAY
InspectedAWNINGS AND CANOPIES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCHIMNEY
InspectedCOPING
Condition 3- Fair
METAL:OPEN TRANSVERSE JOINTS WITH DAMAGED
CAULKING
Deficiency
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom L.F.
Page 4 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
EXTERIOR
COPING
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 2 at Facade A
Violations No violations recorded
CAST STONE:OPEN TRANSVERSE JOINTS WITH
DAMAGED CAULKING
Deficiency
Deficiency Location/Instance
75Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 3 at Corner of Facade A and B
Violations No violations recorded
Does not existCORNICE
InspectedDOORS
InspectedDOOR HARDWARE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 3- Fair
METAL:DETERIORATED DOOR AND FRAME - MINOR
DETERIORATION
Deficiency
Deficiency Location/Instance
4Deficiency Quantity
Page 5 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade H at Stair D (Total doors: 29)
Violations No violations recorded
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTRANSOM/SIDE LIGHT
Condition 2- Between Good and Fair
METAL:DENTED, MINOR RUSTINGDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade E at Exit 10
Violations No violations recorded
InspectedEXTERIOR SOFFITS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedEXTERIOR WALLS
Masonry, SteelMaterial Type(s)
33,000Replacement Quantity
Replacement Uom S.F.
Instance on All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 33,000
Page 6 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Instance Quantity Uom S.F.
METAL PANEL:DETERIORATED CONTROL/EXPANSION
JOINTS WITH DAMAGED CAULKING
Deficiency
Roof Plan Reference
Elevation
Elevation Reference Facade B
60Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade B
Violations No violations recorded
Does not existLOADING DOCK
InspectedLOUVER
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedPARAPETS
Masonry, ConcreteMaterial Type(s)
9,000Replacement Quantity
Replacement Uom C.F.
Instance on All Facades Inspected
3- FairInstance Condition
Instance Quantity 9,000
Instance Quantity Uom CF
BRICK:OPEN JOINTSDeficiency
Deficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Page 7 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
EXTERIOR
PARAPETS
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade L
Violations No violations recorded
CONCRETE:MINOR CRACKS, SPALLINGDeficiency
Deficiency Location/Instance
125Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 3 at Facade A
Violations No violations recorded
BRICK:EFFLORESCENCEDeficiency
Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 1Urgency of Action
LEVEL 2Purpose of Action
Page 8 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
EXTERIOR
PARAPETS
Deficiency Photo 1
Facade D
Violations No violations recorded
Does not existPLAZA DECK
InspectedROOF
InspectedROOFING
Replacement Quantity 39,000
Replacement Uom S.F.
InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOF BARRIER
3- FairCondition
RAILINGS/PANELS:DETERIORATED, MINOR RUSTINGDeficiency
Deficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 2 at Facade A
Violations No violations recorded
Does not existROOF CAGE
Does not existROOF FENCE
InspectedROOF HATCH/SMOKE HATCH
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOFING
Instance on IRMA:All Roofs Inspected
3- FairInstance Condition
Instance Quantity 38,500
Instance Quantity Uom S.F.
