WET STAND PIPE
DRY STAND PIPE
COMBINATION STAND PIPE
SPRINKLER
FIRE WATER SUPPLY
REFRIGERANT LIQUID
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION
HUMIDIFICATION
GLYCOL HEATING RETURN
GLYCOL HEATING SUPPLY
HOT WATER RETURN ( HEATING)
HOT WATER SUPPLY (HEATING)
FUEL OIL VENT
FUEL OIL RETURN
FUEL OIL SUPPLY
FUEL OIL GAUGE
FUEL OIL DISCHARGE
NATURAL GAS
CONDENSATE DRAIN
DRAIN
VENT (PLUMBING)
STORM DRAINAGE
SANITARY DRAINAGE
HOT WATER RETURN (DOMESTIC)
HOT WATER (DOMESTIC)
COLD WATER (DOMESTIC)
LEGEND
EXISTING ITEM TO DEMOLISH
EXISTING ITEM TO REMAIN
ELBOW, TURNED UP
ELBOW, TURNED DOWN
REDUCER, CONCENTRIC
ELBOW, 90 DEGREES
ELBOW, 45 DEGREES
CAP
THERMOMETER
GAGE, PRESSURE WITH COCK
REDUCER, ECCENTRIC
MANUAL AIR VENT
AUTOMATIC AIR VENT
AIR ELIMINATOR
JOINT, EXPANSION
ANCHOR
GUIDE, ALIGNMENT
SLEEVE, PIPE
PUMP
RISE, PIPE
DROP, PIPE
COCK
FLANGE, BLIND
VALVE, CONTROL 3 WAY ELECTRIC
VALVE, CONTROL 3 WAY PNEUMATIC
VALVE, CONTROL 2 WAY PNEUMATIC
THERMOMETER WELL
STRAINER, BLOW OFF
STRAINER
DIFFUSER, PUMP SUCTION
VALVE, SOLENOID / THERMOSTATIC
VALVE, TRIPLE DUTY
CONNECTION, FLEXIBLE
ARROW, FLOW DIRECTION
VALVE, FLOW CONTROL
VALVE, FLOAT
VALVE, LOCK SHIELD
VALVE, PLUG
VALVE, NEEDLE
VALVE, GLOBE
VALVE, BUTTERFLY
VALVE, ANGLE
VALVE, BALL
VALVE, GATE
UNION
TEE
TEE, OUTLET UP
TEE, OUTLET DOWN
VALVE, CHECK
TRAP, STEAM FLOAT & THERMOSTATIC
TRAP, STEAM FLOAT
TRAP, STEAM
VALVE, SAFETY/RELIEF
VALVE, SAFETY
VALVE, QUICK OPENING
VALVE, PRESSURE REDUCING
OUTLET, GAS, OXY, VAC, N20
CLEANOUT, WALL
FIRE ALARM CONTROL PANEL
CONNECTION, FIRE DEPT SIAMESE
BELL, FIRE ALARM
SPRINKLER, AUTOMATIC
SPRINKLER HEAD, SIDEWALL
SPRINKLER HEAD, PENDANT
SPRINKLER HEAD, UPRIGHT
VALVE, OUTSIDE SCREW & YOKE
VALVE, DRY PIPE
VALVE, ALARM CHECK
VALVE, POST INDICATOR
VALVE, TAMPER DETECTION SWITCH
DRAIN, FLOOR
CLEANOUT, FLOOR
HVAC CONTROL PANEL
HYDRANT, WALL
HYDRANT, FIRE
DETECTOR, GAS
DETECTOR, HEAT
DETECTOR, SMOKE
STANDPIPE, DRY STATION
STANDPIPE, WET STATION
GONG, WATER MOTOR ALARM
HORN / SPEAKER
EXTINGUISHER, DRY CHEM MANUAL ACTIVATION
EXTINGUISHER, DRY CHEM AUTO ACTIVATION
EXTINGUISHER, DRY CHEMICAL
DRAIN, ROOF
ABBREVIATIONSA AMP, AMPERES, AIR (COMPRESSED) DIFF DIFFERENCE, DELTA INCL INCLUDING, INCLUSIVE RPM REVOLUTIONS PER MINUTE
ABS ABSOLUTE DIM DIMENSION INSUL INSULATION, INSULATED RS ROOF SUMP, REFRIGERANT SUCTION
AC ALT. CURRENT, AIR COMPRESSOR DISC DISCONNECT INT INTERIOR, INTERNAL S SOUTH, SOLENOID
ACU AIR CONDITIONING UNIT DISCH DISCHARGE INV INVERT SA SUPPLY AIR, SOUND ATTENUATOR
AD ACCESS DOOR DIV DIVISION IPS IRON PIPE SIZE SAN SANITARY DRAIN/SEWER
ADDL ADDITIONAL DN DOWN ISD IONIZATION SMOKE DETECTOR SCFM (STANDARD) CUBIC FEET PER MINUTE
ADDM ADDENDUM
DOM DOMESTIC
JC JANITOR’S CLOSET SCHED SCHEDULE
ADDN ADDITION
DS DOWNSPOUT, DISCONNECT
KW KILOWATTS SCW SOFT COLD WATER
ADJ ADJUSTABLE
DT DRAIN TILE
L LENGTH, LONG, LOUVER SD SMOKE DAMPER
A-E ARCHITECT-ENGINEER
DWC DRINKING WATER COOLER
LAB LABORATORY SDA SUPPLY DIFFUSER TYPE A
AF AIR FOIL
DWG DRAWING
LAT LEAVING AIR TEMPERATURE SE STATIC FAN EFFICIENCY, SOUTHEAST
AFF ABOVE FINISHED FLOOR
DWR DRINKING WATER RETURN
LAV LAVATORY SECT SECTION
AFS AIR FLOW SWITCH
DWS DRINKING WATER SUPPLY
LB/LBS POUND POUNDS SENS SENSIBLE
AHU AIR HANDLING UNIT
DX DIRECT EXPANSION
LP LOW PRESSURE, LIGHTING PANEL
SF SERVICE FACTOR
ALT ALTERNATE, ALTITUDE EA EXHAUST AIR, EACH
LR LONG RADIUS
SGA SUPPLY GRILLE TYPE A
AMB AMBIENT EAT ENTERING AIR TEMPERATURE
LWT LEAVING WATER TEMPERATURE
SH SHOWER, SENSIBLE HEAT
AMS AIR MEASURING STATION ECC ECCENTRIC
M METER, MOTOR
SHT SHEET
ANSI AMERICAN NAT. STANDARDS INSTITUTE ECON ECONOMIZER
MAN MANUAL
SIM SIMILAR
APD AIR PRESSURE DROP
EEW EMERGENCY EYE WASH
MATL MATERIAL
SM SHEET METAL
APPROX APPROXIMATE
EF EXHAUST FAN
MAX MAXIMUM
SP STATIC PRESSURE
ARCH ARCHITECT, ARCHITECTURAL
EFF EFFICIENCY
MBH 1000 BRITISH THERMAL UNITS / HOUR
SPEC SPECIFICATION
AS AUTOMATIC SPRINKLER
EGA EHAUST GRILLE TYPE A
MC MOTOR CONTROL
SPR SPRINKLER
ASME AM. SOCIETY OF MECHANICAL ENGINEERS
EL ELEVATION
MCC MOTOR CONTROL CENTER
SQ SQUARE
ASR AUTOMATIC SPRINKLER RISER
ELEC ELECTRIC, ELECTRONIC
MECH MECHANICAL
SR SUPPLY RISER
ASTM AM. SOCIETY FOR TESTING MATERIALS
ELEV ELEVATOR
MEZZ MEZZANINE
SSTL STAINLESS STEEL
ATM ATMOSPHERE
ELL ELBOW
MFG MANUFACTURING
ST STORM
AUTO AUTOMATIC
EMS ENERGY MANAGEMENT SYSTEM
MFR MANUFACTURER
STA STATION
AUX AUXILIARY
ENCL ENCLOSURE, ENCLOSED
MH MANHOLE
STD STANDARD
AV AIR VENT (AUTOMATIC)
ENT ENTERING
MIN MINIMUM, MINUTE
STL STEEL
AW ACID WASTE
EQ EQUAL
MISC MISCELLANEOUS
STM STEAM
B BOILER, BRINE SUPPLY
EQUIP EQUIPMENT
MM MILLIMETER
STOR STORAGE
BDD BACKDRAFT DAMPER
EVAP EVAPORATOR
MU MAKE UP
STR STRAINER
BET BETWEEN
EWT ENTERING WATER TEMPERATURE
MV AIR VENT (MANUAL)
STRUCT STRUCTURAL
BF BARRIER FREE
EX EXISTING
N NORTH
SUCT SUCTION
BFP BACK FLOW PREVENTER
EXH EXHAUST
NA NOT APPLICABLE
SW SWITCH
BHP BRAKE HORSEPOWER
EXP EXPANSION
NATL NATIONAL
SYS SYSTEM
BI BACKWARD INCLINED / BINARY INPUT
F FAHRENHEIT, FAN
NC NORMALLY CLOSED, NOISE CRITERIA
T THERMOSTAT, TIME, TANK
BLDG BUILDING
FA FACE AREA
NEC NATIONAL ELECTRICAL CODE
TAB TESTING, ADJUSTING & BALANCING
BOD BOTTOM OF DUCT
FC FORWARD CURVED
NEMA NAT. ELECT MANUFACTURERS ASSOC.
TB THRUST BLOCK
BOP BOTTOM OF PIPE
FD FLOOR DRAIN, FIRE DAMPER
NFPA NAT. FIRE PROTECTION ASSOCIATION
TCV TEMPERATURE CONTROL VALVE
BTU BRITISH THERMAL UNIT
FEC FIRE EXTINGUISHER CABINET
NIC NOT IN CONTRACT
TD TEMPERATURE DIFFERENCE
BTUH BRITISH THERMAL UNIT PER HOUR
FEX FIRE EXTINGUISHER
NO NORMALLY OPEN
TDH TOTAL DYNAMIC HEAD
C/C CENTER TO CENTER
FH FUME HOOD
NO. NUMBER
TEMP TEMPERATURE, TEMPORARY
CAV CONSTANT AIR VOLUME
FHC FIRE HOSE CABINET
NRS NON RISING STEM
TG TRANSFER GRILLE
CB CATCH BASIN
FLA FULL LOAD AMPS
NTS NOT TO SCALE
TOT TOTAL
CC COOLING COIL
FLEX FLEXIBLE
OA OUTSIDE AIR
TP TEMPRATURE AND PRESSURE
CFH CUBIC FEET PER HOUR
FLR FLOOR
OC ON CENTER
TSP TOTAL STATIC PRESSURE
CFM CUBIC FEET PER MINUTE
FM FACTORY MUTUAL
OD OUTSIDE DIAMETER
TSTAT THERMOSTAT
CH CHILLER
FP FIRE PROTECTION
OS&Y OUTSIDE SCREW AND YOKE
TU TERMINAL UNIT
CHWR CHILLED WATER RETURN
FPM FEET PER MINUTE
OSHA OCCUPATIONAL SAFETY & HEALTH ACT
TX THERMOSTATIC EXPANSION
CHWS CHILLED WATER SUPPLY
FRP FIBERGLASS REINFORCED PLASTIC
OV OUTLET VELOCITY
TYP TYPICAL
CI CAST IRON
FS FLOW SWITCH, FREEZESTAT
P PUMP
UC UNDERCUT
CIRC CIRCLE, CIRCULAR, CIRCULATION
FSD FIRE & SMOKE DAMPER
PD PRESSURE DROP
UG UNDERGROUND
CL CENTER LINE
FT FOOT, FEET
PERF PERFORATED
UH UNIT HEATER
CLG CEILING
FVEL FACE VELOCITY
PERM PERMANENT
UL UNDERWRITERS LABORATORIES
CO CLEANOUT
G GRAM, GAS (NATURAL)
PH PHASE
UPS UNINTERRUPTABLE POWER SYSTEM
COEF COEFFICIENT
GA GAGE, GAUGE
PHC PREHEAT COIL
UR URINAL
COL COLUMN
GAL GALLON
PIV POST INDICATOR VALVE
V VENT, VALVE, VOLT
CONC CONCRETE
GALV GALVANIZED
PLBG PLUMBING
VA VALVE, VOLT-AMPERE
COND CONDENSATE, CONDENSER
GEN GENERAL
PNL PANEL
VAC VACUUM
CONN CONNECTION
GI GALVANIZED IRON
PP POWER PANEL
VAR VARIABLE
CONT CONTINUATION, CONTINUOUS, CONTROL
GPD GALLONS PER DAY
PPH POUNDS PER HOUR
VAV VARIABLE AIR VOLUME
CONTR CONTRACTOR
GPH GALLONS PER HOUR
PREFAB PREFABRICATED
VB VACUUM BREAKER
COORD COORDINATE
GPM GALLONS PER MINUTE
PREP PREPARATION
VD VOLUME DAMPER
CPVC CHOLORINATED POLYVINYL CHLORIDE
GR GRADE, GRAINS
PRESS PRESSURE
VEL VELOCITY
CTR CENTER
H HIGH, HEIGHT, HUMIDIFIER, HUMIDISTAT
PROJ PROJECT, PROJECTION
VENT VENTILATING, VENTILATION
CU COPPER, CUBIC
HB HOSE BIBB
PROP PROPERTY
VERT VERTICAL
CU FT CUBIC FEET
HC HEATING COIL
PRV PRESSURE REDUCING VALVE
VEST VESTIBULE
CUH CABINET UNIT HEATER
HD HEAVY-DUTY, HEAD, HEAT DETECTOR
PS PRESSURE SWITCH
VOL VOLUME
Cv COEFFICIENT, VALVE FLOW
HEX HEAT EXCHANGER, HEXAGON
PSI POUNDS PER SQUARE INCH
VOLT VOLTAGE
CW COLD WATER, CLOCKWISE
HG MERCURY
PVC POLYVINYL CHLORIDE
VSD VARIABLE SPEED DRIVE
CWR CONDENSER WATER RETURN
HO HUB OUTLET
R RADIUS, RISE
VTR VENT THROUGH ROOF
CWS CONDENSER WATER SUPPLY
HORIZ HORIZONTAL, HORIZONTALLY
R22 REFRIGERANT R22
W WEST, WIDE, WIDTH, WATT
D DRAIN, DAMPER, DROP
HP HORSEPOWER, HIGH PRESSURE
RA RETURN AIR
W&V WASTE AND VENT
DB DRY BULB, DECIBEL
HR HOUR
RD ROOF DRAIN, REFIRGERANT DISCHARGE
W/ WITH
DBT DRY BULB TEMPERATURE
HRU HEAT RECOVERY UNIT
RECIRC RECIRCULATION
W/O WITHOUT
DC DIRECT CURRENT
HTG HEATING
REF REFERENCE
WB WET BULB
DDC DIRECT DIGITAL CONTROL
HTR HEATER
REFRIG REFRIGERANT, REFRIGERATION
WBT WET BULB TEMPERATURE
DEG DEGREE
HUM HUMIDITY, HUMIDIFIER
REQD REQUIRED
WC WATER CLOSET
DEGF DEGREES FAHRENHEIT
HVY HEAVY
RET RETURN
WF WASH FOUNTAIN
DEMO DEMOLISH, DEMOLITION
HW HOT WATER
REV REVISION, REVOLUTION
WG WATER GAUGE
DEPT DEPARTMENT
HWR HOT WATER RECIRCULATION
RF RETURN FAN
WH WALL HYDRANT
DET DETAIL
HZ HERTZ FREQUENCY
RGA RETURN GRILLE TYPE A
WPD WATER PRESSURE DROP
DF DRINKING FOUNTAIN
I/O INPUT/OUTPUT
RH RIGHT HAND, RELATIVE HUMIDITY
WT WEIGHT
DG DOOR GRILLE
ID INSIDE DIAMETER, IDENTIFICATION
RL REFRIGERANT LIQUID
Y YARD
DI DISTILLED WATER / DIGITAL INPUT
IE INVERT ELEVATION
RM ROOM
YH YARD HYDRANT
DIA DIAMETER
IN. INCH, INCHES
RO REVERSE OSMOSIS, ROUGH OPENING
CONTROLS & ELECTRICAL
HVAC
GRILLE, CEILING RETURN/EXHAUST
DIFFUSER, CEILING SUPPLY ROUND
DAMPER, SMOKE
DAMPER, FIRE
DAMPER, ELECTRIC OPERATED
HEATER, ELECTRIC DUCT
DIFFUSER, CEILING LINEAR/SLOT
FAN, LOUVERED ROOF
FAN, ROOF EXHAUST
DIFFUSER, CEILING SUPPLY SQUARE
UNIT, TERMINAL DUAL DUCT
DUCT, ACOUSTIC LINED
LOUVER
ELBOW, RADIUS/SQUARE W/ VANES
DUCT, SUPPLY
DUCT, EXHAUST / RETURN
DIRECTION, FLOW
CONNECTION, FLEXIBLE
GRILLE, WALL SUPPLY
DROP, DUCT
DIFF, SPLY TYP B, 8" NECK, 250 CFM
SIZE, DUCT 12" WIDE X 10" DEEP
DAMPER, PNEUMATIC OPERATED
RISE, DUCT
UNIT, TERMINAL VAV RH
UNIT, TERMINAL VAV W/ ATTENUATOR
UNIT, TERMINAL VAV NO ATTENUATOR
DOOR, ACCESS
ATTENUATOR, SOUND
DAMPER, BACK DRAFT
FLEXIBLE DUCT
DUCT BRANCH, STANDARD
GRILLE, WALL RETURN /EXHAUST
DIFFUSER/GRILLE THROW DIRECTION
LOUVER L-1, 24" X 12", 750 CFM
HUMIDISTAT
SENSOR, HUMIDITY
TEMPERATURE SENSOR
THERMOSTAT
SWITCH, PRESSURE
SWITCH, FLOW
MOTOR CONTROL
POWER PANEL
LIGHTING PANEL
TELEPHONE OUTLET
METER, WATT HOUR
TRANSFORMER
FUSE
CIRCUIT BREAKER
RECEPTACLE, DUPLEX
BOX, JUNCTION
SWITCH
DISCONNECT, FUSED
DISCONNECT, UNFUSED
MOTOR / ACTUATOR ELECTRIC
FAN, CENTRIFUGAL
FAN, AXIAL / PROPELLER
DAMPER, COMBINATION FIRE/SMOKE
SF SUPPLY FAN, SAFETY FACTOR
PIPE FITTING & FP
METER
SENSOR, PRESSURE
SENSOR, LIGHT (PHOTO CELL)
SENSOR, CO2
SENSOR, LEVEL
CONTROLLER
RELAY
AI ANALOG INPUT
AO ANALOG OUTPUT
BO BINARY OUTPUT
DO DIGITAL OUTPUT
PREVENTER, BACKFLOW
FPWH FREEZE PROOF WALL HYDRANT
CTE CONNECT TO EXISTING
PROJECT No.
