Level 2 Electric Vehicle Charging StationCat. No. EVB32
Installation Instructions
WARNINGS AND CAUTIONS:• Iftheinformationinthisinstructionsheetisnotfollowedexactly,SHOCK OR FIRE MAY RESULT CAUSING PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.• Foroutdoorinstallations,hardwireconnectionisrequiredtomaintainNEMA4weatherproofrating.• Hard-wireinstallationandservicemustbeperformedbyanelectrician.• IMPORTANT:Savetheseinstructionsforlocalelectricalinspector’suseandfuturereference. NOTE:Unitoperateson208Vor240Vcircuit,itwillnotoperateon120V.
DI-001-EVB32-00A-X1
ThankyouforpurchasingtheLevel232AElectricVehicleChargingStation.Thisinstallationsheetincludesthelatestinformationatthetimeofprinting.Levitonreservestherighttomakechangestothisproductwithoutfurthernotice.Changesormodificationstothisproductbyotherthananauthorizedserviceprovidercouldvoidtheproductwarranty.Ifyouhavequestionsabouttheuseofthisproduct,contactyourCustomerServiceRepresentative.RefertotheCustomerSupportsectionlocatedintheseinstructions.Important Notes to the Installer:• Readallinstructionscontainedintheseinstallationinstructionsbeforeinstalling
hard-wiredversionoftheChargingStation.• Theinstallerisresponsibleforverifyingthatthewallstructure/surfacewillsafely
supportatotalloadof200lbs.• Observeallgoverningcodesandordinances.• Besuretoleavetheseinstructionswiththeconsumer.Important Notes to the Consumer:• KeeptheseinstructionswithyourUserGuideforfuturereference.• EnsureyourChargingStationisinstalledproperlybyanelectricianorservice
technician.
INTRODUCTION MOUNTING LOCATIONTheChargingStationshouldbelocatedincloseproximitytotheelectricvehicle’sparkinglocation.TheChargingStationmustconnecttotheelectricvehicleviaa ChargeConnectorandChargeConnectorCord.NOTE:ThepathfromtheChargingStationtotheelectricvehicleshouldbefreefromobstacles,andbewithintherangeoftheChargeConnectorCord(18or25footstandardlengths).TherecommendedmountingheightoftheChargingStationisnottoexceed48inches,butnotlessthan42inches.Thisprovidesconvenientaccessandoperation oftheChargingStation,andmeetsADArequirementsforaccess.NOTE:TheareasurroundingtheChargingStationenclosureshouldbefreefromobstruction.Recommendedclearancearoundstation:5"aboveand3-1/2"on eitherside.
MOUNTING INSTALLATIONSelectalocationthatissuitableformountingtheChargingStationbasedon thecriteriapresentedintheMOUNTINGLOCATIONsection.Forstudwalls,theChargingStationcanbemountedtobarestudsorwallswithdrywall.Formetalstudorsolidwallapplications,youwillneedtoprocurewallanchorsfortheChargingStation,capableofsupportingamaximumallowableloadof200lbs.Forsolidwallapplicationsyouwillalsoneedtoprocureappropriateconduitandappropriatewallanchors.
NOTE:ThePlug-InChargingStationmustbeinstalledwithaLevitonPre-WireKit(sold separately).FailuretodosomeansthestationnolongercomplieswithitsULlisting.Thelistingrequiresthestationberemovablewithouttools.RefertoPre-WireKitinstructionsfirstifamountinglocationhasnotbeenestablished.1. Locatetheslotabovethethumbscrew.LocatethefourMountingButtonsonthe
backoftheChargingStation(see Figure 1).2. Aligntheslotwiththeguidepin,andthefourMountingButtonswiththefourkey
holesontheMountingBracket.3. Oncealigned,gentlypresstheChargingStationontotheMountingBracket.4. AllowtheChargingStationtoslowlyslidedownintoplace.5. TightenthethumbscrewtosecureChargingStationtoMountingBracket.Proceed to POWER CHARGING STATION section.
PLUG-IN INSTALLATION
Gathertherequiredtoolsandpartsbeforestartinginstallation.Besuretofollowmanufacturer’sinstructionsforuseofanytoolsorpartsusedforthisinstallation.
