Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road
Kewaunee, Wl 54216-9511 Two Rivers, Wl 54241
NM C 920.388.2560 920.755.2321
Committed to Nuclear Excellence Kewaunee / Point Beach Nuclear Operated by Nuclear Management Company, LLC
NRC-02-015
February 22, 2002 10CFR50.55a
U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555
Ladies and Gentlemen:
Docket 50-305 Operating License Kewaunee Nuclear Power Plant 2001 Inservice Inspection (ISI) Summary Report
As required by ASME Boiler and Pressure Vessel Code, Section XI; Code of Federal Regulation 1OCFR50.55a; and Wisconsin Administrative Code, Subchapter V ILHR 41.55(3) and ILHR 41.56; various ISI examinations were performed as part of the 2001 Refueling Outage. The outage took place from September 24, 2001 through December 4, 2001; i.e. closing of G1. This letter transmits the Inservice Inspection Summary Report as required by paragraph IWA-6230 of Section XI.
Two separate ASME Section XI inservice examination programs are implemented at the KNPP. One program is for pressure retaining piping/vessel and component supports and the other program for the metal containment. The 2001 refueling outage constituted the first inspection year of the third period of the third interval for the piping/vessel and component support program, including preservice examinations associated with steam generator replacement. The 2001 refueling outage was also the first inspection year of the second period of the first interval for the metal containment program. Examinations for the piping/vessel and component support program, including preservice examinations associated with steam generator replacement, were performed in accordance with the ASME Boiler and Pressure Vessel Code Section XI 1989 Edition. Examinations for the metal containment program were performed in accordance with the 1992 Edition up to and including the 1992 Addenda of Section XI of the ASME Boiler and Pressure Vessel Code. These requirements were implemented in accordance with the "Kewaunee Nuclear Power Plant Third Ten-Year Inservice Inspection (ISI) Program 1994-2004," "Kewaunee Nuclear Power Plant First 10-Year Inservice Inspection Class MC (ISI) Program 1996-2006," Plant Technical Specifications, and nondestructive examination procedures.
Docket 50-305 NRC-02-015 February 22, 2002 Page 2
The following items were examined for Class 1, Class 2, Class 3 Components and their supports:
1. Reactor Vessel Closure Head Flange Weld 2. Reactor Vessel Closure Head Studs, Nuts, Washers and Control Rod Drive Mechanisms 3. Pressurizer Circumferential and Longitudinal Welds 4. Steam Generator Head Circumferential Weld, Nozzle Inside Radius Sections and Nozzle To
Shell Weld 5. Reactor Coolant Pump Main Flange Bolting and No. 1 Seal Housing Bolting 6. Seal Water Injection Filter Shell Circumferential Weld 7. Letdown Heat Exchanger Head Circumferential Weld 8. Charging Pump Pulsation Dampener Head Circumferential Weld 9. Class 1 Valve Bodies
10. Class 1 and Class 2 Piping Welds 11. Class 1 Piping Integrally Welded Attachment 12. Class 2 Piping Integrally Welded Attachments 13. Class 2 Safety Injection Pump Casing Weld and Welded Attachments 14. Class 1, Class 2 and Class 3 Piping and Component Supports and Hangers 15. Class 1 and Class 2 Reactor Vessel Conoseal Bolting, Pressurizer Manway Bolting, Flange
Bolting and Valve Bonnet Bolting 16. Class 1 System Leakage Test 17. Class 2 and Class 3 System Inservice and Functional System Pressure Tests
The following items were examined for the Replacement Steam Generators:
1. Replacement Steam Generators: Tubesheet to Head Welds, Nozzle Inside Radius Sections, Nozzle to Safe End Butt Welds, Primary Side Manway Bolting, Integrally Welded Attachments, Shell Circumferential Welds, Tubesheet to Shell Welds and Class 1 Support Components
2. New Class 1 Reactor Coolant Piping Welds 3. New and Replacement Class 2 Main Steam and Feedwater Piping Welds 4. Reexamination of Existing Steam Generator, Circumferential Welds SG-W2 and SG-W10 to
verify previously recorded Ultrasonic Planar Indications 5. Existing 16", 8" and 1" Feedwater Inside Diameter Surfaces 6. Existing Steam Generator Inside Diameter Feedwater Nozzle Inner Radius and Shell
Circumferential Welds 7. Existing Steam Generator Class 2 Supports
Docket 50-305 NRC-02-015 February 22, 2002 Page 3
The following items were examined for the Class MC Reactor Building Containment Vessel:
1. Accessible Surface Areas 2. Longitudinal Welds and Circumferential Welds 3. Sleeve to Bellows Welds 4. Flange Welds 5. Seals and Gaskets 6. Moisture Barriers 7. Dissimilar Metal Welds 8. Bolted Connections 9. Containment Penetration Bellows
10. Airlocks
The following items were examined in accordance with Kewaunee Nuclear Power Plant Technical Specifications:
1. Eddy Current Testing of Replacement Steam Generators 2. Functional Testing, Disassembly and Overhaul of Steam Generator 900 KIP Hydraulic
Snubbers
In addition, the following examinations were performed in excess of ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Requirements and included:
1. Portions of the Service Water System were radiographed for wall loss, pits, nodules, and sand, mud or other sediments.
