STEP AND TOUCH VOLTAGE TESTER
GROUND RESISTANCE
TESTER
MPC-20 (20 A) code 7 70 123
MPC-50 (50 A) code 7 70 075
INSTRUCTION MANUAL
( M98113601-20 / 03A )
(c) CIRCUTOR S.A.
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
2/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 2
1.- MPC-20 - MPC-50 .................................................................... 41.1 Usual operating procedure 41.2 Precautions whilst operating 5
2.- DESCRIPTION OF THE MAIN COMPONENTS ...................................... 62.1 Source of regulated voltage 62.2 Control and protection circuit 62.3 Voltage and current tester 62.4 Touch electrodes 62.5 Accessories 6
3.- CONTROL AND CONNECTION FEATURES OF THE MPC-20 / MPC-50 .... 73.1 Control Components 73.2 External connection components 7
3.3 Internal connection components 8
4.- MAIN FEATURES ............................................................................. 104.1.- Power supply 104.2.- Dimensions, weight:5.1.1 Attaching the equipment 144.3.1 Features as a step and touch voltage tester. MPC-20 TESTER 114.3.2 Features as a step and touch voltage tester. MPC-50 TESTER 124.4.- Features as an ground resistance tester 13
5.- TESTING STEP OR CONTACT VOLTAGE............................................ 14
5.1 Installation and start-up 145.2 Attaching the MPC-20 / MPC-50 145.3 Auxiliary ground for current injection 145.4 Connecting the current circuit 165.5 Connecting the power supply 165.6 Setting the maximum default current 175.7 Attaching the testing electrodes 185.8 Button for testing erratic currents 185.9 Adjusting the current and testing the
STEP or TOUCH VOLTAGE 195.10 Test results 20
6.- TESTING GROUND RESISTANCE ..................................................... 216.1 Attaching and connecting the MPC-20 / MPC-50 226.2 Attaching the "MEASURING ROD" 226.3 Testing erratic voltages 226.4 Testing ground resistance 226.5 Test results 236.6 Repeating tests 24
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
3/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 3
CHAPTER II
7.- EXISTING STANDARDS ................................................................... 257.1 Abstract and table of voltages 257.2 Standards relating to the MPC-20 / MPC-50 26
8.- CORRECTION OF THE READ OUTS .......................................................... 279.- MAINTENANCE............................................................................... 2910.- TECHNICAL SERVICE ..................................................................... 29
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
4/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 4
MPC-20 & MPC-50
1.- PRELIMINARY WARNINGS:
1.1.- USUAL OPERATING PROCEDURE
The MPC-20 and MPC-50testers are compact and robust and aredesigned to test where large powers are needed for a short period of time:
- MPC-20: up to 12 kVA
- MPC-50: up to 20 kVA
Its microprocessor controlled testing system ensures that tests are madein approximately 10 seconds.
Its portability means that weight has been kept to a minimum with theuse of minimal loss toroidal transformers.
Heat generated by the transformer windings is continuously eliminatedby an in-built ventilation system. It is able to operate indefinitely, making 12 sec.tests at 40 sec. intervals. If for any reason it overheats, a red indicator light willshow why and will prevent it from operating until normal temperature is re-established.
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
5/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 5
1.2.- WARNINGS!
THE CURRENT USED FOR MEASUREMENTS, 20 A with the MPC-20 and 50 A in the MPC-50, IS SUFFICIENT TO CREATE SIGNIFICANT
VOLTAGES AROUND THE ELECTRODES, ESPECIALLY THE AUXILIARYELECTRODES.
PLEASE TAKE ALL NECESSARY PRECAUTIONS TO AVOIDACCIDENTS.
For example: A 5 Ohms auxiliary electrode creates a voltage of 250 V arounditself.
VOLTAGE MAY REACH 600 V AROUND THE CABLE OUTPUT with theMPC-20 and 400 V with the MPC-50.
THE POWER CIRCUIT CONNECTIONS MUST NEVER BE
HANDLED WITHOUT HAVING FIRST STOPPED THE EQUIPMENT ANDREMOVED THE OPERATING KEY.