Tools:• Drillwith3/16"bit • Studfinder • Level• Scratchawl • #2and#3Phillipsscrewdriver • Utilityknife• Measuringtape • Wirecutters/strippers • Keyholesaw
Additional Parts (not included):• Copperelectricalcable(10AWGminimum) • Conduit• 40ACircuitBreaker • Strainrelief(ifapplicable)• #14woodmountingscrews(2)-studmount • H100-TBHub
(orengineeringequivalent)For Metal Stud Applications: • Wallanchorscapableofsupportingamaximumallowableloadof200lbs.For Solid Wall Applications: • Wallanchorscapableofsupportingamaximumallowableloadof200lbs. • Appropriateconduitandapplicablemountinghardware.
HARD-WIRE INSTALLATION
TO INSTALL:1. Toinstallthechargingstationbyuseofmountingscrews,firstremovethe
4mountingbuttonsfromthechargingstation(See Figure 1 Rear View).2. LocateawallstudintheareainwhichtheChargingStationwillbeinstalled
(See Figure 2).3. Measure48"upfromthefloorandplaceamarkonthestudthatwillbeused
formounting.4. Forwoodstuds,drilla3/16"diameterpilothole,2-1/2"deep,directlyinthe
middleofthestud.Formetalstuds,followmanufacturer’sinstructionsforwallanchorinstallation.
5. Looselyfastena#14x2-1/2"Lwoodscrewbyturningthescrewintothepilotholeuntilapproximately1/2"lengthremains.HooktheChargingStationontothescrewusingthetopkeyholeslot.Secureinplacebyinstallinganadditionalscrewthroughthebottomsetscrewhole.
6. CutoffandremoveWarrantyVoidPadlock(See Figure 5).7. UseastandardscrewdrivertoopentheEnclosureDoorfromthesidetogain
accessandtightentopmountingscrew.Proceedwithhard-wiredinstallation.
Mounting buttons(bracket mount)
Mountingbracket(mountedto wall)
Guide pin
Thumbscrew
Keyhole (stud mount)
Charging Station Mounting
Figure 1 Rear view
NOTE:Ahard-wiredinstallationcanbemounteddirectlytothewall,orwiththeuseoftheMountingBracketincludedinthePre-WireKit(purchasedseparately).Tomountdirectlytoastudwall,followdirectionsbelow:
Topmountingscrew
Bottommountingscrew
Pilot holefor mountingscrew
Center linefor wall stud
Wall stud
DrywallHard-Wire
Stud Wall Installation
Figure 2
48"
For more information call 1-877-338-7473 or visit leviton.com/evrgreen
LIMITED THREE (3) YEAR WARRANTY AND EXCLUSIONSLeviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship undernormal and proper use for three years from the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option, if within such three year period the productis returned prepaid, with proof of purchase date, and a description of the problem to Leviton Mfg. Co., Inc. 201 North Service Road, Melville, N.Y. 11747.This warranty excludes and there is disclaimedliability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered inany manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particularpurpose, is limited to three years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
RATINGS
120/208V60Hz3-phaseY(L1-G/L2-G-120V,L1-L2–208V)120/240V60HzSplit-phase(L1-G/L2-G-120V,L1-L2–240V)
32A
Voltage
Current
NOTE:ChargingStationoperateson120/208Vor120/240Vcircuitonly.Doesnotoperateon120Vcircuit.
©2012LevitonMfg.Co.,Inc. DI-001-EVB32-00A-X1
CUSTOMER SUPPORT
CallourCustomerSupportHotlineat1-877-338-7473.Ifyourcallismadeafterbusinesshoursoronweekends,pleaseleaveyourname,telephonenumber,theunit’sserialnumber,andabriefdescriptionoftheproblem.ThesecanbefoundonthelabelontheleftsideoftheChargingStationenclosure.ACustomerServiceRepresentativewillcallbackattheearliestopportunity.Manyquestionsandanswerscanbefoundinourknowledgebasecommunity.Justgotoleviton.comandclickontheKnowledgebaselink,orgodirectlyto leviton.com/evrgreen.
