INSTALLATION MANUALMST-S3W
DB98-29359A(3)E
System Air Conditioner
MST-S3W_IM_E_29359-3.indd 25 2008-08-18 ソタネト 3:34:57
2
CAUTION
Please read this installation manual thoroughly before installing the product. (Please refer to appropriate installation manual for any optional product installation.)
SAFETY INFORMATION
Contact service center or dealer for installation. Potential risk of fire or damage to
the product.
Install the product on a hard and even place that can support its weight. If the place cannot support its
weight, the product may fall down and it may cause injury.
Consult the place of purchase or a contact center to disassemble or repair the product. Potential risk of unit malfunction,
water leakage, electric shock, or fire.
Install the product correctly according to the installation manual. Incorrect installation may cause
a water leakage, electric shock or fire and so on.
Install the product with proper power supply. Potential risk or electric shock or
product damage.
Do not disassemble or reinstall the product on your own discretion. Potential risk of electric shock or
fire.
Risk of death or serious personal injury.
Potential risk of personal injury or material damage.
WARNING CAUTION
The electric work must be done by service agent or similarly qualified persons according to national wiring regulations and use only rated cable. If the capacity of the power cable
is insufficient or electric work is not properly completed, electric shock or fire may occur.
Please recycle or dispose of the packaging material for this product in an environmentally responsible manner.
MST-S3W_IM_E_29359-2.indd 2 2008-07-17 ソタネト 10:08:44
3
WARNING
Do not install the product where there’s combustible gas. Potential risk of fire and explosion.
Do not install the product in areas exposed to oil or vapor. Potential risk of product damage
or malfunction.
Ensure no water gets into the air conditioner. Potential risk of fire or electric
shock.
Do not put undue stress on the power cable or place heavy objects on it. Damaged power cable may
cause fire.
Install the air conditioner away from direct exposure to sunlight, in room temperature range of 0°C~39°C. Potential risk of electric shock or
malfunction.
Do not install the product in areas with frequent use of acid or alkali spray. Potential risk of electric shock or
product malfunction.
Do not handle the product with sharp objects. Potential risk of electric shock or
product damage.
Do not connect power cable to a communication terminal. Potential risk of fire or explosion.
Be cautious not to interfere any other electrical devices if the product is installed in a place such as hospital. Potential risk of product malfunction.
SAFETY INFORMATION (Continued)
MST-S3W_IM_E_29359-2.indd 3 2008-07-17 ソタネト 10:08:45
4
BEFORE INSTALLATION
Check List
(1) S-NET mini IP • You need a public IP if you want to use the S-NET mini with connection to the
DMS. • If you have a private IP, you may use the private IP. • S-NET mini supports DHCP. DHCP(Dynamic Host Configuration Protocol) is a protocol used by network devices
(clients) to obtain various parameters necessary for the clients to operate in an Internet Protocol (IP) network.
(2) Network equipment Hub, network cable and other network equipment are not included in a package.
These equipment should be purchased separately.
(3) Installation cable • Wire work must be done prior to product installation, make sure LAN cable,
Centralized controller and transmitter communication line(C1, C2) to reach the product without any shortage.
MST-S3W_IM_E_29359-2.indd 4 2008-07-17 ソタネト 10:08:45
5
�������
• S-NET mini should be installed by qualified service technician.
• Before installing S-NET mini, make sure power is off.
• Use power cable supplied by manufacturer for S-NET mini.
• Make sure you have installed cables according to the electrical standards. Install the cables through the wall to keep them out of user’s reach. (Use VCTF 2Cx0.75 mm2 cable.)
ITEM S-NET mini
QUANTITY 1
IMAGE
AccessoriesMake sure you have each item. Supplied items may vary, depending on your country or service provider.
Cable-tie Cable clamp M4X16 tapped screw Power code
2 3 5 1
Adapter User’s manual Installation manual
1 1 1
BEFORE INSTALLATION (Continued)
MST-S3W_IM_E_29359-2.indd 5 2008-07-21 ソタネト 5:14:03
6
VIEWING THE PARTS
Main Parts
Front view
USB (Device) port
SD card slot
USB (Host) port
Reset button
RS232 Communication terminal
LAN port
Digital input terminal
485 Communication terminal
Power terminal
LAN indicator (Green)
Data indicator (Green)
Error indicator (Red)
Speaker
Menu button
Soft keyboard button
Lock button
Power & LCD backlight button
Power indicator (Red)Rear view
Bottom view
MST-S3W_IM_E_29359-2.indd 6 2008-07-17 ソタネト 10:08:46
7
Dimension
������
������
����� �����
(Unit : mm)
VIEWING THE PARTS (Continued)
MST-S3W_IM_E_29359-2.indd 7 2008-07-17 ソタネト 10:08:46
8
INSTALLING S-NET mini
System Organization
• Connecting S-NET mini with DMS. (Type ) You can control up to 4 DMS and 256 indoor units by using S-NET mini.