Page 9 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2007
Source of Installation Year Documented
IRMA:FLASHING:BASE FLASHING DETERIORATEDDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1 at Facade D
Violations No violations recorded
IRMA:ROOFING:LOSS OF GRAVELDeficiency
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 3
Violations No violations recorded
IRMA:FLASHING:CAP FLASHING DAMAGEDDeficiency
Page 10 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
Deficiency Location/Instance
125Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 3 at Facade L
Deficiency Photo 2
Roof 1 at Facade D
Violations No violations recorded
Instance on Modified Bitumen:Part of Roof 1(near BH) Inspected
5- PoorInstance Condition
Instance Quantity 500
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2007
Source of Installation Year Documented
MODIFIED BITUMEN:ROOFING:DELAMINATIONDeficiency
Deficiency Location/Instance
250Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITH MAJOR EQUIPMENT REMOVAL
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Page 11 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
Deficiency Photo 1
Roof 1 near Bulkhead
Violations No violations recorded
InspectedROOFING DRAINS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSPECIALTIES
InspectedBULKHEAD/PENTHOUSE
2- Between Good and FairCondition
BULKHEAD/PENTHOUSE WALLS/INTERIOR:CMU
CRACKS/SPALLING
Deficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Bulkhead
Violations No violations recorded
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
Does not existDUNNAGE STEEL
Does not existROOF/GRAVITY TANK
Does not existSKYLIGHT/ROOF VENT
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedBUILDING CHEEK/FLANK WALLS
Condition 3- Fair
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency
Page 12 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade H at HC Ramp
Violations No violations recorded
InspectedRAILINGS
Condition 3- Fair
RUST - MINORDeficiency
Deficiency Location/Instance
12Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade H at HC Ramp
Violations No violations recorded
InspectedSTAIRS/RAMPS
Condition 3- Fair
CONCRETE:CRACKS/SPALLING - MINORDeficiency
Page 13 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade B at Exit 1
Deficiency Photo 2
Facade H at HC Ramp
Violations No violations recorded
InspectedWINDOWS
7,500Replacement Quantity
Replacement Uom S.F.
InspectedEXTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Other:All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 7,500
Instance Quantity Uom S.F.
Installation Year 2007
Source of Installation Year Documented
ALUMINUM - OTHER:BROKEN PANEDeficiency
Page 14 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
Roof Plan Reference
Elevation
Elevation Reference Facade C, G and M
50Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 5Urgency of Action
LEVEL 6Purpose of Action
Deficiency Photo 1
Facade G at Corridor near Room 241 shown, also Corridor
Windows near Rooms 201, 302/Stair 3A, 310 and in Room 410
Deficiency Photo 2
Facade M at Room 410
Violations No violations recorded
INTERIOR Inspected
AUDITORIUM
Instance on 1st Floor (330 seats) Inspected
Ceiling
Instance on 1st Floor (330 seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor (330 seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed H/C Lift
Instance on 1st Floor (330 seats) Does not exist
Page 15 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Fixed Seating
Instance on 1st Floor (330 seats) Inspected
2- Between Good and FairInstance Condition
DAMAGED/BROKEN/INOPERABLEDeficiency
Seat F/101, 102, G/112, K/15Deficiency Location/Instance
4Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Seat G/112
Violations No violations recorded
DAMAGED/BROKEN/INOPERABLEDeficiency
Seat G/114, H/101, J/113Deficiency Location/Instance
3Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 6Purpose of Action
Deficiency Photo 1
Seat G/114
Violations No violations recorded
Floor Finish
Instance on 1st Floor (330 seats) Inspected
2- Between Good and FairInstance Condition
SHEET VINYL:DETERIORATED SUBSTRATEDeficiency
Near seat C/114Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 16 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Floor Finish
Deficiency Photo 1
Near seat C/114
Violations No violations recorded
Sliding-folding Partition
Instance on 1st Floor (330 seats) Does not exist
Stage
Instance on 1st Floor (330 seats) Inspected
Stage
Instance on 1st Floor (330 seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtain Rigging
Instance on 1st Floor (330 seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtains
Instance on 1st Floor (330 seats) Inspected
3- FairInstance Condition
WORN/DETERIORATEDDeficiency
Stage Right, Stage LeftDeficiency Location/Instance
200Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stage Right
Deficiency Photo 2
Stage Left
Violations No violations recorded
Walls
Page 17 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Walls
Instance on 1st Floor (330 seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor (330 seats) Does not exist
CAFETERIA
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on 1st Floor Does not exist
