Manual for VSIG with DEIF controller
1.1 Block diagrams, schematic and wiring.
Figure 1 Internal connection block diagram when enginegovernor is equipped with CANBUS connection
GENSET
POWER
ELECTRONICS
CANBUS
3
CANBUS2
CANBUS4
GENSET
CONTROLLER
ENGINE
GOVERNOR
CGT-DEIF
PROTOCOL
J1939 PROTOCOL
WU ( wake up)
CANBUS1
B-B+
+12V 0
7/27/2019 manual F inc aux DC.pdf
2/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
Figure 2 Internal connection block diagram when engine governor has not
equipped with CANBUS connector.
GENSET
POWER
ELECTRONICS
CANBUS3
CANBUS2
GENSET
CONTROLLER
ENGINE
GOVERNOR
CGT-DEIF
PROTOCOL
SP (Analog speed signal 0V-5V)
WU ( wake up)
CANBUS1
B-B+
+12V 0
7/27/2019 manual F inc aux DC.pdf
3/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
Figure 3 Detailed wiring diagram
WU
4044
CAN HCAN L
120 ohm
TO CANBUS 3
CANBUS
1
CANBUS 2
1 2 3
CANL
C
ANH
TO CANBUS 4
GND
GND42
7/27/2019 manual F inc aux DC.pdf
4/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
1.2 VSIG operation topologies
Figure 4 Stand alone mode of operation.
POWER
ELECTRONICS
4
POWER ELECTRONICS BOX
4LOAD
EC1ENGINE
CAN + WU
CONT 1
Generator volta es
Mains volta es
7/27/2019 manual F inc aux DC.pdf
5/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
Figure 5 Parallel and grid with automatic synchronisation.
POWER
ELECTRONICS
4
POWER ELECTRONICS BOX
MAINS
4
LOAD
LOAD
ENGINE
CAN + WU
CONT 1
EC1
Mains voltage sensing
Generator volta es
Mains volta es
7/27/2019 manual F inc aux DC.pdf
6/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
Figure 6 Parallel mode of operation with standard Genset or VSIGusing frequency (4%) and voltage (2%) droop
4LOAD
LOAD
EC1
EC1
POWER
ELECTRONICS
4
POWER ELECTRONICS BOX
ENGINE
ENGINE
POWER
ELECTRONICS
4
POWER ELECTRONICS BOX
CAN + WU
CAN + WU
CONT 1
CONT 1
Common bus
STANDARD
GENERATOR
ENGINE
STANDARD GENSET
Mains voltage sensing
Mains voltage sensing
Generator volta es
Mains volta es
Generator volta es
Mains volta es
7/27/2019 manual F inc aux DC.pdf
7/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
1.2.1 Structure of the menu for VSIG part in DEIF EC1
7/27/2019 manual F inc aux DC.pdf
8/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
Figure 7 Structure of the menu for VSIG part in EC1
7/27/2019 manual F inc aux DC.pdf
9/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
1.2.2 Display Description.
1. Window shows frequency of the mains and actual powerfactor
2. Window shows Generator (before contactor) line voltagesL1,L2,L3. When contactor is closed Mains and Generatorvoltages are the same.
3. Window shows line to line Generator voltages L1L2,L2l3,L3L1
4. Window shows Mains line voltages (after contactor)L1,L2,L3. When contactor is closed Mains and Generatorvoltages are the same.
5. Window shows Mains line to line voltages L1L2, L2L3,L3L16. Window displays Generator load RMS current for phase
L1,L2,L37. Window displays active power in kW for each phase
L1,L2,L38. Window shows Total Generator active power Ptot in kW,
total reactive Qtot kVAR and total apparent power Stot in VA.9. Window displays produced power over the time since last
start of the system (kWh since last start) and temperature ofthe internal Heat sink temp.
10. Window shows Number of starts of the generating set and
running hours since last start.11. Window shows power electronics power (PE rating) ratingin VA, software version SW and power electronics serialnumber (PE serial nb)
12. Window shows required engine speed from powerelectronics box (demanded speed) and actual engine speed.DC-link voltage it is internal system voltage should bedepending of the output voltage setting 600V or 800V.