BEFORE ANY MEASUREMENTS ARE TAKEN, SIGNS MUST
PREVENT PEOPLE FROM PASSING THROUGH OR REMAINING IN THEINJECTED CURRENT AREA. IN THE EVENT OF HIGH GROUNDRESISTANCES, VOLTAGES UP TO 600 V MAY BE CREATED, WHICH ARE
FATAL TO ANIMALS OR PERSONS NEAR TO THE DISPERSERS DURINGTESTS.
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
6/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 6
2.- DESCRIPTION OF THE MAIN COMPONENTS
2.1.- VOLTAGE SOURCE
MPC-20:voltage source, with 10 regulating scales using a switch and
fine adjustment using a dial. Supplies a regulable voltage between 0 and 600 Vand is set for a current of 20 A. It can test to 20 A in installations with a 30Ohms resistance (ground and auxiliary added).
MPC-50:voltage source, with 8 regulating scales using a switch and fineadjustment using a dial. Supplies a regulable voltage between 0 and 400 V andis set for a current of 50 A. It can test to 50 A in installations with a 8 Ohmsresistance (ground and auxiliary added).
The remaining components are the same in each:
2.2.- CONTROL AND PROTECTION CIRCUITButton for testing erratic currents. Two directional selector key to control thecurrent injection (0 and 180): Line voltage indicator. Over heating indicator.Fuse protection for the operating circuit Protective circuit breakers for all theequipment and for the output circuit.
2.3.- VOLTAGE AND CURRENT TESTER, controlled by micro-processor. Ittest and also calculates Vp, Vc and Rt. The alphanumeric liquid crystal displayshows preset data, measurements and calculations.
2.4.- TOUCH ELECTRODES, that are cylindrical, 200 square cm at the baseand weigh 250 N, with carrying handles and terminals for connecting the testingcables.
2.5.- ACCESSORIES. 50 metre cables, 10 mm in diameter with terminals forcurrent injection. 50 metre cables for voltage reading. Bridging cable to join thetwo touch electrodes.
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
7/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 7
3.- CONTROL AND CONNECTION COMPONENTS OF THE MPC-20 & MPC-503.1.- CONTROL ELEMENTS
1 VOLTAGE OUTPUT SWITCHMPC-20: FROM 1 TO 10
MPC-50: FROM 1 TO 8
SwitchPosition
MPC-20 MPC-50
1 0 to 60 V 0 to 50 V
2 0 to 120 V 50 to 100 V
3 20 to 180 V 100 to 150 V
4 180 to 240 V 150 to 200 V
5 240 to 300 V 200 to 250 V
6 300 to 360 V 250 to 300 V
7 360 to 420 V 300 to 350 V8 420 to 480 V 350 to 400 V
9 480 to 540 V
10 540 to 600 V
2 FINE REGULATION CONTROL (according to previous table)3 RED TEMPERATURE INDICATOR4 RED SYSTEM VOLTAGE INDICATING LIGHT5 ANALOGUE AMMETER FOR ADJUSTMENT AND ASSISTANCE6 GENERAL AND OUTPUT CIRCUIT BREAKER7 SELECTOR WITH KEY OPERATE THE TEST
8 LIQUID QUARTZ DISPLAY9 3 BUTTONS TO PRESET Imax VALUE10 BUTTON TO SELECT OPERATING MODE (Vp/c or Rt)11 BUTTON FOR ERRATIC VOLTAGE MEASUREMENTS
999999999999
ENTERENTERENTERENTER MODEMODEMODEMODE
3.2.- EXTERNAL CONNECTION COMPONENTS
12 OUTPUT TERMINALS: MAX 50 A, MAX 600 V13 VOLTAGE INPUT TERMINALS TO THE VOLTMETER
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
