View
1
Download
0
Category
Preview:
Citation preview
TAC1354 Clifford AvenueP. O. Box 2940Loves Park, IL 61132-2940www.tac.com
Typical Spring Return
Typical Non-Spring Return
*
* Refer to Table-2 and Table-3 to identify specific models that are in compliance with CE requirements.
Typical MP6(Hazardous Locations)
Typical -6xx Suffix(CP-8301-xxx or CP-8391-91x Installed)
MP-3xx Series, MP-4xx Series, MP-2xxx Series, and
MP-4xxx Series
Reversible and Proportional Electric ActuatorsGeneral Instructions
ApplicationThe MP series actuators are used for two-position, floating, and proportional control of dampers, valves, and program switches in heating, ventilating, air conditioning, and similar applications.
Hazardous location models offer a sturdy cast aluminum case with bolted cover. They have two 3/4" pipe tapped openings for joints with rigid metal conduit. All wiring is brought out to separate terminals for ease of installation. These factory enclosure and actuator assemblies are Underwriters Laboratories Listed.
Features• Proportional actuators with built-in feedback
potentiometers• Spring return and non-spring return models
available• 24 Vac, 120 Vac, and 240 Vac models are available• Actuator has a rugged die cast aluminum housing
with two 1/2” conduit openings.• Hazardous location actuator housing has two 3/4"
pipe taped openings for rigid metal conduit connection
• Oil-immersed motor and gear train
Applicable Literature• TAC Valve Selection Guide, F-26094• AV-29x Valve Linkage for Hazardous Location Gear
Train Actuators General Instructions, F-27441.• Apparatus for Hazardous Locations EN-56-2,
F-18451.• AV-390 Series, Valve Linkage for Gear Train
Actuators, General Instructions, F-24376 • Material Safety Data Sheet MSDS-4• AM-363 Gasket Cover Kit General Instructions,
F-25598• CP-8301 Solid State Actuator Drive General
Instructions, F-14940• CP-8391-716 Electronic Actuator Drive General
Instructions, F-21220• CP-8391-910 Series 4 to 20 mA Electronic Actuator
Drive General Instructions, F-22453• AE-504 Solid State Paralleling Relay General
Instructions, F-16524
Printed in U.S.A. 3/07 © Copyright 2007 TAC All Rights Reserved. F-15479-8
SPECIFICATIONS
Actuator InputsInput Control Signals: Refer to the actuator selection tables beginning on page 3 for input control signal capability versus specific actuator models.
Floating, Requires one Single Pole Double Throw (SPDT) switch with floating (center off) position rated at 0.9 amps @ 24 Vac or two Single Pole Single Throw (SPST) switches rated at 0.9 amps @ 24 Vac.Two-Position,
SPDT Requires snap acting switch rated at 0.9 amps @ 24 Vac.SPST Can be used with certain spring return actuators. Switch must be rated to handle actuator power requirements.
TAC Microtherm®, Proportional Electrical system with the following typical controllers: PP-22x series, TP-1xx series, TP-2xx series, TP-3xx series, TP-4xx series, TP-1xxx series, and TP-1xxxx series.
Standard Control of a single actuator.Sequencing Control of two actuators in sequence.Five-Position Used typically for adjustable minimum position (five positions) of an economizer actuator.
Slidewire and Paralleling, Requires AE-504 paralleling relay. Refer to AE-504 Solid State Paralleling Relay General Instructions F-16524. AE-504 accepts 100 Ω to 1000 Ω slidewires.Voltage Vdc, Requires CP-8301-xxx series of solid state actuator drives. Refer to CP-8301 Solid State Actuator Drive General Instructions F-14940. Refer to the actuator selection tables beginning on page 3.Current mAdc, Requires CP-8391-xxx series of solid state actuator drives. Refer to the actuator selection tables beginning on page 3.
Power Requirements: Refer to the actuator selection tables beginning on page 3 to determine power requirements.Connections:
MP-3xx, 4xx, 2xxx, 4xxx, Coded screw terminals.Models with “-600” Suffix, Coded screw terminals except for input signal which are color coded pigtails.
Actuator OutputsTorque: Refer to the actuator selection tables beginning on page 3 to determine the actuator torque rating.Nominal Damper Area: Actuator selection should be made in accordance with the damper manufacturer’s specifications.
Stroke (Degrees of Rotation), Refer to the actuator selection tables beginning on page 3 for information on degrees of rotation.Auxiliary Switch, Refer to the actuator selection tables beginning on page 3 for the models that include an auxiliary switch. Refer to Table-6 for ratings.
Spring Return: Refer to the actuator selection tables beginning on page 3 for models that are spring return.
EnvironmentAmbient Temperature Limits:
Shipping and Storage, -40 to 160 °F (-40 to 71 °C).Operating, -40 to 136 °F (-40 to 58 °C).
Humidity: 5 to 95% RH, non-condensing.Locations: NEMA 1
NEMA 4 for non-spring return actuators with AM-363.Agency Listings:
UL 873, Underwriters Laboratories (File #E9429 Category Temperature Indicating and Regulating Equipment).CSA, Canadian Standards Association (File #LR3728).European Community, EMC Directives (89/336/EEC and 92/31/EEC). Low Voltage Directive (72/23/EEC). Refer to Table-2 and Table-3 to identify specific models that are in compliance with CE requirements.Hazardous Location Models, UL file #29291. Designed for use in hazardous locations N.E.C., Class 1, Groups C and D, and Class 2, Groups E, F, and G. Temperature code T6 for hazardous housing.
2 © Copyright 2007 TAC All Rights Reserved. F-15479-8
F-15479-8©
Copyright 2007 TA
C All R
ights Reserved.
3
l CP-8301s have a fixed span of 3 Vdc
91-910 Series 4 to 20 mA Electronic (factory set for 16) and adjustable start -8391-716 Electronic Actuator Drive
utput Shaft
Aux.Switch
Built-inTrans-
former bgdsad)
Degrees ofRotation
SpringReturn
180 (nonAdj.) No SPDT –
180 (non-Adj.) No SPDT Yes
tput Shaft
Aux.Switch
Built-inTrans-
former bgdsad)
Degrees ofRotation
SpringReturn
180 (Adj.f) CW SPDT –
180 (Adj.f) CW SPST –
180 (nonAdj.) CCW SPDT –
180 (nonAdj.) CCW SPST –
180 (nonAdj.) CCW None –
180 (Adj.f) No SPDT –
o dj.) 180 (Adj.f) No SPDT –
180 (Adj.f) No SPST –
180 (Adj.f) No None –
the actuator. Red (24 Vac) to terminal 8 and Blue to “-2” suffix had transformer wired directly to
is fixed.
Actuators in the actuator selection tables below with “-600” suffix have the CP-8301-120 factory installed. Alto drive the actuator full stroke and a start point adjustable from 2 to 12 Vdc (factory set 6 Vdc).
The CP-8391-91x series have a fixed range of 4 to 20 mAdc to drive the actuator full stroke. Refer to CP-83Actuator Drive General Instructions F-22453. The CP-8391-716 has an adjustable span of 4 to 16 mAdc point of 2 to 16 mAdc (factory set for 4). The input signal on CP-8391-716 is optically isolated. Refer to CPGeneral Instructions F-21220.
Table-1 MP-2xxx Series Model Chart.
Table-2 MP-3xx Series Model Chart.
ActuatorPart
Number
InternalWiring(See
Figure)
Input Control Signal External Wiring (and required Interface Module that must be purchased separately)(See Figure) Power Requirements O
2-PositionSPSTSpringReturn
2-Positionor
FloatingSPDT
TAC Microtherm a(Proportional Electric) 135 to
1,000 ΩSlidewire
Voltage Vdc Current mAdc Volts Hz. AmpsTorqueLb.-in.(N-m)
TiminSecon(No LoStandard
Sequencingof Two
Actuators
5-Position(Adj. MinPosition)
MP-2113-500 Figure-27 – Figure-5 Figure-7 – – Figure-14 (AE-504)
Figure-17 (CP-8301-024)
Figure-19 (CP-8391-913) 24 60 2.2 50 (5.6) 25
MP-2150-500 Figure-29 – Figure-6 – – – Figure-15 (AE-504)
Figure-18 (CP-8301-120)
Figure-21c or Figure-23d 120 60 0.5 50 (5.6) 25
ActuatorPart
Number
InternalWiring(See
Figure)
Input Control Signal External Wiring (and required Interface Module that must be purchased separately)(See Figure)
Power Requirements Ou
2-PositionSPSTSpringReturn
2-Positionor
FloatingSPDT
TAC Microtherma
(Proportional Electric) 135 to1,000 Ω
SlidewireVoltage Vdc Current mAdc Volts Hz. Amps
TorqueLb.-in.(N-m)
TiminSecon(No LoStandard
Sequencingof Two
Actuators
5-Position(Adj. MinPosition)
MP-361e Figure-24 Figure-3 Figure-5 Figure-7 – – Figure-14 (AE-504)
Figure-17 (CP-8301-024)
Figure-19 (CP-8391-913) 24 60 2.5 50 (5.6) 90
MP-367e Figure-32 – – – Figure-11 – – – – 24 60 2.5 50 (5.6) 90
MP-371e g Figure-24 Figure-3 Figure-5 Figure-7 – –Figure-14
(AE-504)
Figure-17 (CP-8301-024)
Figure-19 (CP-8391-913) 24 60 2.5 50 (5.6) 90
MP-377e Figure-32 – – – Figure-11 – – – – 24 60 2.5 50 (5.6) 90
MP-379e Figure-30 – – – – Figure-12 – – – 24 60 2.5 50 (5.6) 90
MP-381e Figure-24 – Figure-5 – – – Figure-14 (AE-504)
Figure-17 (CP-8301-024)
Figure-19 (CP-8391-913) 24 60 2.2 220 (24.9) 130
MP-382e Figure-24 – Figure-5 – – – Figure-14 (AE-504)
Figure-17 (CP-8301-024)
Figure-19 (CP-8391-913) 24 60 2.2 220 (24.9) 130 t
1300 (A
MP-387e Figure-32 – – – Figure-11 – – – – 24 60 2.2 220 (24.9) 130
MP-389e Figure-30 – – – – Figure-12 – – – 24 60 2.2 220 (24.9) 130
a Typical TAC Microtherm Controllers: PP-22x Series; TP-1xx Series; TP-4xx Series; TP-101x Series; TP-103x Series; and TP-1xxxx Series.b Units with a “-2” suffix, e.g. MP-xxxx-xxx-2-x, include a built-in transformer (used for TAC Microtherm or with AE-504) with secondary leads wired externally to terminals 7 and 8 of
(12 Vac) to terminal 7. When these actuators are used with controllers other than TAC Microtherm or AE-504, disconnect the Red and Blue leads and tape off. Note: Models prior potentiometer. To disconnect the transformer, remove the back plate of the actuator, disconnect and tape the transformer leads.
c Requires CP-8391-910.d Requires CP-8391-716.e Units with a “-0-0-2” suffix are in compliance with CE requirements.f Rotation adjustable 45 to 320°. Caution: On actuators with proportional input signals changing the rotation will affect the control, since the internal feedback potentiometer’s travelg MP-371 models with the “-621” suffix are obsolete.
4©
Copyright 2007 TAC
All R
ights Reserved.
F-15479-8
Output Shaft
Aux.Switch
Built-inTrans-
former bTimingSeconds(No Load)
Degrees ofRotation
SpringReturn
) 25 180 (Adj.f) No SPDT –
) 25 to 250(Adj.) 180 (Adj.f) No SPDT –
) 13 90 (Adj.f) No SPDT –
) 13 to 130(Adj.) 90 (Adj.f) No SPDT –
9) 80 180 (Adj.f) No SPDT –
9) 80 to 800(Adj.) 180 (Adj.f) No SPDT –
9) 40 90 (Adj.f) No SPDT –
9) 40 to 400(Adj.) 90 (Adj.f) No SPDT –
) 90 180 (Adj.f) CW SPDT –
) 90 180 (Adj.f) CW SPDT Yes
) 90 180 (non-Adj.) CCW None Yes
) 90 180 (non-Adj.) CCW SPDT –
) 90 180 (non-Adj.) CCW SPDT Yes
9) 130 180 (Adj.f) No None Yes
9) 130 180 (Adj.f) No SPDT –
9) 65 90 (Adj.f) No SPDT Yes
9) 130 180 (Adj.f) No SPDT Yes
9) 130 to 1300(Adj.) 180 (Adj.f) No SPDT Yes
9) 130 180 (Adj.f) No SPDT Yes
Table-3 MP-4xx Series Model Chart.