• Connecting S-NET mini with Centralized controller. (Type ) You can control up to 16 Centralized controllers and 256 indoor units by using S-NET mini.
• Connecting S-NET mini with Transmitter. (Type ) You can control up to 16 Transmitters and 256 indoor units by using S-NET mini.
a
b
c
Centralized controller
DMS
Max. 32 units (DVM +)
S-NET mini
Transmitter Transmitter Transmitter
a
b
c
������� Only one of the type among ⓐⓑⓒ can be connected as S-NET mini.
• When connecting as type ⓐ, S-NET 3 cannot be connected with DMS.• When connecting as type ⓑ, DMS cannot be connected with Centralized
controller. • When connecting as type ⓒ, Centralized controller cannot be connected to
Transmitter.
MST-S3W_IM_E_29359-2.indd 8 2008-07-17 ソタネト 10:08:47
9
• Press the Power & LCD backlight button to turn on the S-NET mini. • Check if the power indicator turns red.
If the power indicator has not turned on, check the power terminal and make sure power cable is correctly connected.
Checking the power cable
• Check if the LAN indicator and the Data indicator turns green. • Check if the Error indicator turns red.
If the Error indicator has turned red, check the power and communication cable connection.
Checking the indicators
Connected with DMS• Make sure LAN cable is correctly connected to the LAN port. • Make sure power terminal is correctly connected.
Connected to Centralized controller/Transmitter• Make sure communication cable is correctly connected to 485 communication
terminal. Check the polarity of the 485 communication cable. When the polarity changes, communication will be unavailable.
• Make sure power terminal is correctly connected.
Checking the connection
Compatible models
Type Maximum number of connections Remarks
Centralized controller 256 Indoor units Maximum 16 Centralized controller connection
Transmitter 256 Indoor units Maximum 16 Transmitter connection
DMS 256 Indoor units Maximum 4 DMS connection
Maximum number of connections
Type Model Remarks
Centralized controller MCM-A202/MCM-A202A -
Transmitter
MIM-B04A -
MIM-B13(For DVM PLUS II) -
MIM-B13A(For DVM PLUS III) -
DMS MIM-D00 -
INSTALLING S-NET mini (Continued)
MST-S3W_IM_E_29359-2.indd 9 2008-07-17 ソタネト 10:08:47
10
Installing the Hardware
(1) Secure the installation plate on the wall with 4 screws.
(2) Hold the S-NET mini and attach the S-NET mini to the installation plate by fasten the hooks on the bottom of the installation plate.
• Make sure to tighten the S-NET mini to prevent from damage by dropping the product.
������� • It is recommended to install S-NET mini on the wall for safe use and to prevent possible malfunction, damage of the product.
Hooks
INSTALLING S-NET mini (Continued)
MST-S3W_IM_E_29359-2.indd 10 2008-07-17 ソタネト 10:08:48
11
Connecting DMS
(2) Connect the LAN cable to the LAN port on the bottom of the S-NET mini.
• Incorrect connection may cause communication error.
(1) Connect the supported adapter(DC 12V/3A) to the power terminal on the bottom of S-NET mini.
(3) Hold the S-NET mini and attach the S-NET mini to the installation plate by fasten the hooks on the bottom of the installation plate.
• Make sure to tighten the S-NET mini to prevent from damage by dropping the product.
������� • S-NET mini supports up to 4 DMS connections.
• Separate the power cable from communication cables when connecting Centralized controller to S-NET mini. (Communication error may occur due to electromagnetic interference.)
Hooks
Power cable
Power cableLAN cable
INSTALLING S-NET mini (Continued)
MST-S3W_IM_E_29359-2.indd 11 2008-08-07 ソタネト 4:14:11
12
Connecting Centralized Control
(2) Connect the communication cable (C1, C2) for Centralized controller to 485 communication terminal on the bottom of the S-NET mini.
• Incorrect connection may cause communication error.
• Use the appropriate tools for wiring, and make sure to connect them tightly within the tightening torque to withstand the external pressure.
(1) Connect the supported adapter(DC 12V/3A) to the power terminal on the bottom of S-NET mini.
(3) Hold the S-NET mini and attach the S-NET mini to the installation plate by fasten the hooks on the bottom of the installation plate.
• Make sure to tighten the S-NET mini to prevent from damage by dropping the product.
������� • S-NET mini supports up to 16 Centralized controller connections.
• Separate the power cable from communication cables when connecting Centralized controller to S-NET mini. (Communication error may occur due to electromagnetic interference.)