DRAWN BY
DATE
CAD FILE
SHEET
ISSUE DATE (Y-M-D) No. ISSUED FOR
CLIENT
SCALE
374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E studio@passa.ca
Passa Associates Inc. WWW.PASSA.CA
PROJECT
ARCHITECTS
Please note that all information included in these drawing files is protected by
copyright. Unauthorized use of these files without the written permission of
Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects
is responsible only for information shown on a mechanical reproduction of these
drawings that have been signed and stamped by an architect with signing
authority employed by the firm.
If you require further information please contact our office at the numbers listed.
A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR
2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.
AUG. 09, 2021
UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.
2021-06-25 1 PROGRESS
2021-06-30 2 PERMIT
2021-07-14 3 FINAL REVIEW
2021-07-27 4 PROGRESS
2021-08-09 5 PERMIT & TENDER
JACE #21-023 M1
LEGENDS, ABBREVIATIONS & MECHANICAL DRAWING LIST
NA
2021-08-0921-023
PROJECT No.
DRAWN BY
DATE
CAD FILE
SHEET
ISSUE DATE (Y-M-D) No. ISSUED FOR
CLIENT
SCALE
374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E studio@passa.ca
Passa Associates Inc. WWW.PASSA.CA
PROJECT
ARCHITECTS
Please note that all information included in these drawing files is protected by
copyright. Unauthorized use of these files without the written permission of
Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects
is responsible only for information shown on a mechanical reproduction of these
drawings that have been signed and stamped by an architect with signing
authority employed by the firm.
If you require further information please contact our office at the numbers listed.
A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR
2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.
AUG. 09, 2021
UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.
2021-06-25 1 PROGRESS
2021-06-30 2 PERMIT
2021-07-14 3 FINAL REVIEW
2021-07-27 4 PROGRESS
2021-08-09 5 PERMIT & TENDER
JACE #21-023 M2
MECHANICAL SPECIFICATIONS
1/8" - 1'-0"
MECHANICAL SPECIFICATIONS
SECTION 15000 - GENERAL SPECIFICATIONS
1.0 GENERAL
1.1 THIS GENERAL SPECIFICATION APPLIES TO ALL MECHANICAL WORK INCLUDING
HVAC, PLUMBING, FIRE PROTECTION AND CONTROLS. SEE THE RESPECTIVE
SECTIONS.
1.2 ALL WORK SHALL COMPLY WITH APPLICABLE CODES, REGULATIONS, ORDINANCES,
STANDARDS, GOOD PRACTICE, MANUFACTURER'S RECOMMENDATIONS & PRODUCT
LISTING CONDITIONS FOR NEW, RENOVATON AND/OR DEMOLITION WORK. THIS
INCLUDES BUT NOT LIMITED TO ASHRAE, SMACNA, NFPA, IMC, IPC, IFGC, IFC, UL/ULC,
FM, OWNERS INSURANCE REQUIREMENTS & LOCAL CODES, REGULATIONS & BYLAWS.
SHOULD A CONFLICT OCCUR BETWEEN DRAWINGS, SPECIFICATIONS, CODES,
REGULATIONS, ORDINANCES, STANDARDS, GOOD PRACTICE, MANUFACTURER'S
RECOMMENDATIONS & PRODUCT LISTING CONDITIONS THE MOST STRINGENT
REQUIREMENTS SHALL PREVAIL.
1.3 QUALIFICATIONS: EXECUTE WORK ONLY WITH SKILLED TRADESMEN EMPLOYED
BY A QUALIFIED TRADE CONTRACTORS IN ONTARIO REGULARLY ENGAGED IN THE
INSTALLATION OF THEIR RESPECTIVE SYSTEMS.
1.4 INSTALLATION SHALL BE COMPLETE AND FULLY FUNCTIONAL. PROVIDE ALL
MATERIALS, EQUIPMENT, ACCESSORIES, CONSUMABLES, LABOR, SUPERVISION,
TOOLS, SERVICES, ETC. AS REQUIRED.
1.5 PROVIDE THE FOLLOWING SYSTEMS AS PART OF THIS CONTRACT: HVAC,
PLUMBING, FIRE PROTECTION WET SPRINKLERS, FIRE EXTINGUISHERS AND
ASSOCIATED CONTROLS.
1.6 PROVIDE A SCHEDULE WITHIN 5 WORKING DAYS OF AWARD OF CONTRACT.
SCHEDULE TO INCLUDE TIME FOR CONTRACTOR COMMISSIONING CLEARLY
INDICATED. PROVIDE A BILLING BREAKDOWN FOR REVIEW PRIOR TO FIRST DRAW
SUBMISSION.
1.7 ARRANGE FOR ALL PERMITS, APPROVALS, EXAMINATION, TESTS AND INSPECTION
SERVICES. PAY ALL REQUIRED FEES & CHARGES. PROVIDE ALL THE NECESSARY
APPLICATIONS, DOCUMENTATION, DRAWINGS AND SPECIFICATIONS. NO WORK SHALL
COMMENCE UNTIL ALL REQUIRED PERMITS, APPROVALS, ETC. ARE OBTAINED FROM
AUTHORITIES HAVING JURISDICTION.
1.8 EXAMINE ALL DRAWINGS AND SPECIFICATIONS AND REPORT ALL CONFLICTS,
DISCREPANCIES TO THE CONSULTANT FOR CLARIFICATION AND /OR CORRECTION.
1.9 DRAWINGS: DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL
ARRANGEMENT OF MECHANICAL SYSTEMS AND WORK INCLUDED. DO NOT SCALE
DRAWINGS. OBTAIN DIMENSIONS FROM ENGINEER'S PLANS, MANUFACTURER'S SHOP
DRAWINGS AND ONSITE INSPECTIONS.
1.10 ELECTRICAL WORK: ALL WIRING AND CONDUIT FOR POWER AND CONTROL SHALL
BE BY ELECTRICAL DIVISION, EXCEPT FOR WIRING, CONDUIT AND CONNECTIONS
BELOW 50V WHICH ARE RELATED TO AUTOMATIC CONTROL SYSTEMS SHALL BE BY
CONTROLS CONTRACTOR.
1.11 SUBMIT SHOP DRAWINGS AND PRODUCT DATA FOR ALL EQUIPMENT. THE SHOP
DRAWINGS SHALL INDICATE THE MANUFACTURER, MODEL, AND PHYSICAL,
ELECTRICAL, MECHANICAL, AND PERFORMANCE CHARACTERISTICS.
1.12 PROTECT WORK AND STRUCTURE FROM DAMAGE, WEATHER, TEMPERATURE
AND HUMIDITY EXTREMES.
1.13 PROVIDE SCHEDULE 40 PIPE SLEEVES AT PENETRATIONS THROUGH MASONRY
AND CONCRETE, OR FIRE RATED ASSEMBLIES.
1.14 PROVIDE FIRE STOPPING MATERIAL AT PENETRATIONS THROUGH FIRE RATED
ASSEMBLIES TO MAINTAIN FIRE RATING INTEGRITY.
1.15 PROVIDE ACCESS FOR SERVICING EQUIPMENT AS RECOMMENDED BY THE
MANUFACTURER.
1.16 INSTALL EQUIPMENT, DUCTS AND PIPES PARALLEL TO OR PERPENDICULAR TO
BUILDING LINES.
1.17PROVIDE SPACE, UNIONS AND FLANGES FOR EASE OF MAINTENANCE,
DISASSEMBLY AND REMOVAL OF EQUIPMENT.
1.18 PIPE EQUIPMENT DRAINS TO FLOOR DRAINS, JANITOR / SERVICE SINKS, ETC AS
APPLICABLE.
1.19 PIPE PAINTING AND IDENTIFICATION SHALL COMPLY WITH STANDARDS. IDENTIFY
PIPES AT EVERY BRANCH AND AT EVERY EQUIPMENT. USE PLASTIC COATED CLOTH
MATERIAL WITH COLORS AND IDENTIFICATION AND WATER PROOF ADHESIVE.
1.20 RECORD ALL DEVIATIONS FROM THE CONSTRUCTION DRAWINGS. ON PROJECT
COMPLETION, PROVIDE REPRODUCIBLE “AS BUILT” DRAWINGS SHOWING WORK AS
ACTUALLY INSTALLED.
1.21 CONDUCT TESTS IN ACCORDANCE WITH APPLICABLE CODES ANS STANDARDS.
1.22 PROVIDE 3 COPIES OPERATING AND MAINTENANCE MANUALS FOR HVAC,
PLUMBING, FIRE PROTECTION, AND CONTROL EQUIPMENT/SYSTEMS. INCLUDE: “AS
BUILT” DRAWINGS, SHOP DRAWINGS, PRODUCT DATA, OPERATING & MAINTENANCE
INSTRUCTIONS, TROUBLE SHOOTING, PART LISTS, T & B REPORT, WARRANTIES,
WIRING AND CONTROL DIAGRAMS. O&M TO BE INDEXED AND PDF TO BE OCR
SEARCHABLE. SUBMIT TO CONSULTANT AND OWNER 10 DAYS PRIOR TO REQUESTING
SUBSTANTIAL COMPLETION.
1.23 DEMONSTRATE AND INSTRUCT CLIENT'S PERSONNEL IN OPERATING,
CONTROLLING, ADJUSTING, TROUBLE SHOOTING, AND SERVICING ALL SYSTEMS AND
EQUIPMENT. INSTRUCTIONS SHALL BE HELD DURING REGULAR WORK HOURS PRIOR
TO ACCEPTANCE. TOTAL TIME SHALL NOT BE LESS THAN 2 HOURS.
1.24 FURNISH A GUARANTEE COVERING ALL EQUIPMENT, COMPONENTS,
ACCESSORIES AND SYSTEMS FOR MINIMUM OF ONE YEAR FROM THE DATE OF
ACCEPTANCE.
1.25 START-UP AND COMMISSIONING: PROVIDE START-UP, TESTING AND
COMMISSIONING. PROVIDE TECHNICAL SERVICE REPORT OF TEST RESULTS. THIS
INCLUDES A DEFICIENCY LIST. CONTRACTOR IS RESPONSIBLE TO ENSURE ALL
EQUIPMENT FUNCTIONS AS PER DESIGN DOCUMENTS. CONTRACTOR TO NOTIFY
CONSULTANT 5 DAYS PRIOR TO START OF CONTRACTOR COMMISSIONING FOR
OPTIONAL WITNESSING. CONTRACTOR TO MAINTAIN A DEFICIENCY LIST THAT
INCORPORATES ALL DEFICIENCIES NOTED FROM ALL PARTIES. PRINTOUT OF BAS
GRAPHICS TO BE PROVIDED TO CONSULTANT FOR REVIEW.
1.26 DEMOLITION & RENOVATIONS:
1.26.1 REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL SCOPE OF DEMOLITION.
COORDINATE WITH ARCHITECTURAL, STRUCTURAL & ELECTRICAL DEMOLITION.
1.26.2 DRAWINGS ARE BASED ON FIELD OBSERVATIONS & EXISTING RECORD
DRAWINGS. NOT EVERY MECHANICAL EQUIPMENT, COMPONENT, ACCESSORY,
DEVICE, PIPE, DUCT, SERVICE, UTILITY HAVE BEEN SHOWN. EXISTING SYSTEMS
SHOWN ON THE DRAWINGS MAY DIFFER FROM ACTUAL
1.26.3 THE DRAWINGS INDICATE ONLY AFFECTED EQUIPMENT IN THE DESIGNATED
DEMOLITION AREAS OF THIS PROJECT. EXCEPT FOR ITEMS DESIGNATED TO REMAIN,
REMOVE ALL NECESSARY ITEMS REQUIRED BY THIS DEMOLITION WHETHER SHOWN
OR NOT.
1.26.4 PRIOR TO BID/TENDER, EXAMINE ENTIRE DEMOLITION SCOPE/AREAS, ALL
DRAWINGS & SPECIFICATIONS INCLUDING EQUIPMENT LOCATIONS, AREAS OF
SERVICE, EXISTING EQUIPMENT / SERVICES TO REMAIN, PIPE/DUCT RUNS, ETC. TO
UNDERSTAND THE ENTIRE DEMOLITION SCOPE. REPORT ALL CONFLICTS,
DISCREPANCIES TO THE CONSULTANT FOR CLARIFICATION & /OR CORRECTION. NO
ALLOWANCE SHALL BE MADE FOR FAILURE TO DO SO.
1.26.5 PRIOR TO DEMOLITION & REMOVAL, SURVEY BUILDING & SITE TO COMFIRM NO
SERVICES / UTILITIES DESIGNATED FOR DEMOLITION WILL INTERRUPT SERVICES
OUTSIDE OF DEMOLITION AREA. IF CERTAIN SERVICES WILL BE DISRUPTED, REROUTE
SERVICES PRIOR TO DEMOLITION TO ENSURE CONTINUED SERVICE.
1.26.6 PRIOR TO DEMOLITION OF HVAC, PLUMBING, FIRE PROTECTION EQUIPMENT,
CONTROLS, COMPONENTS, SYSTEMS, ETC. ENSURE THAT THESE ARE NOT NEEDED &
WILL NOT BE USED FOR THE NEW WORK.
1.26.7 LIMIT DEMOLITION WORK TO THE DESIGNATED EQUIPMENT, APPLIANCES,
COMPONENTS, AREAS, ETC. REMOVE ALL DEMOLISHED ITEMS COMPLETE INCLUDING
ASSOCIATED PIPING, DUCTS, EQUIPMENT, INSULATION, SUPPORTS, COMPONENTS,
ACCESSORIES, CONTROLS, EQUIPMENT PADS, ETC. ASSOCIATED WITH DEMOLISHED
ITEMS UP TO DEMOLITION AREA LIMITS & SERVICES / UTILITIES TO REMAIN. VALVE,
CAP & TERMINATE UTILITIES, SERVICES, ETC.
1.26.8 NO SERVICES, UTILITIES, EQUIPMENT, APPLIANCES, PIPES, DUCTS, ETC. WITHIN
THE DEMOLITION AREAS THAT ARE NO LONGER NEEDED OR USED SHALL BE
ABANDONED IN PLACE. ALL UNNECESSARY SERVICES, UTILITIES, EQUIPMENT,
APPLIANCES, PIPES, DUCTS, ETC. SHALL BE COMPLETELY DEMOLISHED WITHIN THE
DESIGNATED DEMOLITION AREAS UNLESS INDICATED OTHERWISE.
1.26.9 CONTROLS, PIPES, SERVICES, UTILITIES, ETC. LOCATED IN WALLS, OR WALL
SURFACES, BEING DEMOLISHED SHALL BE COMPLETELY REMOVED BACK TO THEIR
RESPECTIVE SOURCES WHICH ARE TO REMAIN. CAP UTILITIES & SERVICES AT POINT
OF DEMOLITION.
1.26.10 ALL MECHANICAL EQUIPMENT & DEVICES (I.E. CONTROLS, THERMOSTATS,
SWITCHES, PIPES, DUCTS, ETC.) SHOWN TO BE REMOVED FROM A WALL WHICH IS TO
REMAIN, SHALL HAVE THESE MECHANICAL ITEMS ABANDONED WITHIN THE WALLS OR
COMPLETELY REMOVED / DEMOLISHED OTHERWISE. FURNISH & INSTALL A BLANK
COVERPLATE AS NEEDED.
1.26.11 DO NOT DISABLE OR DISRUPT BUILDING FIRE OR LIFE SAFETY SYSTEMS
WITHOUT PRIOR WRITTEN NOTICE TO & APPROVAL OF OWNER, GENERAL, ARCHITECT
& AUTHORITIES.
1.26.12 REMOVE DESIGNATED BUILDING MATERIALS, EQUIPMENT, TANKS, PIPING,
FIXTURES & CONSTRUCTION COMPLETE WITH ALL COMPONENTS, ACCESSORIES, ETC.
1.26.13 COORDINATE & SCHEDULE WORK WITH OWNER, GENERAL, ARCHITECT &
OTHER TRADES TO MINIMIZE CONFLICTS, DELAYS, INTERFERANCE & DISRUPTION OF
EXISTING SERVICES, OPERATIONS & ADJACENT BUILDING AREAS. PREVENT SPREAD
OF DUST, ODOURS, & NOISE TO PERMIT CONTINUED USE & OCCUPANCY. PERFORM
NOISY, MALODOROUS, DUSTY, &/OR DISRUPTIVE WORK ON DAYS & TIMES AGREED
WITH OWNER.