8/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 8
3.3.- INTERNAL CONNECTION COMPONENTS
MPC-20:
30 AND 31 SINGLE PHASE POWER SUPPLY: 230 VT.T TERMINAL WITH OBLIGATORY EARTHING CONNECTION
MPC-50:
30 AND 32 SINGLE PHASE POWER SUPPLY: 400 V30 AND 31 SINGLE PHASE POWER SUPPLY: 230 V (EXCEPTIONAL)T.T TERMINAL WITH OBLIGATORY EARTHING CONNECTION
SIZE:
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
9/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 9
Control panel:
999-> 999 ENTER ESC
RT-VPC0 OFF 180
(LLAVE)
ERRATICAS
ENTRADA TENSION
Vm
PILOTO RED
PILOTO TERMICO
CONMUTADOR DESALIDAS 1 AL 8
1
2
0
50
AMPERIMETRO
INT. GENERAL
DISPLAY
VOLTAGE INPUT
CIRCUIT BREAKER LIGHT
SYSTEM LIGHT
GENERAL SWITCH
AMMETER
OUTPUT 1 TO 8SWITCH
ERRATICS
(KEY)
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
10/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 10
4.- MAIN FEATURES
4.1.- POWER SUPPLY
POWER SUPPLY MPC-20 MPC-50
VOLTAGE
FREQUENCY
MAXIMUM CURRENT
CIRCUIT BREAKERPOWER SUPPLY CABLEMAXIMUM POWER
230 10 %SINGLE PHASE
50 / 60 Hz
54 A
100 A2 X 10 + 6 T.T.12 kVA
400 10 %SINGLE PHASE230 V exception50 / 60 Hz
57 A to 400 V(95 A to 230 V)
100 A2 x 16 + 16 T.T.20 kVA
4.2.- SIZES AND WEIGHT
SIZES:HEIGHT 800 mmWIDTH 550 mm
LENGTH 500 mm
WEIGHT: 142 Kg WITHOUT ELECTRODES
ELECTRODE SIZES:
HEIGHT 210 mm APPROX.
DIAMETER 160 mm APPROX.
WEIGHT: 25.5 Kg EACH
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
11/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 11
4.3.- TESTING STEP AND CONTACT VOLTAGE4.3.1.- MPC-20 TESTER
CURRENT 0 20 A REGULABLE
OVERVOLTAGE 1, 1 In, 1 Min
VOLTAGE 0 600 V,10 SCALES AND FINE ADJUSTMENT
MAX. RESISTANCE 30 OHMS (GROUND TESTED + AUXILIARYGROUND)
RESISTANCE OFHIGHER VALUES
ALLOWS TESTING AT LOWER CURRENTS
METHOD USED INJECTION AND TESTING OF CURRENT(Ip)
TESTING VOLTAGE IN SURFACE AREA(Vm)
DEFAULT SETTING Imax CALCULATES: Vp/c=Vm xMax/Ip
ANALOGUE AMMETER CLASS: 1.5 RANGE: 20 A
DIGITAL AMMETER CONTROLLED BY MICROPROCESSORACCURACY: 0.5 % MEASUREMENTS 2
digits MAX. : 99.9 A RESOLUTION : 10 mA
MINIMUM READING : 20 mADIGITAL VOLTMETER CONTROLLED BY MICROPROCESSOR
SCALES : 30 V and 600 V SCALE CHANGE : AUTOMATICACCURACY: 0.5 % MEASUREMENTS 2
digits MINIMUM READING : 20 mV IMPEDANCE CUR. : 1000 ohms or 600
kohms (switch) RESOLUTION : 10 mV
MAX. PROGRAMMABLE
CURRENT VALUE
9999 A
SELECTION OPERATINGMODE (Vp/c or Rt)
BY BUTTON (MODE) + Rt/Vp-c Selector
DEFAULT CURRENTPRESELECTION
BY BUTTONS
TESTING ERRATICVOLTAGES
VOLTMETER CONTROL BY BUTTON
CONTROL OF STOP ANDSTART
BY SELECTOR WITH KEY:ON 0--- OFF --- ON 180
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
12/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 12
4.3.2.- TESTING STEP AND CONTACT VOLTAGE: MPC-50 TESTER
CURRENT 0 50 A REGULABLE
OVERVOLTAGE 1, 1 In, 1 Min
VOLTAGE 0 400 V,8 SCALES AND FINE ADJUSTMENT
MAX. RESISTANCE 8 OHMS (GROUND TESTED + AUXILIARYGROUND)
RESISTANCE OFHIGHER VALUES
ALLOWS TESTING AT LOWER CURRENTS
METHOD USED INJECTION AND TESTING OF CURRENT(Ip)
TESTING VOLTAGE IN SURFACE AREA(Vm)
DEFAULT SETTING Imax CALCULATES: Vp/c=Vm x Max/Ip