13. Genset controller software version14. Menu, which leads to Power Electronics box system
setting. To access settings press ENTER key.15. Setting output voltage to change setting press enter put
password of 2000 and set required voltage with arrows.Warning not all voltages have been implemented.
16. PE Volt dip sets maximum allowed voltage dip of thegenerator voltages during full step load. Warning: Minimum
7/27/2019 manual F inc aux DC.pdf
10/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
engine speed much be set accordingly to fulfil thisrequirement. This is can be determined by test on theengine.
17. In this menu operator can adjust output voltage of thegenerator. Waning this feature does work only in StandAlone mode.
18. In this menu operator can set required mode of operation.Stand Alone, Grid operation , Parallel operation accordingwith the Figure 4 to Figure 6.
19. In this menu operator can set required output voltagefrequency.
20. In this menu operator can set minimum engine speed toachieve required voltage dip during step load.
21. Demanded reactive power in Grid operation Mode.
Operator can set required demanded reactive powerdelivered to the grid. Only in Grid operation mode.
22. Operator can set required demanded active powerdelivered to the grid. Only in Grid operation mode.
23. If system is equipped with Aux DC supply operator canchange modes of operation. OFF, 12V, 24V, 42V
24. Operator can adjust voltage of the Aux DC supplyFor 12V mode ( from 10V-15V step 1V)For 24V mode ( from 19V-30V step 1V)For 42 mode (from 32V-52V step 1V)25. This menu display actual Aux DC voltage and Aux DC
current.
7/27/2019 manual F inc aux DC.pdf
11/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
1.3 Configuration and operation.
1.3.1 Configuration mode (common for all modes)
Turn power ON to the DEIF controller.When engine is not running, set in DEIF controller parameters like
Voltage, frequencyOperation mode type:1. Stand alone2. Parallel with grid3. Parallel with Genset (droop method)
To make changes go to Parameter menu and press ENTER.Password for accessing Parameter menu is 2000.Go to required option and press ENTER to edit parameter.Change value of parameter by arrows and accept it by pressingENTER.
Warning: PE controller will not accept new settings of mode ofoperation, output voltage and frequency when engine isrunning. Changing those parameters during when system is in
GENERATING MODE will cause system to stop.
1.3.2 Start-up and shut down.
To start Genset and system press green start button( I ) on theGenset controller front panel.If engine has successfully stared after few seconds Green LEDover the generator symbol (sine wave in a circle) should come on.
There is one minute engine warming time when engine will beworking with speed greater than 1500 rpm. After one minuteengine will settle at the minimum set speed.This means that Generator is working correctly. After 20-30seconds (depends of set mode of operation) contactor 1 will be
7/27/2019 manual F inc aux DC.pdf
12/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
closed which will put set voltage on VSIG terminals. This isindicated by green LED situated over switch symbol.
To stop press red button ( O ).Green LED over switch symbol will immediately switch OFF andcontactor 1 open. When engine stops Green LED over generatorsymbol will start blinking. This means that system is shutting down.When LED will go off this means that system has shut down fullyand is ready to start again.Warning: Do not press start button before system has fully shutdown (while LED is blinking).
Figure 8 Front panel of EC1
7/27/2019 manual F inc aux DC.pdf
13/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
1.3.3 Setting output voltage
To make changes go to Parameter menu and press ENTER.Password for accessing Parameter menu is 2000.Go to PE volt mode (15) option and press ENTER to edit
parameter. Set required output voltage using arrows and acceptit by pressing ENTER. Change will have effect on the next startof the system.
1.3.4 Setting output frequency
To make changes go to Parameter menu and press ENTER.Password for accessing Parameter menu is 2000.Go to Freq mode (19) option and press ENTER to editparameter. Set required frequency using arrows and accept it
by pressing ENTER. Change will have effect on the next start ofthe system.
1.3.5 Adjusting output voltage (17)
-10% -10% around previously selected valueValue of the output voltage can be adjusted from -10% to +10% with 0.1% minimum step.To make changes go to Parameter menu and press ENTER.