1.26.14 DEMOLISH IN AN ORDERLY & CAREFUL MANNER. PROTECT EXISTING
STRUCTURE. KEEP PROJECT SITE IN A CLEAN & ORDERLY MANNER. REMOVE TRASH
AT REGULAR INTERVALS TO PREVENT BUILDUP OF RUBBISH.
1.26.15 EXISTING ITEMS DESIGNATED FOR RELOCATION SHALL BE REMOVED,
CLEANED, CHECKED & REINSTALLED AS INDICATED ON PLANS. REPORT
DEFICIENCIES TO THE CONSULTANT.
1.26.16 AT THE OWNER'S DISCRETION, EXISTING ITEMS DESIGNATED FOR REMOVAL
SHALL BE REMOVED & STORED IN THE OWNER'S STORAGE FACILITIES OR REMOVED
FROM THE OWNER'S PREMISES & DISPOSED PROPERLY BY THE CONTRACTOR. DO
NOT BURN OR BURY MATERIALS ON SITE. REMOVE MATERIALS AS WORK
PROGRESSES. REMOVE TEMPORARY WORK. UPON COMPLETION, LEAVE AREAS IN
CLEAN CONDITION.
2.0 PRODUCTS
2.1 CONDENSATE DRAIN PIPES SHALL BE COPPER TUBE TYPE DWV TO ASTM B306.
FITTINGS SHALL BE WROUGHT COPPER TO CSA B125 SOLDERED JOINTS AND CAST
BRASS TO CSA B125. SOLDER SHALL BE TIN-LEAD 50:50 TO ASTM B32 TYPE 50A.
2.2 HANGERS & SUPPORTS - HANGERS SHALL BE IN ACCORDANCE WITH ANSI B31.1.
HORIZONTAL PIPE HANGERS SHALL BE CLEVIS TYPE CARBON STEEL WITH BLACK
FINISH. FINISH SHALL BE COPPER OR PLASTIC FOR DIRECT SUPPORT COPPER TUBE
OR PIPE. RODS SHALL BE BLACK CARBON STEEL THREADED RODS WITH LOCK NUTS,
AND PROTECTION SADDLES (FOR INSULATED PIPES).
2.3 INSULATION SHALL BE FIBERGLASS, NON-COMBUSTIBLE WITH VAPOR BARRIER
JACKET AND FIRE RETARDANT ADHESIVE. FLAME SPREAD AND SMOKE DEVELOPED
RATINGS SHALL NOT EXCEED 25/50 BASED ON THE STANDARDS OF FIRE HAZARD
CLASSIFICATION FOR BUILDING MATERIALS.
2.4 PIPE INSULATION FOR CONDENSATE LINES SHALL BE 1” THICK RIGID FIBER SLEEVE
WITH FACTORY APPLIED ALL SERVICE VAPOR BARRIER JACKET AND SELF ADHESIVE
TAPE.
2.5 PIPE INSULATION FOR REFRIGERATION SYSTEMS SHALL BE FLEXIBLE
ELASTOMERIC, CLOSED-CELL, SPONGE- OR EXPANDED-RUBBER MATERIALS,
COMPLYING WITH ASTM C 534, TYPE I, 2 INCHES THICK, INDOORS AND OUTDOORS.
ACCEPTABLE PRODUCT: ARMACELL LLC; AP ARMAFLEX.
2.6 VALVES, FITTINGS & FLANGE INSULATION SHALL BE MOLDED AND FABRICATED
INSULATION SEGMENTS OF A THICKNESS EQUAL TO THAT OF THE PIPE.
2.7 INSULATION:
2.7.1INSULATION SHALL BE PROVIDED PER ASHRAE 90.1 - 2010 & AS SPECIFIED
HEREIN. FIRE AND SMOKE RATING IN ACCORDANCE WITH CAN/ULC-S102, MAXIMUM
FLAME SPREAD / SMOKE DEVELOPED RATING: 25/50.
2.7.2 INSULATION: MINERAL FIBRE SPECIFIED FOR GLASS FIBRE, ROCK WOOL, SLAG
WOOL, THERMAL CONDUCTIVITY ("K" FACTOR) < SPECIFIED VALUES AT 24 DEGREES C
MEAN TEMPERATURE WHEN TESTED IN ACCORDANCE WITH ASTM C335.
2.7.3 PIPE INSULATION: APPLY INSULATION TO MECHANICAL EQUIPMENT & SYSTEMS.
2.7.3.1 RIGID MOULDED MINERAL FIBRE WITH FACTORY APPLIED VAPOUR RETARDER
JACKET, MINERAL FIBRE, JACKET, MAXIMUM "K" FACTOR TO ASTM C547 CAN/ULC-S702.
2.7.3.2 MINERAL FIBRE BLANKET FACED WITH FACTORY APPLIED VAPOUR RETARDER
JACKET MINERAL FIBRE ASTM C547, JACKET, MAXIMUM "K" FACTOR TO ASTM C547
CAN/ULC-S702.
2.7.3.3 FLEXIBLE UNICELLULAR TUBULAR ELASTOMER WITH VAPOUR RETARDER
JACKET, CERTIFIED BY MANUFACTURER: FREE OF POTENTIAL STRESS CORROSION
CRACKING CORRODANTS.
2.7.4 DUCT INSULATION:
2.7.4.1 RIGID MINERAL FIBRE BOARD TO ASTM C612, WITH FACTORY APPLIED VAPOUR
RETARDER JACKET TO CGSB 51-GP-52MA.
2.7.4.2 MINERAL FIBRE BLANKET TO ASTM C553 FACED WITH FACTORY APPLIED
VAPOUR RETARDER JACKET TO CGSB 51-GP-52MA, MINERAL FIBRE: TO ASTM C553,
JACKET: TO CGSB 51-GP-52MA, MAXIMUM "K" FACTOR: TO ASTM C553.
2.7.4.3 TAPE: SELF-ADHESIVE, ALUMINUM, PLAIN REINFORCED, 75 50MM WIDE
MINIMUM.
2.7.4.CONTACT ADHESIVE: QUICK-SETTING, MAXIMUM VOC LIMIT 250 50 200G/L TO
SCAQMD RULE 1168 GSES GS-36.
2.8 EQUIPMENT INSULATION:
2.8.1 RIGID MOULDED MINERAL FIBRE WITH FACTORY APPLIED VAPOUR RETARDER
JACKET. MINERAL FIBRE: ASTM C547. JACKET: TO CGSB 51-GP-52MA. MAXIMUM "K"
FACTOR: ASTM C547.
2.8.2 RIGID MINERAL FIBRE BOARD FACED WITH FACTORY APPLIED VAPOUR
RETARDER JACKET. MINERAL FIBRE: ASTM C612. JACKET: TO CGSB 51-GP-52MA.
MAXIMUM "K" FACTOR: ASTM C612.
2.8.3 MINERAL FIBRE BLANKET FACED WITH FACTORY APPLIED VAPOUR RETARDER
JACKET. MINERAL FIBRE: ASTM C553. JACKET: TO CGSB 51-GP-52MA. MAXIMUM "K"
FACTOR: ASTM C553.
2.8.4 FLEXIBLE UNICELLULAR TUBULAR ELASTOMER. INSULATION: WITH VAPOUR
RETARDER JACKET. JACKET: TO CGSB 51-GP-52MA. MAXIMUM "K" FACTOR.
CERTIFIED BY MANUFACTURER FREE OF POTENTIAL STRESS CORROSION CRACKING
CORRODENTS.
3.0 EXECUTION
3.1 PROVIDE DRAIN PIPES FROM EQUIPMENT AND/OR FIXTURES TO FLOOR DRAINS AS
REQUIRED.
3.2 ALL EQUIPMENT CONNECTIONS SHALL HAVE ISOLATION VALVES AND UNIONS OR
FLANGED CONNECTIONS.
3.3 VALVE SIZES SHALL BE THE SAME LINE SIZE UNLESS NOTED OTHERWISE.
PROVIDE ISOLATING VALVES IN EACH BRANCH FROM THE MAIN LINE AND WHERE
SHOWN. PROVIDE ISOLATING VALVES FOR ALL EQUIPMENT.
3.4 PROVIDE SHOCK ABSORBERS UPSTREAM OF ALL SOLENOID VALVES, FLUSH
VALVES AND/OR OTHER QUICK CLOSING VALVES.
3.5 PROVIDE VACUUM BREAKERS AND BACKFLOW PREVENTERS WHERE REQUIRED BY
CODE.
3.6 ALL PIPE, FITTINGS, FIXTURES AND EQUIPMENT SHALL BE RIGIDLY SUPPORTED.
ALL FASTENINGS TO BUILDING STRUCTURE SHALL BE FIRMLY MADE WITHOUT
DAMAGE TO BUILDING STRUCTURE.
3.7 PIPES SHALL BE CONCEALED IN WALLS, CEILINGS, CHASES, PIPE SHAFTS, ETC.
EXCEPT IN MECHANICAL ROOMS, SERVICE ROOMS AND AS INDICATED OTHERWISE.
3.8 PROVIDE DIELECTRIC UNIONS BETWEEN PIPES OF DISSIMILAR MATERIAL.
3.9 PROVIDE CHROME PLATED ESCUTCHEONS AT ALL POINTS WHERE PIPES PASS
THROUGH FINISHED WALLS, CEILINGS OR FLOORS.
3.10 SUPPORT CAST IRON PIPES AT 1.5 M MAXIMUM INTERVALS; COPPER PIPES AT 2.4
M MAXIMUM INTERVALS; STEEL PIPE AT 3 M MAXIMUM INTERVALS.
SECTION 15200 - FIRE PROTECTION
1.0 GENERAL
1.01 SEE SECTION 15000 ABOVE.
2.0 PRODUCTS
2.1 ALL FIRE PROTECTION PRODUCTS, COMPONENTS, PARTS, ASSEMBLIES,
ACCESSORIES, ETC. SHALL BE SUITABLE FOR THE INTENDED APPLICATION, MEETING
APPLICABLE CODES & STANDARDS INDICATED, SHALL BE APPROVED AND BEAR THE
ULC, UL, FM LISTING / LABEL.
2.2 FIRE EXTINGUISHERS:
2.2.1 MULTI-PURPOSE DRY CHEMICAL: MULTI-PURPOSE (ABC) TYPE, DRY CHEMICAL,
SIZE:10 LB. (4.54 KG), RATING: MINIMUM 6A:80BC, NATIONAL FIRE EQUIPMENT
ABC-100WWD.
2.2.2 CARBON DIOXIDE CO2: CARBON DIOXIDE CO2 (BC), SIZE: 10 LB. (4.54 KG),
RATING:MINIMUM 10B:C, BRACKET: VB-2 (20976) NATIONAL FIRE EQUIPMENT BADGER
10 BV-C (24208).
2.3 SPRINKLER PIPING:
2.3.1 STEEL PIPE: ASTM A53; JOINED WITH THREADED FITTINGS OR CUT GROOVE PIPE
AND FITTINGS: SCHEDULE 40 FOR SIZES 6" (150MM) DIAMETER AND SMALLER,
SCHEDULE 30 FOR SIZES 8" (200MM) DIAMETER AND LARGER.
2.3.2 STEEL FITTINGS: ASME B16.9, WROUGHT STEEL, BUTTWELDED; CAST IRON
FITTINGS: ASME B16.1, FLANGES AND FLANGED FITTINGS; MALLEABLE IRON FITTINGS:
ASME B16.3, THREADED FITTINGS.
2.3.3 MECHANICAL GROOVED COUPLINGS: MALLEABLE IRON HOUSING CLAMPS TO
ENGAGE AND LOCK, "C" SHAPED ELASTOMERIC SEALING GASKET, STEEL BOLTS,
NUTS, AND WASHERS; GALVANIZED FOR GALVANIZED PIPE.
2.3.4 MECHANICAL FORMED FITTINGS: CARBON STEEL HOUSING WITH INTEGRAL PIPE
STOP AND O-RING POCKED AND O-RING, UNIFORMLY COMPRESSED INTO PERMANENT
MECHANICAL ENGAGEMENT ONTO PIPE.
2.4 SPRINKLERS:
2.4.1 SUSPENDED CEILING: SEMI-RECESSED PENDANT TYPE WITH MATCHING PUSH
ON ESCUTCHEON PLATE, ULC LISTED. SPRINKLER & ESCUTCHEON PLATE FINISH:
(COLOR SELECTION BY ARCHITECT) CHROME PLATED. FUSIBLE LINK: GLASS BULB
TYPE TEMPERATURE RATED FOR SPECIFIC AREA HAZARD.
2.4.2 EXPOSED AREA TYPE: STANDARD UPRIGHT TYPE WITH GUARD, ULC LISTED.
FINISH: BRASS.FUSIBLE LINK: GLASS BULB TYPE TEMPERATURE RATED FOR SPECIFIC
AREA HAZARD.
2.4.4 GUARDS: FINISH TO MATCH SPRINKLER FINISH.
2.4.5 SPRINKLERS, EXCUTHEONS, COVER, ACCESSORIES, FINISH, ETC. TO MATCH.
2.4.6 PROVIDE SPRINKLERS PER ABOVE UNLESS NOTED OTHERWISE. COORDINATE
WITH ARCHITECTURAL DOCUMENTS.
3.0 EXECUTION
3.1 FURNISH AND INSTALL FIRE EXTINGUISHERS & AUTOMATIC WET SPRINKLERS
THROUGHOUT ALL AREAS OF THE BUILDING AS INDICATED UNLESS SPECIFICALLY
EXEMPTED BY APPLICABLE CODES & STANDARDS.
3.2 FIRE PROTECTION SYSTEM SHALL BE DESIGNED & INSTALLED IN ACCORDANCE
WITH APPLICABLE CODES & STANDARDS.
3.3 REFER TO ARCHITECTURAL DRAWINGS FOR BUILDING CODE DETAILS –
CONSTRUCTION TYPE, CONSTRUCTION MATERIALS, AREAS, ELEVATIONS, SPRINKLER
& STANDPIPE REQUIREMENTS, ETC.
3.4 PERFORM FIRE HYDRANT FLOW TEST WITNESSED AUTHORITIES. FLOW TEST
INFORMATION SHALL BE USED FOR SPRINKLER DESIGN AND HYDRAULIC
CALCULATIONS. SUBMIT TO CONSULTANT AND OWNER FOR REVIEW AND COMMENT.
3.5 PREPARE SUBMITTAL DOUMENTS (PLANS, SPECIFICATIONS, LAYOUTS, DETAILS,
DIAGRAMS, CALCULATIONS, EQUIPMENT INFORMATION/CUTSHEETS, ETC.)
CONFORMING TO APPLICABLE CODES & STANDARDS INDICATED ABOVE.
CALCULATIONS, EQUIPMENT SELECTIONS, SIZING, ETC. SHALL BE BASED ON ACTUAL
EQUIPMENT / COMPONENTS USED, LAYOUT / INSTALLATION, FLOW TEST RESULTS,
MEASUREMENT LOCATIONS, DESIGN AREAS, DESIGN DENSITIES, & HOSE
ALLOWANCES INDICATED. DOCUMENTS SHALL INDICATE THE CODES, STANDARDS,
EDITIONS, ETC. USED IN THE PREPARATIONS OF THE DOCUMENTS AND COMPLIANCE
WITH THOSE CODES & STANDARDS. SUBMITTAL DOCUMENTS SHALL BE SIGNED &
STAMPED / SEALED BY FIRE PROTECTION ENGINEER OF RECORD PRIOR TO
SUBMISSION. CONTRACTOR & HIS ENGINEER OF RECORD SHALL BE RESPONSIBLE
FOR THE COMPLETE & FULLY FUNCTIONAL FIRE PROTECTION SYSTEM DESIGN,
ENGINEERING & INSTALLATION.
3.6 PROVIDE SUBMITTAL DOCUMENTS TO CONSULTANT / ENGINEER AFTER SUBMITTAL
DOCUMENTS HAVE BEEN SUBMITTED, REVIEWED, CORRECTED, UPDATED AND
APPROVED BY AUTHORITIES HAVING JURISDICTION.
3.7 SPRINKLER MINIMUM AREA & DESIGN WATER FLOW DENSITY SHALL BE AS
FOLLOWS:
LIGHT HAZARD: 1500 SQFT 0.1 GPM/SQFT
ORDINARY GROUP 11500 SQFT 0.15 GPM/SQFT
ORDINARY GROUP 21500 SQFT 0.2 GPM/SQFT
EXTRA HAZARD GROUP 12500 SQFT 0.3 GPM/SQFT
EXTRA HAZARD GROUP 22500 SQFT 0.4 GPM/SQFT
3.8 HOSE STREAM ALLOWANCE & WATER SUPPLY DURATION SHALL BE AS FOLLOWS:
LIGHT HAZARD 100 GPM 30 MINUTES
ORDINARY HAZARD 250 GPM 60-90 MINUTES
EXTRA HAZARD 500 GPM 90-120 MINUTES
3.9 PIPING INSTALLATION
3.10 ALL SPRINKLERS SHALL HAVE DEFLECTORS INSTALLED BELOW ROOF AND/OR
CEILING ASSEMBLIES BETWEEN 1" TO 22" MAXIMUM DEPENDING ON THE TYPE OF
ROOF AND/OR CEILING CONSTRUCTION CLASSIFICATION.
3.11 INSTALL AUTOMATIC SPRINKLERS BELOW DUCTWORK, HORIZONTAL OVERHEAD
DOORS AND OTHER OBSTRUCTIONS 48" IN WIDTH AND LARGER. THIS INCLUDES
MULTIPLE DUCTS, PIPES, CONDUITS, ETC. LOCATED SUCH THAT TOGETHER A 48"
OBSTRUCTION IS FORMED. PROVIDE SPRINKLERS ABOVE AND BELOW THE
HORIZONTAL DOORS UNLESS NOTED OTHERWISE.