ANALOGUE AMMETER CLASS : 1.5 RANGE : 50 A OVERRANGE : 300 A
DIGITAL AMMETER CONTROLLED BY MICROPROCESSORACCURACY: 0.5 % MEASUREMENTS 2
digits MAX. : 99.9 A RESOLUTION : 10 mAMINIMUM READING: 20 mA
DIGITAL VOLTMETER CONTROLLED BY MICROPROCESSOR SCALES : 30 V and 500 V SCALE CHANGE : AUTOMATICACCURACY: 0.5 % MEASUREMENTS 2
digits MINIMUM READING: 20 mV IMPEDANCE CUR. : 1000 ohms or 600
kohms (switch) RESOLUTION : 10 mV
MAX PROGRAMMABLECURRENT VALUE
9999 A
SELECTION WORKMODE (Vp/c or Rt)
BY BUTTON (MODE) + Rt/Vp-c Selector
DEFAULT CURRENTPRESELECTION
BY BUTTONS
TESTING ERRATICVOLTAGES
VOLTMETER CONTROL BY BUTTON
CONTROL OF STOP ANDSTART
BY SELECTOR WITH KEYON 0-- OFF --- ON 180
4.4.- TESTING GROUND RESISTANCES(USING CURRENTS UP TO 20 A or 50 A)
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
13/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 13
METHOD USED INJECTION AND TESTING OF CURRENT
MPC-20 : 0 20 A
MPC-50 : 0 50 A
TESTING VOLTAGE BETWEEN GROUND AND NEUTRAL AREA(Vm)CALCULATES: Rt.=Vm/Ip
ELECTRODES NEEDED GROUND TO MEASURE DISTANT AUX ELECTRODE "ROD" ELECTRODE FOR TAKING
VOLTAGE
MAXIMUM ERROR 3 % OF MEASUREMENTS 2 digits
DIGITAL AMMETER CONTROLLED BY MICROPROCESSORACCURACY: 0.5 % MEASUREMENTS 2
digits MAX. : 99.9 ARESOLUTION : 10 mA MINIMUM READING: 20 mA
DIGITAL VOLTMETER CONTROLLED BY MICROPROCESSOR RANGES : 30 V and 500 V RANGE CHANGE : AUTOMATIC
ACCURACY: 0.5 % MEASUREMENTS 2 digits MINIMUM READING: 20 mV IMPEDANCE CUR. : 600 kohms RESOLUTION : 10 mV
SELECTION WORKMODE (Vp/c or Rt)
BY BUTTON (MODE) + Rt/Vp-c Selector
TESTING ERRATICVOLTAGES
VOLTMETER CONTROL BY BUTTON
CONTROL OF STOPAND START
BY SELECTOR WITH KEYON 0-- OFF --- ON 180
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
14/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 14
5.- TESTING STEP OR CONTACT VOLTAGE
5.3.- INSTALLATION AND START-UP
This manual contains information and warnings that must be followed by theuser to ensure the safe operation of the equipment and to maintain it in a safecondition.
Usual operation must not be started until the final assembly of the cablesand weights, as recommended in section 1.2.- Connection instructionsof thismanual.
If the equipment is used in a way not specified by the manufacturer, theprotection of the equipment and the people operating it may be
compromised.
When it is likely that there has been a loss of safety (e.g. when damage isvisible), the equipment must be disconnected from the power supply. In theevent please contact a qualified service representative.
5.4.- ATTACHING THE MPC-20/ MPC-5
To test correctly, the MPC-20 or the MPC-50 must be placed 20 or more
metres from the ground to be tested. Do not place it in the area occupied by theelectrodes in the ground.
5.5.- AUXILIARY GROUND FOR CURRENT INJECTION
There must be auxiliary ground for current injecting 50 or more metres awayfrom the ground to be tested Resistance between the auxiliary ground added tothe ground to be measured must not exceed 8 ohms for the MPC-50 and 30Ohms for the MPC-20.
