AL1002ULADAJNAC Power Extender
Installation Guide(See Application Guide for additional information)
Altronix Corp.140 58th St. Brooklyn, NY
- 2 - AL1002ULADAJ
Agency Listings:• ULListedControlUnitsforFireProtective SignalingSystems(UL864).• MEA-NYCDepartmentofBuildingsApproved.• CSFM-CaliforniaStateFireMarshalApproved.• FM-FactoryMutualApproved.• NFPA72Compliant.Input:• Powerinput120VAC60Hz,5amp.• Two(2)ClassA,StyleZortwo(2)ClassB, StyleW,YFACPinputs.• Two(2)NCdrycontacttriggerinputs.Output:• Class2Ratedpower-limitedoutputs.• 24VDC@10ampmaxtotalalarmcurrent.• 2.5ampmaxcurrentperoutput.• Separate1.0ampauxiliaryoutput.• Programmablesupervisedindicatingcircuitoutputs: Four(4)ClassB,StyleW,YorTwo(2)ClassA, StyleZorOne(1)ClassA,StyleZandTwo(2)ClassB, StyleW,Y(see Application Guide).•Thermalandshortcircuitprotectionwithautoreset.Battery Backup:•Built-inchargerforsealedleadacidorgeltypebatteries.•Automaticswitchovertostand-bybatterywhen ACFails.• Zerovoltagedropwhenswitchingoverto batterybackup.
Supervision: •ACfailsupervision(form“C”contact,1amp/28VDC). Factorysetfor1.5hourswithoptional30seconds delaysetting(fieldselectable).• InstantlocalACtroublereportingrelay (form“C”contact,1amp/28VDC).•Batterypresenceandlowbatterysupervision (form“C”contact,1amp/28VDC).Visual Indicators: •InputandoutputstatusLEDindicators.Special Features:• 2-wirehorn/strobeSyncmodeallowsaudible notificationappliances(horns)tobesilenced whilevisualnotificationappliances(strobes) continuetooperate.• SyncprotocolsincludePotter/Amseco,Faraday, Gentex®,SystemSensor®,andCooperWheelock®.• TemporalCode3,SteadyMode,InputtoOutput FollowerMode(maintainssynchronizationof notificationappliancescircuit).• Compatiblewith12VDCor24VDCfirepanels.•Outputloopsupervisionsteeredtoinput1orinput2.• Signalcircuittroublememory(helpsidentify intermittentloopproblems).• Commontroubleinputandoutput.• Groundfaultdetection.•Unitincludespowersupply,redenclosure,camlock, andbatteryleads.Enclosure Dimensions (approx. H x W x D):18”x14.5”x4.5”(457.2mmx368.3mmx114.3mm).
Overview:TheAltronixAL1002ULADAJisanextremelycosteffective10ampremotepowersupply/batterycharger.Itmaybecon-nectedtoany12or24voltFireAlarmControlPanel(FACP).PrimaryapplicationsincludeNotificationApplianceCircuit(NACsuchasstrobesandhorns)expansionsupporttomeetADArequirements.Italsoprovidesauxiliarypowertosupportsystemaccessories.Theunitdeliverselectronicallyregulatedandfiltered24voltpowertoClassB,StyleW,YorClassA,StyleZNACloopcircuits.Additionally,aseparate1.0Aauxiliaryoutputforfour(4)-wiresmokedetectorsisavailable.The10ampmax.alarmcurrentcanbedividedbetweenthefour(4)outputsforpoweringNACdevices.Eachoutputisratedat2.5ampmax.,andcanbeindependentlyprogrammedforSteady,TemporalCode3orStrobeSynchronization.AlloutputsmaybeprogrammedforInputtoOutputFollowerMode(outputwillfollowinput.i.e.MarchTimeInput,MarchTimeOutput).Innon-alarmconditionindependentloopsupervisionforClassA,StyleZand/orClassB,StyleW,YFACPNACcircuitsisprovided.Intheeventofalooptrouble,theFACPwillbenotifiedviathesteeredinput(input1orinput2).Inaddition,therearecommontroubleoutputterminals(NC,C,NO)whichareusedtoindicategeneralloop/systemtrouble.AcommontroubleinputisprovidedforoptionalNC(normallyclosed)devicestoreporttroubletotheFACP.Two(2)FACPsignalingoutputscanbeemployedanddirectedtocontrolsupervisionandpowerdeliverytoanycombinationofthefour(4)outputs.