3.12 LOCATE SPRINKLERS AT CENTER OF ACOUSTIC TILE / GRID CEILINGS WHENEVER
POSSIBLE. SPRINKLER HEAD LOCATIONS MAY CHANGE FOR COORDINATION WITH
EXISTING CONDITIONS & OTHER TRADES.
3.13 PIPES 1" TO 4" SHALL BE SUPPORTED WITH 3/8" ALL THREAD ROD AND 3/8"
HANGER ASSEMBLIES. 5" TO 6" PIPE TO BE SUPPORTED WITH 1/2" ALL THREAD ROD
AND 1/2" HANGER ASSEMBLIES.
3.14 BEFORE ANY SPRINKLER PIPING IS CONCEALED, NOTIFY THE FIRE DEPARTMENT
FOR INSPECTION 48 HOURS IN ADVANCE.
3.15 CONDUCT PIPING SYSTEM FLUSHING, HYDROSTATIC SYSTEM TEST & MAIN DRAIN
TEST. HYDROSTATIC TEST OVERHEAD PIPING @ 200 PSI FOR 2 HOURS. NOTIFY FIRE
DEPARTMENT 48 HOURS IN ADVANCE. CORRECT DEFFICIENCIES ENCOUNTERED
UNTIL ALL SYSTEM TESTS ARE PASSED. PERFORM ALL TESTING IN THE PRESENCE OF
THE AUTHORITIES. SUBMIT ALL TEST RESULTS TO THE CONSULTANT. SUBMIT
INSPECTOR'S TEST REPORT ON COMPLETION.
3.16 PROVIDE A CERTIFICATE STATING THAT THE FIRE PROTECTION SYSTEM WAS
INSTALLED IN FULL COMPLIANCE WITH APPLICABLE CODES & STANDARDS INDICATED
ABOVE AND THAT ALL APPLICABLE TESTS HAVE PERFORMED AND PASSED AT THE
CLOSURE OF THE PROJECT.
3.17 SUBMIT AS-BUILT DRAWINGS AND FINAL HYDRAULIC CALCULATIONS
REPRESENTING THE SYSTEM AS INSTALLED TO THE FIRE DEPARTMENT FOR FINAL
REVIEW AND ACCEPTANCE.
3.18 PROVIDE CONTRACTOR'S MATERIAL AND TEST CERTIFICATES WITH O & M
MANUALS.
SECTION 15400 - PLUMBING
1.0 GENERAL
1.1 SEE SECTION 15000 ABOVE.
2.0 PRODUCTS
2.1 PLUMBING FIXTURES:
2.1.1 ALL PLUMBING FIXTURES & EQUIPMENT SHALL MEET THE LATEST SAFETY &
WATER EFFICIENCY REQUIREMENTS OF THE APPLICABLE CODES & STANDARDS.
2.1.2 DF1: WATER FOUNTAIN: BI-LEVEL TYPE, SURFACE MOUNTED, STAINLESS STEEL
CONSTRUCTION, 115 V/ 60HZ , ADA COMPLIANT WITH A TOUCHLESS ACTIVATED
WATER FILLING STATION, GREEN TICKER DISPLAYING COUNT OF PLASTIC BOTTLES
SAVED, INTEGRATED WATER COOLING SYSTEM, ANTI-MICROBIAL FLEXI-GUARD
BUBBLER. ACCEPTABLE PRODUCT PRODUCT: ELKAY EZH2O BOTTLE FILLING STATION
EZSTL8WS(S)K OR APPROVED EQUAL.
2.1.3 S1: KITCHEN SINK: STAINLESS STEEL, TYPE 304 (18/10), NO. 4 SATIN FINISHED,
SINGLE COMPARTMENT, SELF-RIMMING DROP SINK (16.75” L X16.75” W X 8“ D) WITH
FAUCET LEDGE, 18 GAUGE (1.2 MM) WITH NO OVERFLOW, UNDERCOAT, 3 ½’’ CUP
STRAINER, 1 ½’’ BRASS TAILPIECE. ACCEPTABLE PRODUCT: FRANKE LBS6808 OR
APPROVED EQUAL. FAUCET: SINGLE HOLE, SINGLE LEVER, CHROME PLATED, 9 ½’’
CENTER TO CENTER INTEGRAL CAST BRASS SPOUT, 1.5 GPM (5.7 L/S) MAX.,
NON-AERATING OUTLET, CERAMIC CARTRIDGE, USER ADJUSTABLE TEMPERATURE
CONTROL MIXER, TEMPERATURE LIMITER, RATED OPERATING PRESSURE: 20-125 PSI,
RATED OPERATING TEMPERATURE: 40-140°F, ADA COMPLIANT. ACCEPTABLE
PRODUCT: CHICAGO FAUCET 430-ABCP OR APPROVED EQUAL. MCGUIRE LFH170BV
FAUCET SUPPLIES, CHROME PLATED FINISH POLISHED BRASS, COMMERCIAL DUTY 1/4
TURN BALL VALVE ANGLE STOPS, 13 MM (1/2") I.D. INLET X 127 MM (5") HORIZONTAL
EXTENSION TUBES, COMBINATION V.P. LOOSE KEY HANDLES, ESCUTCHEON AND
FLEXIBLE COPPER RISERS, 8912CB P-TRAP, CHROME PLATED FINISH, HEAVY CAST
BRASS ADJUSTABLE BODY WITH SLIP NUT, 38 MM (1-1/2") SIZE, WITH CLEANOUT, BOX
FLANGE AND SEAMLESS TUBULAR WALL BEND.
2.2 PLUMBING EQUIPMENT:
2.2.1 WATER HAMMER ARRESTOR: STAINLESS STEEL OR COPPER CONSTRUCTION,
PISTON OR BELLOW STYPE: TO PDI-WH201.
2.2.2 BACKFLOW PREVENTER: TO CSA-B64 SERIES, APPLICATION DOUBLE CHECK
VALVE ASSEMBLY AS INDICATED, REDUCED PRESSURE PRINCIPLE TYPE BACK FLOW
PREVENTER WITH INTERMEDIATE VACUUM BREAKER ATMOSPHERIC VENT.
2.2.3 STRAINERS: 860KPA, Y TYPE WITH 20 MESH, MONEL, BRONZE OR STAINLESS
STEEL REMOVABLE SCREEN. NPS 2 AND UNDER, BRONZE BODY, SCREWED ENDS,
WITH BRASS CAP. NPS 2 1/2 AND OVER, CAST IRON BODY, FLANGED ENDS, WITH
BOLTED CAP.
2.2.4 WH1 POINT OF USE ELECTRIC MINI STORAGE TANK WATER HEATER: COMPACT
DESIGN ETL TESTED TO UL 174 & NSF 372 WITH ENAMELED GLASS LINED SINGLE WELD
TANK, WATER CONNECTIONS, T&P VALVE, STATUS INDICATOR LIGHT, ADJUSTABLE
THERMOSTAT (50°-140°F), 6-YEAR WARRANTY, FLOOR / WALL MOUNT / BRACKET,
STANDARD 120 VOLT POWER CORD & PLUG. ACCEPTABLE PRODUCT: RHEEM
MINI-TANK PROE OR APPROVED EQUAL.
2021-08-0921-023
PROJECT No.
DRAWN BY
DATE
CAD FILE
SHEET
ISSUE DATE (Y-M-D) No. ISSUED FOR
CLIENT
SCALE
374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E studio@passa.ca
Passa Associates Inc. WWW.PASSA.CA
PROJECT
ARCHITECTS
Please note that all information included in these drawing files is protected by
copyright. Unauthorized use of these files without the written permission of
Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects
is responsible only for information shown on a mechanical reproduction of these
drawings that have been signed and stamped by an architect with signing
authority employed by the firm.
If you require further information please contact our office at the numbers listed.
A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR
2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.
AUG. 09, 2021
UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.
2021-06-25 1 PROGRESS
2021-06-30 2 PERMIT
2021-07-14 3 FINAL REVIEW
2021-07-27 4 PROGRESS
2021-08-09 5 PERMIT & TENDER
JACE #21-023 M3
MECHANICAL SPECIFICATIONS
1/8" - 1'-0"
2.3 PLUMBING PIPING
2.3.1 SANITARY DRAINAGE PIPING – BURIED: 2" (50 MM) AND SMALLER DIAMETER,
HARD TEMPER COPPER PIPE, TYPE L; 3" (75 MM) AND LARGER DIAMETER, CAST IRON
SOIL PIPE, NO-HUB MECHANICAL JOINT WITH NEOPRENE GASKETS AND STAINLESS
STEEL PIPE CLAMPS.
2.3.2 SANITARY DRAINAGE PIPING - ABOVE GRADE: 2" (50 MM) AND SMALLER
DIAMETER, HARD TEMPER COPPER TUBE, TYPE DWV, SOLDERED, WITH WROUGHT
COPPER OR COPPER DRAINAGE FITTINGS OR CAST BRASS DRAINAGE FITTINGS; 3" (75
MM) AND LARGER DIAMETER, CAST IRON SOIL PIPE, NO-HUB MECHANICAL JOINT WITH
NEOPRENE GASKETS AND STAINLESS STEEL PIPE CLAMPS WITH CAST IRON
DRAINAGE FITTINGS.
2.3.3 VENT PIPING – BURIED: 2" (50 MM) AND SMALLER DIAMETER, HARD TEMPER
COPPER PIPE, TYPE L, TO ASTM B42-87, WITH WROUGHT COPPER OR COPPER ALLOY
SOLDER JOINT TO ANSI B16.29-73 OR CAST BRASS SOLDER JOINT TO CSA B158.1-1976.
2.3.4 VENT PIPING - ABOVE GRADE: 2" (50 MM) AND SMALLER DIAMETER, HARD
TEMPER COPPER TUBE, TYPE DWV 3" (75 MM) AND LARGER DIAMETER, CAST IRON
SOIL PIPE, NO HUB MECHANICAL JOINT WITH CAST IRON DRAINAGE FITTINGS
2.3.5 STORM - HUBLESS CAST-IRON PIPE AND FITTINGS TO ASTM A 888 OR CISPI 301.
SHIELDED COUPLINGS TO ASTM C 1277 METAL SHIELD OR HOUSING,
CORROSION-RESISTANT FASTENERS, RUBBER SLEEVE, CENTER PIPE STOP.
2.3.6 WATER PIPING - ABOVE GRADE: COPPER TUBING 3" (75MM) AND SMALLER TYPE L,
HARD DRAWN FITTINGS: CAST COPPER ALLOY OR WROUGHT COPPER AND BRONZE.
2.3.7 ISOLATING VALVES: UP TO AND INCLUDING 2" (50 MM): MANUFACTURER: KITZ
69AMLL, CONSTRUCTION: MSS SP-110, 1034 KPA (150 PSIG) 600 WOG, FORGED BRASS,
TWO PIECE BODY, STAINLESS STEEL BALL AND STEM, FULL PORT, VIRGIN PTFE SEATS
AND STEM PACKING OR DOUBLE "O" RING, BLOW-OUT PROOF STEM, LEVER HANDLE,
STEM EXTENSIONS FOR INSULATED PIPING, SOLDER ENDS.
SECTION 15600 – HEATING, VENTILATING & AIR CONDITIONING
1.0 GENERAL
1.1 SEE SECTION 15000 ABOVE.
2.0 PRODUCTS
2.1 DUCTWORK & ACCESSORIES:
2.1.1 DUCT LEAKAGE: PER SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL.
2.1.2 SEAL CLASSIFICATION: 125 PA MAX: UNSEALED, 500 PA MAX: SMACNA SEAL
CLASS C. CLASS C: TRANSVERSE JOINTS AND CONNECTIONS MADE AIR TIGHT WITH
TAPE SEALANT GASKETS OR COMBINATION THEREOF. LONGITUDINAL SEAMS
UNSEALED.
2.1.3 SEALANT: ADHESIVES AND SEALANTS: VOC LIMIT 30 70 250G/L MAXIMUM TO
SCAQMD RULE 1168 GS-36. SEALANT: OIL RESISTANT, WATER BORNE, POLYMER TYPE
FLAME RESISTANT CLEAR DUCT SEALANT. TEMPERATURE RANGE OF MINUS
30DEGREES C TO PLUS 93DEGREES C.
2.1.4 FITTINGS: FABRICATION TO SMACNA.
2.1.4.1 RADIUSED ELBOWS: RECTANGULAR: STANDARD RADIUS SHORT RADIUS WITH
SINGLE THICKNESS TURNING VANES, CENTRELINE RADIUS: 1.5 TIMES WIDTH OF
DUCT. ROUND: SMOOTH RADIUS FIVE PIECE, CENTRELINE RADIUS: 1.5TIMES
DIAMETER.
2.1.4.2 MITRED ELBOWS, RECTANGULAR: TO 400MM: WITH SINGLE DOUBLE
THICKNESS TURNING VANES. OVER 400MM: WITH DOUBLE THICKNESS TURNING
VANES.
2.1.4.3 BRANCHES: RECTANGULAR MAIN AND BRANCH: WITH 45 DEGREES ENTRY ON
BRANCH RADIUS ON BRANCH 1.5 TIMES WIDTH OF DUCT. ROUND MAIN AND BRANCH:
ENTER MAIN DUCT AT 45 DEGREES WITH CONICAL CONNECTION. PROVIDE VOLUME
CONTROL DAMPER IN BRANCH DUCT NEAR CONNECTION TO MAIN DUCT. MAIN DUCT
BRANCHES: WITH SPLITTER DAMPER.
2.1.4.4 TRANSITIONS: DIVERGING: 20DEGREES MAXIMUM INCLUDED ANGLE.
CONVERGING: 30DEGREES MAXIMUM INCLUDED ANGLE.
2.1.4.5 OFFSETS: AS INDICATED SHORT FULL RADIUSED ELBOWS. OBSTRUCTION
DEFLECTORS: MAINTAIN FULL CROSS-SECTIONAL AREA. MAXIMUM INCLUDED
ANGLES: AS FOR TRANSITIONS.
2.2 FIRE STOPPING: RETAINING ANGLES AROUND DUCT, ON BOTH SIDES OF FIRE
SEPARATION. FIRE STOPPING MATERIAL AND INSTALLATION MUST NOT DISTORT
DUCT.
2.3 HANGERS AND SUPPORTS: STRAP HANGERS: OF SAME MATERIAL AS DUCT BUT
NEXT SHEET METAL THICKNESS HEAVIER THAN DUCT. MAXIMUM SIZE DUCT
SUPPORTED BY STRAP HANGER: 500 MM. HANGER CONFIGURATION: TO SMACNA &
ASHRAE. HANGERS: GALVANIZED BLACK STEEL ANGLE WITH BLACK GALVANIZED
STEEL RODS TO ASHRAE & SMACNA. UPPER HANGER ATTACHMENTS: FOR
CONCRETE: MANUFACTURED CONCRETE INSERTS. FOR STEEL JOIST:
MANUFACTURED JOIST CLAMP STEEL PLATE WASHER. FOR STEEL BEAMS:
MANUFACTURED BEAM CLAMPS.
2.4 DUCT MATERIAL:
2.4.1 GALVANIZED STEEL: LOCK FORMING QUALITY: TO ASTM A653/A653M, Z90ZINC
COATING. THICKNESS, FABRICATION AND REINFORCEMENT: TO SMACNA ASHRAE.
JOINTS: TO SMACNA PROPRIETARY MANUFACTURED DUCT JOINT ASHRAE.
PROPRIETARY MANUFACTURED FLANGED DUCT JOINT TO BE CONSIDERED TO BE A
CLASS A SEAL.
2.4.2 DUCTS AND FITTINGS SHALL BE FABRICATED FROM GALVANIZED SHEET STEEL,
LOCK FORMING QUALITY TO ASTM A525 WITH Z275 ZINC COATING. DUCT
CONSTRUCTION SHALL BE PER SMACNA FOR 2 INCHES W.C. PRESSURE CLASS WITH
MAXIMUM LEAKAGE RATE OF 5%. DUCT CONNECTIONS AND TRANSVERSE JOINTS
SHALL BE SEALED WITH SEALANT AND TAPE.
2.4.3 DUCT MATERIAL THICKNESS SHALL BE AS FOLLOWS:
MAXIMUM SIZE OR DIAMETERTHICKNESS
UP TO 300 MM 26 U.S. STANDARD GAUGE
301 TO 750 MM 24 U.S. STANDARD GAUGE
2.4.4 FLEXIBLE DUCT: INSULATED, UL-181/ETL CLASS I AIR DUCT, NFPA 90A COMPLIANT,
LOW TO MEDIUM PRESSURE APPLICATION, ALUMINUM FOIL, FIBREGLASS AND
ALUMINIZED POLYESTER LAYERS, CORROSION RESISTANT GALVANIZED STEEL HELIX,
FIRE RETARDANT REINFORCED VAPOUR BARRIER, FIBERGLASS INSULATION BLANKET,
FACTORY WRAPPED, 5 FEET MAXIMUM LENGTH. FLEXMASTER 5B OR APPROVED
EQUAL.
2.4.5 FLEXIBLE CONNECTIONS SHALL BE FIRE RESISTANT, SELF EXTINGUISHING,
NEOPRENE COATED GLASS FABRIC WITH GALVANIZED SHEET METAL FRAME.