-----------------------------------------------------------------
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
15/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 15
DIAGRAM FOR TESTING STEP VOLTAGE
-----------------------------------------------------------------------------------------------------------
DIAGRAM FOR TESTING CONTACT VOLTAGE
GROUND
TO BETESTED
1 metre
Testedvoltage
L (minimum 20metres)
Test intensity lp
AUXILIARYGROUND
L (minimum 20 metres)
GROUND
TO BE
TESTED
Metal parts
Tested
voltage
L (minimum 20
metres)
Test intensity lp
AUXILIARYGROUND
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
16/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 16
5.6.- CONNECTING THE CURRENT CIRCUIT
ENSURE THAT THE SELECTOR (ON-OFF-ON) ON THE
MPC-20 & MPC-50 IS DISCONNECTED AND WITHOUT THE KEY.
Connect the "OUTPUT CABLES": to the ground to be measured and theother to the auxiliary ground.
5.7.- CONNECTING THE POWER SUPPLY
5.7.1.- POWER SUPPLY FOR THE MPC-20:
Connect the supply cable to a 230 V II+TT system or an independentgenerator with the same VOLTAGE.
5.7.2.- POWER SUPPLY FOR THE MPC-50:
Connect the supply cable to a 400 V II+TT system or an independentgenerator with the same VOLTAGE (As an exception the MPC-50 may beconnected to 230 V).
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
17/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 17
5.8.- SETTING THE MAXIMUM DEFAULT CURRENT
Once the connections described above have been made and after takingSAFETY MEASURES, testing can be done in the following way:
Place the regulator on the "0%" position.
Place the Voltage switch on position "1".
CONNECT THE MPC SWITCH. The model type and the version of thesetting will appear on the display.
Place the "OPERATING MODE" selector on "V p/c".(Connect the 1000 Ohms resistance switch located on the back of the
equipment: voltmeter internal impedance of 1000 ).
PRESS the upper right "MODE" button (operating mode) and the display isready to start testing voltage ("V") or resistance ("Rt"). Use the said button toselect "V" on the display.
MAXIMUM CURRENT must be entered as preset in the installationprocedure. The value in A of the maximum current must be entered as a testingconstant. This value must be supplied by the electricity supply companyaccording to MIE-RAT-19.
Using the 3 buttons above the display, (, and Enter), SET THEMAXIMUM DEFAULT CURRENT (maximum 9999):
a.- To enter setting, press () . The first lx digit will flash.
b.- To enter or change this value press () repeatedly: the digit flashingat that time will increase.
c.- When the required value appears on the screen move on to the nextdigit by pressing (), and so on changing the remaining values.
d.- To enter press (Enter) button.
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
18/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 18
5.9.- ATTACHING THE TESTING ELECTRODES
- Attach the touch electrodes (25 kg weights) in a suitable place to starttesting:
STEP VOLTAGE
Attach the two touch electrodes 1 metre apart and near to the ground to betested. Each electrode are joined by a different cable from the voltmeter.
TOUCH VOLTAGE
Attach the two electrodes together 1 metre from the vertical of the testedobject, both connected by a single cable from the voltmeter. The othervoltmeter cable is connected to the tested object with a crocodile clip.
NUMBER OF TESTS
To ensure that there are no dangerous step or touch voltages, it isnecessary to take many measurements within the test area as well as onneighbouring land. To do this, it is useful to have a plan of the installation withdistances of 1 metre marked on it.Whilst testing touch voltage, one must be aware of the possible transmission ofdangerous voltages away from the ground electrode via long metallic structures(metal fences, pipes, rails etc). Testing must be done further away from theseconductive devices.
5.10.- TESTING VOLTAGES DUE TO STATIC CURRENTS
Prior to starting, press the "ERRATIC VOLTAGES" button (keeping itpressed down).
If the Vm value remains at 0 V the presence of erratic voltages andcurrents will be ruled out. If any value appears, it must be noted to
subsequently compare it with the 20 A and 50 A measurements and tomake the appropriate numerical corrections).(See section 8 "CORRECTING READ OUTS").