Hooks
Power cable
Communication cable
INSTALLING S-NET mini (Continued)
Tightening torque (kgf•cm)
M4 12.0~14.7
Power cable
MST-S3W_IM_E_29359-2.indd 12 2008-08-07 ソタネト 4:14:11
13
Connecting Transmitter
(2) Connect the communication cable (R1,R2) for Centralized controller to 485 communication terminal on the bottom of the S-NET mini.
• Incorrect connection may cause communication error.
• Use the appropriate tools for wiring, and make sure to connect them tightly within the tightening torque to withstand the external pressure.
(1) Connect the supported adapter(DC 12V/3A) to the power terminal on the bottom of S-NET mini.
(3) Hold the S-NET mini and attach the S-NET mini to the installation plate by fasten the hooks on the bottom of the installation plate.
• Make sure to tighten the S-NET mini to prevent from damage by dropping the product.
������� • S-NET mini supports up to 16 Transmitter connections.
• Separate the power cable from communication cables when connecting Transmitter to S-NET mini. (Communication error may occur due to electromagnetic interference.)
Hooks
Power cable
Communication cable
INSTALLING S-NET mini (Continued)
Tightening torque (kgf•cm)
M4 12.0~14.7
Power cable
MST-S3W_IM_E_29359-2.indd 13 2008-08-07 ソタネト 4:14:12
14
Level Selection for External Contact Signal on DI Port(Optional)
• Use only for external contact signal control for DI port. • Factory default setting
PatternDIP Switch
Control Details1 2
Pattern 1 ON ON No response to the external contact signal control.(Factory default setting)
Pattern 2 ON OFF
Used for emergency cases such fire. Responds when there is an input signal on DI-1 Operation:
Turns off all the indoor units when there is an ON signal input, and disables the use of all the remote controllers. During an emergency stop, the controller will ignore any request from the user. Also the schedules will not operate as well. The controller enables to accept request normally when the input signal changes to OFF. (The DI-2 is not used for pattern 2.)
Pattern 3 OFF ON
Responds when there is an input signal on DI-1 and DI-2. Operation:
Changes the on/off status of all the indoor units depending on the ON/OFF status of the DI-1 input. Enables/disables the remote controllers depending on the ON/OFF status of the DI-2 input. (ON: enable/ OFF: disable) The schedules will run regardless of pattern 3.
Pattern 4 OFF OFF
Responds when there is a pulse input on DI-1,2. Operation:
Turns on all the indoor units when there is a pulse input on DI-1. Turns off all the indoor units when there is a pulse input on DI-2. Turns off all the indoor units when there is a pulse input on DI-1, DI-2. (The pulse width is valid only for 0.5~1.0 sec.) The schedules will run regardless of pattern 4.
DIP Switch (SW1)
DIP Switch pattern
INSTALLING S-NET mini (Continued)
������ ������
���� ����
DI port
MST-S3W_IM_E_29359-3.indd 14 2008-08-28 ソタネト 3:25:08
15
DI(Digital Input) circuit structure depending on DIP switch pattern
• Pattern 2 (Usable to connect fire sensor contact signal)
• Pattern 3 (Interlocked control by external contact signal)
• Pattern 4 (Interlocked control by pulse signal)
���
����
����
Emergency stop/ Resume operation
No function
���
����
����
Start/Stop Indoor units
Enable/Disable Remote controllers
���
����
����
Resume operation
Stop operation
SW1
SW1
SW1
INSTALLING S-NET mini (Continued)
• Pattern 1 (No Function)
MST-S3W_IM_E_29359-2.indd 15 2008-07-17 ソタネト 10:08:49
16
GETTING STARTED
Starting S-NET mini
(1) When the main display appears, select [Centralized controller & Transmitter] or [DMS].
• They should be connected to S-NET mini before starting the system.
(2) Tap [Apply]. • Selected communication device will be applied and the S-NET mini will re-start.
1
2
MST-S3W_IM_E_29359-2.indd 16 2008-07-17 ソタネト 10:08:50
17
(3) Touchscreen calibration window appears after rebooting S-NET mini.
(4) Use stylus to tap center of the cross. Tap from 1 to 5 in order as shown in the above figure.
������� • Do not use sharp objects to touch the LCD screen. LCD screen can be damaged.
• Using finger or other dull object to press the cross will result incorrect screen calibration.
• Stylus pen is not included in a package.
GETTING STARTED (Continued)
1
2 5
3 5
MST-S3W_IM_E_29359-2.indd 17 2008-07-17 ソタネト 10:08:50
18
(5) Tap anywhere in the screen after calibration. • Changed setting will be applied, and S-NET mini will restart. • If you want to stay with the previous setting, wait 30 seconds without touching the
LCD and the buttons.