Note:TheinformationinthisdocumentisvalidformodelsAL1002ULADAJandAL1002UL2ADAJ.ModelAL1002ULADAJisequivalenttomodelAL1002UL2ADAJ.
Specifications:
AL1002ULADAJ - NAC Power Extender
AL1002ULADAJ - 3 -
Power Supply Specifications:AC Input: 120VAC60Hz,5ampsuppliedbyamaximum15ampdedicatedbranchcircuit.
Output:Four(4)regulatedsupervisedNACoutputcircuits,24VDC,2.5ampmaximumcurrent.One(1)aux.specialapplication24VDCpoweroutputcircuit1amp,non-supervisedtotaloutputcurrentmustnotexceedcurrent10ampinAlarmCondition.
Battery:Usetwo(2)12VDC/12AHortwo(2)12VDC/7AHbatteriesconnectedinseries.
Stand-by/Alarm Current Consumption:
130mA/300mA
EOL Resistor (end of line): 2.2K(2200ohm),AltronixModel#AL-EOL22(included).Ground fault maximumtest impedance:
1000ohm.
Stand-by Specifications:
Stand-by Batteries Stand-by Time Total Amp/Minutes Alarm Output Current Aux. Output24VDC/7AH 24Hours 10amp/5minutes ---
24VDC/12AH(usetwo(2)12VDCbatteriesinseries)
24Hours 10amp/5minutes 50mA
24VDC/36AH 24Hours 10amp/5minutes 1ampNote: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 10 amp total alarm current (example: AUX = 1 amp, outputs up to 9 amp).
Installation Instructions:WiringmethodsshallbeinaccordancewiththeNationalElectricalCode/NFPA70/NFPA72/ANSI,andwithalllocalcodesandauthoritieshavingjurisdiction.Productisintendedforindooruseonly. Carefully review: Application Guide for AL802ULADAJ, AL1002ULADAJ Power Supply Specifications (pg. 3) Stand-by Specifications (pg. 3) Output Programming Selection Table (pg. 4) Sync Mode Selection Table (pg. 4) Terminal Identification Table (pgs. 5-6) LED Status Indication Table (pg. 6)1.Mountunitinthedesiredlocation.Markandpredrillholesinthewalltolineupwiththetoptwokeyholesinthe enclosure.Installtwoupperfastenersandscrewsinthewallwiththescrewheadsprotruding.Placetheenclosure’s upperkeyholesoverthetwoupperscrews;levelandsecure.Markthepositionofthelowertwoholes.Removethe enclosure.Drillthelowerholesandinstalltwofasteners.Placetheenclosure’supperkeyholesoverthetwoupper screws.Installthetwolowerscrewsandmakesuretotightenallscrews(Enclosure Dimensions, pg. 12). Secureenclosuretoearthground(Fig. 1, pg. 3).2. Connectgreenleadtoearthground (Fig 1).Connecttheline(L)andneutral(N)terminalstoaseparateunswitched ACcircuit(120VAC,60Hz)dedicatedtotheFireAlarmSystem.3. Measureoutputvoltagebeforeconnectingdevices.Thishelpsavoidingpotentialdamage.4. Connectbatterytotheterminalsmarked[+BAT--]onthePowerSupplyBoard(batteryleadsincluded). Note:IfbatteriesbeingusedinyourinstallationdonotfitintotheAL1002ULADAJunit,itisrequiredtoinstalla separateenclosure,ULListedforappropriateapplication.Separatebatteryenclosureisrequiredtohave50cubicinches ofadditionalopenspace.AllwiringmethodsshallbeinaccordancewiththeNationalElectricalCode NFPA70/NFPA72/ANSIandwithalllocalcodesandauthoritieshavingjurisdiction.Batterycircuitsarenotpower- limited;provide0.25”spacingfrompower-limitedcircuitsanduseseparateknockout.Ifadditionalbatteryenclosure isrequired,itmustbeULListedfortheapplicationandmountedwithin5’oftheAL1002ULADAJenclosureinthe sameroom;minimum12AWGwireinappropriateconduitisrequiredforconnection.Whenusingconduit,make sureitisinstalledinamannerwhereitcannotturn.5.Setoutputselectionswitchesmarked[OUT1throughOUT4]tofollowcorrespondinginput[IN1&IN2]and desiredoutputsignaltype (Output Programming Selection Table, pg. 4).