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
19/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 19
5.11.- ADJUSTING THE CURRENT AND TESTING OF STEP OR TOUCHVOLTAGE
Turn the key in one of the two directions and keep it there.
BEFORE TURNING THE SELECTOR MAKE SURE THAT NO ONE IS
USING THE POWER OR TESTING CIRCUIT. PREVENT PEOPLEREMAINING OR PASSING THROUGH THE AREA WHERE THE CURRENTIS TO BE INJECTED BY USING THE APPROPRIATE SIGNS. IN THE EVENT
OF HIGH GROUND RESISTANCES, VOLTAGES UP TO 600 V MAY BECREATED, WHICH ARE FATAL TO ANIMALS OR PERSONS NEAR TO THEDISPERSERS DURING TESTS.
Adjust the current to 20 A with the MPC-20 and 50 A or slightly higherfor the MPC-50:
FINE REGULATOR:
Starting with the switch on position "1", slowly turn the fine regulator towardsthe right (from 0% to 100%). To find out the current being injected, the needleon the analogue ammeter is the guide at first and then the read out lp. on thedigital indicator.
SWITCHING SCALES:
If the nominal current is not reached, even with the regulator on 100%, it will
then be necessary to increase the switch regulation by one scale.
Adjustments are done by trial and error between the different regulationscales, starting with the lowest: 1 to 10 on the MPC-20 and from 1 to 8 on theMPC-50. Switching from one scale to another is always done off line, i.e.without turning the selector key and placing the regulator in the 0% position.
Voltage testing will be done AUTOMATICALLY at the same time asthe MPC-20 or MPC-50 are adjusted with the operating key. (The voltmeterbegins testing when the key is turned and blocks measurements when the keyis no longer turned.)
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
20/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 20
READ TESTED VOLTAGE (V) on the display.
Note: If the read out on the display is less than 30 V the internal scale isautomatically changed to 30 V AC.
DISENGAGE THE OPERATION SELECTOR. Once the test hasfinished the values remain displayed until the key is turned again, theequipment is switched off or the Imax value is set again.
5.12.- TEST RESULTS (THAT WILL REMAIN DISPLAYED)
Real current Maximum current
of the test made
Im. NN,N I x. NNNNdefault theory
Voltage testedduring the test
Vm. NN,N V NNNNN Calculated voltagedefault theory
(step or touch)
Vm x IxSTEP VOLTAGE (Vp) : V = --------------------
Im
Vm x IxTOUCH VOLTAGE (Vc) : V = ---------------------
Im
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
21/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 21
6.- TESTING GROUND RESISTANCE
The main advantage of testing ground resistance using high currents isthat as well as being measured, the ground is also being tested to see if it iscapable of accepting such a current. By doing it this way, one avoids errors of
measurement from low currents due to, for example, surface moisture or ahighly corroded cable or one with defective lining.
CONNECTION DIAGRAM
TESTED
VOLTAGE
TESTINGROD
TESTING GROUND RESISTANCE
GROUND TO
BE TESTED
AUXILIARY
GROUND
TEST INTENSITY lp
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
22/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 22
6.3.- ATTACHING AND CONNECTING THE MPC-20 or MPC-50
The "OPERATING MODE" selector must be placed on Rt.
Attaching and connecting the MPC to the system is the same as that
for testing step and touch voltage.
Connecting the current circuit using the two output sockets is also thesame.
6.4.- ATTACHING THE MEASURING ROD
One of the voltmeter cables is connected to the ground to bemeasured.
The other voltmeter cable is connected to the GROUND using the"MEASURING ROD" in an area in between the ground to be measured and theauxiliary ground.
6.5.- TESTING VOLTAGES DUE TO ERRATIC CURRENTS
Prior to starting, press the "ERRATIC VOLTAGES" button (keeping itpressed down).
If the Vm value remains at 0 V the presence of erratic voltages andcurrents will be ruled out. If any value appears, it must be noted to besubsequently compared with the 20 A and 50 A measurements and theappropriate numerical corrections made).(See section 8 "CORRECTING READ OUTS").
6.6.- TESTING GROUND RESISTANCE
If testing has to be done at 20 A (MPC-20) or at 50 A (MPC-50),adjustments are made according to section 11.3.2.