ActuatorPart
Number
InternalWiring(See
Figure)
Input Control Signal External Wiring (and required Interface Module that must be purchased separately)(See Figure)
Power Requirements
2-PositionSPSTSpringReturn
2-Positionor
FloatingSPDT
TAC Microtherma
(Proportional Electric)135 to
1,000 ΩSlidewire
Voltage Vdc Current mAdc Volts Hz. Amps
TorqueLb.-in.(N-m)Standard
Sequenc-ing
of TwoActuators
5-Position(Adj. MinPosition)
MP-421 Figure-25 – Figure-6 – – – – Figure-16 (CP-8301-120)
Figure-20 c or Figure-22d 120 60 0.65 60 (6.8
MP-422 Figure-25 – Figure-6 – – – – Figure-16 (CP-8301-120)
Figure-20 c or Figure-22d 120 60 0.65 60 (6.8
MP-423 Figure-25 – Figure-6 – – – – Figure-16 (CP-8301-120)
Figure-20 c or Figure-22d 120 60 0.65 60 (6.8
MP-424 Figure-25 – Figure-6 – – – – Figure-16 (CP-8301-120)
Figure-20 c or Figure-22d 120 60 0.65 60 (6.8
MP-451 Figure-25 – Figure-6 – – – – Figure-16 (CP-8301-120)
Figure-20 c or Figure-22d 120 60 0.65 220 (24.
MP-452 Figure-25 – Figure-6 – – – – Figure-16 (CP-8301-120)
Figure-20 c or Figure-22d 120 60 0.65 220 (24.
MP-453 Figure-25 – Figure-6 – – – – Figure-16 (CP-8301-120)
Figure-20 c or Figure-22d 120 60 0.65 220 (24.
MP-454 Figure-25 – Figure-6 – – – – Figure-16 (CP-8301-120)
Figure-20 c or Figure-22d 120 60 0.65 220 (24.
MP-461-600e Figure-25 – 1.5 – – – – Figure-16h – 120 60 0.5 50 (5.6
MP-465 Figure-26 Figure-4 Figure-6 Figure-9 – – Figure-15 (AE-504)
Figure-18 (CP-8301-120)
Figure-21 c or Figure-23d 120 60 0.5 50 (5.6
MP-470 Figure-31 – – – – Figure-13 – – – 120 60 0.5 50 (5.6
MP-471-600e g Figure-25 – – – – – – Figure-16h – 120 60 0.5 50 (5.6
MP-475 Figure-26 Figure-4 Figure-6 Figure-9 – – Figure-15 (AE-504)
Figure-18 (CP-8301-120)
Figure-21 c or Figure-23d 120 60 0.5 50 (5.6
MP-480 Figure-31 – – – – Figure-13 – – – 120 60 0.5 220 (24.
MP-481-600e Figure-25 – – – – – – Figure-16h – 120 60 0.5 220 (24.
MP-483 Figure-26 – Figure-6 – – – Figure-15 (AE-504)
Figure-18 (CP-8301-120)
Figure-21 c or Figure-23d 120 60 0.5 220 (24.
MP-485 Figure-26 – Figure-6 – – – Figure-15 (AE-504)
Figure-18 (CP-8301-120)
Figure-21 c or Figure-23d 120 60 0.5 220 (24.
MP-486 Figure-26 – Figure-6 – – – Figure-15 (AE-504)
Figure-18 (CP-8301-120)
Figure-21 c or Figure-23d 120 60 0.5 220 (24.
MP-495iFigure-26 – Figure-6 – – – Figure-15
(AE-504)Figure-18
(CP-8301-120)Figure-21 c or
Figure-23d 120 60 0.95 450 (50.
Footnotes for this table are listed on the following page.
F-15479-8©
Copyright 2007 TA
C All R
ights Reserved.
5
Ta
A
N
Output Shaft
Aux.Switch
Built-inTrans-
former bing
onds Load)
Degrees ofRotation
SpringReturn
M 08 180 (Adj.f) CW SPDT Yes
M 90 180 (non-Adj.) CCW None Yes
M 08 180 (non-Adj.) CCW SPDT Yes
M 30 180 (Adj.f) No SPDT Yes
M 56 180 (Adj.f) No SPDT Yes
8 of the actuator. Red (24 Vac) to terminal 8 and Blue prior to “-2” suffix had transformer wired directly to
ravel is fixed.
ble-4 MP-4xxx Series Model Chart.
ctuatorPartumber
InternalWiring(See
Figure)
Input Control Signal External Wiring (and required Interface Module that must be purchased separately)(See Figure)
Power Requirements
2-PositionSPSTSpringReturn
2-Positionor
FloatingSPDT
TAC Microtherma
(Proportional Electric) 135 to1,000 Ω
SlidewireVoltage Vdc Current
mAdc Volts Hz. AmpsTorqueLb.-in.(N-m)
TimSec(NoStandard
Sequencingof Two
Actuators
5-Position(Adj. MinPosition)
P5-4651 Figure-26 Figure-4 Figure-6 – – – Figure-15(AE-504)
Figure-18(CP-8301-240)
Figure-21c or Figure-23d 240 50 0.25 50 (5.6) 1
P-4701 Figure-31 – – – – Figure-13 – – – 240 60 0.25 50 (5.6)
P5-4751 Figure-26 Figure-4 Figure-6 – – – Figure-15(AE-504)
Figure-18 (CP-8301-240)
Figure-21c or Figure-23d 240 50 0.25 50 (5.6) 1
P-4851 Figure-26 – Figure-6 – – – Figure-15(AE-504)
Figure-18 (CP-8301-240)
Figure-21c or Figure-23d 240 60 0.25 220 (24.9) 1
P5-4851 Figure-26 – Figure-6 – – – Figure-15(AE-504)
Figure-18 (CP-8301-240)
Figure-21c or Figure-23d 240 50 0.25 220 (24.9) 1
a Typical TAC Microtherm Controllers: PP-22x Series; TP-1xx Series; TP-4xx Series; TP-101x Series; TP-103x Series; and TP-1xxxx Series.b Units with a “-2” suffix, e.g. MP-xxxx-xxx-2-x, include a built-in transformer (used for TAC Microtherm or with AE-504) with secondary leads wired externally to terminals 7 and
(12 Vac) to terminal 7. When these actuators are used with controllers other than TAC Microtherm or AE-504, disconnect the Red and Blue leads and tape off. Note: Models potentiometer. To disconnect the transformer, remove the back plate of the actuator, disconnect and tape the transformer leads.
c Requires CP-8391-910.d Requires CP-8391-716.e Units with a “-0-0-2” suffix are in compliance with CE requirements.f Rotation adjustable 45 to 320°. Caution: On actuators with proportional input signals changing the rotation will affect the control, since the internal feedback potentiometer’s tg MP-371 models with the “-621” suffix are obsolete.h Integral solid state drive accepts 2-15 Vdc voltage.i MP-495 is not rated for UL or CSA
Table-5 Actuator Part Numbers for Hazardous Location Applications.
Table-6 Auxiliary Switch Ratings.
Standard ActuatorPart Numbers
Hazardous Location ActuatorPart Numbersa b
Damper Actuators Valve Actuatorsc
MP-381 — MP6-381
MP-421 — MP6-421
MP-423 MP6-423 —
MP-453 MP6-453 —
MP-483 MP6-483 —
MP-485 — MP6-485
MP-361 — MP6-361
MP-367 — MP6-367
MP-371 — MP6-371
MP-377 — MP6-377
MP-379 — MP6-379
MP-465 — MP6-465
MP-470 — MP6-470
MP-475 — MP6-475
MP5-4651 — MP7-4651
MP5-4751 — MP7-4751a Class 1, Groups C & D, and Class 2, Groups E, F, and G hazardous locations; refer to EN-56-2.b Models for hazardous locations are only available as factory-built enclosure/actuator assemblies.c Hazardous location valve actuators can also be used for hazardous location damper applications.
Switch Electrical Rating 120 Vac 240 VacRunning 5.8 amps 2.9 amps
Locked Rotor 34.8 amps 17.4 amps
Non-Inductive 12 6
6 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Figure-1 Part Number System for MP-2xxx-xxx-x-x Series Actuators.
Note: This figure is for information only. Do not use it for ordering or selecting product.
5 -50 Hz6 -Includes 60 Hz Hazardous Location Housing7 -50 Hz Hazardous Location Housing
0 - No Transformer Unless Noted in Base Part Number
2 - Internal Transformer3 - Old Engineering Revision
1 -Old Engineering Revision2 -Actuators that can be Ungrounded
A - Old Actuator (Eng. Revision)Ax10 - Old Actuator Equals - 110 as an ExampleAV5 - Old Actuator Equals - 205 as an Example1xx - Specials100 - AM-363 Installed2xx - Unit Ventilator Specials304 - AE-504 Installed321 - AM 321 Installed332 - AM-332 Installed341 - AM-341 Installed500 - Aux. Switch600 - CP-8301-620 (CP-8301-120) Installed (120 Vac), No Aux. Switch
CP-8301-624 (CP-8301-024) Installed (24 Vac), No Aux. Switch CP-8301-640 (CP-8301-240) Installed (240 Vac), No Aux. Switch
601 - CP-8301-620 (CP-8301-120) Installed (120 Vac), Aux. Switch CP-8301-624 (CP-8301-024) Installed (24 Vac), Aux. Switch CP-8301-640 (CP-8301-240) Installed (240 Vac), Aux. Switch
7xx - OEM Specials
Voltage0 - 120 Vac1 - 240 Vac2 - 208 Vac3 - 24 Vac
1 - 180°, No Transformer3 - 90°, No Transformer5 - 180°, Transformer
1800:1 Gear Train50 Lb.-In. Torque25 Sec./180° @ 60 HzNo Load Timing
MPx-21xx-xxx-x-xMechanical Stops
Motor (Actuator)
Proportional
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 7
Figure-2 Part Number System for MP-3xx, MP-4xx, or MP-4xxx Series Actuators.
Note: This figure is for information only. Do not use it for ordering or selecting product.
Gear Train (Torque/Timing* for 180°)1 - 1025:1 (35 Lb.-In./13 Sec.)2 - 1960:1 (60 Lb.-In./25 Sec.)3 - 2980:1 (85 Lb.-In./35 Sec.)4 - 4018:1 (130 Lb.-In./50 Sec.)5 - 6760:1 (220 Lb.-In./80 Sec.)6 - 6760:1 Spring Return CW (50 Lb.-In./90 Sec.)7 - 6760:1 Spring Return CCW (50 Lb.-In./90 Sec.)8 - 10292:1 (220 Lb.-In./130 Sec.)9 - 10413:1 (450 Lb.-In./130 Sec.)*No Load @ 60 Hz.