L G Nline
ground
neutral
Fig. 1
- 4 - AL1002ULADAJ
6.ConnectFACPoutputtothedesiredAL800LGKlogicboardinputs,andnotificationappliancestothedesired AL800LGKlogicboardoutputs(see Application Guide). Note:The2-wirehorn/strobesyncmodewillonlysynchronizehorns,horn/strobes,strobeswith synchronizationcapability.7.Forconnectionofsmokedetectors,digitaldialerseeOptional Hookup Diagram, pg. 7.
Class A, Style Z Class B, Style W, Y, SW1 & SW2 Settings:• ForallClassB,StyleW,Y,hookupsSW1&SW2ontheAL800LGKlogicboardmustbeopen. ForallClassA,StyleZhookupsSW1&SW2ontheAL800LGKlogicboardmustbeclosed.
Output Programming Selection Table:Outputs must be programmed independently (OUT1 - OUT4)
FunctionSwitch Positions
DescriptionsON OFF
InputtoOutputFollowerMode 1 2,3Outputfollowssignalitreceivesfromthecorrespondinginput(i.e.FACPSyncmodule-maintainssynchronizationofnotificationappliancecircuit).
TemporalCode3Mode 3 1,2EnablesTemporalCode3signalgenerationoutput.Thismodewillacceptasteadyorapulsinginput.
SteadyMode 1,2,3Asteadyoutputsignalwillbegenerated.Thismodewillacceptsteadyorpulsinginput.
For the above modes Dip Switch 4 determines which Input controls the corresponding output:Switch 4 in the ON position causes output(s) to be controlled by input 1.Switch 4 in the OFF position causes output(s) to be controlled by input 2.
Sync Mode Selection Table:
FunctionSwitch Positions
DescriptionsON OFF
AmsecoSyncMode*
1,3,4 2
ThismodeisdesignedtoworkwiththeAmsecoseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
FaradaySyncMode*
2,4 1,3
ThismodeisdesignedtoworkwiththeFaradayseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
Gentex®
SyncMode*GentexisaregisteredtrademarkofGentexCorporation.
1,2,3,4
ThismodeisdesignedtoworkwiththeGentex®seriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
SystemSensor®SyncMode*SystemSensorisaregisteredtrademarkofHoneywell.
1,2,4 3
ThismodeisdesignedtoworkwiththeSystemSensor®seriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
CooperWheelock®
SyncMode*CooperWheelockisaregisteredtrademarkofCooperWheelock.
2,3,4 1
ThismodeisdesignedtoworkwiththeCooperWheelockseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
*Note:TheAL1002ULADAJwillonlysynchronizehorns,horn/strobesandstrobesthatcontainsynchronizationcapabilityContactsignalmanufacturerformoredetailedinfo.Thesamesynchronizationmodemustbeselectedforalloutputs.
(AL800LGK Board)Output Dip Switches
INPUT SELECTTEMPORAL
STROBE SYNCIN>OUT SYNC
AL1002ULADAJ - 5 -
Note: It is required to control visual notification appliances (strobes) via input 1 (IN1) and audible notification appliances (horns) via input 2 (IN2). This allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate.
Amount of Notification Appliances per unit:Amseco 27perNAC* SystemSensor® 32perNAC*Faraday 39perNAC* CooperWheelock® 32perNAC*Gentex® 32perNAC*
*Not to exceed a maximum of 2.5 amp per NAC.