2.4.6 VOLUME DAMPERS (SINGLE BLADE UP TO 12 INCHES DEEP) SHALL BE SAME
MATERIAL AS DUCT, NEXT GAUGE HEAVIER THAN DUCT, V GROVE STIFFENED,
LOCKING QUADRANT, SHAFT EXTENSION, BRONZE END BEARINGS, CHANNEL FRAME
AND ANGLE STOP. DAMPERS FOR DUCTS GREATER THAN 12 INCHES DEEP SHALL BE
PARALLEL BLADE, PIN IN BRONZE BUSHING, LOCKING QUADRANT, SHAFT EXTENSION,
ANGLE STOP, CHANNEL FRAME INTERCONNECTED. BLADES UP TO 30 INCHES IN
LENGTH SHALL HAVE A MAXIMUM WIDTH OF 10 INCHES, BLADES LONGER THAN 30
INCHES SHALL HAVE A MAXIMUM WIDTH OF 12 INCHES. KERR HUNT OR APPROVED
EQUAL.
2.4.6 MULTI LEAF CONTROL DAMPERS SHALL BE OPPOSED OR PARALLEL BLADE,
STRUCTURALLY FORMED STEEL, INTERLOCKING BLADES, EXTRUDED VINYL SEALS,
STAINLESS STEEL SPRING SIDE SEALS, STRUCTURALLY FORMED AND WELDED
GALVANIZED STEEL FRAME, PRESSURE FIT SELF LUBRICATED BRONZE BEARINGS,
PLATED STEEL TIE RODS, BRASS PIVOTS, PLATED STEEL BRACKETS AND CONTROL
ROD. JOHNSON CONTROLS, HONEYWELL, OR SIEMENS.
2.4.7 DAMPER MOTORS SHALL BE 2 POSITION OR MODULATING, 24 VAC, SPRING
RETURN, NORMALLY OPEN/CLOSED AS APPLICABLE. JOHNSON CONTROLS, BELIMO,
HONEYWELL, SIEMENS.
2.4.10 FIRE DAMPERS SHALL BE FACTORY FABRICATED GALVANIZED STEEL, CHANNEL
FRAME, CURTAIN TYPE, LOW RESISTANCE TYPE B, INTERLOCKING BLADES, 160
DEGREES F FUSIBLE LINK, UL LISTED AND LABELED FOR 1 ½ HOUR RATING. FUSIBLE
LINKS FOR 105 DEGREES F, 182 DEGREES F OR 285 DEGREES F, SHALL BE PROVIDED
AS INDICATED ON DRAWINGS. RUSKIN, CONTROLLED AIR OR APPROVED EQUAL.
2.4.8 TURNING VANES SHALL BE FACTORY OF SHOP FABRICATED SINGLE THICKNESS
WITH TRAILING EDGE.
2.4.9 ACCESS DOORS SHALL BE SANDWICH CONSTRUCTION OF SAME MATERIAL AS
DUCT, ONE SHEET METAL THICKNESS HEAVIER, MINIMUM 0.0236 INCH THICK WITH
SHEET METAL ANGLE FRAME, 1-1/2 IN. RIGID FIBER GLASS INSULATION, AND
NEOPRENE OR FOAM RUBBER GASKETS.
2.5 DIFFUSERS, GRILLES & REGISTERS
2.5.1 CEILING DIFFUSERS: ADJUSTABLE, SQUARE CONE STEEL CONSTRUCTION, 24
INCHES X 24 INCHES FACE, ROUND INLET, OFF WHITE BAKED ENAMEL FINISH,
MOUNTING TYPE TO MATCH CEILING. FINISH SHALL BE AS SELECTED BY ARCHITECT.
EH PRICE SCDA OR APPROVED EQUAL.
2.5.2 RETURN/EXHAUST GRILLES SHALL BE ½ IN X ½ IN X ½ IN ALUMINUM GRID EGG
CRATE CORE, ALUMINUM BORDER AND FRAME, T BAR LAY IN TYPE, OFF WHITE BAKED
ENAMEL FINISH. SEE DRAWINGS FOR SIZE AND TYPE. E. H. PRICE 80 SERIES OR
APPROVED EQUAL.
2.5.3 TRANSFER GRILLE: HEAVY DUTY EXTRUDED ALUMINUM CONSTRUCTION, LARGE
FREE AREA, COMPLETELY SIGHTPROOF OR LIGHTPROOF CORE, AND RUGGED
MANDREL TUBE CONSTRUCTION OF HEAVY GAUGE EXTRUDED ALUMINUM AS
REQUIRED FOR SEVERE USE APPLICATIONS. FINISH SELECTION BY ARCHITECT.
ACCEPTABLE MANUFACTURER: PRICE MODEL ATG / ATGH SERIES.
2.5.4 HOODED WALL CAP: FOR OUTSIDE WALL APPLICATIONS, STEEL CONSTRUCTION
WITH BLACK ENAMEL FINISH, BUILT-IN BIRDSCREEN, DAMPER, SQUARE OR
RECTANGULAR CONNECTIONS. PERFORMANCE SHALL NOT EXCEED 0.1” STATIC
PRESSURE DROP AT DESIGN FLOW RATE. ACCEPTABLE PRODUCT: GREENHECK
MODEL WC OR APPROVED EQUAL.
2.6 CROSS TALK SILENCER: CONSTRUCTED TO ASHRAE & SMACNA STANDARDS
(PRESSURE & VELOCITY CLASSIFICATION OF THE AIR DISTRIBUTION SYSTEM) WITH 22
GAUGE SOLID STEEL CASING, 26 GAUGE SOLID STEEL INTERNAL NOSES AT IN-LET
AND OUTLET, ¾ INCH DUAL DENSITY ABSORPTIVE FIBERGLASS ACOUSTIC MEDIA
(SHOT-FREE INORGANIC GLASS FI-BER WITH LONG, RESILIENT FIBERS, BONDED WITH
THERMOSETTING RESIN) WITH BUTTON LOCK, PITTSBURGH LOCK, AND WELDS &
COMPLIANCE TO ASTM STANDARD E477, UL 181, ASTM C1071, ASTM E84, NFPA 255 OR
UL 723. ACCEPTA-BLE PRODUCT: EH PRICE XTL, XTZ, XTU OR APPROVED EQUAL.
2.7 TERMINAL UNIT (FAN POWERED): PRESSURE INDEPENDENT UNIT WITH
ZINC-COATED STEEL HOUSING, MECHANICALLY SEALED, LEAK-RESISTANT
CONSTRUCTION, 22 OR 20 GAUGE CONSTRUCTION, 2 IN. COLLAR, 3/4 IN. [19] THICK,
MIN. 1.5 LB DENSITY FIBERGLASS INTERNAL INSULATION, RECIRCULATING FAN,
BOTTOM ACCESS PANEL, ECM MOTORS (60 CYCLE, SINGLE PHASE, 115, 208, 240, 277
VAC LUBRICATED, PERMANENT SPLIT CAPACITOR TYPE), VIBRATION ISOLATORS,
SOLID STATE SPEED CONTROLLER, SCR TO AHRI 880, UL1995, CSA NO. 236, UL 181
AND NFPA-90A. ACCEPTABLE PROD-UCT: PRICE FPC, TITUS, KRUEGER, CARNES.
2.8 FANS
2.8.1 PERFORMANCE REQUIREMENTS: BASED ON TESTS PERFORMED IN
ACCORDANCE WITH ANSI/AMCA STANDARD 210, UNIT TO BEAR AMCA CERTIFIED
RATING SEAL. STATICALLY AND DYNAMICALLY BALANCED. CONSTRUCTED TO
ANSI/AMCA STANDARD 99. SOUND RATINGS: TO ANSI/AMCA STANDARD 301, TESTED
TO ANSI/AMCA STANDARD 300. UNIT SHALL BEAR AMCA CERTIFIED SOUND RATING
SEAL. PANASONIC.
2.8.2 BEARINGS: HEAVY DUTY GREASE LUBRICATED BALL OR ROLLER BEARINGS,
SEALED LIFETIME, BALL, OILITE BEARINGS, SELF ALIGNING TYPE WITH OIL RETAINING,
DUST EXCLUDING SEALS AND A CERTIFIED MINIMUM RATED LIFE OF 80,000
100,000HOURS.
2.8.3 CEILING FANS: CEILING MOUNTED EXHAUST FANS, CENTRIFUGAL DIRECT DRIVE,
FAN HOUSING OF HEAVY-GAUGE GALVANIZED STEEL, LINED WITH 1/2 INCH (13 MM)
ACOUSTICAL INSULATION, OUTLET DUCT COLLAR, BACKDRAFT DAMPER, HORIZONTAL
OR VERTICAL DISCHARGE, DESIGNER GRILLE, MOTOR DISCONNECT PLUG-IN TYPE,
MOTOR VIBRATION ISOLATORS, FAN WHEEL FORWARD-CURVED CENTRIFUGAL,
DYNAMICALLY BALANCED, AMCA CERTIFIED RATINGS SOUND AND AIR PERFORMANCE
SEAL, UL/CUL LISTED. PERFORMANCE: 155 CFM, 0.375" ESP, 1400 RPM, 115VAC, 54.2
WATTS. ACCEPTABLE MANUFACTURE: GREENHECK MODELS SP-A190 OR EQUAL
FROM PENN BARRY, PANASONIC, BROAN, NUTONE.
2.9 CONTROLS:
2.9.1 THE CONTRACTOR SHALL PROVIDE A COMPLETE BUILDING DDC CONTROL
SYSTEM TO COMPLY WITH SEQUENCES OF OPERATIONS OUTLINED HEREIN. PROVIDE
SENSORS, RELAYS, CONTROL WIRING, CONTROL POWER WIRING FROM DEDICATED
J-BOX (J-BOX BY E.C.), TRANSFORMERS, ENCLOSURES, MOUNTING HARDWARE, AND
CT'S AS REQUIRED TO MONITOR, ADJUST, AND COMMUNICATE THE SEQUENCES
INDICATED. SUBMIT BAS SCREEN SHOTS OF THE GRAPHICS TO THE CONSULTANT
FOR REVIEW AS PART OF THE COMMISSIONING PROCESS.
2.9.2 PROVIDE A GLOBAL CONTROL SYSTEM THAT CAN COMMUNICATE WITH ALL
EQUIPMENT. THE SYSTEM SHALL BE VIEWABLE AND EDITABLE FROM A COMPUTER
USING INTERNET WEB BROWSER COMMUNICATING EITHER DIRECTLY OR REMOTELY
WITH THE BAS MAIN CONTROL PANEL.
2.9.3 DIRECT DIGITAL CONTROL (DDC) TECHNOLOGY SHALL BE USED TO PROVIDE
THE FUNCTIONS NECESSARY FOR CONTROL OF MECHANICAL SYSTEMS.
2.9.4 THE CONTROL SYSTEM SHALL BE DESIGNED SUCH THAT IN THE EVENT OF A
NETWORK COMMUNICATION FAILURE, OR THE LOSS OF ANY OTHER CONTROLLER,
THE SCHEDULE SYSTEM SHALL CONTINUE TO INDEPENDENTLY OPERATE UNDER
LOCAL CONTROL.
2.9.5 OWNER SHALL PROVIDE WAN/LAN CONNECTION TO THE BUILDING
AUTOMATION SYSTEM.
2.9.6 UNIT LEVEL CONTROLLERS SHALL USE BACNET MSTP PROTOCOL.
CONTROLLERS SHALL BE BACNET BTL CERTIFIED.
2.9.7 THE SYSTEM MUST BE PROVIDED, INSTALLED, WIRED AND PROGRAM BY THE
MANUFACTURER'S LOCAL FACTORY OFFICE OR APPROVED CONTRACTOR.
2.9.8 PROVIDE ONE YEAR PARTS AND LABOR WARRANTY OF THE BAS.
2.9.9 PROVIDE PORTABLE UN-INTERRUPTIBLE POWER SUPPLY (APC BACK-UPS
1500VA, OR EQUAL) TO POWER CONTROL SYSTEM IF REQUIRED BY OWNER.
2.9.10 PROVIDE 4 HOURS OF OWNER'S TRAINING AT JOBSITE ON THE BUILDING
AUTOMATION SYSTEM OPERATION.
2.9.11 ALL CONTROL SETPOINTS SHALL BE ADJUSTABLE, INDICATED TEMPERATURE
SETPOINTS SHOULD BE USED FOR ORIGINAL SYSTEM SET-UP. ANY CHANGES IN
SETPOINT SETTINGS REQUIRED FOR INTENDED SYSTEM OPERATION SHALL BE
INDICATED ON AS-BUILT DRAWINGS.
2.9.12 DUCT SMOKE DETECTORS SHALL BE FURNISHED AND WIRED TO THE FIRE
ALARM SYSTEM BY ELECTRICAL OR OWNER APPROVED CONTRACTOR. ELECTRICAL
OR APPROVED CONTRACTOR SHALL INSTALL DETECTOR IN DUCT AND WIRE UNIT
FROM FIRE ALARM SYSTEM (DRY CONTACTS) FOR UNIT SHUT-DOWN UPON
ACTIVATION.
2.9.13 LOCATE VERASYS SMART BUILDING CONTROL HUB FOR BAS IN MECHANICAL
ROOM OR IT CLOSET. COORDINATE EXACT LOCATION OF PANELS WITH ALL OTHER
TRADES AND BUILDING OWNER PRIOR TO INSTALLATION. PROVIDE PORTABLE UPS IF
REQUIRED BY OWNER.
2.9.14 THE SEQUENCE OF OPERATION DOES NOT COMPLETELY DEFINE THE SCOPE
OF WORK FOR CONTROLS. THE CONTROLS SUBMITTAL SHALL FULLY DEVELOP THE
SEQUENCE OF OPERATIONS FOR ALL SYSTEMS IDENTIFIED AND SHALL PRESENT ALL
SETPOINTS, CONTROL PARAMETERS, AND ALARM POINTS. INCORPORATE STANDARD
FEATURES SUCH AS MINIMUM RUN TIME DELAYS AND DEAD BANDS FROM SETPOINTS
TO PREVENT EQUIPMENT FROM SHORT CYCLING WHEN NEAR SETPOINTS. THESE
BASIC FEATURES THAT ARE NECESSARY AND ARE PART OF A COMPLETE CONTROLS
INSTALLATION SHALL BE INCLUDED IN THE SCOPE OF SERVICES FOR DELIVERABLES
AT NO ADDITIONAL COSTS TO THE OWNER.
2.9.15 ALL CONTROL AND POWER WIRING SHALL BE PLENUM-RATED WITH A MINIMUM
FIRE SPREAD RATING OF 25 AND A MINIMUM SMOKE DEVELOPED RATING OF 50 PER
ASTM E84. ANY EXPOSED WIRING SHALL BE MOUNTED IN ELECTRO-MAGNETIC TUBING
(EMT) OR SUSPENDED BY UL APPROVED DATA CABLE HOOKS.
2.9.16 MOTORIZED DAMPER POSITIONING FOR OUTSIDE AIR, EXHAUST, AND RETURN
AIR SHALL BE COMPLETELY PROGRAMMABLE WITH POSITION DETERMINED DURING
TEST AND BALANCE WITH SETTINGS CONTAINED WITHIN THE BAS SYSTEM.
2.9.17 THE SYSTEM SHALL HAVE THE FOLLOWING FUNCTIONS: TIME OF DAY
SCHEDULING INCLUDING OPTIMAL START/STOP, HOLIDAY AND EXCEPTION
SCHEDULES, DATA LOGGING AND TRENDING, USER SECURITY LEVEL ASSIGMENT,
SYSTEM AND ALARMS REPORTS, ALARM REPORTING VIA TEXT MESSAGE OR EMAIL,
FLOOR PLANS, SYSTEM, EQUIPMENT GRAPHICS IN A STATIC DISPLAY FORMAT, ALARM
E-MAIL ROUTING, GLOBAL NAVIGATION ICONS TO MANAGE ALARMS AND USER
CREDENTIALS, ALL SETPOINTS, ALARMS, TRENDING, AND MONITORING FUNCTIONS
SHALL BE AVAILABLE OVER WEBPAGE.
2.9.18 CONTROLS SHALL BE PROVIDED BY JOHNSON CONTROLS. ALERTON, CARRIER,
HONEYWELL, SIEMENS, OR TRANE SHALL BE CONSIDERED AS ALTERNATES.
REGARDLESS OF VENDOR, DDC SYSTEM SHALL BE OPEN PROTOCOL, WITH ALL
LICENSES INCLUDED. WHERE ALTERNATES ARE PROPOSED, CONTRACT PRICE
REDUCTIONS SHALL BE INDICATED IN TENDER / BID.
2.10 ENERGY RECOVERY VENTILATOR: BOLT ON ACCESSORY VENTILATOR FOR EXIST.
RTU CONSTRUCTED OF G90 GALVANIZED MATERIAL WITH POWDERED ENAMEL PAINT
FINISH, INSULATED CABINET PANELS, POWER OPENINGS, TEST PORTS, MULTIPLE
SPEED INDIVIDUALLY CONTROLLED CENTRIFUGAL INTAKE & EXHAUST AIR BLOWERS,
SILICA GEL DESICCANT ENTHALPY ENERGY RECOVERY WHEEL (ARI 1060 & UL LISTED),
BALANCING DAMPERS, BAROMETRIC RELIEF, SUPPORT LEGS, FILTERS & SINGLE
POINT POWER CONNECTION, 2200 - 2800 CFM, 208/230-3-60 ELECTRICAL, DUAL POINT
POWER. OPTIONS INCLUDED: EQUIPMENT SUPPORT, ROOF CURB, LOW AMBIENT KIT,
MOTORIZED INTAKE DAMPER, STOP-START-JOG CONTROLS & PRESSURE SENSOR.
ACCEPTABLE PRODUCT: YORK / JCI V SERIES OR APPROVED EQUAL.
3.0 EXECUTION
3.1 DUCT SIZE CHANGES SHALL HAVE THE SAME FRICTION DROP PER 100 FT AS THE
DUCT SHOWN ON DRAWINGS. DUCT ASPECT RATIO SHALL NOT EXCEED 4 TO 1.