1 - 180°, Fixed Speed2 - 180°, Adj. Speed3 - 90°, Fixed Speed4 - 90°, Adj. Speed5 - 180°, Fixed Speed, Transformer6 - 180°, Adj. Speed, Transformer7 - 180°, Fixed Speed, Sequencing8 - 180°, Adj. Speed, 5-Position9 - 180°, Fixed Speed, 5-Position0 - 180°, Fixed Speed, 5-Position, Transformer
A - Old Actuator (Eng. Revision)Ax10 - Old Actuator Equals - 110 as an ExampleAV5 - Old Actuator Equals - 205 as an Example1xx - Specials100 - AM-363 Installed, Not Available on
Spring Return Actuators2xx - Unit Ventilator Specials304 - AE-504 Installed321 - AM-321 Installed332 - AM-332 Installed341 - AM-341 Installed600 - CP-8301-620 (CP-8301-120) Installed (120 Vac)
CP-8301-624 (CP-8301-024) Installed (24 Vac) CP-8301-640 (CP-8301-240) Installed (240 Vac)
7xx - OEM Specials
Voltage3xx -24 Vac4xx -120 Vac4xx1 -240 Vac4xx2 -208 Vac
1 - Old Engineering Revision2 - Actuators that can be Ungrounded
MPx-xxxx-xxx-x-x
0 - No Transformer Unless Noted in Base Part Number
1 - Leeds Northrup Capacitor Start Motor with Internal Capacitor
2 - Internal Transformer3 - Old Engineering Revision
5 -50 Hz6 -Includes 60 Hz Hazardous Location Housing7 -50 Hz Hazardous Location Housing
Motor (Actuator)
Proportional
8 © Copyright 2007 TAC All Rights Reserved. F-15479-8
ACCESSORIESDamper linkage accessoriesAM-111 Crank arm for 5/16" (7.9 mm) diameter damper shaftAM-112 Crank arm for 3/8" (9.5 mm) diameter damper shaftAM-113 Crank arm for actuator or 1/2" (12.7 mm) diameter damper shaftAM-115 Crank arm for 7/16" (11.1 mm) diameter damper shaftAM-116 Splined crank arm for actuatorAM-122 Linkage connector, straight typeAM-123 Damper clipAM-125 5/16" x 20" (7.9 mm x 0.5 m) damper rodAM-125-048 5/16" x 48" (7.9 mm x 1.2 m) damper rodAM-132 Ball joint connectorAM-161 Damper linkage kitAM-161-1 Damper linkage kitAM-301 90 degree mounting bracketMiscellaneous actuator accessoriesAM-321 Two step switch kitAM-332 Potentiometer kitAM-341 Four step switch kitAM-342 Two step switch and potentiometer kitAM-363 NEMA 4 gasket kit for non-spring return actuators onlyAM-402 Hazardous location housing for spring return units except suffix “-600”TOOL-201 Calibration kit for TAC System 8000TM
TOOL-209 135 Ω slidewire calibration kitValve linkage for 50 lb.-in. minimum, 180° actuatorAV-329 Valve linkage for 2-1/2" and 3" VB-9323AV-391 Valve linkage for 15 to 50 mm and 1/2" to 2” VB-72xx or VB-73xx (also valve
linkage for obsolete 1/2” to 1-1/4" VB-92xx or VB-93xx)AV-392 Valve linkage for obsolete 1-1/2" and 2" VB-92xx or VB-93xxAV-395 Valve linkage for 65 and 80 mm VB-9215 or VB-9315, and 2-1/2" to 4" VB-9213 or
VB-9313Valve linkage for 130 lb.-in. minimum, 180° actuatorAV-330 Valve linkage for 2-1/2" and 3" VB-9323AV-352 Valve linkage for 2-1/2" to 6" VB-921x or VB-931x, 4" to 6" VB-9323AV-393 Valve linkage for 15 to 50 mm and 1/2” to 2” VB-72xx or VB-73xx (also valve
linkage for obsolete 1/2" to 1-1/4" VB-92xx or VB-93xx)AV-394 Valve linkage for obsolete 1-1/2" and 2" VB-92xx or VB-93xxAV-396 Valve linkage for 65 and 80 mm VB-9215 or VB-9315, and 2-1/2" to 4" VB-921x or
VB-931xValve Linkage for 50 lb.-in. MP6-xxx and MP7-xxx Hazardous Location ActuatorsAV-291 Valve linkage for ½ to 2" VB-7xxx valves assembled with hazardous location
actuator assemblies.AV-295 Valve linkage for 2½ to 3" VB-9xxx valves assembled with hazardous location
actuator assemblies.Valve Linkage for 220 lb.-in. MP6-xxx and MP7-xxx Hazardous Location ActuatorsAV-293 Valve linkage for ½ to 2" VB-7xxx valves assembled with hazardous location
actuator assembliesAV-296 Valve linkage for 2½ to 3" VB-9xxx valves assembled with hazardous location
actuator assemblies
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 9
TYPICAL APPLICATIONS (wiring diagrams)
List of FiguresFigure-3 External Wiring for SPST Control of MP-361 and MP-371, 24 Vac
Actuators.page 11
Figure-4 External Wiring for SPST Control of MP-465, MP-475, MP5-4651, and MP5-4751 Line Voltage Actuators.
page 11
Figure-5 External Wiring for SPDT (Snap Acting or Floating) Switch for Control of 24 Vac Actuators MP-361, MP-371, MP-381, MP-382 and MP-2113-500.
page 12
Figure-6 External Wiring for SPDT (Snap Acting or Floating) Switch for Control of Line Voltage Actuators.
page 12
Figure-7 TAC Microtherm Controller with 24 Vac Actuators – Standard Wiring Diagram.
Page 13
Figure-8 TAC Microtherm Controller with 24 Vac Actuators – Reversed (Cooling) Wiring Diagram.
page 13
Figure-9 External Wiring of TAC Microtherm Controller with Line Voltage Actuator – Standard Wiring.
page 14
Figure-10 External Wiring of TAC Microtherm Controller with Line Voltage Actuator – Reversed (Cooling) Wiring.
page 14
Figure-11 External Wiring for TAC Microtherm Controller with 24 Vac Sequencing Actuators.
page 15
Figure-12 External Wiring for TAC Microtherm Controller with Five-Position 24 Vac Actuators.
page 16
Figure-13 External Wiring for TAC Microtherm Controller with Five-Position Line Voltage Actuator.
page 17
Figure-14 External Wiring for Slidewire Controller with 24 Vac Actuators. page 18
Figure-15 External Wiring for Slidewire Controller with Line Voltage Actuator. page 18
Figure-16 External Wiring for CP-8301-120, Vdc Interface with Line Voltage Actuators without Internal Transformer.
page 19
Figure-17 External Wiring for CP-8301-024, Vdc Interface with 24 Vac Actuators. page 20
Figure-18 External Wiring for CP-8301-120 and CP-8301-240, Vdc Interface with Line Voltage Actuators with Internal Transformer.
page 21
Figure-19 External Wiring for CP-8391-913, 4 to 20 mAdc Interface with 24 Vac Actuators.
page 22
Figure-20 External Wiring for CP-8391-910, 4 to 20 mAdc Interface with Line Voltage Actuators without Internal Transformer.
page 22
Figure-21 External Wiring for CP-8391-910 and CP-8391-911, 4 to 20 mAdc Interface with Line Voltage Actuators with Internal Transformer.
page 23
Figure-22 External Wiring for CP-8391-716, mAdc Interface with Line Voltage Actuators without Internal Transformer.
page 23
Figure-23 External Wiring for CP-8391-716, mAdc Interface with Line Voltage Actuators with Internal Transformer.
page 24
Figure-24 Internal Wiring for 24 Vac Actuator. page 24
Figure-25 Internal Wiring for Line Voltage Actuators. page 25
Figure-26 Internal Wiring for Line Voltage Actuator with Built-in Transformer. page 25
Figure-27 Internal Wiring for 24 Vac Actuator without Limit Switches (Actuator is Stall Type with Built-in Mechanical Stops).
page 26
Figure-28 Internal Wiring for Line Voltage Actuators without Limit Switches (Actuator is Stall Type with Built-in Mechanical Stops.)
page 26
Figure-29 Internal Wiring for Line Voltage Actuators without Limit Switches and Built-in Transformer (Actuator is Stall Type with Built-in Mechanical Stops).
page 27
Figure-30 Internal Wiring for 24 Vac Five-Position Actuators. page 27
Figure-31 Internal Wiring for LIne Voltage Five-Position Actuators. page 28
Figure-32 Internal Wiring for 24 Vac Sequencing Actuators. page 28
10 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Figure-3 External Wiring for SPST Control of MP-361 and MP-371, 24 Vac Actuators.
Figure-4 External Wiring for SPST Control of MP-465, MP-475, MP5-4651, and MP5-4751 Line Voltage Actuators.
4 5 6 7
3 8
2 H
1 GX
Green Wires
SPST Control Switch(Rated to Handle Power
Requirements of Actuator)
To 24 VacPower Supply
Add Jumper
4 5 6 7
3 8
2 H
1 GX
Green Wires
SPST Control Switch(Rated to Handle Power
Requirements of Actuator)
To 24 VacPower Supply
Add Jumper
CaseGround Screw
CaseGround Screw
MP-361 Actuator drives CCW when 24 Vac is applied and spring returns CW with no power.
MP-371 Actuator drives CW when 24 Vac is applied and spring returns CCW with no power.
4 5 6 7
3 8
2 L1
1 L2X
Green Wire
SPST Control Switch(Rated to Handle Power
Requirements of Actuator)
To ACPower Supply
Add Jumper
4 5 6 7
3 8
2 L1
1 L2X
Green Wire
SPST Control Switch(Rated to Handle Power
Requirements of Actuator)
To ACPower Supply
Add Jumper
CaseGround Screw
CaseGround Screw
Typical Actuators: MP-465 and MP5-4651 Actuator drives CCW when Power is applied and spring returns CW with no power.
Typical Actuators: MP-475 and MP5-4751 Actuator drives CW when Power is applied and spring returns CCW with no power.
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 11
Typical Actuators: MP-361, MP-371, MP-381, MP-382, and MP-2113-500.
Note: Each pole of a switch or a relay can control only one actuator.
Figure-5 External Wiring for SPDT (Snap Acting or Floating) Switch for Control of 24 Vac Actuators MP-361, MP-371,MP-381, MP-382, and MP-2113-500
Typical Actuators: MP-421, MP-422, MP-423, MP-424, MP-451, MP-452, MP-4553, MP-454, MP-465, MP-483, MP-485, MP-486, MP-495, MP-2130-500, MP-2150-500, MP5-2151-500, MP5-4651, MP5-4751, MP-4851, and MP5-4851.
Note: Each pole of a switch or a relay can control only one actuator.
Figure-6 External Wiring for SPDT (Snap Acting or Floating) Switch for Control of Line Voltage Actuators.
4 5 6 7
8
H
1 G
Green WiresTo 24 Vac
Power Supply
WhiteBlue
Red
CaseGround Screw
SPDT Snap Acting orFloating Switch ratedfor.9 Amps @ 24 Vac
1 The use of a snap acting switch will result in a two-position control actuator.
2 With actuator terminal X shorted to terminal 2, actuator drives CW. With actuator terminal X shorted to terminal 3, actuator drives CCW. With actuator terminal X open to both terminals 2 and 3, actuator maintains position.
Typical DDCControllers
DO1
DO2
COM
COM
To SPDT Switchor
From 3
From 3
From 2
From X
From 2
CYZR-818Arc Suppressor
Purchased Separately
3
2
X
orDDC Controller
2
1
From X
Typical DDCControllers
DO1
DO2
COM
COM
From 3
From 3
From 2
From X
From 2
From X
4 5 6 7
8
L1
1 L2
Green WiresTo AC
Power Supply
WhiteBlue
Red
CaseGround Screw
SPDT Snap Acting orFloating Switch ratedfor.9 Amps @ 24 Vac
1 The use of a snap acting switch will result in a two-position control actuator.
2 With actuator terminal X shorted to terminal 2, actuator drives CW. With actuator terminal X shorted to terminal 3, actuator drives CCW. With actuator terminal X open to both terminals 2 and 3, actuator maintains position.
Typical DDCControllers
DO1
DO2
COM
COM
To SPDT Switchor
From 3
From 3
From 2
From X
From X
CYZR-818Arc Suppressor
Purchased Separately
3
2
X
orDDC Controller
2
1
From 2
12 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Typical Actuators: MP-361, MP-371, MP-381, MP-382, and MP-2113-500.
Typical TAC Microtherm Controllers: PP-22x Series, TP-2xx Series, TP-3xx Series, TP-4xx Series, and TP-101x Series.C =Common of Switch to R and B.