If testing has to be done with currents below 20 A or 50 A respectively,the adjustment is also done by trial and error between the different regulationscales starting with the lowest (1, 2, 3, ...). Switching from one scale to anotheris always done off line, i.e. without turning the selector key (according tosection 11.3.2.).
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
23/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 23
Measurements are taken automatically on turning the key (the
voltmeter and the ammeter begin testing on turning the key and blockmeasurements when the key is no longer turned).
BEFORE TURNING THE SELECTOR MAKE SURE THAT NO ONEIS USING THE POWER OR TESTING CIRCUIT.
READ TESTED VOLTAGE (V) on the display.
Note: If the read out on the display is less than 30 V the internal scale isautomatically changed to 30 V AC.
DISENGAGE THE OPERATION SELECTOR Once the test hasfinished the values remain displayed until the key is turned again, the
equipment is switched off or the equipment is disconnected.
The MPC-5 will automatically calculate resistance and store theresults.
6.7.- MEASUREMENT RESULTS (THAT WILL REMAIN DISPLAYED)
Real current
of the test made
Im. NN,N Rt :
Voltage testedduring the test
Vm. NN,N NNN.N Calculated groundresistance
Rt.= Vm./Im.
Ensure that the measuring electrode is actually testing the voltage drop inthe ground that is being tested which is a consequence of the current injectedby the MPC itself. Placing the measuring electrode in the right position is vital. Itis important that it is far from the area under the influence of both themeasuring electrode and the auxiliary electrode to obtain maximum accuracy.
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
24/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 24
6.8.- REPEATING TESTS
Ensure that the measuring electrode is actually testing the voltage drop inthe ground that is being tested which is a consequence of the current injected
by the MPC itself. Placing the measuring electrode in the right position is vital. Itis important that it is far from the area under the influence of both themeasuring electrode and the auxiliary electrode to obtain maximum accuracy.
It is advised that the measuring rod is moved +10% and then -10% from itsstarting position along the axis formed by the earthing and the auxiliaryelectrode separated by a distance L (if its position L=20 metres, it is to bemoved 2 metres from its original position). Make a note of the resistance valuefor each position of the rod. If the values are the same or vary slightly themeasurement is correct. On the other hand if it is within the area influenced bythe two power slopes. The distance between the ground to be measured and
the auxiliary ground has to be increased.
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
25/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 25
CHAPTER II
7.- EXISTING STANDARDS
7.3.- SUMMARY OF HIGH VOLTAGE REGULATIONS
The Technical Complementary instruction MIE-RAT-13 published in theB.O.E. (Official State Gazette) 183 of 1
stAugust 1984, section 1.1. sets the
maximum admissible step and touch voltages for EARTHINGINSTALLATIONS.
In sections 8.1 and 8.2 it establishes the requirement to verify that thestep and touch voltages are within the admissible limits. It establishes therequirement for periodical checking every 3 years as a maximum. It lays downthat the measuring electrodes that simulate feet must have a surface area of
200 square cm each and that they each have a downward force onto theground of 250 N.
STEP VOLTAGE-The voltage that can occur between the feet of somebody standing one
step away whilst the installation is operating" (I.E.C. standard 11-8, sec.176).
TOUCH VOLTAGE-The voltage that a human body may experience whilst in contact with
housings and metallic structures that normally do not carry voltages.
MAXIMUM ADMISSIBLE VOLTAGES- Maximum admissible step and touch voltages in a certain installation,
(B.O.E. 291 5-12-87), are determined by the following summarised formulae:
10 K KVp = -------------- Vc = -----------
t n t n
Being:
K=72 and n=1 for times less than 0.9 s.
K=78.5 and n=0.18 for times between 0.9 and 3 s.t = length of the fault in seconds.For times between 3 and 5 seconds the touch voltage will not exceed 64V and the step voltage 640 V.
For times above 5 seconds touch voltage will not exceed 50 V and stepvoltage 500 V.