CONSULT ENGINEER BEFORE CHANGING DUCT SIZE OR LOCATION.
3.2 PROVIDE FLEXIBLE DUCT CONNECTIONS AT SUCTION AND DISCHARGE
CONNECTIONS TO FANS AND AIR CONDITIONING UNITS.
3.3 SEAL DUCT CONNECTIONS AND TRAVERSE JOINTS WITH SEALANT.
3.4 PROVIDE FIRE DAMPERS WITH STEEL ANGLES AROUND PERIMETER AND ACCESS
DOORS.
3.5 FIVE DAYS PRIOR TO CLOSING CEILING, NOTIFY CONSULTANT AND PROJECT
MANNER FOR A SITE INSPECTION. FAILURE TO DO SO CAN RESULT IN CONTRACTOR
RE-OPENING AND RE-CLOSING CEILING TILES AT THEIR EXPENSE TO PERMIT THIS
INSPECTION.
3.6 INSULATE ALL DUCTS AND PLENUMS HANDLING OUTSIDE AIR WITH 2 INCHES (50
MM) FIBERGLASS FOIL FACED VAPOR SEAL DUCT INSULATION 31 DENSITY. EXHAUST
DUCTS SHALL BE INSULATED WITH 2 IN. (50 MM) FIBERGLASS FOIL FACED VAPOR SEAL
INSULATION UP TO 7 FEET (2 METERS) FROM OUTSIDE WALL.
3.6 TESTING ADJUSTING & BALANCING:
3.6.1 TESTING AND BALANCING SHALL CONFORM TO AABC, NEBB, AND/OR SMACNA
STANDARDS FOR THE ADJUSTMENT OF AIR SYSTEMS USING TAB STANDARD
PROVISIONS: CHECKLISTS, REPORT FORMS, FIRM AND SPECIALIST QUALIFICATIONS
AND CALIBRATION OF TAB INSTRUMENTS.
3.6.2 PERFORM TAB TO TEST TO VERIFY PROPER AND SAFE OPERATION, DETERMINE
ACTUAL POINT OF PERFORMANCE, EVALUATE QUALITATIVE AND QUANTITATIVE
PERFORMANCE OF EQUIPMENT, SYSTEMS AND CONTROLS AT DESIGN, AVERAGE AND
LOW LOADS USING ACTUAL OR SIMULATED LOADS. ADJUST AND REGULATE
EQUIPMENT AND SYSTEMS TO MEET SPECIFIED PERFORMANCE REQUIREMENTS AND
TO ACHIEVE SPECIFIED INTERACTION WITH OTHER RELATED SYSTEMS UNDER
NORMAL AND EMERGENCY LOADS AND OPERATING CONDITIONS. BALANCE SYSTEMS
AND EQUIPMENT TO REGULATE FLOW RATES TO MATCH LOAD REQUIREMENTS OVER
FULL OPERATING RANGES.
3.6.3 START-UP: PERFORM STARTUP FOLLOWING START-UP PROCEDURES PER
EQUIPMENT MANUFACTURER.
3.6.4 START TAB WHEN BUILDING IS ESSENTIALLY COMPLETED AND ENCLOSED,
MECHANICAL SYSTEMS INSTALLED COMPLETE, PRESSURE TESTED, ETC. AND
OPERATIONAL.
3.6.5 DO TAB TO FOLLOWING TOLERANCES OF DESIGN VALUES: HVAC SYSTEMS: HVAC
SYSTEMS: PLUS 5%, MINUS 5%. REPORTED RESULTS SUBJECT TO VERIFICATION BY
CONSULTANT. PROVIDE PERSONNEL AND INSTRUMENTATION TO VERIFY UP TO 30%
OF REPORTED RESULTS. PAY COSTS TO REPEAT TAB AS REQUIRED TO
SATISFACTION OF CONSULTANT. TAB CONSIDERED COMPLETE WHEN FINAL TAB
REPORT RECEIVED AND APPROVED BY CONSULTANT.
3.6.7 AIR SYSTEM MEASUREMENTS: AIR VELOCITIES, TOTAL/STATIC PRESSURES,
FLOW RATES, PRESSURE DROPS (OR LOSS), TEMPERATURES (DRY BULB, WET BULB,
DEWPOINT), DUCT CROSS-SECTIONAL AREAS, RPMS, ELECTRICAL POWER, VOLTAGE,
NOISE, VIBRATION, ETC. AT INLET AND OUTLET OF DAMPERS, FILTERS, COILS, FANS,
ACUS, CONTROLLED DEVICES, MAIN DUCTS, MAIN BRANCHES, SUB-BRANCHES,
RUN-OUTS (GRILLES, REGISTERS OR DIFFUSERS).
3.6.8 TEST FOR PROPER OPERATION OF ALL SMOKE AND FIRE DAMPERS, SENSORS,
DETECTORS.
3.6.9 PARTICIPATE IN SYSTEMS CHECKS TWICE DURING WARRANTY PERIOD - #1
APPROXIMATELY 3 MONTHS AFTER ACCEPTANCE AND #2 WITHIN 1 MONTH OF
TERMINATION OF WARRANTY PERIOD.
3.6.10 PROVIDE 3 COPIES OF A WRITTEN REPORT INDICATING ALL MEASUREMENTS
AND A LETTER CERTIFYING THAT ALL SYSTEMS AND EQUIPMENT HAVE BEEN TESTED
AND BALANCED AS REQUIRED. TESTING & BALANCING REPORTS SHALL INCLUDE A
COPY OF THE ENGINEERS HVAC DUCT / PIPING LAYOUT IDENTIFYING EACH ITEM /
EQUIPMENT / POINTS IN THE SYSTEM WHERE ALL THE MEASUREMENTS WERE TAKEN.
3.6.11 PROVIDE A PRELIMINARY TAB REPORT TO CONSULTANT AND OWNER WITHIN 5
DAYS OF SITE MEASUREMENT AND A FINAL REPORT AFTER PRELIMINARY REPORT
HAS BEEN REVIEWED BY CONSULTANT AND OWNER.
3.6.12 TAB REPORT TO CLEARLY STATE MINIMUM AND MAXIMUM CONDITIONS.
PROVIDE A PLAN VIEW WITH ALL TEST LOCATIONS IDENTIFIED. TAB CONTRACTOR
REPORT TO CLEARLY INDICATE DEFICIENCIES RELATED TO DIFFUSERS, DAMPERS,
VAVS, FANS THAT ARE NOT OPERATING IN A MANNER TO PERMIT MEASUREMENTS TO
MEET DESIGN CONDITIONS.
3.6.13 PRIOR TO HVAC DEMOLITION, MODIFICATIONS & RENOVATIONS OF EXISTING
EQUIPMENT & SYSTEMS, MEASURE THE SUPPLY, RETURN, EXHAUST & OUTSIDE AIR
FLOW RATES AT EACH DIFFUSER, GRILLE, REGISTER, FAN, AHU, ACU, LOU-VER, ETC.
AFFECTED BY THE RENOVATIONS. THIS INCLUDES HVAC 3, 4 & 7. MEASURE TOTAL &
EXTERNAL STATIC PRESSURES, RPM, BHP, VOLTAGE, AMP DRAW, ETC. AT EACH
SUPPLY, RETURN, EXHAUST & OUTSIDE AIR CONNECTIONS OF EACH FAN, AHU, ACU,
EF, RF, ETC. SUBMIT PRE DEMOLITION BALANCING REPORT TO ENGINEER FOR
ANALYSIS TO DETERMINE FINAL BALANCING VALUES. UPON COMPLETION OF THE
HVAC SYSTEM MODIFICATIONS & RENOVATIONS, TAB EXISTING & NEW EQUIPMENT,
TERMINAL UNITS, DIFFUSERS, GRILLES, REGISTERS, FANS, AHUS, ETC. TO VALUES
DETERMINED BY ENGINEER AFTER REVIEW & ANALYSIS OF PRE DEMOLITION
BALANCING REPORT.
3.6.14 IN BALANCING HVAC SYSTEMS, ADJUST FAN SPEED AS NECESSARY VIA
EXISTING UNIT VFD. WHERE NO VFD IS AVAILABLE, CHANGE BELTS & SHEAVES AS
REQUIRED. FINALLY, INLET OR DISCHARGE DAMPERS MAY BE USED AS LAST RESORT.
WHERE REDUCTION IN AIRFLOW IS NO LONGER POSSIBLE DUE TO RTU MINIMUM
FLOW RATE, BYPASS DUCTS MAY BE ADJUSTED OPEN TO ACHIEVE THE REQUIRED
MINIMUM FLOW RATE. MAKE DRIVE SPEED ADJUSTMENTS OR REPLACE SHEAVES AS
REQUIRED TO ATTAIN DESIGN CONDITIONS. FURNISH NEW OR EXCHANGE FURNISHED
SHEAVES WITH UNIT MANUFACTURER, AT NO CHANGE IN CONTRACT PRICE.
3.6.15 ACCEPTABLE TAB AGENCIES: MEMBERS OF NEBB AND / OR AABC.
3.7 SEQUENCE OF OPERATION
3.7.1 A COMPLETE AND OPERATIONAL DDC CONTROL SYSTEM (BAS) SHALL BE
INSTALLED IN ACCORDANCE WITH THE SEQUENCE OF OPERATIONS, POINTS LIST, AND
NOTES.
3.7.2 MECHANICAL CONTRACTOR SHALL COORDINATE ALL BAS INTEGRATION
REQUIREMENTS WITH EQUIPMENT VENDORS AND CONTROLS CONTRACTOR PRIOR TO
PURCHASING EQUIPMENT AND PROVIDE ALL EQUIPMENT WITH COMMUNICATION /
INTERFACE CARDS AS REQUIRED FOR SYSTEM INTEGRATION.
3.7.3 ROOFTOP UNIT: ROOFTOP UNITS (RTU) SHALL BE STOPPED / STARTED ON A
TIME OF DAY SCHEDULE THROUGH THE BAS. THIS SCHEDULE SHALL BE MODIFIED BY
A START STOP OPTIMIZATION PROGRAM. START / STOP OPTIMIZATION SHALL BE
CAPABLE OF BEING DISABLED. UPON PROOF OF AIR FLOW THRU THE SUPPLY FAN,
THE NORMALLY CLOSED OUTSIDE AIR DAMPER SHALL BE ENABLED. A DISCHARGE
AIR TEMPERATURE SENSOR SHALL STAGE COMPRESSORS ON, AS REQUIRED TO
MAINTAIN SUPPLY AIR TEMPERATURE.
13.7.4 SUPPLY AIR TEMPERATURE RESET: SUPPLY AIR TEMPERATURE SHALL VARY
LINEARLY BETWEEN THE HIGH AND LOW TEMPERATURES. STATE THE HIGH & LOW
TEMPERATURES (ADJ) IN CONTROL DRAWINGS. THE INITIAL SETPOINT FOR THE
DISCHARGE AIR SUPPLY TEMPERATURE SHALL BE 55° F. SUPPLY AIR TEMPERATURE
SETPOINT SHALL HAVE A HIGH LIMIT OF 62° REGARDLESS OF OUTSIDE AIR
TEMPERATURE, WHEN ANY ZONE ON THE RTU HAS A CALL FOR COOLING.
3.7.5 SUPPLY DUCT STATIC PRESSURE SENSOR: SENSOR SHALL MODULATE THE
BYPASS DAMPERS TO MAINTAIN THE SETPOINT ESTABLISHED DURING FINAL TESTING
AND BALANCING. THE PRELIMINARY SETPOINT SHALL BE 0.6” (ADJ.) STATIC PRESSURE.
THIS SETPOINT SHALL BE RESET BASED ON THE ZONE REQUIRING THE MOST
PRESSURE; I.E., THE SETPOINT IS RESET LOWER UNTIL ONE TERMINAL BOX DAMPER
IS NEARLY WIDE OPEN.
3.7.6 SUPPLY FAN: WHILE IN THE OCCUPIED MODE, THE SUPPLY FAN SHALL
OPERATE CONTINUOUSLY. WHILE IN THE UNOCCUPIED MODE, THE UNIT SUPPLY FAN
SHALL CYCLE WITH HEATING AND COOLING LOADS, UPON A CALL FOR HEATING OR
COOLING TO MEET UNOCCUPIED SETPOINTS, THE UNIT FAN SHALL BE STARTED AND
THE UNIT SHALL OPERATE AS DESCRIBED BELOW AS REQUIRED BY THE SPACE
TEMPERATURE. THE STAGED HEATER OR COMPRESSORS SHALL ALSO BE STARTED
AS REQUIRED TO SATISFY SETPOINTS.
3.7.7 UNOCCUPIED HEATING MODE WITH STAGED HEAT: WHILE THERE IS A CALL
FOR HEATING IN THE UNOCCUPIED MODE, THE SUPPLY FAN SHALL RUN TO SUPPLY
HEATING AIRFLOW. THE MOTORIZED OUTSIDE AIR DAMPER SHALL REMAIN FULLY
CLOSED, AND THE RETURN AIR DAMPER SHALL OPEN TO 100%. THE GAS-FIRED
HEATER SHALL OPERATE IN STAGES TO MAINTAIN A UNIT DISCHARGE AIR
TEMPERATURE OF 85 DEGREES F (ADJ.) UNTIL ALL ZONES ARE SATISFIED. VAV
TERMINAL PRIMARY AIR DAMPERS SHALL OPEN TO A PREDETERMINED POSITION. THE
UNIT SHALL OPERATE FOR A MINIMUM OF 15 MINUTES OR AS REQUIRED TO SATISFY
UNOCCUPIED SETPOINT. WHEN OCCUPIED, STAGED HEATING SHALL INCREASE RTU
SUPPLY AIR TEMPERATURE. WHEN HOT AIR IS SENSES IN THE SUPPLY DUCT, THE
VAV TERMINAL UNIT SHALL MODULATE TO MAINTAIN SPACE TEMPERATURE.
3.7.8 DEMAND CONTROL VENTILATION: OUTSIDE AIR INTAKE SHALL BE PROVIDED
WITH A MOTORIZED DAMPER. ON UNIT START, THE OUTSIDE AIR INTAKE DAMPER
SHALL REMAIN CLOSED UNTIL THE RETURN AIR TEMPERATURE IS ABOVE 65° F (ADJ)
AND BELOW 75° F. (ADJ). ONCE RETURN AIR TEMPERATURE IS SATISFIED, THE
OUTSIDE AIR DAMPER SHALL OPEN TO THE OCCUPIED MINIMUM SETPOINT. THE
OUTSIDE AIR INTAKE DAMPER SHALL BE CLOSED WHILE UNIT IS IN THE UNOCCUPIED
MODE. BAS SHALL BE CAPABLE OF OPENING AND CLOSING ALL DAMPERS.
3.7.9 CO2 SENSOR: CO2 SENSOR MOUNTED IN THE RETURN DUCT SHALL MODULATE
THE OUTSIDE AIR DAMPER BASED ON CO2 LEVELS IN THE SPACE. DAMPER SHALL
MODULATE OPEN FROM THE OCCUPIED MINIMUM SETPOINT OF 800 PPM TO DESIGN
MAXIMUM AT 1200 PPM.
.7.10 CO2 ZONING: A SPACE CO2 SENSOR IN THE ZONES SHALL INCREMENTALLY
OPEN THE MINIMUM VAV BOX DAMPER POSITION FOR ITS RELATED ZONE DAMPER.
3.7.11 AIRSIDE ECONOMIZER COOLING CYCLE: DURING THE OCCUPIED PERIOD, WHEN
THE OUTSIDE AIR TEMPERATURE IS BELOW 70° F (ADJ.) AND THE OUTDOOR ENTHALPY
IS BELOW THE RETURN AIR ENTHALPY (OPTIONAL), THE ECONOMIZER CYCLE SHALL
BE ENABLED. UNDER THOSE CONDITIONS, THE OUTDOOR AIR DAMPER AND RETURN
AIR DAMPER SHALL MODULATE AS REQUIRED TO MAINTAIN THE DISCHARGE AIR
TEMPERATURE SETPOINT WHILE THE UNIT IS IN COOLING MODE.
3.7.12 ECONOMIZER RELIEF DAMPERS: UNIT MOUNTED RELIEF SHALL RELIEVE
EXCESS RETURN AIR WHEN IN ECONOMIZER OPERATION.
3.7.13 HUMIDITY CONTROL: HUMIDITY CONTROL SHALL BE A FUNCTION WITHIN THE
UNIT. HUMIDITY LEVELS SHALL BE MAINTAINED BETWEEN 35-55% RH AS MEASURED
VIA A DUCT MOUNTED SENSOR.
3.7.14 SMOKE DETECTION & RTU SHUTDOWN: UPON DETECTION OF SMOKE IN THE
AIR HANDLING SYSTEM BY THE DUCT-MOUNTED RETURN AIR SMOKE DETECTOR, AN
ALARM CONDITION SHALL BE SENT TO THE BUILDING FIRE ALARM SYSTEM AND ALL
AIR HANDLING UNITS SHALL BE SHUTDOWN BY THE BUILDING FIRE ALARM SYSTEM.
3.7.15 ZONE TEMPERATURE SENSORS / THERMOSTATS: ZONE TEMPERATURE
SENSORS / THERMOSTATS SHALL BE PROVIDED WHERE INDICATED ON THE
DRAWINGS. THERMOSTATS SHALL HAVE MANUAL ADJUSTMENT, AND SHALL BE
INITIALLY SET IN THE OCCUPIED MODE FOR COOLING TO 76° AND HEATING TO 71°.