1 =Feedback from actuator (24 Vac with actuator full Counterclockwise rotation (CCW) to 12 Vac at Clockwise rotation (CW) end).
R =Closes on temperature (pressure) drop and drives the actuator CCW (opens valve).
B =Closes on temperature (pressure) rise and drives the actuator CW (closes valve).
Typical Cooling TAC Microtherm: TP-1031.C =Common of switch to R and B.
1 =Feedback from Actuator (24 Vac with actuator full CCW to 12 Vac at CW end).
R =Closes on temperature rise and drives the actuator CCW (opens valve).
B =Closes on temperature drop and drives the actuator CW (closes valve).
Figure-7 TAC Microtherm Controller with 24 Vac Actuators – Standard Wiring Diagram.
Typical TAC Microtherm Controllers: PP-22x Series, TP-2xx Series, TP-3xx Series, TP-4xx Series, and TP-101x Series.C =Common of Switch to R and B.
1 =Feedback from Actuator (12 Vac with Actuator full CCW to 24 Vac at CW end).
R =Closes on temperature (pressure) drop and drives the actuator CW (closes valve).
B =Closes on temperature (pressure) rise and drives the actuator CCW (opens valve).
Figure-8 TAC Microtherm Controller with 24 Vac Actuators – Reversed (Cooling)Wiring Diagram.
4 5 6 7
3 8
2 H
1 GX
Green WiresTo 24 Vac
Power Supply
CaseGround Screw
C
2
R
1
B
CaseGroundScrew
AddJumper
Add Resistor(Supplied With Actuator)
100
4 5 6 7
3 8
2 H
1 GX
Green WiresTo 24 Vac
Power Supply
CaseGround Screw
C
2
R
1
B
CaseGroundScrew
AddJumper
Add Resistor(Supplied With Actuator)
100
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 13
Typical Actuators: MP-465, MP-475, MP-485, MP-486, MP-495, MP-2130-500, MP-2150-500, MP5-2151-500, MP5-4651, MP5-4751, MP-4851, and MP5-4851.
Typical TAC Microtherm Controllers: PP-22x Series, TP-2xx Series, TP-3xx Series, TP-4xx Series, and TP-101x Series.Standard Wiring:
C=Common of Switch to R and B.
1 =Feedback from actuator (24 Vac with actuator full CCW to 12 Vac at CW end).
R =Closes on temperature (pressure) drop and drives the actuator CCW (opens valve).
B =Closes on temperature (pressure) rise and drives the actuator CW (closes valve).
Typical Cooling TAC Microtherm: TP-1031.C =Common of switch to R and B.
1 =Feedback from actuator (24 Vac with actuator full CCW to 12 Vac at CW end).
R =Closes on temperature rise and drives the actuator CCW (opens valve).
B =Closes on temperature drop and drives the actuator CW (closes valve).
Figure-9 External Wiring of TAC Microtherm Controller with Line VoltageActuator – Standard Wiring.
Typical Actuators: MP-465, MP-475, MP-485, MP-486, MP-495, MP-2130-500, MP-2150-500, MP5-2151-500, MP5-4651, MP5-4751, MP-4851, and MP5-4851.
Typical TAC Microtherm Controllers: PP-22x Series, TP-2xx Series, TP-3xx Series, TP-4xx Series, and TP-101x Series.Reversed Wiring:
C =Common of switch to R and B.
1 =Feedback from actuator (12 Vac with actuator full CCW to 24 Vac at CW end).
R =Closes on temperature (pressure) drop and drives the actuator CW (closes valve).
B =Closes on temperature (pressure) rise and drives the actuator CCW (opens valve).
Figure-10 External Wiring of TAC Microtherm Controller with Line Voltage Actuator – Reversed (Cooling) Wiring.
4 5 6 7
3 8
2 L1
1 L2X
Green Wire To ACPower Supply
CaseGround Screw
C
2
R
1
B
Blue
Red
ActuatorTransformerLeads
4 5 6 7
3 8
2 L1
1 L2X
Green Wire To ACPower Supply
CaseGround Screw
C
2
R
1
B
Red
Blue
NOTE: ActuatorTransformer LeadsMust Be Reversed
14 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Typical Actuators: MP-367, MP-377, and MP-387.
Typical TAC Microtherm Controllers: PP-22x Series, TP-2xx Series, TP-3xx Series, TP-4xx Series, and TP-101x Series.C =Common of switch to R and B.
1 =Feedback from actuators (24 Vac with both actuators full CCW to 12 Vac both full CW).
R =Closes on temperature (pressure) drop and drives the actuator CCW (opens valve).
B =Closes on temperature (pressure) rise and drives the actuator CW (closes valve).
Sequence of OperationOn a temperature rise, the controller completes a circuit through B to terminal 2 of actuator number one, causing CW rotation. When actuator number one reaches the CW end of travel, it transfers the control circuit to actuator number two, causing it to rotate CW. Conversely, on a temperature drop, first actuator number two, then actuator number one rotates to CCW end of travel.
Figure-11 External Wiring for TAC Microtherm Controller with 24 Vac Sequencing Actuators.
4 5 6 7
3 8
2 H
1 Gx
Green WiresTo 24 Vac
Power Supply
CaseGround Screw
C
2
R
1
B4 5 6 7
3 8
2 H
1 GX
Green Wires
CaseGround Screw
AddJumper
Add Resistor(Supplied With Actuator)
Splice
100
AddJumper
Actuator Number 1Typical Actuators: MP-367,MP-377, and MP-387
RemoveJumper
Actuator Number 2Typical Actuators: MP-367,MP-377, and MP-387
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 15
Typical TAC Microtherm Controllers: TP-2xx Series, TP-3xx Series, and TP-4xx Series.C =Common of switch to R and B.
1 =Feedback from actuator (24 Vac with actuator full CCW to 12 Vac at CW end).
R =Closes on temperature drop and drives the actuator CCW (closes damper).
B =Closes on temperature rise and drives the actuator CW (opens damper).
Cycle of OperationWith the fan running:
1. Rotates actuator to CCW end (damper closed).
2. Allows actuator to modulate between 33% from CCW end to CW (damper open).
3. Allows actuator to modulate between 50% from CCW end to CW (damper open).
4. Allows actuator to modulate between 67% from CCW end to CW (damper open).
5. Rotates actuator to CW end (damper open).
When the fan is off, the damper is closed.
Figure-12 External Wiring for TAC Microtherm Controller with Five-Position 24 Vac Actuators.
4 5 6 7
3 8
2 H
1 GX
Green WiresTo 24 Vac
Power Supply
CaseGround Screw
C
2
R
1
B
AddJumper
CaseGroundScrew
100
SPDT Relay
To Load ofFan MotorStarter. TheCoil VoltageSame asFan Motor.
Typical Actuators:MP-379 and MP-389
Five-Position Switch
1Close
3 2
5Open
4
Add Resistor(Supplied with Actuator)
16 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Typical TAC Microtherm Controllers: TP-2xx Series, TP-3xx Series, and TP-4xx Series.C =Common of switch to R and B.
1 =Feedback from actuator (24 Vac with actuator full CCW to 12 Vac at CW end).
R =Closes on temperature drop and drives the actuator CCW (closes damper).
B =Closes on temperature rise and drives the actuator CW (opens damper).
Cycle of OperationWith the fan running:
1. Rotates actuator to CCW end (damper closed).
2. Allows actuator to modulate between 33% from CCW end to CW (damper open).
3. Allows actuator to modulate between 50% from CCW end to CW (damper open).
4. Allows actuator to modulate between 67% from CCW end to CW (damper open).
5. Rotates actuator to CW end (damper open).
When the fan is off, the damper is closed.
Figure-13 External Wiring for TAC Microtherm Controller with Five-Position Line Voltage Actuator.
4 5 6 7
3 8
2 L1
1 L2X
Green Wire To ACPower Supply
CaseGround Screw
C
2
R
1
B
Blue
SPDT Relay
To Load ofFan MotorStarter. TheCoil VoltageSame asFan Motor.
Typical Actuators:MP-470, MP-480, and MP-4701
Five-Position Switch
1Close
3 2
5Open
4
Red
ActuatorTransformer Leads
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 17
Typical Actuators which require AE-504 purchased separately: MP-361, MP-371, MP-382, and MP-2113-500.
Figure-14 External Wiring for Slidewire Controller with 24 Vac Actuators.
Typical Actuators which require AE-504 purchased separately: MP-465, MP-475, MP-483, MP-485, MP-486, MP-495, MP-2130-500, MP-2150-500, MP5-4651, MP5-4751, MP-4851, MP5-4851.
Figure-15 External Wiring for Slidewire Controller with Line Voltage Actuator.
4 5 6 7
3 8
2 H
1 GX
Green
To 24 VacPower Supply
CaseGround Screw
AddJumper
CCW CW
COM
Br / Yel
Black
680
680
50Blue / Blk
Red / BlkBrown
AE-504Paralleling Relay
Yel / Blk
Controlling potentiometer: 135 Ω 1.5 watts min.: 1,000 Ω 3 watts min., or AM-332 Actuator Potentiometer Kit.
Wires
1
1 Direction in which actuator will drive.
2 Install two 680 Ω resistors and one 50 Ω resistor. Supplied AE-504.
1
2
4 5 6 7
3 8
2 L1
1 L2X
Green WireTo AC
Power Supply
CaseGround Screw
ActuatorTransformer
CCW CW
COM
Br / Yel
Black
680
680
Blue / Blk
Red / BlkBrown
AE-504Paralleling Relay
Yel / Blk
BlueRed Leads
Controlling potentiometer: 135 Ω 1.5 watts min.: 1,000 Ω 3 watts min., or AM-332 Actuator Potentiometer Kit.
*DirectionActuatorWill Drive
1
21 Direction in which actuator will drive.
2 Install two 680 Ω resistors. Supplied AE-504.
1
18 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Typical Actuators which require CP-8301-120 purchased separately: MP-421, MP-422, MP-423, MP-424, MP-451, MP-452, MP-454.
Typical Actuators with CP-8301-120 factory installed and wired: MP-461-600, MP-471-600, MP-481-600, MP-2110-601.
Note: CP-8301-120 is marked CP-8301-620 on factory assemblies.
Figure-16 External Wiring for CP-8301-120, Vdc Interface with Line VoltageActuators without Internal Transformer.
4 5 6 7
3 8
2 L1
1 L2X
Green Wire
CaseGround Screw
CP-8301-120Solid State
Actuator Drive(Vdc InputSignal with3 Vdc FixedSpan and
2 to 12 VdcAdjustableStart Point
Blue (-, Common)
Yellow (+, Input Signal)
Red (+20 Vdc,50 mA Power Supply)
Yellow / BlackBlue / BlackRed / Black
Brown
Brown / White
Brown / Black
Black
White
To ACPower Supply
1
1 The Blue wire on the CP-8301-120 is grounded. To unground the Blue wire, remove the Green jumper wire between terminal x and the case ground screw.
2 The actuator rotates clockwise on an increasing Vdc input signal between Blue (-, Common) and Yellow (+). To rotate the actuator counterclockwise on an increase in input signal, reverse the Blue/Black and Red/Black leads and reverse the Brown/Black and Brown/White leads.
3 Whenever it is not connected, tape off the red power supply lead from the CP-8301-120 actuator drive.
2
1
Red
Yellow
Blue
+20
OP
COM
TypicalControllers
Yellow
Blue
AO
COM
SH
Typical DDCControllers
3
CP-8102SLC-8xxxTP-8xxx
To Controller(Below)
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 19
Typical Actuators which require CP-8301-024 purchased separately: MP-361, MP-371, MP-381, MP-382, MP-2113-500.
Figure-17 External Wiring for CP-8301-024, Vdc Interface with 24 Vac Actuators.
4 5 6 7
3 8
2 H
1 GX
Green Wires
CaseGround Screw
Yellow / BlackBlue / BlackRed / Black
Brown
Brown / White
Brown / Black
Black / Blue
Black
To 24 VacPower Supply
1
1 The Blue wire on the CP-8301-024 is grounded. To unground the Blue wire, remove the Green jumper wire between terminal X and the case ground screw.