Terminal Identification Table:AL800LGK Logic Board
TerminalLegend Function/Description
IN1+,IN1-IN2+,IN2-(Supervised)
Theseterminalsconnecttothe12VDCor24VDCFACPnotificationappliancecircuitoutputs. (ClassA,StyleZorClassB,StyleW,Y)Inputtriggervoltageis8-33VDC@5mAmin.Terminalpolarityisshowninalarmcondition.Duringanalarmconditiontheseinputswillcausetheselectedoutputschosentodrivenotificationappliances.Thedesignatedoutputsaresetbyoutputswitches[OUT1throughOUT4](Output Programming Selection Table, pg. 4). AtroubleconditiononanoutputloopwillcausethecorrespondinginputtotriptheFACPbyopeningtheFACPloop.Analarmconditionwillalwaysoverridetroubletodrivenotificationappliances.
RET1+,RET1-RET2+,RET2-(Supervised)
For(ClassA,StyleZhookupstheseterminalpairsreturntoFACPNAC1and/orNAC2.ForClassB,StyleW,YhookupstheFACPEOLresistorfromtheNAC1and/orNAC2outputsareterminatedattheseterminals.
C“DRY1”NC C“DRY2”NC (Dryinputtrigger)
Anopenacrosstheseinputs,willcausetheselectedoutputschosentodrivenotificationappliances.Thedesignatedoutputsaresetbyoutputswitches[OUT1throughOUT4](Output Programming Selection Table, pg. 4).Notetheseinputsareunidirectionalandwillnot reportatroubleconditiontotheFACP.
+OUT1--+OUT2--+OUT3--+OUT4--(Supervised)
Notificationappliancesareconnectedtotheseregulatedoutputs (see Application Guide pg. 2-4). Eachpower-limitedoutputwillsupply2.5amp.Totalsupplycurrentis10amp(see note below). Outputsarecontrolledbydesignatedinput1[IN1]orinput2[IN2](Output ProgrammingSelection Table, pg. 4). Maximumlinelossorvoltagedrop(testedwith2.5V).
C“FAULT”NC(Commontroubleinput)
Anopencircuitacrossthispairofterminalswillcause[IN1andIN2]tosimultaneouslysignalatroubleconditionbacktotheFACP(TypicallyusedtoreportACorBATFail).(form“C”contact1amp/28VDC)(Fig. 2, pg. 7).
NC,C,NO(Commontroubleinput)
Thesearedrycontacttroubleoutputsthatfollowanygeneralloop/systemtroubleconditions.(Typicallyusedtotriggeradigitalcommunicatororotherreportingdevice).(form“C”contact1amp/28VDC0.35PowerFactor)(Fig. 2, pg. 7) .
--AUX+Thisseparate1ampmaxauxiliarySpecialApplicationPoweroutputcircuitistypicallyusedto power4-wiresmokedetectors.Seeattachedlistofdevices(Appendix A, pgs. 10-12).
+DC-- 24VDCfrompowersupply.
Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 10 amp total alarm current (example: AUX = 1 amp, outputs up to 9 amp).
- 6 - AL1002ULADAJ
Terminal Identification Table:Power Supply Board*Terminal Legend Function/DescriptionL,N Connect120VACtotheseterminals:Ltohot,Ntoneutral.-DC+ 24VDC@10ampinalarmnonpower-limitedoutput.
ACFAILNO,C,NC
Form“C”drycontactsusedtoinstantaneouslysignalthelossACtolocalannunciationdevices,withACpresentterminalsmarkedNOandCareopen,NCandCareclosed.WhenlossofACoccursterminalsmarkedNOandCareclosed,NCandCareopen.
ACLOCALNC,NO,C
Form“C”drycontactsusedtoinstantaneouslysignalthelossACtolocalannunciationdevices,withACpresentterminalsmarkedNOandCareopen,NCandCareclosed.WhenlossofACoccursterminalsmarkedNOandCareclosed,NCandCareopen.