THERMOSTATS SHALL HAVE A 5° (ADJ.) DEADBAND RANGE IN WHICH THEY ARE
SATISFIED. MANUAL ADJUSTMENT SHALL HAVE THE CAPABILITY TO ADJUST THE
HEATING AND COOLING SETPOINTS BY 3° (ADJ.) IN EACH DIRECTION, BUT MAINTAIN A
MINIMUM 5° SPREAD BETWEEN THE HEATING AND COOLING SETPOINT. UNOCCUPIED
SETTINGS SHALL BE 85° COOLING AND 60° HEATING. COORDINATE FINAL SETPOINTS,
SETBACK, SCHEDULING, MORNING WARM-UP, COOL-DOWN, ETC WITH OWNER DURING
OWNER. THERMOSTATS SHALL HAVE AN OVERRIDE FUNCTION THAT WILL PLACE THE
UNIT IN OCCUPIED MODE FOR A PERIOD OF TWO HOURS (ADJ.). THE OVERRIDE SHALL
ACTIVATE THE SYSTEM AHU AS REQUIRED TO MAINTAIN SPACE TEMPERATURE.
3.7.16 HEATING / COOLING SELECTION: ALL SENSORS / THERMOSTATS CONNECTED
TO THE RTU SHALL ALL BE MONITORED AND USED TO DETERMINE THE RTU
OPERATION IN COOLING OR HEATING MODE. RTU OPERATION IN HEATING & COOLING
WILL DETERMINE VAV BOX MODULATION IN HEATING OR COOLING MODE. IF A ZONE IS
HOT & RTU IS IN COOLING MODE, VAV DAMPER MODULATES OPEN TO SATISFY
COOLING SETPOINT. ON A DROP IN TEMPERATURE BUT STILL IN COOLING MODE, VAV
DAMPER MODULATES CLOSED. IF A ZONE IS COLD & RTU IS IN HEATING MODE, VAV
DAMPER MODULATES OPEN TO SATISFY HEATING SETPOINT. ON A RISE IN
TEMPERATURE BUT STILL IN HEATING MODE, VAV DAMPER MODULATES CLOSED.
3.7.17 VAV BOXES: THE FAN POWERED VARIABLE VOLUME (VAV) TERMINAL UNITS
SHALL BE CONTROLLED INDEPENDENT OF SYSTEM PRESSURE FLUCTUATIONS BY AN
APPLICATION SPECIFIC DDC CONTROLLER UTILIZING ELECTRIC ACTUATION. DURING
OCCUPIED AND UNOCCUPIED OPERATION, A TEMPERATURE SENSOR SHALL BE
UTILIZED TO MAINTAIN SPACE TEMPERATURE SETPOINT. UPON A RISE IN SPACE
TEMPERATURE ABOVE SETPOINT IN COOLING MODE, THE VOLUME DAMPER SHALL
MODULATE OPEN AS REQUIRED TO MAINTAIN SPACE TEMPERATURE. UPON A DROP IN
SPACE TEMPERATURE BELOW SETPOINT IN COOLING MODE, THE VOLUME DAMPER
SHALL MODULATE CLOSED UNTIL THE MINIMUM DAMPER POSITION IS REACHED. UPON
CONTINUED DROP IN SPACE TEMPERATURE BELOW HEATING SETPOINT SETPOINT &
WITH HOT AIR SUPPLIED BY THE RTU, THE VAV BOX SHALL MODULATE OPEN UNTIL
FULL OPEN.
3.7.18 NORMAL NON ECONOMIZER MODE:
3.7.18.1 SPACE THERMOSTAT SENDS A SIGNAL TO THE RTU FOR COOLING, HEATING
OR FAN ONLY OPERATION. ERV IS INTERLOCKED & ACTIVATED SIMULTANEOUSLY
WITH THE RTU SUPPLY BLOWER. THE ERV INTAKE & EXHAUST BLOWERS & ERV
WHEEL MOTORS ARE ACTIVATED & REMAIN ENERGIZED AS LONG AS THE RTU SUPPLY
BLOWER IS ENERGIZED. MOTORIZED FRESH AIR DAMPER OF THE ERV OPENS WHEN
THE ERV IS ENERGIZED.
3.7.18.2 LOW AMBIENT MODE: IF TEMPERATURE SENSED BY LOW AMBIENT SENSOR
LEAVING EXHAUST SIDE OF WHEEL DROPS BELOW SET POINT (ADJ.), MOTORIZED
FRESH AIR DAMPER WILL CLOSE AND THE INTAKE BLOWER WILL DE-ENERGIZE.
EXHAUST AIR BLOWER & WHEEL ROTATION MOTOR WILL CONTINUE TO OPERATE.
WHEN THE TEMPERATURE SENSOR HAS A SIXTEEN-DEGREE RISE, THE WHEEL IS
DEFROSTED AND THE MOTORIZED DAMPER WILL OPEN & THE FRESH AIR BLOWER
WILL REACTIVATE.
ECONOMIZER OPERATION (PIVOTING MODELS): SPACE THERMOSTAT SENDS A SIGNAL
TO RTU FOR COOLING OPERATION. RTU OUTDOOR AIR SENSOR SENSES OUTDOOR
AIR & DETERMINES IT IS APPROPRIATE FOR ECONOMIZER OPERATION. AS
ECONOMIZER OUTSIDE AIR DAMPERS OPEN, ERV ECONOMIZER END SWITCH IS
ACTIVATED & SENDS SIGNAL TO THE ERV THAT THE SYSTEM IS IN ECONOMIZER MODE.
INTAKE BLOWER, EXHAUST BLOWER & ERV WHEEL MOTOR ALL DEACTIVATE FOR UP
TO TWO MINUTES. MOTORIZED FRESH AIR DAMPER CLOSES. ERV ENTHALPY WHEEL
PIVOTS OUT OF AIR STREAM & BYPASS DAMPERS OF THE INTAKE BLOWER OPEN.
AFTER A TIME DELAY FOR THE WHEEL TO PIVOT OUT OF THE AIRSTREAM & BYPASS
DAMPERS TO OPEN, MOTORIZED FRESH AIR DAMPER OPENS TO ALLOW FOR FULL
ECONOMIZER OPERATION. THE EXHAUST BLOWER IS REACTIVATED TO PROVIDE
POWER EXHAUST FOR THE SYSTEM.
2021-08-0921-023
PHASE 1(GROUP D)
PHASE 2(GROUP A2)
E
1
2
3
4
5
6
DCBA
EX. SUMP& PUMP, TO
REMAIN
EX. 4"Ø SAN RISERS,
TO REMAIN
EX. LAVEX. ABANDONED DHW
HEATER, TO REMAIN
EX. ABANDONED DHW
HEATER
EX. ABANDONED DHW
HEATER
EX. 6"Ø F
EX. CAPPED TEE
EX. SPRINKLER RISER,
VALVE, & PRESS.
MAINTENANCE PUMP
EX. SPRINKLER LINES
TO SPRINKLER HEADS
EX. SPRINKLER LINES
TO SPRINKLER HEADS
EX. FIXTURES TO
REMAIN, TYP.
EX. FIXTURES TO
REMAIN, TYP.
EX. ABANDONED
COMPRESSOR, TO
REMAIN
EX. FIXTURES TO
REMAIN, TYP.
EX. FIXTURES TO
REMAIN, TYP.
EX. FIXTURES TO
REMAIN, TYP.
EX. FIXTURES TO
REMAIN, TYP.M BFP
EX. 4"Ø DCW SERVICE
1"Ø
EX. 1"Ø METER
EX. BFP
EX. 1 1/2"Ø CW TO
FIXTURES
EX. ELECTRICAL
PANEL, TYP
EX. ELECTRICAL
PANEL, TYP
EX. ABANDONED ACU
EX. ELECTRICAL
PANEL, TYP
EX. FD
EX. FD
EX. 6"Ø SAN?
EX. FFD
EX. FD
EX. CO
2 1/2"Ø3"Ø3"Ø4"Ø
4"Ø
2 1/2"Ø
2 1/2"Ø
2"Ø2"Ø
EX. 3"Ø SANEX. 3"Ø SAN & V
5"Ø5"Ø
2"Ø
2 1/2"Ø
2"Ø
OPENED PIPE
BOTH ENDS
EX. 6"Ø, RELOCATE
EX. 6"Ø INS
DN
FD3
FD2 FD2
NOT IN
SCOPE
FD2
FD2
FD2
E
1
2
3
4
5
6
DCBA
JS W/ DRAINS,
DEMOLISH
EX. SPRINKLER DRAIN,
TO REMAIN
EX. FDC, TO REMAIN
FD1
FD1
EX. SPRINKLER
HEADS, TYP
EX. PLUMB SAN, V, CW,
DHW, DEMOLISH
EX. 2"Ø PIPE
EX. 1"Ø D
EX. 1 1/2"Ø D,
DEMOLISH
EX. PLUMB SAN, V, CW,
DHW, DEMOLISH
EX. SAN, V, CW, DHW, & NG,
DEMOLISH
EX. SAN & DRINK
DISPENSER,
DEMOLISH
EX. 6"Ø F RISER,
RELOCATE
NOT IN
SCOPE
EX. SAN, V, DRAIN TO
SINK, RELOCATE &
EXTEND TO BASEMENT
PROJECT No.
DRAWN BY
DATE
CAD FILE
SHEET
ISSUE DATE (Y-M-D) No. ISSUED FOR
CLIENT
SCALE
374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E studio@passa.ca
Passa Associates Inc. WWW.PASSA.CA
PROJECT
ARCHITECTS
Please note that all information included in these drawing files is protected by
copyright. Unauthorized use of these files without the written permission of
Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects
is responsible only for information shown on a mechanical reproduction of these
drawings that have been signed and stamped by an architect with signing
authority employed by the firm.
If you require further information please contact our office at the numbers listed.
A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR
2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.
AUG. 09, 2021
UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.
2021-06-25 1 PROGRESS
2021-06-30 2 PERMIT
2021-07-14 3 FINAL REVIEW
2021-07-27 4 PROGRESS
2021-08-09 5 PERMIT & TENDER
JACE #21-023
SCALE:
BASEMENT FLOOR PLAN - PLUMBING AND FIRE PROTECTION DEMOLITION1/8"=1'-0" SCALE:
FLOOR PLAN - PLUMBING AND FIRE PROTECTION DEMOLITION1/8"=1'-0"
M4
FLOOR PLANS - PLUMBING AND FIRE PROTECTION DEMOLITION
1/8" - 1'-0"
FIRE PROTECTION DEMOLITION NOTES:
FD1 REMOVE EX. SPRINKLER PIPING THAT WILL NOT ACCOMODATE THE NEW
LAYOUT SHOWN IN M6.
FD2 EX. SPRINKLER LINE LAYOUT & SIZES APPROXIMATE TO BE
CONFIRMED BY SPRINKLER DESIGNER, ENGINEER & CONTRACTOR.
FD3 TEST & INSPECT EX. SPRINKLER SYSTEM TO ENSURE PROPER FUNCTION
& SUITABILITY FOR NEW SERVICE. REPORT DEFFICIENCIES IDENTIFIED TO
ARCH & ENGINEER.
2021-08-0921-023
PHASE 1(GROUP D)
PHASE 2(GROUP A2)
E
1
2
3
4
5
6
DCBA
EX. SAN, V, DRAINS TO
NEW DRAIN
EX. SUMP & PUMP,
TO REMAIN
EX. 4"Ø SAN RISERS,
TO REMAIN
EX. LAVEX. ABANDONED DHW
HEATER, TO REMAIN
EX. ABANDONED DHW
HEATER
EX. ABANDONED DHW
HEATER
EX. 6"Ø F
EX. CAPPED TEE
EX. SPRINKLER RISER,
VALVE, & PRESS.
MAINTENANCE PUMP
EX. SPRINKLER LINES
TO SPRINKLER HEADS
EX. SPRINKLER LINES
TO SPRINKLER HEADS
EX. FIXTURES TO
REMAIN, TYP.
EX. ABANDONED
COMPRESSOR, TO
REMAIN
EX. FIXTURES TO
REMAIN, TYP.
EX. FIXTURES TO
REMAIN, TYP.
EX. FIXTURES TO
REMAIN, TYP.
EX. FIXTURES TO
REMAIN, TYP.M BFP
EX. 4"Ø DCW SERVICE
1"Ø
EX. 1"Ø METER
EX. BFP
EX. 1 1/2"Ø CW TO
FIXTURES
EX. ELECTRICAL
PANEL, TYP
EX. ELECTRICAL
PANEL, TYP
EX. ABANDONED ACU
EX. ELECTRICAL
PANEL, TYP
EX. FD
EX. FD
EX. 6"Ø SAN?
EX. FFD
EX. FD
EX. CO
2 1/2"Ø3"Ø3"Ø4"Ø
4"Ø2 1/2"Ø
2 1/2"Ø
2"Ø2"Ø
EX. 3"Ø SAN
EX. 3"Ø SAN & V
5"Ø5"Ø
2"Ø
2 1/2"Ø
2"Ø
EX. ABANDONED PIPE
EX. 6"Ø INS
DN
RELOCATED 6"Ø F
RISER
CONN TO EX. 1 1/2"Ø
COPPER CW LINE
3/4"Ø CW
1/2"Ø CW
1/2"Ø CW
1/2"Ø CW
CO
1 1/2"Ø SAN
CONN TO EX. 3"Ø SAN
@ FLOOR, TYP
1 1/2"Ø SAN & 1/2"Ø
CW UP TO SINK
1 1/2"Ø SAN & 1/2"Ø
CW UP TO SINK
1 1/2"Ø SAN & 1/2"Ø CW
UP TO DRINKING
FOUNTAIN
CONN TO EX.
3"Ø SAN , TYP
CONN TO EX.
FEX
FEX
FEX
FP2
FP2
FP2
CONN TO EX.
CLASSROOM 3
103
CLASSROOM 1
104
CLASSROOM 2102
RESOURCECENTRE
101
KITCHENETTE
105
LOUNGE
106
BUSINESSCENTRE
107
OFFICE 1108 STORAGE
112
OFFICE 2
109
P.T. STAFF110
MEETING RM.111
CORRIDOR
113
VESTIBULE
114
STAIR
115
E
1
2
3
4
5
6
DCBA
S1 (NEW)
1 1/2"Ø SAN & 1/2"Ø CW,
TO BELOW FLOOR
FP1
EX. SPRINKLER
HEADS, TYP
FP1
RELOCATED 6"Ø F
RISER
EX. SPRINKLER
HEADS, TYP
EX. SPRINKLER
HEADS, TYP
FP1
FP1
FP1
S1 (NEW)1 1/2"Ø SAN & 1/2"Ø CW,
TO BELOW FLOOR
CONN TO EX.
JOIST SPACE
GROUND FLOOR &
JOIST SPACE
SPRINKLERS
INSTANTANEOUS
WATER HEATER
HW1
NOT IN
SCOPE
EX. SPRINKLER DRAIN,
TO REMAIN
EX. 2"Ø PIPE
EX. 1"Ø D
EX. FDC, TO REMAIN
EX. SPRINKLER
HEADS, TYP
RELOCATED SAN, V,
DRAIN TO BASEMENT
FEX
FEX
FP2
FP2
DF1 (NEW)
1 1/2"Ø SAN & 1/2"Ø CW,
TO BELOW FLOOR
PROJECT No.
DRAWN BY
DATE
CAD FILE
SHEET
ISSUE DATE (Y-M-D) No. ISSUED FOR
CLIENT
SCALE
374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E studio@passa.ca
Passa Associates Inc. WWW.PASSA.CA
PROJECT
ARCHITECTS
Please note that all information included in these drawing files is protected by
copyright. Unauthorized use of these files without the written permission of
Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects
is responsible only for information shown on a mechanical reproduction of these
drawings that have been signed and stamped by an architect with signing
authority employed by the firm.
If you require further information please contact our office at the numbers listed.
A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR
2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.
AUG. 09, 2021
UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.
2021-06-25 1 PROGRESS
2021-06-30 2 PERMIT
2021-07-14 3 FINAL REVIEW
2021-07-27 4 PROGRESS
2021-08-09 5 PERMIT & TENDER
JACE #21-023
SCALE:
BASEMENT FLOOR PLAN - PLUMBING AND FIRE PROTECTION1/8"=1'-0" SCALE:
FLOOR PLAN - PLUMBING AND FIRE PROTECTION1/8"=1'-0"
M5
FLOOR PLANS - PLUMBING AND FIRE PROTECTION
1/8" - 1'-0"
FIRE PROTECTION NOTES:
FP1 RECONFIGURE EX. SPRINKLER SYSTEM TO MATCH NEW LAYOUT. PROVIDE NEW BRANCH PIPING,
CONNECTIONS, HEADS, ETC. AS REQUIRED TO SATISFY NEW SPACE LAYOUT.
FP2 FEX 2A, TYPICAL FOR MAIN FLOOR UNLESS NOTED OTHERWISE.
2021-08-0921-023
E
1
2
3
4
5
6
DCBA
EX. EWH,
TO REMAIN
EX. 24X24 RA GRILLE
EX. 24X24 RA UP TO HVAC-5
EX. SA FROM HVAC-5 ON ROOF
EX. 24X24 RA GRILLE
EX. 24X24 RA UP TO HVAC-4
EX. SA FROM
HVAC-4 ON ROOF
EX. 24X24 RA
UP TO HVAC-3
EX. SA FROM
HVAC-3 ON ROOF
EX. 20X24 UP TO HVAC-2
EX. 48X20 SA FROM
HVAC-1 ON ROOF
EX. 24X24 RA UP TO HVAC-2
EX. 24X12 SA FROM
HVAC-7 ON ROOF
EX. EXH CAP
EX. 24X24 RA UP
TO HVAC-6
EX. SA FROM HVAC-6 ON ROOF
EX. 14X14 EXH UP TO ROOF, DEMOLISH
EX. 5"Ø EXH
TO ROOF
EX. 50X22 RA GRILLE
EX. 24X24 RA
GRILLE
8"Ø
SA DIFF.