2 The actuator rotates clockwise on an increasing Vdc input signal between Blue (-, Common) and Yellow (+). To rotate the actuator counterclockwise on an increase in input signal, reverse the Blue/Black and Red/Black leads and reverse the Brown/Black and Brown/White leads.
3 Whenever it is not connected, tape off the red power supply lead from the CP-8301-024 actuator drive.
2
CP-8301-024Solid State
Actuator Drive(Vdc InputSignal with3 Vdc FixedSpan and
2 to 12 VdcAdjustableStart Point
Blue (-, Common)
Yellow (+, Input Signal)
Red (+20 Vdc,50 mA Power Supply)
1
Red
Yellow
Blue
+20
OP
COM
TypicalControllers
Yellow
Blue
AO
COM
SH
Typical DDCControllers
3
CP-8102SLC-8xxxTP-8xxx
To Controller(Below)
20 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Typical Actuators which require CP-8301-120 purchased separately: MP-465, MP-475, MP-483, MP-485, MP-486, MP495, MP-2130-500, MP-2150-500.
Typical Actuators which require CP-8301-240 purchased separately: MP5-2151-500, MP5-4651, MP5-4751, MP-4851, MP5-4851.
Figure-18 External Wiring for CP-8301-120 and CP-8301-240, Vdc Interface with Line VoltageActuators with Internal Transformer.
4 5 6 7
3 8
2 L1
1 L2X
Green Wire
CaseGround Screw
Yellow / BlackBlue / BlackRed / Black
Brown
Brown / WhiteBrown / Black
Black
To ACPower Supply
White (CP-8301-120, 120 Vac)White / Black (CP-8301-240, 240 Vac)
TapeRed
Blue
1
1 The Blue wire on the CP-8301-120 and CP-8301-240 is grounded. To unground the Blue wire, remove the Green jumper wire between terminal X and the case ground screw.
2 The actuator rotates clockwise on an increasing Vdc input signal between Blue (-, Common) and Yellow (+). To rotate the actuator counterclockwise on an increase in input signal, reverse the Blue/Black and Red/Black leads, and reverse the Brown/Black and Brown/White leads.
3 Remove Red and Blue actuator transformer leads from actuator terminals 7 and 8 and tape the leads off. On older actuators, remove back cover of actuator and cut and tape the leads from the transformer to the feedback transformer.
4 Whenever it is not connected, tape off the red power supply lead from the CP-8301-120 or CP-8301-240 actuator drive.
2
Blue (-, Common)
Yellow (+, Input Signal)
Red (+20 Vdc,50 mA Power Supply)
1
CP-8301-120(120 Vac)
CP-8301-240(240 Vac)Solid State
Actuator Drive(Vdc Input Signalwith 3 Vdc Fixed
Span and2 to 12 Vdc
Adjustable StartPoint
3
Red
Yellow
Blue
+20
OP
COM
TypicalControllers
Yellow
Blue
AO
COM
SH
Typical DDCControllers
4
CP-8102SLC-8xxxTP-8xxx
To Controller(Below)
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 21
Typical Actuators which require CP-8391-913 purchased separately: MP-361, MP-371, MP-381, MP-382, MP-2113-500.
Figure-19 External Wiring for CP-8391-913, 4 to 20 mAdc Interface with 24 Vac Actuators.
Typical Actuators which require CP-8391-910 purchased separately: MP-421, MP-422, MP-424, MP-451, MP-452, MP-453, MP-454.
Figure-20 External Wiring for CP-8391-910, 4 to 20 mAdc Interface with Line Voltage Actuators without Internal Transformer.
4 5 6 7
3 8
2 H
1 GX
Green Wires
CaseGround Screw
Blue (-)4 to 20 mAdc
Controller Input
Yellow / BlackBlue / BlackRed / Black
Brown
Brown / White
Brown / BlackCP-8391-913
Solid StateActuator Drive(4 to 20 mAdcNonadjustable
Range)Black
To 24 VacPower Supply
Orange (+)
Black / Blue
1
1 The Blue wire on the CP-8391-913 is grounded. To unground the Blue wire, remove the Green jumper wire between terminal x and case ground screw.
2 The actuator rotates clockwise on an increasing mAdc input signal between Blue (-) and Orange (+). To rotate the actuator counterclockwise on an increase in input signal, reverse Blue/Black and Red/Black leads and reverse Brown/Black and Brown/White leads.
2
1
4 5 6 7
3 8
2 L1
1 L2X
Green Wire
CaseGround Screw
Blue (-)4 to 20 mAdc
Controller Input
Yellow / BlackBlue / BlackRed / Black
Brown
Brown / White
Brown / BlackCP-8391-910
Solid StateActuator Drive(4 to 20 mAdcNonadjustable
Range)Black
To 120 VacPower Supply
Orange (+)
White
1
2
1
1 The Blue wire on the CP-8391-910 is grounded. To unground the Blue wire, remove the Green jumper wire between terminal x and case ground screw.
2 The actuator rotates clockwise on an increasing mAdc input signal between Blue (-) and Orange (+). To rotate the actuator counterclockwise on an increase in input signal, reverse Blue/Black and Red/Black leads and reverse Brown/Black and Brown/White leads.
22 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Typical Actuators which require CP-8391-910 purchased separately: MP-465, MP-475, MP483, MP-485, MP-486, MP-495, MP-2130-500, MP-2150-500.
Figure-21 External Wiring for CP-8391-910 and CP-8391-911, 4 to 20 mAdc Interface with Line Voltage Actuators with Internal Transformer.
Typical Actuators which require CP-8391-716 purchased separately: MP-421, MP-422, MP-423, MP-424, MP-451, MP-452, MP-453, MP-454.
Figure-22 External Wiring for CP-8391-716, mAdc Interface with Line Voltage Actuators without Internal Transformer.
4 5 6 7
3 8
2 L1
1 L2X
Green Wire
CaseGround Screw
Blue (-)4 to 20 mAdc
Controller Input
Yellow / BlackBlue / BlackRed / Black
Brown
Brown / White
Brown / Black
CP-8391-910(120 Vac)
Solid StateActuator Drive(4 to 20 mAdcNonadjustable
Range)
Black
To ACPower Supply
Orange (+)
TapeRed
Blue
White
1
2
1
1 The Blue wire on the CP-8391-910 is grounded. To unground the Blue wire, remove the Green jumper wire between terminal x and case ground screw.
2 The actuator rotates clockwise on an increasing mAdc input signal between Blue (-) and Orange (+). To rotate the actuator counterclockwise on an increase in input signal, reverse Blue/Black and Red/Black leads and reverse Brown/Black and Brown/White leads.
3 Remove Red and Blue actuator transformer leads from actuator terminals 7 and 8 and tape the leads off. On older actuators, remove back cover of actuator and cut and tape the leads from the transformer to the feedback transformer.
3
4 5 6 7
3 8
2 L1
1 L2X
Green Wire
CaseGround Screw
Black (-)To mAdc
Controller Input
Red / YellowWhite / BlueBlack / Blue
Brown
Orange
Yellow
CP-8391-716Solid State
Actuator Drive(mAdc Input;
Span Adj. 4 to 16Factory Set 16,
Start PointAdj. 2 to 16
Factory Set 4)
Blue (120 Vac)
To 120 VacPower Supply
Red (+)
Black / White (240 Vac)Tape
Violet (Com)
1
1 The actuator rotates clockwise on an increasing mAdc input signal between Black (-) and Red (+). To rotate the actuator counterclockwise on an increase in input signal, reverse Blue/Black and White/Blue leads and reverse Orange and Yellow leads.
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 23
Typical 120 Vac Actuators which require CP-8391-716 purchased separately: MP-465, MP-475. MP-483, MP-485, MP-486, MP-495, MP-2130-500, MP-2150-500.
Typical 240 Vac Actuators which require CP-8391-716 purchased separately: MP5-2151-500, MP5-4651, MP5-4751, MP-4851, MP5-4851.
Figure-23 External Wiring for CP-8391-716, mAdc Interface with Line Voltage Actuators with Internal Transformer.
Typical Actuators: MP-361, MP-371, MP-381, and MP-382.
Figure-24 Internal Wiring for 24 Vac Actuator.
4 5 6 7
3 8
2 L1
1 L2X
Green Wire
CaseGround Screw
Black (-)To mAdc
Controller Input
Red / YellowWhite / BlueBlack / Blue
Brown
Orange
Yellow
CP-8391-716Solid State
Actuator Drive(mAdc Input;
Span Adj. 4 to 16Factory Set 16,
Start PointAdj. 2 to 16
Factory Set 4)
Blue (120 Vac)Black / White (240 Vac)
Tape Unused Wire
To ACPower Supply
Red (+)
TapeRed
Blue
Violet (Com)
1
1 The actuator rotates clockwise on an increasing mAdc input signal between Black (-) and Red (+). To rotate the actuator counterclockwise on an increase in input signal, reverse Black/Blue and White/Blue leads and reverse Orange and Yellow leads.
2 Remove Red and Blue actuator transformer leads from actuator terminals 7 and 8 and tape the leads off. On older actuators, remove back cover of actuator and cut and tape the leads from the transformer to the feedback transformer.
2
H
8
7
6
5
4
3
2
1
X
GFieldCoil
Motor
CW CCW
CWCCW
ShadingCoils
100 ΩInternal
Potentiometer
CCW
CW
Limit Switches
AuxiliarySwitch
CaseScrew
GreenWire Green Case
Ground Screw
Green
CaseScrew
2
2Wire
1
1 Used for field grounding.
2 External green jumpers from terminals X and G to case ground is only available on current MP-xxx-xxx-x-2 models.
24 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Typical Actuators: MP-421, MP-422, MP-423, MP-424, MP-451, MP-452, MP-453, MP-454, MP-461-600, MP-471-600, and MP-481-600.
Figure-25 Internal Wiring for Line Voltage Actuators.
Typical Actuators: MP-465, MP-475, MP-483, MP-486, MP-495, MP5-4651, MP5-4751, MP-4851, and MP5-4851.
Figure-26 Internal Wiring for Line Voltage Actuator with Built-in Transformer.
L1
8
7
6
5
4
3
2
1
X
L2
Motor
CW CCW
CWCCW
ShadingCoils
100 ΩInternal
Potentiometer
CCW
CW
Limit Switches
AuxiliarySwitch
CaseScrew
GreenWire
Green CaseGround Screw
Field Coil
2 1
1 Used for field grounding.
2 External green jumper from terminal X to case ground is only available on current MP-xxx-xxx-x-2 models.
L1
8
7
6
5
4
3
2
1
X
L2
Motor
CW CCW
CWCCW
ShadingCoils
100 ΩInternal
PotentiometerCCW
CW
Limit Switches
AuxiliarySwitch
CaseScrew
GreenWire
InternalTransformer
0 Vac
Blue12 Vac
24 Vac
Red
FieldCoil
Green CaseGround Screw2 1
1 Used for field grounding.
2 External green jumper from terminal x to case ground is only available on current MP-xxx-xxx-x-2 models.
3 On models prior to current MP-xxx-xxx-2-x the Red and Blue transformer leads were wired directly to potentiometer.
3
3
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 25
Typical Actuator: MP-2113-500.
Figure-27 Internal Wiring for 24 Vac Actuator without Limit Switches (Actuator is Stall Type with Built-in Mechanical Stops).
Typical Actuator: MP-2110-600.
Figure-28 Internal Wiring for Line Voltage Actuators without Limit Switches (Actuator is Stall Type with Built-inMechanical Stops.)