GETTING STARTED (Continued)
MST-S3W_IM_E_29359-2.indd 18 2008-07-17 ソタネト 10:08:50
19
Connecting Centralized Controller and the Transmitter
(1) Make sure communication cables(C1, C2) of Centralized controller and Transmitter are connected.
• Communication cable(C1, C2) have to be connected for S-NET mini to communicate with Centralized controller and the Transmitter.
• Be aware of the fact that the communication cable for Centralized controller and the Transmitter have polarity.
(2) Execute tracking. • S-NET mini communicates with Centralized controller and the Transmitter to bring all
the information on indoor units and outdoor units. • Indoor unit control and other menu can be used after tracking. • Refer to S-NET mini user’s manual for instructions on tracking.
Connecting DMS
(1) Make sure LAN cable is connected to the LAN port on the bottom side of the S-NET mini.
• LAN cable must be connected in order to establish communication connection between S-NET mini and DMS.
(2) Set IP for S-NET mini. • IP for S-NET mini should be set up in order to communicate with DMS. • Refer to S-NET mini user’s manual for instructions on setting up the IP.
(3) Set IP for DMS. • IP for DMS should be set up in order to communicate with S-NET mini. • Refer to S-NET mini user’s manual for instructions on setting up the IP.
(4) Execute tracking. • S-NET mini communicates with DMS to bring all the information on indoor units and
outdoor units. • Indoor unit control and other menu can be used after tracking. • Refer to S-NET mini user’s manual for instructions on tracking.
(5) Synchronize the time on S-NET mini and DMS. • S-NET mini and DMS should have synchronized time to operate accurate indoor unit
schedule. • Refer to S-NET mini user’s manual to set up date/time on S-NET mini.
GETTING STARTED (Continued)
MST-S3W_IM_E_29359-2.indd 19 2008-07-17 ソタネト 10:08:50
20
In Case of Tracking Failure
(1) Check the model number for Centralized controller and the Transmitter.
(2) Check the communication status of Centralized controller and the Transmitter.
• Main Address : When communication with outdoor unit is normal, main address will be displayed.
• RMC Address : Below indication will be displayed. When communication with outdoor unit become normal, Indoor unit address will be displayed.
(3) Check the polarity between S-NET mini and the Centralized controller.
• If polarity of C1, C2 changes, communication will be suspended. • Make sure none of the cables are disconnected.
Type Normal communication Communication error
Centralized controller No display. Power indicator and indoor unit indicators
will blink periodically.
Transmitter displays right side of the 7-Segment. No display. displays on right side of the
7-Segment.
Transmitter 7-Segment display
Display Message
Stand by position for communication with centralized controller.
Normal communication.
None Communication is suspended with Centralized controller. (Connection check required.)
Main Address RMC Address
S-NET mini TRACKING
������� • Display may vary depending on the Transmitter. Contact service center for the detail.
MST-S3W_IM_E_29359-2.indd 20 2008-07-17 ソタネト 10:08:51
21
1. Public IP : Ordinary IP used to connect internet is called public IP.
1-1. Static IP : Static IP is a number that is assigned to a computer by an Internet service provider (ISP) to be its permanent address on the Internet.
1-2. Dynamic IP : Dynamic IP is a number, which changes every time when computer or model has restarted.
2. Private IP : This is a local IP which can not be used for internet connection. If you share internet connection through router, internet sharing software or, through OS, you may check the Client IP and they will be similar to below number system. 10.X.X.X, 172.X.X.X, 192.168.X.X
2-1. Static IP : Designated IP assigned by user. 2-2. Dynamic IP : User sets up to obtain their IP automatically.
OTHERS
IP Terminology
• S-NET mini needs IP address to contact other computers.
1. Public IP 1-1. Static IP
1-2. Dynamic IP
2. Private IP 2-1. Static IP
2-2. Dynamic IP
MST-S3W_IM_E_29359-2.indd 21 2008-07-17 ソタネト 10:08:51
22
Examples of S-NET mini Installation with DSL
• Direct connection between S-NET mini and DMS
• Direct connection between S-NET mini and DMS through HUB
DMS S-NET miniCross cable
Private IP : 192.168.0.2 Private IP : 192.168.0.1
S-NET miniDMS
Private IP : 192.168.0.2 Private IP : 192.168.0.1
HUB
Local management without external control : Use private IP
Others (Continued)
MST-S3W_IM_E_29359-2.indd 22 2008-07-17 ソタネト 10:08:51
23
��������
S-NET miniDMS
HUB
Static IP(Public)
External control is required : Use static IP(Public)
Others (Continued)
������� • All IP related matter should be consulted to a network specialist. (Especially firewall related matters.)
MST-S3W_IM_E_29359-2.indd 23 2008-07-17 ソタネト 10:08:52