BATFAILNO,C,NC
Form“C”drycontactsusedtosignallowbatteryvoltageorlossofbatteryvoltage.UndernormalconditionsterminalsmarkedNOandCareopen,NCandCareclosed.DuringatroubleconditionterminalsmarkedNOandCareclosed,andNCandCareopen(Fig. 3, pg. 8).
+BAT- Stand-bybatteryinput(leadsprovided)(Fig. 3, pg. 8).
*Power Board Parameter Specifications:• ACFailconditionwillreportapproximately1.5hoursafterlossofAC.TosetACDelayto30seconds,powertheunit down(ACsupplyandBattery)priortochangingswitchposition.• OpenSwitch“ACDelay”orclose“ACDelay”switch,respectively.• Lowbatteryconditionwillreportatapproximately20VDC.• Batterypresencedetectionwillreportwithin180secondsafterbatteryremainsundetected(missingorremoved). Arestoredbatterywillreportwithin30seconds.
LED Diagnostics:Power Supply BoardRed (DC) Green (AC) Power Supply StatusON ON Normaloperatingcondition.ON OFF LossofAC,Stand-bybatterysupplyingpower.OFF ON NoDCoutput.OFF OFF LossofAC.Dischargedornostand-bybattery.NoDCoutput.
AL800LGK - Logic BoardLED OFF ON BLINK (LONG)* BLINK (SHORT)**ON Normal AlarmCondition TroubleCondition TroubleConditionMemoryON Normal AlarmCondition TroubleCondition TroubleConditionMemoryOFF Normal AlarmCondition TroubleCondition TroubleConditionMemoryOFF Normal AlarmCondition TroubleCondition TroubleConditionMemoryInput1 Normal AlarmCondition TroubleCondition ---Input2 Normal AlarmCondition TroubleCondition ---Fault Normal AlarmCondition --- ---
* Indicatescurrenttroublecondition.Whentrouble(open,shortorground)occursonaspecificoutput,the correspondingredoutputLED,[OUT1-OUT4]willblink.ThecorrespondinggreeninputLEDwill blinkaswell.Looptroublewillreportwithin30seconds.
**Indicatestroubleconditionmemory.Whenatroubleconditionrestores,theunitsredoutputLED,[OUT1-OUT4] willblinkwithashorteranddistinctlyadifferentduration.ThegreeninputLEDswillbeoff(normalcondition). Toresetthememorydepresstheresetbutton(Fig. 2c, pg. 7).TheLED(s)willextinguish.Note:Ifindicatingcircuitshavebeenrestored,memoryresetisnotrequiredfornormaloperationoftheunit.
AL1002ULADAJ - 7 -
NEC Power-Limited Wiring Requirements for AL1002ULADAJ Models:Power-limitedandnonpower-limitedcircuitwiringmustremainseparatedinthecabinet.Allpower-limitedcircuitwiringmustremainatleast0.25”awayfromanynonpower-limitedcircuitwiring.Furthermore,allpower-limitedcircuitwiringandnonpower-limitedcircuitwiringmustenterandexitthecabinetthroughdifferentconduits.Onesuchexampleofthisisshownbelow.Yourspecificapplicationmayrequiredifferentconduitknockoutstobeused.Anycon-duitknockoutsmaybeused.Forpower-limitedapplications,useofconduitisoptional.AllfieldwiringconnectionsmustbemadeemployingsuitablegaugeCMorFPLjacketedwire(orequivalentsubstitute).OptionalbatteryenclosuremustbemountedadjacenttothepowersupplyviaClass1wiringmethods.Note:RefertowirehandlingdrawingbelowfortheproperwaytoinstalltheCMorFPLjacketedwire,(Fig, 2a).
Fig, 2
Fig, 2a
ExternalJacketedShield
Incorrect WireHandling
Correct WireHandling
Pull backexternal jacketedshield approx. 1/2”.