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
VINYL TILES:DETERIORATED SUBSTRATEDeficiency
Near Exit 9, Near the windowsDeficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Exit 9
Violations No violations recorded
Sliding-folding Partition
Instance on 1st Floor Does not exist
Stage
Instance on 1st Floor Does not exist
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency
Page 18 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Main Entrance VestibuleDeficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Main Entrance Vestibule
Violations No violations recorded
ACOUSTIC TILES:DAMAGED/MISSINGDeficiency
Room 405, 406, 410, 427Deficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 410
Deficiency Photo 2
Corridor near Room 406
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
VINYL TILES:DETERIORATED SUBSTRATEDeficiency
Corridor near Room 117Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
Page 19 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
LEVEL 3Purpose of Action
Deficiency Photo 1
Corridor near Room 117
Violations No violations recorded
Does not existSpecialties
InspectedWalls
Condition 2- Between Good and Fair
GYPSUM BOARD:DETERIORATEDDeficiency
Corridor near Room 402, 404Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room 404
Violations No violations recorded
GYMNASIUM
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Does not exist
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor Inspected
3- FairInstance Condition
WOOD:DAMAGED/DETERIORATEDDeficiency
North side, South SideDeficiency Location/Instance
300Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
Page 20 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
INTERIOR
GYMNASIUM
Floor Finish
LEVEL 2Purpose of Action
Deficiency Photo 1
North side
Violations No violations recorded
Seating
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage
Instance on 1st Floor Does not exist
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
MASONRY:CRACKS/SPALLINGDeficiency
South SideDeficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
South Side
Violations No violations recorded
WALL PADDING:DETERIORATEDDeficiency
North sideDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 21 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
INTERIOR
GYMNASIUM
Walls
Deficiency Photo 1
North side
Violations No violations recorded
Window Curtains/Shades/Blinds
Instance on 1st Floor Does not exist
InspectedINTERIOR DOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
KITCHEN
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LIBRARY
Instance on Room 324 Inspected
Built-in Furnishing
Instance on Room 324 Does not exist
Ceiling
Instance on Room 324 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Room 324 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Room 324 Inspected
2- Between Good and FairInstance Condition
Page 22 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
INTERIOR
LIBRARY
Floor Finish
No deficiencies recordedDeficiency
Walls
Instance on Room 324 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LOCKER ROOM
Instance on 4th Floor - Boys Inaccessible
Instance on 4th Floor - Girls Inaccessible
MULTI-PURPOSE ROOM
Instance on Room 438 Inspected
Ceiling
Instance on Room 438 Inspected
2- Between Good and FairInstance Condition
ACOUSTIC TILES:DAMAGED/MISSINGDeficiency
Center of RoomDeficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Center of Room
Deficiency Photo 2
Center of Room
Violations No violations recorded
Door(s)
Instance on Room 438 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on Room 438 Does not exist
Floor Finish
Instance on Room 438 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on Room 438 Does not exist
Stage
Page 23 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Stage
Instance on Room 438 Does not exist
Walls
Instance on Room 438 Inspected
2- Between Good and FairInstance Condition
WALL PADDING:DETERIORATEDDeficiency
Center of RoomDeficiency Location/Instance
80Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Center of Room
Violations No violations recorded
GYPSUM BOARD:DETERIORATEDDeficiency
Rear of RoomDeficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Rear of Room
Violations No violations recorded
Window Curtains/Shades/Blinds
Instance on Room 438 Does not exist
Does not existPOOLS
Does not existSCIENCE DEMO ROOM
SCIENCE LAB
Instance on Rooms 313, 413, 427 Inspected
NoAlternative Use
Fixed Equipment
Instance on Rooms 313, 413, 427 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
SCIENCE PREP ROOM
Instance on Rooms 311, 415 Inspected
NoAlternative Use
Page 24 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
INTERIOR
SCIENCE PREP ROOM
Fixed Equipment
Instance on Rooms 311, 415 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existSHOWER ROOM
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? Yes
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existPartition
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs and Landings
Condition 2- Between Good and Fair
CONCRETE:CRACKS/SPALLING - MAJORDeficiency
Stair A/4Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair A/4