Password for accessing Parameter menu is 2000.Go to Volt adj (17) option and press ENTER to edit parameter.Set adjust voltage using arrows and accept it by pressingENTER. Change will have effect on the output voltage.
Note: This function works only in stand alone operating mode.
1.3.6 Setting voltage dip parameter (16).
Voltage dip parameter sets allowable transient voltage dipduring full step load. Lower the voltage dip -> higher theminimum speed.To make changes go to Parameter menu and press ENTER.Password for accessing Parameter menu is 2000.
7/27/2019 manual F inc aux DC.pdf
14/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
Go to PE Volt dip (16) option and press ENTER to editparameter. Set required voltage dip using arrows and accept itby pressing ENTER. Change will have immediate effect on thevoltage dip parameter.
Note: Voltage dip during step load is depended of minimumengine speed. If voltage dip during step load (from no loadcondition to full load condition) is higher than set in the menu,minimum speed (20) of the engine must be increasedaccordingly.
1.3.7 Min RPM (minimum engine speed) (20)
To make changes go to Parameter menu and press ENTER.
Password for accessing Parameter menu is 2000.Go to Min RPM (20) option and press ENTER to editparameter. Set required minimum engine speed using arrowsand accept it by pressing ENTER. Change will have immediateeffect on the minimum engine speed.
Minimum engine speed parameter is to set idle speed of theengine at no load condition. Lower engine speed means lovernoise and fuel consumption of the whole Genset at small loadless than 30% of the total Genset power. Unfortunately itimpacts voltage dip during the full step load (0-100%). If voltagedip is not within set voltage dip parameter(16) this means thatminimum engine speed must be increased. Operator has todetermine optimal engine speed needed to fulfil requirement bytest. If full step load will never be applied to the Gensetminimum engine speed can be significantly decreased.Depends of the engine but typically 1200 rpm can be sufficientto achieve 30%-50% step load with 10% voltage dip.
1.4 Modes of operation description
7/27/2019 manual F inc aux DC.pdf
15/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
1.4.1 Stand Alone mode.
This mode can be used only when Genset will be operating asa single unit as it is shown on Figure 4.
1.4.2 Grid connection with back synchronisation.
After start-up PE will go into synchronisation mode. Insynchronisation mode, system checks mains parameters asphase sequence, voltage, frequency and compares them withsettings send in configuration mode.
When grid parameters are correct with internal settings, PEoutput voltages will be synchronised with grid voltages.
When synchronisation is finished and PE controller will closecontactor1 and indicate it by green diode over switch symbolon EC1.Amount of power (active and reactive) injected to the grid is setby DEIF Genset controller.It can be changed in Parameter \ DEPMAND P for active powerand Parameter \ DEPMAND Q for reactive power.When grid parameters are not correct, PE controller will reportappropriate error message and system will shut down.
Messages can be:f not ack frequency of the bus varies from set frequencyTerm volt not ack voltage of the bus varies from set voltagePhase sych not ack wrong phase sequence
When grid is lost, PE controller will open contactor1 and waitfor two minute for the grid voltages reappear.If grid voltages reappear during two minute period system willsynchronise back to the grid and will start producing power with
the recently set values.If grid voltage will not reappear after two minutes, system willshut down with the appropriate error.
7/27/2019 manual F inc aux DC.pdf
16/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
1.4.3 Parallel operation of two Gensets any type (synchronous orVSIG)
After start-up PE will go into synchronisation mode. In
synchronisation mode, system checks mains parameters asphase sequence, voltage, frequency and compares them withsettings send in configuration mode.
When bus parameters are correct with internal settings, PEoutput voltages will be synchronised with line voltages.When synchronisation is finished, PE controller will close outputcontactor1 and systems will start sharing load using droopmethod 4% speed droop and 2% voltage droop.
Note:In all modes system will report faults of its internalcomponents, overloads, short circuits.
1.4.4 Aux DC charger. (23)
If system is equipped with Aux DC supply, operator can selectone of required output modes (OFF,12V,24V,42V).If set output mode is not available from the supplied unit orsystem is not equipped with Aux DC supply system will issueinitialisation error.