WireInsulation
Solid CopperConductors
120VACInput60Hz
(nonpower-limited)
SupervisoryConnections(power-limited)non-supervised
Aux.Output(power-limited)non-supervised
NACCircuits(power-limited)supervised
SignalingCircuitsfromFACP(nonpower-limited)
supervised
BatteryConnections(nonpower-limited)supervised
- 8 - AL1002ULADAJ
Optional hookups:1- BatteryandACmonitoring:ACorBatteryFailconditionwillcausethecommontroubleinput[C“FAULT”NC]to reportbacktotheFACPviainput1andinput2.Thecommontroubleinputmayalsobeusedforotheroptional supervisorymonitoring. ToreportACandBatteryTroubleconnectthebatteryandACFailrelayoutputshownin(Fig. 3a, pg. 8)tothe commontroubleinput.2- Drycontactinput(C“DRY1”NC)(C“DRY2”NC)canbeusedtoalarmoutputfroman addressablemodule(theseinputsareunidirectionandcannotreportbacktotriggermodule). Connection to triggering devices must be made within 20ft of distance and using conduit for wiring.3- Auxiliaryoutput(-AUX+)24VDCat1ampmax.4- ACLocal[NC,NO,C]shouldconnecttothehostcontrolpanelforlocalannunciationof thetroublecondition. Note: Ifcommontroubleinput,terminalsmarked[C“FAULT”NC]arenotused,theseterminalsmustbe shorted(connectjumper)toremaininactive.Foroptionalhookups(Fig. 3b, pg. 8).
Optional Hookup Diagram:Fig. 3
Maintenance:Unitshouldbetestedatleastonceayearfortheproperoperationasfollows:Output Voltage Test:Undernormalloadconditions,theDCoutputvoltageshouldbecheckedforpropervoltagelevel(26.2-26.4VDC recommended range).Battery Test:Undernormalloadconditionscheckthatthebatteryisfullycharged.Checkspecifiedvoltagebothatbatteryterminalandattheboardterminalsmarked[+BAT--]toensurethatthereisnobreakinthebatteryconnectionwires.Fuses:Checkinputandoutputfusesonthepowersupplyboard,replaceifnecessary.Inputfuseratingis6.3amp@250V,Outputfuseratingis15amp@32VNote:Maximumchargingcurrentis1.5amp.Note:Expectedbatterylifeis5years;however,itisrecommendedchangingbatteriesin4yearsorlessifneeded.
These circuits are used to monitor AC andBat Fail and will cause a simultaneous trouble
condition to the FACP's IN1 and IN2 (Non-Supervised)
4-wire SmokeDetector
+
--
+
--
4-wire SmokeDetector
Fire AlarmControl Panel
(FACP)
EOL PowerSupervision Relay
(Not Supplied)
EOLResistor
from FACP
SW1
-- DC +
SW2
+ OUT1 --
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
NC
C N
O
C "F
AULT
" N
C
OUT1 OUT3
OUT2 OUT4INPUT SELECT
TEMPORALSTROBE SYNC
IN > OUT SYNC
IN1+ IN1-- IN2-- IN2+ C "DRY1" NC RET1+ RET1-- RET2-- RET2+ C "DRY2" NC
+ OUT2 -- + OUT3 -- + OUT4 --
INPUT SELECTTEMPORAL
STROBE SYNCIN > OUT SYNC
-- AUX +
UPPER TERMINALSLOWER TERMINALS
Addressable ControlModule Trigger Output
See Note 2(Non-Supervised)
RESET
Supervised
Non-Supervised Input fromPower Supply
BAT
FAIL
AC F
AIL D
CA
C
AC D
ELAY
NC C NO NC C NOAC
LOC
AL NC C NOL N
6.3A
250
V
Digital Communicatoror Local AnnunciatorDry output Contact(Form "C" contacts)
Power-Limited Outputs2.5 amp per output in alarm
Total = 10 amp(Supervised)
AC
FAIL
NC
C N
OB
AT
FAIL
NC
C N
O
Fig. 3a
-- DC +
OUT1 OUT3
OUT2 OUT4 INPUT SELECT
TEMPORAL STROBE SYNC
IN > OUT SYNC
INPUT SELECT TEMPORAL
STROBE SYNC IN > OUT SYNC
RESET
Fig. 3cTroubleMemoryResetButton
Fig. 3bCommontroubleInput/Output
NC
CN
OC
"FA
ULT
" N
C
AL1002ULADAJ - 9 -
Battery Calculation Worksheet
DeviceNumber of Devices
Current per DeviceStand-by Current
Alarm Current
Foreachdeviceusethisformula: Thiscolumn x Thiscolumn = Equals Currentpernumberofdevices.