2. Balance of plant piping subject to erosion/corrosion was examined by radiographic, ultransonic, and visual techniques.
Docket 50-305 NRC-02-015 February 22, 2002 Page 4
Please find attached a copy of the following documentation that summarizes the inservice inspection activities and results for the Kewaunee Nuclear Power Plant 2001 Refueling Outage.
1. Summary of recordable indications and a description of how they were dispositioned (Attachment 1)
2. Summary of Class 1 and 2 Repairs and Replacements of Components 1 inch in diameter or smaller (Attachment 2)
3. Form NIS-1 Owner's Report for Inservice Inspections of Class 1, Class 2, and Class 3 Components (Attachment 3)
4. Form NIS-I Owner's Report for Inservice Inspections for Class MC Components (Attachment 4) 5. Form NIS-I Owner's Report for Inservice Inspections of Replacement Steam Generators
(Attachment 5) 6. Form NIS-2 Owner's Report for Repair or Replacements (74 Total) (Attachment 6) 7. Examination Summary for Scheduled and Augmented Inservice Inspection (ISI) Program
(Attachment 7) 8. Examination Summary for Inservice Inspection (ISI) Class MC Program (Attachment 8) 9. Examination Summary for Preservice Inspection (PSI) of Steam Generators (Attachment 9)
10. Examination Summary for Replacement Steam Generator Eddy Current (Attachment 10) 11. Examination Summary for Steam Generator 900 KIP Hydraulic Snubbers (Attachment 11) 12. A summary of examinations which were limited by geometric, metallurgical, or design/access
restrictions and their associated data sheets (Attachment 12)
The final reports for each of these examinations are on file in the QA/QC Records Vault at the Kewaunee Nuclear Power Plant. These records are available for review as deemed necessary.
Additional Comments
The next Refueling Outage at the Kewaunee Nuclear Power Plant is tentatively scheduled for April 4, 2003 through April 30, 2003.
Sincerely,
Thomas Coutu
Manager-Kewaunee Plant
PEB/CAT
Attach. cc - U.S. NRC - Region III (w/o attach)
U.S. NRC - Senior Resident Inspector (w/o attach)
ATTACHMENT 1
Letter from T. Coutu (NMC)
To
Document Control Desk (NRC)
Dated
February 22, 2002
Summary of Recordable Indications and Description of Disposition
Docket 50-305 NRC-02-015 February 22, 2002 Attachment 1, Page 1
TABLE 1
TYPE OR LOCATION OF RECORDABLE i O INDICATION (RI) METHOD NO. OF RI'S
Reactor Vessel Closure Head Flange Weld Surface (MT) 1 Weld Steam Generator Circumferential Head Weld Volumetric (UT) 1 Weld Seal Water Injection Filter Shell Weld Volumetric (UT) 1 Weld Piping Integrally Welded Attachment Surface (PT) 1 Weld Piping Circumferential Butt Weld Surface (PT) 1 Weld Piping Socket Weld Surface (PT) 1 Weld Reactor Vessel Conoseal Bolting Visual (VT-3) 1 Conoseal RC Pump No. 1 Seal Housing Bolting Visual (VT-1) 1 Pump Pressurizer Manway Bolting Visual (VT-3) 1 Manway Component Supports and Hangers Visual (VT-3) 31 Supports Valve Bonnet Bolting Visual (VT-1) 1 Valve Valve Bonnet Bolting Visual (VT-3) 6 Valves System Pressure Tests Visual (VT-2) 51 Items Replacement Steam Generator Integrally Welded Surface (MT) 1 Weld Attachment SG-1B-23B Replacement Steam Generator Tubesheet To Head Weld Volumetric (UT) 1 Weld SG-W32 Replacement Steam Generator Primary Side Manway SG- Visual (VT-i) 1 Stud 1B-CLMWB Replacement Steam Generator Tubesheet To Shell Weld Volumetric (UT) I Weld SG-W31 Existing Steam Generator Feedwater Nozzle Inner Radius Surface (MT) 1 Nozzle SG-IR8 Existing Steam Generator Feedwater Nozzle Inner Radius Surface (MT) & 1 Nozzle SG-IR16 Visual (VT-1) Existing Steam Generator Circumferential Welds SG-W2 Volumetric (UT) 2 Welds and SG-W10 Existing 16", 8" and 1" Feedwater Piping FW-W27BC Surface (MT) 1 ID Section Existing 16", 8", and 1" Feedwater Piping FW-W55BC Surface (MT) & 1 ID Section
Visual (VT-1) Reactor Building Containment Vessel General Visual 11 Plates Reactor Building Containment Vessel Moisture Barriers VT-3 5 Plates Reactor Building Containment Vessel Emergency Airlock VT-1 1 Bolt
Docket 50-305 NRC-02-015 February 22, 2002 Attachment 1, Page 2
Disposition of Class 1, Class 2, and Class 3 indications have been completed in accordance with the rules of ASME Boiler and Pressure Vessel Code Section XI 1989 Edition and ASME Boiler and Pressure Vessel Code Section XI 1992 Edition up to and including 1992 Addenda for Class MC Components. Applicable codes, standards, and engineering criteria were used to disposition indications associated with the non-code-required examinations. Recordable indications for Class 1, Class 2, Class 3 and Class MC have been dispositioned as summarized below:
1. A 0.125" long linear indication was recorded on the Reactor Vessel Closure Head Flange Weld RV-W12 during performance of magnetic particle examination. This linear indication was acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWB-3510-3.