1.4.5 Aux DC voltage adjustment (24)
Operator can adjust output voltage around previously selectedoutput mode.For 12V supply adjustments are 10V-15V with step of 1V.For 24V supply adjustments are 19V-30V with step of 1V.For 42V supply adjustments are 32V-52V with step of 1V.Actual output voltage and load current is displayed on screen25.
If Aux DC charger is overloaded it will issue Aux DC overloaderror. For internal transistor failure Aux DC driver errormessage will be issued.
7/27/2019 manual F inc aux DC.pdf
17/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
7/27/2019 manual F inc aux DC.pdf
18/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
1.5 ERROR messages.
Inv U drv UnAckInv V drv UnAckInv W drv UnAckBoost top drv UnAckBoost bot drv UnAck
Break chop drv UnAck
This is low level hardwareerror from IGBT drivers andshould never occur innormal condition. If thiserror occurs every timesystem is started thismeans that PE must beserviced.Possible causes for thiserror are
transistor failure,driver failure,short circuit inside the PEbox.
Break chopper driver errorDC-link over V UnAck This error is caused when
there is big regenerativeload. ( to much power
flowing into the system)
Heat sink trip UnAck Heat sink temperature is tohigh. Usually it means thatthere is something wrongwith cooling system notsufficient water flow.
FPGA UnAck Internal error of the main
controller. Should neverappear during normaloperation. If this erroroccurs every time system isstarted PE box must beserviced.
7/27/2019 manual F inc aux DC.pdf
19/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
Overload UnAck Inverter was overloadedGov fail UnAck Engine speed is not
achieving demandedspeed. It means problem
with the engine or governoror wiring.DC-link asym UnAck Internal error can be
caused by regenerativeload or failure of internalcomponents. If this erroroccurs every time system isstarted PE box must beserviced.
Term U pres UnAck When system is set to
stand alone mode and thereare voltages present on theterminals it will issue thiserror.
Term U NOK UnAck If system is set to parallelmode or grid mode andvoltage settings of thesystem do not match to theactual voltages measured
on the terminals this errorwill be issued. Customershould check settings.
Term f NOK UnAck If system is set to parallelmode or grid mode andfrequency settings of thesystem do not match to theactual frequency measuredon the terminals this errorwill be issued. Customer
should check settings.Phase seq UnAck If system is set to parallel
mode or grid mode andphase sequence on theterminals do not much to
7/27/2019 manual F inc aux DC.pdf
20/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date:
05/03/08
Drawn:
ArturKrasnodebski
Approved: Cummins Generator
Technologies (CGT)
Stamford UK
Issue:
F
the phase sequence of thesystem this error will beissued. Customer shouldcheck terminal phase
sequence.Init error UnAck This error will occur whensystem havent receivedcorrect settings before start.This is usually problembetween DEIF andCummins. This error shouldnever occur in normaloperation.
PMG temp UnAck If PMG temp will be higher
than max specified thiserror will be issued andsystem will be stopped
PCB temp UnAck If PCB temp (Printed CircuitBoard inside PE box) will behigher than max specifiedthis error will be issued andsystem will be stopped
Choke temp UnAck If choke will be higher than
max specified this error willbe issued and system willbe stopped
Heat sink temp UnAck If IGBT heatsink temp willbe higher than maxspecified this error will beissued and system will bestopped
Over voltage UnAck If voltage is higher thannominal for more than 3 s
this error will be issued andsystem will be stopped
Under voltage UnAck If voltage is lower thannominal for more than 8 sthis error will be issued and
7/27/2019 manual F inc aux DC.pdf
21/21
A: B: C: D: E: F:
G: H: J: K: L: M:
Date: Drawn: Approved: Cummins Generator Issue:
system will be stoppedAux DC overload If Aux DC supply is
overloaded this error will beissued and Aux DC will be
turned OFFAux DC driver error This is low level hardwareerror from IGBT drivers andshould never occur innormal condition. If thiserror occurs every timesystem is started thismeans that PE must beserviced.Possible causes for this
error aretransistor failure,driver failure,short circuit inside the PEbox.
Recommended