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
26/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 26
SUMMARY TABLE OF MAXIMUM VOLTAGES
TIME MAXIMUM STEPVOLTAGE
VOLTAGE TOUCHVOLTAGE
Over 5 s 500 V * 50 VFrom 3 to 5 s 640 V 64 V
2 s 690 V 69 V
1 s 785 V 78.5 V
0.9 s 800 V 80 V
0.7 s 1020 V 102 V
0.5 s 1440 V 144 V
0.2 s 3600 V 360 V
0.1 s or less 7200 V 720 V
* Supposes that the real step voltage on the human body is less than thatmeasured (shoes, etc.).
7.4.- STANDARDS REFERRING TO THE MPC-20 / MPC-50
MIE-RAT-01MIE-RAT-13MIE-RAT-19BOE 183 1
stAugust 1984
BOE 291 5thDecember 1987
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
27/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 27
8.- CORRECTING THE READ OUTS
Results from testing touch or step voltages may be incorrect due to theexistence of erratic, vagabond or parasite currents passing through the ground.
The B.O.E. 291, of 5 of December of 1987 establishes:
1.1.12 "... unless a test method is used that eliminates the effect (in testing)of these parasite currents, e.g. polarity inversion, it will mean that the injectedcurrent will be 1% of the current set for the installation and will not be less than50 A for stations and substations and 5 A for transforming stations."
As a result of currents not indicated by the B.O.E. being used, it will benecessary to use phase inversion for testing.
It is also found that in practice, the tested erratic voltages are always
negligible in terms of those created by injected currents (as long as theyconform to the set minimum).
However, in certain cases it will be possible to do a pretest on existingvoltages without injecting a current. To do this tests by pressing "Erraticvoltages" are done. Only when measurements of erratic voltages are above10% of measurements with current injection, the following calculation must bemade:
Vp =( ) ( )
( )V V
Ve0 180
2
2 22+
Vp = Step or touch voltageVe = Voltage tested "ERRATIC VOLTAGES"V0 = Voltage tested "ON 0"V180 = Voltage tested "ON 180"
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
28/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 28
DERIVATION OF THE FORMULA FOR STEP AND CONTACT VOLTAGE
The following equations are derived from the graph:
V Vp Ve Ve 12 2 2= + + ( sen ) ( cos )
Vp Ve Ve 22 2 2= + ( sen ) ( cos )
Developing the equations:
Vp Vp Ve Ve Ve 1 22 2 2 2 2 2= + + + sen sen cos Vp Vp Ve Ve Ve 2 22 2 2 2 2 2= + + sen sen cos
If the two equations are added, we have to:
V Vp Ve Vp Ve1 2 2 2 2 22 2 2 2 2 2 2 2
+ = + + = +(sen cos )
Solving Vp: Vp =( ) ( )
( )V V
Ve1 2
2
2 22+
V1 = read voltage on injecting current at 0V2 = read voltage on injecting current at 180Ve = read voltage without injecting current
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
29/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 29
9.- MAINTENANCE
The MPC does not require specialised maintenance. As far as possibleavoid any adjustment, maintenance or repairs when the equipment is open. Ifthis is unavoidable it must be done by qualified personnel or technicians well
informed of the procedure to follow.
Before any modification to the connections, replacement, maintenance orrepair, the equipment must be disconnected from the supply.
If any operating fault or equipment protection fault is suspected, theequipment must be taken out of service ensuring that no accidentalreconnection may occur. The equipment is designed to have any of itscomponents replaced quickly in the event of breakdown.
10.- TECHNICAL SERVICE
In the event of any equipment failure or any operational queries pleasecontact the technical service of CIRCUTOR S.A.
CIRCUTOR S.A. - After sales servicec / Lepanto , 4908223 - TERRASSAtel - (+34) 93 - 745 29 00e-mail: central@circutor.es
7/26/2019 MPC-20 MPC-50 Indirect Earth Simulator Manual
30/30
--- MPC 20 & 50 TESTER - M-981136 (vers. BD) --- Page 30
APPENDIX
MPC-50 INTERNAL TERMINAL BOARD
FUSIBLEMANIOBRA
400 V 230 V
CAMBIO DETENSIN
CHANGE OF VOLTAGE:
- Attach the voltage bridge in the required position- Attach the indicating tag on the external supply cable
OPERATING
FUSE
CHANGING
VOLTAGE
Recommended