H
8
7
6
5
4
3
2
1
X
G
Motor
CW CCW
CWCCW
ShadingCoils
100 ΩInternal
Potentiometer
CCW
CW
AuxiliarySwitch
CaseScrew
GreenWire
FieldCoil
Green CaseGround Screw
Case ScrewGreen
2
1
1 Used for field grounding.
2 External green jumpers from terminals X and G to case ground is only available on current MP-xxx-xxx-x-2 models.
Wire
2
L1
8
7
6
5
4
3
2
1
X
L2
Motor
CW CCW
CWCCW
ShadingCoils
100 ΩInternal
Potentiometer
CCW
CW
AuxiliarySwitch
CaseScrew
GreenWire
Green CaseGround Screw
Field Coil
1
1 Used for field grounding.
2 External green jumper from terminal X to case ground is only available on current MP-xxx-xxx-x-2 models.
2
26 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Typical Actuators: MP-2130-500, MP-2150-500, MP5-2151-500.
Figure-29 Internal Wiring for Line Voltage Actuators without Limit Switches and Built-in Transformer(Actuator is Stall Type with Built-in Mechanical Stops).
Typical Actuators: MP-379 and MP-389.
Figure-30 Internal Wiring for 24 Vac Five-Position Actuators.
L1
8
7
6
5
4
3
2
1
X
L2
Motor
CW CCW
CWCCW
ShadingCoils
100 ΩInternal
PotentiometerCCW
CW
AuxiliarySwitch
CaseScrew
GreenWire
InternalTransformer
0 Vac
Blue
12 Vac
24 Vac
Red
FieldCoil
Green CaseGround Screw
21
1 Used for field grounding.
2 External green jumper from terminal X to case ground is only available on current MP-xxx-xxx-x-2 models.
3 On models prior to current MP-xxx-xxx-2-x the Red and Blue transformer leads were wired directly to potentiometer.
3
3
H
8
7
6
5
4
3
2
1
X
G
Motor
CW CCW
CWCCW
ShadingCoils
100 ΩInternal
Potentiometer
CCW
CW
CaseScrew
GreenWire
FieldCoil
Limit Switches
Green CaseGround Screw
Case Screw
GreenWire
1
1 Used for field grounding.
2 External green jumpers from terminals X and G to case ground is only available on current MP-xxx-xxx-x-2 models.
2
2
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 27
Typical Actuators: MP-470, MP-480, and MP-4701.
Figure-31 Internal Wiring for LIne Voltage Five-Position Actuators.
Typical Actuators: MP-367, MP-377, and MP-387.
Figure-32 Internal Wiring for 24 Vac Sequencing Actuators.
L1
8
7
6
5
4
3
2
1
X
L2
Motor
CW CCW
CWCCW
ShadingCoils
100 ΩInternal
PotentiometerCCW
CW
CaseScrew
GreenWire
InternalTransformer
0 Vac
Blue
12 Vac
24 Vac
Red
FieldCoil
Limit Switches
Green CaseGround Screw2 1
1 Used for field grounding.
2 External green jumper from terminal X to case ground is only available on current MP-xxx-xxx-x-2 models.
3 On models prior to current MP-xxx-xxx-2-x the Red and Blue transformer leads were wired directly to potentiometer.
3
3
H
8
7
6
5
4
3
2
1
X
G
Motor
CW CCW
CWCCW
ShadingCoils
50 ΩInternal
Potentiometer
CCW
CW
AuxiliarySwitch
CaseScrew
GreenWire
FieldCoil
Limit Switches
Green CaseGround Screw
Case ScrewGreenWire
1
1 Used for field grounding.
2 External green jumpers from terminals X and G to case ground is only available on current MP-xxx-xxx-x-2 models.
2
2
28 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Figure-33 Internal View of a Typical Actuator.
INSTALLATION
Inspection Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products.
Requirements • Wiring diagrams• Tools (not provided):
– Digital volt-ohm meter (DVM)– Appropriate screwdriver(s) for cover, and mounting screws– Appropriate drill and drill bit for mounting screws– Appropriate wrenches for adjustment of damper and valve linkages– TOOL-201, Calibration kit for TAC System 8000 (Vdc)– TOOL-209, 135 Ω slidewire and 0 to 7 mA manual positioner
• Appropriate accessories• Mounting screws (not provided)• Wire nuts (not provided)• Training: Installer must be a qualified, experienced technician
Warning: • Disconnect the power supply (line power) before installation to prevent electrical shock
and equipment damage.• Make all connections in accordance with the wiring diagram and in accordance with
national and local electrical codes. Use copper conductors only.
Caution: • Do not exceed the ratings of the device(s).• Do not apply power to the unit unless the damper linkage and/or the valve assembly
have been installed.• Avoid locations where excessive moisture, corrosive fumes, or vibration is present.• Do not install insulation on any part of the actuator.
TerminalBlockLimit & Aux.
Switch Block
DriveDisc
CamsMotor &
Pinion Assy.
GearTrain
LimitSwitches
Aux. SwitchAdj. Disk
PotentiometerWiper Arm
Feed-ThroughTerminal Block
PotentiometerResistance Card
SpeedAdjustment(Optional)
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 29
European Standard EN 55022Refer to Table-2 and Table-3 to identify applicable models.
Warning: This is a Class A (European Classification) product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
MOUNTINGPreferred mounting is with the actuator in an upright position in a weather protected area.
Note: The MP-21xx series requires upright mounting. The adjustable speed actuators cannot be mounted upside down, with the output shaft up or with speed adjustment screw pointing up.
It is recommended that valve actuators be mounted above the centerline of the valve body. When selecting a location, allow sufficient room for accessories and for service of the product.
Direction of Actuator RotationAll references to the direction of actuator rotation are based on looking at the front of the actuator, where the splined output shaft extends from the front case of the actuator.
Linkage Assembly Damper
Caution: The damper must not stop the actuator before it has reached its electrical limit of travel or permanent damage can occur to the actuator.
1. During installation of the linkage assembly, the actuator should be powered and be able to be controlled manually.
2. Mount the actuator in an appropriate position near the damper. Refer to Figure-35. Actuators must be linked to the damper so that it can complete its full stroke. Damper rod that is too long is not rigid enough for good control and damper rod that is too short makes it difficult to adjust the linkage.
3. Attach a balljoint to the actuator and damper crank arms at the correct position in the crank arm slot depending on the application. Refer to Figure-34, Table-7, and Table-8 for application settings. The use of 180° rotation damper actuators provides the best close-off at the end of stroke and the best controllability (turn down ratio).
4. Typically the damper should be linked for an angular rotation of less than 90° that provides the required flow (typically 60°). This provides the optimum close-off and controllability.
Table-7 Balljoint Position on Actuator and Damper Crank Arms with 180 Degree Rotation Actuators.
Desired Damper Rotation Balljoint Position on Actuator Crank Arm
Balljoint Position on Damper Crank Arm
90° Prick Point (2-1/4") End of Slot (3-1/8")
80° 2" End of Slot (3-1/8")
70° 1-3/4" 3"
60° 1-1/2" 3"
30 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Table-8 Balljoint Positioning Actuator and Damper Crank Arms with 90 Degree Rotation Actuators.
Figure-34 Proper Balljoint Position on Crank Arm.
5. With the actuator powered, manually position the actuator to the position that is required for the closed position of the damper. Rotate the damper to its midstroke position. Referring to Figure-36, install the crank arms on the damper shaft and the actuator so that crank arms are parallel. The crank arm on damper shaft should be secured to the shaft and the crank arm on the actuator should be free to rotate.
6. Attach the push rod to the ball joint connectors on both crank arms and tighten the ball joint screws only thumb tight.
7. Rotate by hand the crank arm on the actuator to drive the linkage and the damper shaft through its full stroke to ensure proper damper action.
8. Return the damper to its closed position and tighten to secure the actuator crank arm.
9. While pushing the damper closed, tighten the ball joint screws to secure the damper rod.
10. Run the actuator back and forth through its full stroke and check for proper damper and linkage operation. Adjust the linkage if required.
Caution: If the crank arm does not provide proper travel, reset the linkage. Never attempt to turn the actuator shaft with a wrench or a crank; this may damage the actuator.
Figure-35 Typical Actuator Mounting Positions.
Desired Damper Rotation Balljoint Position Actuator Crank Arm
Balljoint Position Damper Crank Arm
90° End of Slot (3-1/8") End of Slot (3-1/8")
80° 2-3/4" 3"
70° 2-1/2" 3"
60° Prick Point (2-1/4") End of Slot (3-1/8")
1 2 3
Prick Point
Slot Provides AdjustmentFrom 7/8" to 3-1/8"
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 31
Figure-36 Typical Damper Linking with 180 Degree or 90 Degree Rotation Actuator.
ValveFor the correct installation of valve linkages, refer to the ACCESSORIES section for form numbers of the appropriate linkage instruction sheets.
90° RotationDamper
Install Ball Jointat Prick Pointon Crank Arm
180° RotationActuator
Typical of Actuator and Damper Rotating in Same Direction
Install Ball Jointat End of Crank Arm
Install Ball Jointat Prick Pointon Crank Arm
180° RotationActuator
90° RotationDamper
= Ball Joint
= Crank Arm Open Position
= Crank Arm Mid-Position
= Crank Arm Closed Position
in Different Directions
Install Ball Jointat End of Crank Arm
Typical of Actuator and Damper Rotating
90° RotationDamper
90° RotationActuator
Typical of Actuator and Damper Rotating in Same Direction
Install Ball Jointat End of Crank Arm
90° RotationActuator
90° RotationDamper
= Ball Joint
= Crank Arm Open Position
= Crank Arm Mid-Position
= Crank Arm Closed Position
Typical of Actuator and Damper Rotatingin Different Directions
Install Ball Jointat End of Crank Arm
180 Degree Rotation Actuator 90 Degree Rotation Actuator
32 © Copyright 2007 TAC All Rights Reserved. F-15479-8
WIRINGThe wiring connectors are made to coded screw terminals. Actuators with “-600” suffixes also have 6" (152 mm) color coded leads for control circuit.
Hazardous Location Models
Hazardous Location Models Make all electrical connections to the assembly in accordance with the job wiring diagram, the National Electric Code Article 500, and in compliance with the local electrical codes.
Two 3/4" pipe tapped openings are provided in the housing for rigid conduit connections. It is recommended to insert a chase nipple from inside of the housing to prevent threads from cutting or damaging wiring.
When wiring, take care to lay all leads in the wiring channel located just under the housing cover to protect the leads from any sharp edges which may be in the vicinity.
The housing and the edge of the cover are stamped with the letter "O." When replacing the cover, the letters must be aligned with each other.
Warning: • The cover-to-housing orientation must be maintained in order to preserve the integrity
of the seal. Failure to observe this warning can result in injury or death.• Do not scrape, scratch, or use abrasives on the machined surfaces.• Ensure the surfaces are clean.• Use only the approved compounds listed in the note below.• If an additional device, such as a drive, is to be installed it must be mounted in the safe
area or enclosed in a separate hazardous location housing.
1. Remove twelve cover screws and cover. Place cover, machined surface up, in a protected location to avoid damage to machined surfaces.
2. Make all wiring connections to actuator taking care to lay all leads in the wiring channel provided.
3. Before enclosing the actuator, wipe machined surfaces of housing clean with a lint free cloth and apply one of the UL approved compounds. See Note below.
4. Secure cover tight against the enclosure in the same position before removal with the twelve screws provided.
5. Refer to Figure-3 thorough Figure-32 for correct model and application wiring.
Note: Underwriters Laboratories has sanctioned the use of the following compounds on hazardous location ground joints: Crouse-Hinds type OSL lubricant, Crouse-Hinds type STL lubricant, or "No-OXID" oil, grade "D."
Two 1/2" conduit knockouts are provided on the actuator case.
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 33
Power Wiring All actuators include a barrier that separates the power wiring compartment from the low voltage wiring compartment. Refer to Table-9 for allowable circuit class for the two wiring compartments.
Table-9 Actuator Circuit Class.
Refer to Table-10 for selection of proper gage wire for the length of wire run (one run has two wires).
Table-10 Power Wire Selection.
When multiple 24 Vac actuators are powered from the same transformer, the actuators must be in phase. Connect the same transformer lead to the “G” terminal on all actuators and same transformer lead to the “H” terminal on all actuators.