WARNING: HARD-WIREINSTALLATIONANDSERVICEMUSTBEPERFORMEDBYANELECTRICIAN.WARNING:TOAVOIDFIRE,SHOCK,ORDEATHTURN OFF POWERATCIRCUITBREAKERORFUSEANDTESTTHATPOWERISOFFBEFOREWIRING!CAUTION:USETHISDEVICEWITHCOPPER OR COPPER CLAD WIRE ONLY.CAUTION: A40ABREAKERSHALLBEUSED.DO NOTUSEWIRELESSTHAN 10AWGREFERTOTABLE 1FORPROPERTORQUEVALUES.1. IfnecessaryuseastandardscrewdrivertoopentheEnclosureDoorfromtheside
togainaccessforwiring.2. Remove(2)WireNutsandloosengroundwirefromterminalblock.Remove
pre-installedhubanddisconnectexistingplugassembly.InstallaH100-TBhub.3. Verifythatappropriate40Acircuitbreaker,conduitandwiregaugehavebeen
selected.4. RunanindividualcircuitaspertheNationalElectricCodeandlocalbuildingcodes.
ThecircuitmustreachthebottomoftheChargingStationwithanadditional5"ofloosewiretoterminatetheconnectionontheinsideofChargingStation. NOTE:Useappropriatestrainreliefforconduitifapplicable.
5. Feedconduitthroughhub.Leaveapproximately5"ofwireleadintheChargingStation.Secureconduittohubusingproperconduitfitting.Theuseofareducermayberequiredbasedonconduitfittingselected(see Figure 3).
6. Stripwires1/2".Insertgroundwireintoterminalblockandsecurewirebytighteningterminalscrews(RefertoTABLE 1forpropertorquevalues).ConnectLine1andLIne2withwirenuts(see Figure 4).
7. CloseEnclosureDoorandsecurelockwithscrewdriver.PlacenewWarrantyVoidPadlockontothelockingtab (see Figure 5).
HARD-WIRING CHARGING STATION
Figure 4 - Terminal Block Connection
B C
D
ound
= Line 1 (Hot)
= Line 2 (Hot)
= Gr
A
B
C= ToroidD
Strip Gage
3/8"(.95 cm)
A
1" NPT Hub
Conduit
Cable
Guide pin slot
Figure 3 - Wiring Charging Station
Thumb screw
2-1/2" mounting screw
POWER CHARGING STATION
NOTE: For Hard-Wire Installation,restorepoweratcircuitbreakerorfuse. For Plug-In Installation,simplyplugtheACSupplyCordintotheNEMA6-50Rgrounded50A,240VACelectricaloutletsuppliedwiththepre-wirekitandingoodworkingconditiontostartpowerupsequence.
Power Up Sequence
• ThePower,ChargingandFaultLEDswillilluminatemomentarilyfollowedbyjustthePowerLED.TheChargingStationwilltheninitiateaself-testsequence.
NOTE:DONOTplugtheChargeConnectorintothevehiclepriorto theself-test;thismaycausetheChargingStationtogointoColdLoad Pick-up,anddelaycharging.
• ThePowerLEDwillflashforapproximately3secondsindicating theself-test,andthenthePowerLEDwillremainlit,indicatingthattheChargingStationisreadyforuse.
Refer to Level 2, 32A Electric Vehicle Charging Station User Guide for operation.
Warranty Void Padlock Placement
Figure 5
Wire Gauge Torque
6 CU/AL 45 in/lbs.8 CU/AL 40 in/lbs.10 CU/AL 35 in/lbs.
TABLE 1
Wiring Diagram - 240V
Meter
G
L1N
L1
L2
L2
MainBreaker
L2
Neutral
L1
Neu
tral
Bu
sG
rou
nd
Bu
s
Ground
40 A
120/240V Charging Station
Local ServicePanel
Wiring Diagram - 208V
G
L1N
L1
L2 L3
L2
MainBreaker
Neu
tral
Bu
sG
rou
nd
Bu
s
40 A
Charging Station
Local ServicePanel
L3
L2
Neutral
L1
Ground
120/208V
Meter
Recommended