AL1002ULADAJ(Currentdrawfrombattery)
1Stand-by: 130mA 130mA
Alarm: 300mA 300mA
A AL1002 Current 130mA 300mA
AuxiliaryDevices Refertodevicemanualforcurrentratings.
Alarm/Stand-by mA mA mA
Alarm/Stand-bymA
mA mA
Alarm/Stand-by mA mA mA
B Auxiliary Devices Current (must not exceed 1 amp)
Refertodevicemanualforcurrentratings.
Alarm: mA 0mA mA
Alarm:mA
0mA mA
Alarm: mA 0mA mAAlarm:
mA 0mA mA
C NotificationAppliancesCurrent must notexceed10amp(10000mA) 0mA mA
D Totalalarmcurrent mA mA
E Totalcurrentratingsconvertedtoamperes(lineDx.001) A A
F Numberofstandbyhours(24forNFPA72,Chapter1,1-5.2.5). H
G MultiplylinesEandF. Totalstand-byAH AH
HAlarmsoundingperiodinhours.(Forexample,5minutes=.0833hours.)
H
I MultiplylinesEandH. TotalalarmAH AH
J AddlinesGandI. Totalstand-byandalarmAH AH
KMultiplylineJby1.30.(30%extrainsurancetomeetdesiredperformance)Totalampere-hoursrequired
AH
Unitsarecapableofrecharging36AHbatterymax.Iftotalampere-hourrequiredexceeds36AH,decreaseAUXcurrenttoprovideenoughstand-bytimefortheapplication.
- 10 - AL1002ULADAJ
Appendix A - UL Listed Compatible Devices
A.1 Four (4) Wire Smoke Detectors
TableA-1belowlistsfour(4)wiresmokedetectorscompatiblewithAL1002ULADAJAUXoutput.
Smoke Detector/Base Detector Type Max StandbyCurrent (mA)
AlarmCurrent (mA)
FenWalCPD-7021(w/70-201000-005Base) Ionization 0.10 *FenWalPSD-7125 Photoelectric 0.10 *FenWalPSD-7125(w/70-201000-005Base) Photoelectric 0.10 *Fire-LiteBLP-12-4W Base * *Gentex824 Photoelectric 0.50 *Gentex824T Photoelectric 0.50 *Gentex824CP Photoelectric 0.50 *Gentex824CPT Photoelectric 0.50 *HochikiHSC-4R Base * *HochikiSPB-24 ProjectedBeam 0.25 *SystemSensorB112LP Base 0.12 36SystemSensorB114LP Base * *SystemSensorB404B Base * *SystemSensorDH100ACDC Photoelectric 0.15 0.70SystemSensorDH100ACDCLP Photoelectric 0.15 0.70SystemSensorDH100ACDCLPW Photoelectric 0.15 0.70SystemSensorDH400ACDCI IonizationDuct 25 95SystemSensorDH400ACDCP PhotoelectricDuct 25 95SystemSensor1112/24/D Ionization 0.05 50SystemSensor1424 Ionization 0.10 41SystemSensor1451(w/B402BBase) Ionization 0.10 39SystemSensor2112/24ATR Photoelectric 0.50 60/70SystemSensor2112/24AITR Photoelectric 0.50 60/70SystemSensor2112/24/D Photoelectric 0.05 50SystemSensor2112/24R Photoelectric 0.50 60/70SystemSensor2112/24TR Photoelectric 0.50 60/70SystemSensor2112/24T/D Photoelectricw/135oThermal 0.05 50
SystemSensor2112/24TSRB Photoelectricw/135o
ThermalSupervisoryRelay 15 45
SystemSensor2312/24TB Photoelectric 0.12 50SystemSensor2412(12volt) Photoelectric 0.12 77SystemSensor2412AT(12volt) Photoelectric 0.12 58SystemSensor2412TH(12volt) Photoelectric 0.12 77SystemSensor2424 Photoelectric 0.10 41SystemSensor2424TH Photoelectric 0.10 41SystemSensor2451 Photoelectric 0.10 39SystemSensor2451TH(with/B402BBase) Photoelectric 0.10 39SystemSensor2W-MOD LoopTest/MaintenanceMod. 30 50SystemSensor4W-B(12/24volt) PhotoelectricI3 0.05 23SystemSensor4WT-B(12/24volt) PhotoelectricI3w/Therm 0.05 23SystemSensor4WTA-B(12/24volt) I3Photow/Therm/Sounder 0.05 35SystemSensor4WTR-B(12/24volt) I3Photow/Therm/Relay 0.05 35
AL1002ULADAJ - 11 -
A.1 Four (4) Wire Smoke Detectors (cont.)