Typical Part Numbers Actuator Description
Power Wiring Compartment Low Voltage Wiring Compartment
Terminals (Function) Circuit Class for Power Wiring Compartment Terminals (Function)
Circuit Class for Low
Voltage Wiring Compartment
MP-361, MP-371, MP-381, MP-382,
MP-2113-500
Low Voltage Proportional
H&G (24 Vac Power) 1, 5, and 6
(Auxiliary Switch)
1.May be Class 2 circuit if auxiliary switch is wired to 24 Vac or is not used.
2.Must be Class 1 circuit if auxiliary switch is wired to line voltage.
X, 2, and 3 (Control Circuit)
4, 7, and 8 (Potentiometer)
May be Class 2 Circuit.
MP-421, MP-422, MP-423, MP-424, MP-451, MP-452, MP-453, MP-454,
MP-461-600, MP-465, MP-471-600, MP-475, MP-481-600, MP-483,
MP-485, MP-486, MP-495, MP-2150-500, MP5-4651, MP5-4751, MP-4851, MP5-4851
Line Voltage Proportional
L1 and L2 (Line Voltage Power)
1, 5, and 6 (Auxiliary Switch)
Must be Class 1 circuit.
X, 2, and 3 (Control Circuit)
4, 7, and 8 (Potentiometer)
May be Class 2 Circuit.
MP-367, MP-377, MP-387
Low Voltage Sequencing
H&G (24 Vac Power) 1, 5, and 6
(Control Switches)May be Class 2 Circuit.
X, 2, and 3 (Control Circuit)
4, 7, and 8 (Potentiometer)
May be Class 2 Circuit.
MP-379, MP-389 Low Voltage Five-Position
H&G (24 Vac Power) 6, 7, and 8
(Potentiometer)May be Class 2 Circuit. X, 1, 2, 3, 4, 5
(Control Circuit)May be Class 2
Circuit.
MP-470, MP-480, MP-4701
Line Voltage Five-Position
H&G (24 Vac Power) 6, 7, and 8
(Potentiometer)Must be Class 1 Circuit. X, 1, 2, 3, 4, 5
(Control Circuit)May be Class 2
Circuit.
Actuator Series Voltage Wire Size(AWG)
MaximumRun ft. (m)
MP-36x, MP-37x 24 Vac141210
115 (35)180 (55)285 (87)
MP-38x 24 Vac141210
130 (40)205 (62)325 (99)
MP-42xMP-445-304
MP-45x120 Vac
141210
810 (247)1275 (388)2040 (622)
MP-46xMP-47xMP-48x
120 Vac141210
1050 (320)1660 (506)2650 (808)
MP-4xx1 240 Vac 14 3340 (1018)
34 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Control Wiring Refer to Figure-3 through Figure-23 for typical wiring of the actuators. Refer to the actuator selection tables beginning on page 3, for an index of External Wiring Figures versus actuator models and control signals. The requirements for the field control wiring are shown below.
SPST Control SignalRefer to Figure-3 and Figure-4. Since the SPST switch is controlling the power to the actuator, the control wiring is limited to the power wiring shown above.
SPDT Control SignalRefer to Figure-5 and Figure-6. Use 18 gage wire for runs up to 1,000 ft. (305 m) between the actuator and the SPDT switch. Use larger gage wires on longer runs.
TAC Microtherm ControlRefer to External Wiring Figure-7 through Figure-13. Use 18 gage wire for runs up to 1,000 ft. (305 m) between the actuator and the TAC Microtherm controller. Use larger gage wires on longer runs.
135 to 1000 Ω Slidewire ControlRefer to External Wiring Figure-14 and Figure-15. Use 18 gage three-conductor twisted leads (part number W-103 or equal) for runs up to 500 ft. (152 m) between the actuator and the slidewire controller. Use larger gage wires for longer runs.
Voltage Vdc (TAC System 8000) ControlRefer to External Wiring Figure-16 through Figure-18. Use 18 gage three-conductor twisted leads (part number W-103 or equal) for runs up to 1,000 ft. (305 m) between the actuator and the Vdc (TAC System 8000) controller. Use larger gage wires for longer runs.
Caution: Use 18 gage three-conductor shielded cable (twisted) when it is necessary to install the control leads in the same conduit with power wiring, or when high RFI/EMI generating devices are near. Do not connect the shield to earth ground or any leads or terminals.
Current mAdc ControlRefer to External Wiring Figure-19 through Figure-23. Use 18 gage two-conductor twisted leads (part number W-102 or equal) for runs up to 500 ft. (152 m) between the actuator and the slidewire controller. Use larger gage wires for longer runs.
Direct Digital Control (DDC)DDC controllers may be used to control these actuators according to one of the methods described below.
SPST Control
Refer to External Wiring Figure-5 and Figure-6. Requires two digital output points programmed as a drive open, drive closed configuration. The digital output must be rated for switching 0.9 amp at 24 Vac.
Voltage Vdc Control
Refer to External Wiring Figure-16, Figure-17, and Figure-18. Requires an analog output from the DDC controller, programmed to provide the desired voltage range. Also requires a CP-8301-120 electronic actuator drive between the DDC controller and the actuator.
Current mAdc Control
Refer to External Wiring Figure-19, Figure-20, and Figure-21. Requires an analog output from the DDC controller, programmed to provide the desired current range (usually 4 to 20 mA). Also requires a CP-8391-913 electronic actuator drive between the DDC controller and the actuator.
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 35
ADJUSTMENTS
Limit Switch Adjustment
The counterclockwise limit switch on certain actuators provides adjustable travel of 45° to 320° rotation. The actuator selection tables beginning on page 3 identify the models that have adjustable travel limits. To adjust travel refer to Figure-37 and Figure-38 while following the steps shown below.
Note: The feedback potentiometers in the actuator have a fixed rotation (typically either 90° or 180°). Therefore, adjusting the travel of the actuator could affect the feedback to the controller. The potentiometer has a slip clutch and will not be damaged by adjusting the actuator travel. If the actuator travels beyond the limit of the potentiometer, the wiper arm on the potentiometer will cease to rotate. The wiper arm will instantly start moving in the opposite direction as soon as the actuator reverses direction.
1. Remove the top cover from the actuator and disconnect the field wiring from terminals, X, 2, and 3 of the actuator.
2. The actuator should be powered and driven to its CW limit by shorting terminal X to terminal 2. Refer to Figure-37.
Figure-37 Actuator Output Shaft Position (Front View).
3. The access hole for the travel adjustment is located in the top plate of the actuator directly ahead of terminal block in the front of the actuator (where output shaft extends from actuator). Refer to Figure-38.
Short Tooth onShaft at 9:00
Short Tooth onShaft at 3:00
Full CW Position Full CCW Position*
180° Rotation Actuator
90° Rotation Actuator
Full CW Position Full CCW Position*
Short Tooth onShaft at 6:00
Short Tooth onShaft at 9:00
*On Certain Models the CCW TravelLimit is Adjustable from 45 to 320°
36 © Copyright 2007 TAC All Rights Reserved. F-15479-8
4. Insert a screwdriver through the access hole and engage the notched cam nearest the front of the actuator.
Figure-38 Limit Switch Adjustment.
5. Turning the cam CW (as seen from the front of the actuator) increases the length of the actuator rotation. Each click of the cam represents about a 3° change in actuator rotation.
6. After adjusting the cam, check the rotation of the actuator by shorting actuator terminal x to terminal 3 to drive the actuator to its new CCW limit setting.
7. If the travel is not what is desired, repeat steps 2 through 6 until desired results are obtained.
Auxiliary Switch Adjustment
Refer to the actuator selection tables beginning on page 3 for the actuators that include an auxiliary switch. The adjustable SPDT auxiliary switch is actuated by the cam nearest the back of the actuator. It is factory set to switch near the CW end of actuator rotation. Terminal 1, the common of the switch, is made to terminal 5, from the CCW end of rotation until the switch point, then terminal 1 is made to terminal 6 for rest of the stroke.
Note: The auxiliary switch is made from terminal 1 to terminal 5 when the switch follower is on the low part of the cam, and from terminal 1 to terminal 6 when the switch follower is on the lobe of the cam.
To adjust the switch point of the auxiliary switch, follow the steps shown below.
Note: If the actuator travel has been increased beyond 180°, the auxiliary switch may, depending on its switch point, operate twice in the actuator stroke.
1. Remove the top cover of the actuator.
2. The actuator should be powered and positioned to desired point in actuator stroke for the auxiliary switch to operate.
3. The access hole for the auxiliary switch adjustment is located in top plate of the actuator directly ahead of the terminal block in the back of the actuator. Refer to Figure-39. Actuators manufactured after 1976 have plastic funnel shield inserted in the access hole.
Caution: Disconnect the power to the actuator at the power terminals (H and G or L1 and L2) plus the auxiliary switch terminals (1, 5, and 6). More than one disconnect may be required.
AccessHole
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 37
4. Insert a screwdriver through the plastic funnel shield, if present, and through the access hole, engaging the screwdriver with the gear-like plastic disc.
Figure-39 Auxiliary Switch Adjustment (Rear View with Top and Back Coversof Actuator Removed).
5. Turning the disc CW (as viewed from the front of the actuator) causes the switch to operate nearer to the CCW end of actuator rotation. Each click of the cam represents about a 3° change in the switch point.
6. Adjust the disc so that the switch just operates.
Speed Adjustment The actuator selection tables beginning on page 3 list the actuators that are adjustable speed. The timing of the adjustable speed actuators is varied by a slotted adjustment screw on the lower left side of the front housing. Refer to Figure-40. Turning the screw CW decreases the speed. Total timing can be increased to about ten times the normal. Take care not to turn the adjustment screw too far CW as this will stall, but not damage, the actuator. If stalling occurs, turn the screw CCW until the actuator resumes operation. The total adjustment is normally 3-1/2 turns on the adjustment screw.
Figure-40 Speed Adjustment Location.
TerminalBlockLimit & Aux.
Switch Block
DriveDisc
CamsMotor &
Pinion Assy.
GearTrain
LimitSwitches
Aux. SwitchAdj. Disk
PotentiometerWiper Arm
Feed-ThroughTerminal Block
PotentiometerResistance Card
SpeedAdjustment(Optional)
38 © Copyright 2007 TAC All Rights Reserved. F-15479-8
CHECKOUTAfter the entire system has been installed and the actuator has been powered up, the following checks can be made for proper system operation.
GO, NO GO Test Slidewire Controller with 24 Vac ActuatorsRefer to Figure-14.
1. Disconnect field wiring from Brown lead of AE-504 and terminals 7 and 8 of the actuator.
2. Apply 24 Vac power to terminals H and G of the actuator.
3. Short the Brown lead of AE-504 to terminal 7 of actuator and the actuator should rotate CW to its limit.
4. Short the Brown lead of AE-504 to terminal 8 of actuator and the actuator should rotate CCW to its limit.
5. If the unit passes steps 3 and 4, the actuator and the AE-504 are good. If the unit does not pass steps 4 and 5, proceed to step 6.
6. Unhook the AE-504 leads from actuator terminals X, 2, and 3.
7. Short actuator terminal X to 2 and the actuator should rotate CW to its limit.
8. Short actuator terminal X to 3 and the actuator should rotate CCW to its limit.
If the unit passes steps 7 and 8, the actuator is good and AE-504 is defective. If the unit does not pass steps 7 and 8, the actuator is defective and the AE-504 may be good.
Slidewire Controller with Line Voltage Actuator Refer to Figure-15.
1. Disconnect field wiring from Brown lead of AE-504 and terminals 7 and 8 of the actuator.
2. Apply proper AC power to terminals L1 and L2 of the actuator.
3. Short the Brown lead of AE-504 to terminal 7 of actuator and the actuator should rotate CW to its limit.
4. Short the Brown lead of AE-504 to terminal 8 of actuator and the actuator should rotate CCW to its limit.
5. If the unit passes steps 3 and 4, the actuator and the AE-504 are good. If the unit does not pass steps 4 and 5, proceed to step 6.