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
MASONRY:CRACKS/SPALLINGDeficiency
Stair A/3, 4Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Page 25 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Stair A/4
Violations No violations recorded
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFLOOR STRUCTURE
Condition 2- Between Good and Fair
CONCRETE SLAB ON GRADE:MINOR CRACKSDeficiency
1st FloorDeficiency Location/Instance
125Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Room 113 shown, also Rooms 105, 112, 116 and 134
Violations No violations recorded
InspectedFOUNDATION WALLS
Material Type(s) Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existVAULTS-BUNKERS
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existStalls
InspectedWalls
Condition 1- Good
No deficiencies recordedDeficiency
InspectedTOILET ROOMS - STUDENTS
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 26 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
SITE Inspected
Does not existCONTAINERIZATION
InspectedDRAINAGE SYSTEM FOR ASPHALT
InspectedCatch Basins/Manhole - Surrounded by Asphalt
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Asphalt Covering
InspectedDRAINAGE SYSTEM FOR CONCRETE
InspectedCatch Basins/Manhole - Surrounded by Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Concrete Covering
InspectedDRAINAGE SYSTEM FOR SOIL
InspectedCatch Basins/Manhole - Surrounded by Soil
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Soil Covering
Does not existDRINKING FOUNTAINS
InspectedFENCES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
3- FairCondition
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Reed Mill LaneDeficiency Location/Instance
75Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 27 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Photo 1
Reed Mill Lane
Violations No violations recorded
HEAVINGDeficiency
Steenwick AvenueDeficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Steenwick Avenue
Violations No violations recorded
Does not existPavers
InspectedSite Sidewalks & Walkways
InspectedAsphalt
2- Between Good and FairCondition
CRACKS - MAJORDeficiency
Exit to Steenwick AvenueDeficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Exit to Steenwick Avenue
Violations No violations recorded
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Page 28 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Does not existPavers
InspectedStudent Non-Use
Gravel Exists? No
Does not existAsphalt
InspectedConcrete
2- Between Good and FairCondition
CRACKS - MAJORDeficiency
Exit to Reed Mill LaneDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Exit to Reed Mill Lane
Violations No violations recorded
Does not existPavers
InspectedStudent Use
Gravel Exists? No
InspectedAsphalt
4- Between Fair and PoorCondition
CRACKS - MAJORDeficiency
SchoolyardDeficiency Location/Instance
600Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Schoolyard
Violations No violations recorded
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existPavers
InspectedPLAYGROUNDS
SchoolyardInstance
Benches
Page 29 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
SITE
PLAYGROUNDS
Benches
Instance on Schoolyard Does not exist
Fence
Instance on Schoolyard Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Pavement
Instance on Schoolyard Does not exist
Play Equipment
Instance on Schoolyard Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Safety Surfacing
Instance on Schoolyard Inspected
2- Between Good and FairInstance Condition
DETERIORATED/MISSINGDeficiency
Near the Play EquipmentDeficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near the Play Equipment
Violations No violations recorded
Unpaved Area
Instance on Schoolyard Does not exist
Does not existPLAYING SURFACE
InspectedRETAINING WALLS
Condition 3- Fair
Are there any Retaining Walls 6' OR higher facing public street/sidewalk? No
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJORDeficiency
Rear of SchoolDeficiency Location/Instance
60Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Page 30 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
SITE
RETAINING WALLS
Rear of School
Violations No violations recorded
InspectedSEATING
InspectedBenches
Does not existConcrete
InspectedMetal/Wood/Plastic
3- FairCondition
DAMAGED/DETERIORATEDDeficiency
SchoolyardDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Schoolyard
Violations No violations recorded
Does not existBleachers
InspectedSITE WALLS (NOT RETAINING WALLS)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedRailings
Condition 3- Fair
MISSINGDeficiency
SchoolyardDeficiency Location/Instance
8Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 6Purpose of Action
Deficiency Photo 1
Schoolyard
Violations No violations recorded
InspectedSite Cheek/flank Walls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs/ramps
Condition 2- Between Good and Fair
Page 31 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
X189Architectural Inspection
Question Response
SITE
STAIRS/RAMPS: EXTERIOR
Stairs/ramps
No deficiencies recordedDeficiency
Page 32 of 32 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)