Smoke Detector/Base Detector TypeMax Stand-byCurrent (mA)
AlarmCurrent (mA)
SystemSensor4WTR-B(12/24volt)I3Photow/Therm/Sounder/Relay
0.05 50
SystemSensor4WITAR-B(12/24volt) I3Photow/IsolatedTherm/Sounder/Relay 0.05 50SystemSensor2W-MOD2 I3LoopTest/MaintenanceMod. 0.05 *SystemSensorRRS-MOD I3ReversingRelay/SyncModule 0.05 *SystemSensor6424 ProjectedBeam 10 28.4SystemSensorBeam1224(S) ProjectedBeam 17 38.5
*Contactmanufacturerforcurrentdraws
A.2 Door Holders
TableA-2belowlistsdoorholderscompatiblewithAL1002ULADAJAUXoutput.
Manufacturer Model Type Current (mA)Edwards DH150A FloorMount 96Edwards DH154A FloorMount 96Edwards DH158A SurfaceMount 96RixonFiremark FM-980 FloorMount,single 68RixonFiremark FM-996 SurfaceWiring 68RixonFiremark FM-998 ConcealedWiring 68
A.3 Relays
TableA-3belowlistsrelayscompatiblewithAL1002ULADAJAUXoutput.
Manufacturer Model Current (mA) Manufacturer Model Current (mA)
AirProducts&Controls,LTD
MR-101/CMR-201/CPAM-1PAM-2PAM-SDA77-716B
153515151520
SystemSensor
PR-1PR-2PR-3EOLR-1R-10TR-14TR-20TR-24TR-10ER-14ER-20ER-24E
153030302323404023234040
- 12 - AL1002ULADAJ
Altronixisnotresponsibleforanytypographicalerrors.
14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056website:www.altronix.com,e-mail:info@altronix.com,LifetimeWarranty,MadeinU.S.A.IIAL1002ULADAJ I06M MEMBER
1.5”(38.1mm)
1.0”(25.4mm)
4.5”(114.3mm)
1.0”(25.4mm)
1.0”(25.4mm)
1.25”(31.75mm)
1.25”(31.75mm)
1.0”(25.4mm)
1.5”(38.1mm)
1.5”(38.1mm)
1.5”(38.1mm)
1.5”(38.1mm)
8.5”(215.9mm)
18.0”(457.2mm)
18.0”(457.2mm)
18.0”(457.2mm)
6.0”(152.4mm)
2.5”(63.5mm)
2.75”(69.85mm)
2.75”(69.85mm)
4.5”(114.3mm)
4.5”(114.3mm)
14.5”(368.3mm)
14.5”(368.3mm)
1.0”(25.4mm)
1.0”(25.4mm)
14.5”(368.3mm)
2.5”(63.5mm)
1.5”(38.1mm)
2.5”(63.5mm)
Enclosure Dimensions (H x W x D approximate):18”x14.5”x4.5”(457.2mmx368.3mmx114.3mm)
Recommended