6. Unhook the AE-504 leads from actuator terminals X, 2, and 3.
7. Short actuator terminal X to 2 and the actuator should rotate CW to its limit.
8. Short actuator terminal X to 3 and the actuator should rotate CCW to its limit.
If the unit passes steps 7 and 8, the actuator is good and AE-504 is defective. If the unit does not pass steps 7 and 8, the actuator is defective and the AE-504 may be good.
CP-8301-120, Vdc Interface (TAC System 8000) with Line Voltage Actuators without Internal Transformer Refer to Figure-16.
1. Disconnect field wiring from Red, Yellow, and Blue leads of CP-8301-xxx.
2. Apply 120 Vac power to terminals L1 and L2 of the actuator.
3. Short the Yellow and Red leads of CP-8301-xxx and the actuator should rotate CW to its limit, unless rewired to rotate CCW on an increase in input signal.
4. Short the Yellow and Blue leads of CP-8301-xxx and the actuator should rotate CCW to its limit, unless rewired to rotate CCW on an increase in input signal.
5. If the unit passes steps 3 and 4, the actuator and the CP-8301-xxx are good. If the unit does not pass steps 3 and 4, proceed to step 6.
6. Unhook the CP-8301-xxx leads from actuator terminals X, 2, and 3.
7. Short actuator terminal X to 2 and the actuator should rotate CW to its limit.
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 39
8. Short actuator terminal X to 3 and the actuator should rotate CCW to its limit.
If the unit passes steps 7 and 8, the actuator is good and CP-8301-xxx is defective. If the unit does not pass steps 7 and 8, the actuator is defective and the CP-8301-xxx may be good.
CP-8301-024, Vdc Interface (TAC System 8000) with 24 Vac Actuators Refer to Figure-17.
1. Disconnect field wiring from Red, Yellow, and Blue leads of CP-8301-xxx.
2. Apply 24 Vac power to terminals H and G of the actuator.
3. Short the Yellow and Red leads of CP-8301-xxx and the actuator should rotate CW to its limit, unless rewired to rotate CCW on an increase in input signal.
4. Short the Yellow and Blue leads of CP-8301-xxx and the actuator should rotate CCW to its limit, unless rewired to rotate CCW on an increase in input signal.
5. If the unit passes steps 3 and 4, the actuator and the CP-8301-xxx are good. If the unit does not pass steps 3 and 4, proceed to step 6.
6. Unhook the CP-8301-xxx leads from actuator terminals X, 2, and 3.
7. Short actuator terminal X to 2 and the actuator should rotate CW to its limit.
8. Short actuator terminal X to 3 and the actuator should rotate CCW to its limit.
If the unit passes steps 7 and 8, the actuator is good and CP-8301-xxx is defective. If the unit does not pass steps 7 and 8, the actuator is defective and the CP-8301-xxx may be good.
CP-8301-120 and CP-8301-240, Vdc Interface (TAC System 8000) with Line Voltage Actuators with Internal Transformer Refer to Figure-18.
1. Disconnect field wiring from Red, Yellow, and Blue leads of CP-8301-xxx.
2. Apply AC power to terminals L1 and L2 of the actuator.
3. Short the Yellow and Red leads of CP-8301-xxx and the actuator should rotate CW to its limit, unless rewired to rotate CCW on an increase in input signal.
4. Short the Yellow and Blue leads of CP-8301-xxx and the actuator should rotate CCW to its limit, unless rewired to rotate CCW on an increase in input signal.
5. If the unit passes steps 3 and 4, the actuator and the CP-8301-xxx are good. If the unit does not pass steps 3 and 4, proceed to step 6.
6. Unhook the CP-8301-xxx leads from actuator terminals X, 2, and 3.
7. Short actuator terminal X to 2 and the actuator should rotate CW to its limit.
8. Short actuator terminal X to 3 and the actuator should rotate CCW to its limit.
If the unit passes steps 7 and 8, the actuator is good and CP-8301-xxx is defective. If the unit does not pass steps 7 and 8, the actuator is defective and the CP-8301-xxx may be good.
CP-8391-xxx Series mAdc Interface Refer to Figure-19 through Figure-23.
1. Unhook the CP-8391-xxx leads from actuator terminals X, 2, and 3.
2. Refer to specific actuator for power hook-ups.
3. Short actuator terminal X to 2 and the actuator should rotate CW to its limit.
4. Short actuator terminal X to 3 and the actuator should rotate CCW to its limit.
5. If the unit passes steps 3 and 4, the actuator is good.
40 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Positioning the Actuator with the Controller
If the sensed media is within the controller’s setpoint range, the actuator can be positioned by adjusting the controller setpoint up and down. Check for proper operation of the actuator (valve or damper) while the actuator is being stroked.
Manually Positioning with Calibration KitTOOL-201, Calibration Kit for TAC System 8000, Vdc Input
Refer to Figure-16 through Figure-18.
1. Disconnect the field wiring from the Red, Yellow, and Blue leads of CP-8301-xxx.
2. Attach the Red, Yellow, and Blue leads of TOOL-201 to the same color leads on the CP-8301-xxx.
3. The actuator can be manually positioned by turning the knob of TOOL-201.
4. Check for proper operation of the valve or damper as the actuator is operated.
5. Disconnect TOOL-201 and reconnect the field wiring.
Theory of OperationActuator variations are shown in Figure-24 through Figure-32. Refer to the actuator selection tables beginning on page 3 to determine which Internal Wiring Figure applies to a certain actuator.
The actuators are powered by shaded pole motors that are of the induction type, using what is commonly know as a squirrel cage rotor. These motors, like all single phase induction motors, must be provided with some means of starting. This is accomplished by the shading coils in the poles of the motor and hence the name “Shaded Pole.” However, unlike most single phase induction motors, the shading coils are also essential for running.
The field coil produces a magnetic field in the iron core (stator) and in the rotor. When actuator terminal x is shorted to a terminal attached to CW shading coils, it causes a lag in part of the field which provides the equivalent of a rotating field. This rotating field induces a voltage and current in the rotor bars, and the attraction between the rotating field and these current carrying bars pulls the rotor around with the field in a CW direction. When actuator terminal x is shorted to a terminal attached to CCW shading coils, it operates the same except it drives the actuator CCW. A voltage of 24 to 30 Vac with current of 9 amps is induced in the shading coils in much the same manner as the secondary of a transformer.
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 41
REPLACEMENT PARTSTable-11 Potentiometer Kit.
Table-12 Additional Potentiometer Kits.
MAINTENANCERegular maintenance of the total system is recommended to assure sustained, optimum performance.
The actuators require a minimum of maintenance since the motor and gear train are submerged in oil for continuous lubrication and cooling. If it is necessary to refill the actuator with oil, always use TAC immersion oil (one quart, part number BYZP-195). Refill capacity is 1-1/4 pints. For best performance, oil level (with the actuator upright) should be up to the edge of the oil fill hole in the front case of the actuator. Refer to Material Safety Data Sheet MSDS-4.
TROUBLESHOOTINGRefer to Section “GO, NO GO Test” on page 39.
REPAIRNone. Replace an inoperable actuator with a functional unit.
Actuator Potentiometer Kit
Part No. DescriptionMP-xx0x-0-0-1MP-xx0x-0-2-1 ADDA-902-2 100 Ω, 180°
MP-xx1x-0-0-1 ADDA-902-2 100 Ω, 180°
MP-xx2x-0-0-1 ADDA-902-2 100 Ω, 180°
MP-xx3x-0-0-1MP-xx3x-0-2-1 ADDA-902-5 100 Ω, 90°
MP-xx4x-0-0-1MP-xx4x-0-2-1 ADDA-902-5 100 Ω, 90°
MP-xx5x-0-0-1MP-xx5x-0-2-1 ADDA-902-2 100 Ω, 180°
MP-xx6x-0-0-1MP-xx6x-0-2-1 ADDA-902-2 100 Ω, 180°
MP-xx7x-0-0-1 ADDA-902-4 50 Ω, 180°
MP-xx8x-0-0-1MP-xx8x-0-2-1 ADDA-902-2 100 Ω, 180°
MP-xx9x-0-0-1 ADDA-902-2 100 Ω, 180°
Potentiometer KitsPart No. Description
ADDA-902-6 500 Ω, 90°
ADDA-902-7 50 Ω, 90°
ADDA-902-8 1000 Ω, 90°
ADDA-902-9 500 Ω, 180°
ADDA-902-10 1000 Ω, 180°
ADDA-907 Shaft seal and gasket kit
42 © Copyright 2007 TAC All Rights Reserved. F-15479-8
DIMENSIONAL DATA
Figure-41 Dimensional Drawing for MP-3xx, MP-4xx, MP-2xxx, and MP-4xxx.
2-3/8"(60 mm)
4-3/4"(121 mm)
5-3/8"(136 mm)
17/64" (6.7 mm)Dia. Holes
2"(51 mm)
1-5/8"(41 mm)
2-1/4"(57 mm)
1-7/16"(36 mm)
1-1/2"(38 mm)
15/16"(24 mm)
4"(102 mm)
1-13/16"(46 mm)
6-5/16"(160 mm)8-1/8"
(206 mm)
3-7/8"(97 mm)
7"(178 mm)
1/2" Conduit Knockouts(Two Each Side)
Spring ReturnOnly
4-3/16"(106 mm)
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 43
Figure-42 Dimensional Drawing for MP-3xx, MP-4xx, MP-2xxx, and MP-4xxx with -6xx Suffix(CP-8301-xxx or CP-8391-91x Installed) or with AE-504 Installed.
2-3/8"(60 mm)
4-3/4"(121 mm)
3-1/8"(79 mm)
17/64" (6.7 mm)Dia. Holes
2"(51 mm)
1-5/8"(41 mm)
2-1/4"(57 mm)
1-7/16"(36 mm)
1-1/2"(38 mm)
15/16"(24 mm)
4"(102 mm)
1-13/16"(46 mm)
6-5/16"(160 mm)
8-1/8"(206 mm)
3-7/8"(97 mm)
7"(178 mm)
Spring ReturnOnly
4-3/16"(106 mm)
4-1/8"(105 mm)
5-3/8"(136 mm)
Two 1/2" ConduitKnockouts
6-13/16"(173 mm)
2"(51 mm)
1/4"(6 mm)
4-13/16"(122 mm)
2-9/16"(65 mm)
3-7/8"(96 mm)
7"(178 mm)
3-1/8"(79 mm)
(A)
Model Dimension A (Width)MP-xxxx With AE-504 Installed
6-11/16 in.(170 mm)
MP-xxxx-6xx Equipped with CP-8301-xxx or CP-8391-91x
7-1/2 in.(191 mm)
CP-8301-xxxor
CP-8391-91x
44 © Copyright 2007 TAC All Rights Reserved. F-15479-8
Figure-43 Dimensional Drawing for Hazardous Location Damper Actuators.
Figure-44 Dimensional Drawing for Hazardous Location Valve Actuators.
4-1/2(114)
15/16(24)
4-7/32(107)
8-1/4(209)
1/2 (13)Dia. Shaft
Dimensions are in inches (mm).
4-13/32(112)
9(228)
1/4 (6)
2-15/16(51)
2-1/8(54)
3/4 (19) Pipe TapOn Each Side
9(229)
9-9/16(243)
10-5/8(270)
1-1/2(40)
On reversible spring returnactuators only.
7(178)
4-1/4(108)
8-1/4(209)
Dimensions are in inches (mm).
4-13/32(112)
9(228)
1/4 (6)4-1/2(114)
2-15/16(51)
2-1/8(54)
3/4 (19) Pipe TapOn Each Side
9(229)
10-13/16(275)
1/8(3)
1-1/2(40)
On reversible spring returnactuators only.
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 45
46 © Copyright 2007 TAC All Rights Reserved. F-15479-8
F-15479-8 © Copyright 2007 TAC All Rights Reserved. 47
Copyright 2007, TACAll brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
F-15479-8
TAC1354 Clifford AvenueP.O. Box 2940Loves Park, IL 61132-2940
www.tac.com
Recommended