24X18 GRILLE
EX. 24X14 UP
TO ROOF, TO REMAIN
HVAC DEMOLITION NOTES:
1 GRILLE IN EXISTING CEILING, DEMOLISH.
2 EXISTING DUCT UP THRU EXISTING CEILING, DEMOLISH.
3 DIFFUSER IN CEILING, DEMOLISH.
4 GRILLE IN EXISTING CEILING, DEMOLISH.
5 GRILLE IN BULKHEAD ABOVE NEW CEILING, DEMOLISH.
6 ABANDONED & BLOCKED EF
7 EX. DUCT IN BULKHEAD, DEMOLISH DUCT & BULKHEAD, COORDINATE WITH ARCH.
12"Ø UP
24X4 24X4
EX. 24X24 RA TO
HVAC-7
EX. 30X30 DAMPER
4"Ø SA
4"Ø RA
EX. 48X72 GRILLE
1
3
4 1
2
3
5
5
1 2
6
1
4
1
6Ø
12Ø
12
Ø
12Ø
12
x12
12Ø
20
x12
24x124Ø
24x12
10Ø
24
x10
4Ø
8Ø
8Ø
6Ø
6Ø6Ø
4Ø4Ø
10x4
12Ø
20
x12
10Ø
10x1
0
10Ø
14x1
2
10Ø
10
Ø
12Ø
10Ø
8Ø
10Ø
6Ø 6Ø
10Ø
10Ø
10Ø
10Ø
10Ø
10Ø 8Ø
24
x10
24
x12
10Ø
10
Ø
4Ø4Ø
4Ø
4Ø 4Ø
12Ø
12
Ø
5Ø
10x6
8Ø
6Ø
24
x12
12
x81
2x8
12
x8
8Ø
8Ø
8Ø
8Ø
10Ø
4Ø6Ø
6Ø
4Ø
10Ø
8Ø
8Ø
8Ø
8Ø
8Ø
24x1
02
4x1
2
10x10
6Ø
6Ø
18x18
20x20
20x20
20x2020x20
20x20
18x1818x18
EX. NG SERVICE & METER
CAP DUCTS,
TYP.
8Ø
8Ø
CAP DUCTS,
TYP.
CAP DUCTS,
TYP.
CAP DUCTS,
TYP.
CAP UNUSED
DUCT CONNECTIONS,
TYP.
EX. DUCTS, DEMOLISH, TYP.
VESTIBULE
10Ø
8Ø
10Ø 12Ø
24
x12
12Ø
24x1
2
EX. 20X6, DEMOLISH.
3 3
3
3
EX. EF, DEMOLISHEX. TRANSFER DUCT,
DEMOLISH
EX. WALL HEATER,
REPLACE
8Ø
8Ø
8Ø
12x1
2
8Ø
8Ø
12
x12
12x1
2
8Ø8Ø
18
x12
6Ø
6Ø
6Ø
20
x12 6Ø
20x12
6Ø
8Ø
8Ø
10
Ø8
Ø
48x20
8Ø
48x20
8Ø
8Ø
SA DUCT OFFSET
EX. RA DUCT DEMOLISH
EX. RA FROM
HVAC-1 ON ROOF
7
7
20x20
EX. EF
6Ø
32x12
8Ø
32x12 24x12
8Ø
6Ø
20
x40
NOT IN
SCOPE
E
1
2
3
4
5
6
DCBA
EX. HVAC-1
EX. HVAC-4 EX. HVAC-5
EX. HVAC-3EX. HVAC-6
EX. HVAC-7
EX. HVAC-2
EX. CHIMNEY
EX. EF3
EX. EF2
EX. EF1
EX. EXH. DUCT, TO REMAIN
EX. GOOSENECK, TO REMAIN
EX. EF4
EX. EF5
EX. 1 1/2"Ø NG
EX. 1"Ø NG
EX. 2"Ø NG
EX. 2 1/2"Ø NG
EX. 3"Ø NG
EX. 2"Ø NG
EX. 1"Ø NG
EX. 1 1/2"Ø NG
EX. 1"Ø NG
EX. GOOSENECK
EX. ROOF HATCH
EX. NG SERVICE & METER
HVAC DEMOLITION NOTES:
1 EX. RTU, REBANLANCE TO MATCH NEW FLOW RATES
DUE TO DEMOLISHED OUTLETS
1
1
1
PROJECT No.
DRAWN BY
DATE
CAD FILE
SHEET
ISSUE DATE (Y-M-D) No. ISSUED FOR
CLIENT
SCALE
374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E studio@passa.ca
Passa Associates Inc. WWW.PASSA.CA
PROJECT
ARCHITECTS
Please note that all information included in these drawing files is protected by
copyright. Unauthorized use of these files without the written permission of
Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects
is responsible only for information shown on a mechanical reproduction of these
drawings that have been signed and stamped by an architect with signing
authority employed by the firm.
If you require further information please contact our office at the numbers listed.
A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR
2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.
AUG. 09, 2021
UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.
2021-06-25 1 PROGRESS
2021-06-30 2 PERMIT
2021-07-14 3 FINAL REVIEW
2021-07-27 4 PROGRESS
2021-08-09 5 PERMIT & TENDER
JACE #21-023
SCALE:
FLOOR PLAN - HVAC DEMOLITION1/8"=1'-0"
SCALE:
ROOF PLAN - HVAC DEMOLITION1/8"=1'-0"
M6
FLOOR AND ROOF PLAN - HVAC DEMOLITION
1/8" - 1'-0"
2021-08-0921-023
E
1
2
3
4
5
6
DCBA
EX. EWH,
TO REMAIN
EX. EF
EX. 24X24 RA GRILLE
EX. 24X24 RA UP TO HVAC-5EX. SA FROM HVAC-5 ON ROOF
EX. 24X24 RA GRILLE
24X24 RA UP TO HVAC-4
EX. SA FROM
HVAC-4 ON ROOF
EX. SA FROM
HVAC-3 ON ROOF
EX. 20X24 SA
FROM HVAC-2
24X24 RA UP
TO HVAC-2
EX. 24X12 SA FROM
HVAC-7 ON ROOF
EXH CAP
EX. 24X24 RA UP TO HVAC-6EX. SA FROM
HVAC-6 ON ROOF
5"Ø EXH
TO ROOF
EX. 24X24 RA
GRILLE
HVAC NOTES:
1 REBALANCE EX. DIFFUSERS, GRILLES, REGISTERS TO VALUES INDICATED. TYP.
2 REBALANCE DIFFUSERS / GRILLES FOR RTUS 3, 4 & 7 TO MATCH AIR FLOW RATES
INDICATED ON PLANS & SCHEDULES FROM PREVIOUS TAB REPORT.
3 TAB TO ADJUST DIFFUSERS THROWS TO VERTICAL FOR MAX. VELOCITY AT 7 FEET
ABOVE FIN. FLOOR = APPROX. 50 FPM IN COOLING & 20 FPM IN HEATING. TYP FOR
NEW 11'-10" HIGH CEILINGS IN RENOVATION AREAS.
EX. 24X24 RA TO
HVAC-7
EX. 30X30 DAMPER
4"Ø SA
4"Ø RA
10
Ø
10Ø
24
x12
10Ø
10Ø8Ø
10Ø
10Ø
8Ø
12Ø
10
Ø10Ø
6Ø10x4
12
Ø
4Ø
12
Ø
4Ø4Ø
4Ø
4Ø
5Ø
10Ø
10Ø
10Ø
10Ø
6Ø
6Ø
4Ø 4Ø
6Ø
24
x10
20x20
20x20
20x20
20x20
20x2020x20
4Ø24x12
6Ø
SDJ-8250
SDJ-6100
SDJ-8300
SDJ-8300
SDJ-8310
SDJ-10390
SDB-8300
SDJ-8245
SDJ-12500
SDJ-12500
SDJ-8275
SDJ-8275
SDJ-8275
SDJ-8275
SDJ-8275
SDJ-695
SDJ-6125
SDJ-8315
SDJ-10390
SDJ-10380
SDJ-10380
RGA-22X221150
SDJ-10380
SDJ-10385
SDJ-10385
RGA-22X221150
SDJ-8245
HVAC-1
SDJ-8250
RGA-22X221375
HVAC-2
HVAC-2
HVAC-2
HVAC-2
HVAC-1 HVAC-1
RGA-22X221000
SDJ-8315
RGA-22X22500
RGA-22X22600
RGA-22X22390
RGA-22X22300
RGA-22X22245
RGA-22X22120
RGA-22X22125
RGA-22X22490
RGA-22X22310
HVAC-1
EX. NG SERVICE & METER
BELL MOUTH
RETURN, TYP.
EF101
CONNECT TO EX. 24X14 DUCT
UP TO GOOSENECK ON ROOF
CTE
CTE
CTE
CTE
CTE
12Ø
EX. 24X24 RA
UP TO HVAC-3
CLASSROOM 3
103
CLASSROOM 1
104
CLASSROOM 2102
RESOURCECENTRE
101
KITCHENETTE
105
LOUNGE106
BUSINESSCENTRE
107
OFFICE 1108
STORAGE112
OFFICE 2109
P.T. STAFF110
MEETING RM.
111
CORRIDOR113
CTE CTE
CROSSTALK
SILENCER, TYP
3
RGA-22X22235
NEW WALL HEATERS,
5.0 KW EACH, TYP.
VAV2-2
VAV1-3
VAV1-4
EX. RA FROM
HVAC-1 ON ROOF
EX. 48X20 SA FROM
HVAC-1 ON ROOF
200REB
107REB
137REB
92REB
309REB
86REB
145REB
258REB
234REB
0REB
80REB
40REB
46REB
221REB
704REB
166REB
158REB
292REB
212REB
183REB
12x12
REB
xREB
282REB
241REB
234REB
3
3
3
3
3
3
3
3
3
3
1
2
10Ø
6Ø
4Ø
2
2
2
2
2
2
2
2
2
2
VAV1-2
VAV2-1
VAV2-3VAV2-4
VAV2-3
VAV1-1
VAV1-5
CTE
8Ø
8Ø
8Ø20x12
10Ø
10
Ø
24x12
10Ø
10Ø
12Ø
10Ø
10Ø
8Ø
12
Ø1
4Ø
12Ø
12Ø
12
Ø
12Ø 12Ø
12Ø
14
Ø
32Ø
16Ø
14
Ø
14Ø
10Ø
8Ø
10
Ø1
2Ø
10
Ø
14Ø
16Ø
10
Ø
12Ø
10Ø
12
Ø
12Ø
12
Ø12
Ø
12Ø
32Ø
16Ø
16
Ø
16
Ø
40REB
296REB
120REB
75REB
35REB
14
x14
14
x14
22x14
ACOUSTIC
LINING, TYP
ACOUSTIC
LINING, TYP
XTS5
XTS2
XTS2
XTS3
XTS3
XTS3
TRANSFER
DUCT, TYP
XTS5
XTS5
12Ø
16
Ø18
x18
24x20
2
2
12
Ø
12Ø
12Ø
12Ø
20
x12
12
Ø
12Ø
6x6
20
x12
24x12
NEW VD, BALANCE BYPASS
AS REQD FOR RTU MIN
NEW VD, BALANCE
BYPASS AS REQD
FOR RTU MIN
10Ø8Ø
8Ø 10Ø
8Ø 4Ø
8Ø
24
x12
8Ø
24
x10
8Ø 12
x81
2x8
12
x8
6Ø
6Ø
8Ø
6Ø
10Ø
10
Ø1
2Ø
10Ø 12Ø
12Ø
24
x12
12Ø
24x1
2
48x20
CTE12Ø
40
x20
40x20
ACOUSTIC
LINING, TYP
NOT IN
SCOPE
EX. HVAC-1
EX. HVAC-4 EX. HVAC-5
EX. HVAC-3EX. HVAC-6
EX. HVAC-7
EX. HVAC-2
EX. CHIMNEY
EX. EXH. DUCT
EX. 1 1/2"Ø NG
EX. 1"Ø NG
EX. 2"Ø NG
EX. 2 1/2"Ø NG
EX. 3"Ø NG
EX. 2"Ø NG
EX. 1"Ø NG
EX. 1 1/2"Ø NG
EX. 1"Ø NG
EX. GOOSENECK
EX. ROOF HATCH
EX. NG SERVICE & METER
EX. GOOSENECK
HVAC NOTES:
1 EX. RTU, REBANLANCE TO MATCH NEW FLOW RATES
2 PROVIDE YORK MODEL OPTIONAL BOLT ON ERV PER SPECS.
1
1
1
1
1
2
EX. EF3
EX. EF2
EX. EF1
EX. EF4
EX. EF5
E
1
2
3
4
5
6
DCBA
PROJECT No.
DRAWN BY
DATE
CAD FILE
SHEET
ISSUE DATE (Y-M-D) No. ISSUED FOR
CLIENT
SCALE
374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E studio@passa.ca
Passa Associates Inc. WWW.PASSA.CA
PROJECT
ARCHITECTS
Please note that all information included in these drawing files is protected by
copyright. Unauthorized use of these files without the written permission of
Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects
is responsible only for information shown on a mechanical reproduction of these
drawings that have been signed and stamped by an architect with signing
authority employed by the firm.
If you require further information please contact our office at the numbers listed.
A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR
2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.
AUG. 09, 2021
UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.
2021-06-25 1 PROGRESS
2021-06-30 2 PERMIT
2021-07-14 3 FINAL REVIEW
2021-07-27 4 PROGRESS
2021-08-09 5 PERMIT & TENDER
JACE #21-023
SCALE:
FLOOR PLAN - HVAC1/8"=1'-0" SCALE:
ROOF PLAN - HVAC1/8"=1'-0"
M7
FLOOR AND ROOF PLAN - HVAC
1/8" - 1'-0"
2021-08-0921-023
PROJECT No.
DRAWN BY
DATE
CAD FILE
SHEET
ISSUE DATE (Y-M-D) No. ISSUED FOR
CLIENT
SCALE
374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E studio@passa.ca
Passa Associates Inc. WWW.PASSA.CA
PROJECT
ARCHITECTS
Please note that all information included in these drawing files is protected by
copyright. Unauthorized use of these files without the written permission of
Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects
is responsible only for information shown on a mechanical reproduction of these
drawings that have been signed and stamped by an architect with signing
authority employed by the firm.
If you require further information please contact our office at the numbers listed.
A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR
2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.
AUG. 09, 2021
UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.
2021-06-25 1 PROGRESS
2021-06-30 2 PERMIT
2021-07-14 3 FINAL REVIEW
2021-07-27 4 PROGRESS
2021-08-09 5 PERMIT & TENDER
JACE #21-023 M8
DETAILS, DIAGRAMS, & SCHEDULES
AS NOTED
STANDARD CLEVIS PIPE HANGER,
GALVANIZED OR ELECTRO-PLATED
FED. SPEC. WW-H-171E, TYPE I,
OR MSS SP-69, TYPE I
5/8 " ROD, STEEL,
GALVANIZED OR
ELECTRO-PLATED
(THREADED ROD
5/8 " HEX. NUTS WITH
OR ELECTRO-PLATED
BOLT CASING
NEW INSULATION PROTECTION SHIELD,
FED. SPEC. WW-H-171E TYPE 41
AND MSS SP-69 TYPE 40
CONCRETE EXPANSION
FLAT WASHERS, GALVANIZED
NOT ALLOWDED)
CEILING HUNG CLEVIS HANGER
FOR INSULATED PIPE
FLOW
CONCRETE SURFACE OR FLOOR
COVERING AS REQUIRED
CLEANOUT COVER
CSK SCREW
CLEANOUT PLUG
FINISHED FLOOR
CAULKING FERRULE
FLOOR CLEANOUT-FINISHED ROOMSSCALE: NONE
SCALE: NONE
MAY EXTEND ASWASTE OR VENT
FOR WALL CONST.REF. ARCH. DWGS.
POLISHED S.S.ACCESS COVER
CLEANOUT TEE
WASTE LINE LENGTH TO SUIT 1/8" BEND AND END
OF LINE CLEANOUT
WASTE LINE
CLEANOUTPLUG
COUNTERSUNKSCREW
FLOW
WALL CLEANOUT-FINISHED ROOMSSCALE: NONE
DIMENSIONS
BRANCH DUCT
EQUAL TO REQ'D
WIDTH, BUT MIN. 4"
1/4 BRANCH DUCT
AND BOTTOM
1" MIN. ON TOP
MAIN DUCT
AROUND
SEAL ALL
AND BOTTOM
1" MIN. ON TOP
MAIN DUCT
AROUND
SEAL ALL
ELBOW RINGS
ADJUSTABLE
AIRFLOW
SUPPLY
BRANCH DUCT DIA.
EQUAL TO REQ'D
45°45°
BRANCH TAKE OFF FITTINGSCALE: NONE
CONTROL DIAGRAM
SCALE: NONE
THERMOSTAT /
ZONE CONTROLLER
ZONE DAMPER, TYP.
ACTUATOR, TYP
BYPASS DAMPER
SUPPLY AIR SENSOR
RETURN AIR SENSOR
SENSOR / TRANSDUCER
STATIC PRESSURE
OUTDOOR AIR SENSOR
RTU, TYP.
OSA
SUPPLY AIR DUCT
ROOFTOP CONTROLLER
RETURN AIR DUCT
DIRECT EXP.
DDC
CONTROLLER
LOCAL
GRAPHICAL
INTERFACE
(GUI)
NOTE: SEE FLOOR PLANS FOR ACTUAL NUMBER OF ZONES PER RTU.
2021-08-0921-023