2. A spot indication on Steam Generator 1B Circumferential Head Weld SG-W9 was recorded during performance of ultrasonic examination. This ultrasonic spot indication was acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWC-3510-1.
3. Five (5)laminar indications combined into four (4) laminar indications due to proximity of the indications. The indications are on seal water injection filter IA circumferential shell weld AFSI-Wl and were identified during performance of ultrasonic examinations. These laminar indications were acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWC-3510-2 and were typical of laminations recorded on seal water injection filters 1A and 1B during Refueling Outages 1982, 1986, 1988, 1992 and 1998.
4. Three (3) rounded indications (0.625", 0.125" and 0.1875" in diameter) were recorded on 2" piping integrally welded attachment RSI-H72 during performance of liquid penetrant examinations. These three (3) rounded indications were acceptable per ASME Boiler and Pressure Vessel Code Section III 1989 Edition Section NC-5352(b).
5. A 0.125" long linear indication and a 0.125" rounded indication were recorded on 6" diameter Circumferential Butt Weld ICS-W43 during performance of liquid penetrant examinations. The 0.125" long linear indication was acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWB-3514-2. The 0.125" rounded indication was acceptable per ASME Boiler and Pressure Vessel Code Section III 1989 Edition Section NC-5352.
6. A 0.55" long linear indication on 2" diameter socket weld SI-W6S was recorded during performance of liquid penetrant examinations. This linear indication was unacceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWB-3514-2. The linear indication was removed under Work Order 01-016342 by light filing with a jewelers file, reexamined and accepted with no indications.
Docket 50-305 NRC-02-015 February 22, 2002 Attachment 1, Page 3
7. Visual (VT-1, VT-2 and VT-3) indications were recorded on reactor vessel conoseal bolting, reactor coolant Pump No. 1 seal housing bolting, pressurizer manway bolting, valve bonnet bolting, piping supports and hangers and during system pressure tests. The indications were either (1) evaluated and accepted or (2) repaired, reexamined and accepted by: Nuclear Management Company, LLC - Maintenance, Quality Control, Engineering and Technical Support or Inservice Inspection Personnel and reviewed by the Authorized Nuclear Inservice Inspector.
8. Two (2) separate linear indications on replacement steam generator 1B integrally welded attachment SG-1B-23B were recorded during performance of magnetic particle examinations. These two linear indications due to their close proximity to each other were classified as one linear indication with a length of 0.21875." This linear indication was acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Sections IWB-3516.1, IWB-3510.3 and IWB-3510-3.
9. Ultrasonic recordable indications at three separate locations on replacement steam generator lB tubesheet to head weld SG-W32 were noted during performance of manual ultrasonic examinations. These three separate planar indications were acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWB-3510-1.
10. One visual indication was recorded by the VT-1 method on replacement steam generator 1B primary side manway stud SG-1B-CLMWB#17. Although this primary manway stud was acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Section IWB-3517.1 (b), a new VT-1 acceptable replacement stud was installed.
11. Ultrasonic recordable indication at one location on replacement steam generator 11B tubesheet to shell weld SG-W31 was noted during performance of manual ultrasonic examination. This planar indication was acceptable per ASME Boiler and Pressure Vessel Code Section XI 1989 Edition Table IWC-3510-1.
12. Recordable indications on the existing steam generator lB feedwater nozzle inside radius section SG-IR8 were recorded during augmented examination by magnetic particle. These indications were repaired by Bechtel Corporation under Bechtel's NCR's and Kewaunee Nuclear Power Plant Work Orders as part of replacement steam generator activities.
13. Recordable indications on the existing steam generator 1A feedwater nozzle inside radius section SG-IR16 were recorded during augmented examinations by magnetic particle and visual (VT-1) methods. These indications were repaired by Bechtel Corporation under Bechtel's NCR's and Kewaunee Nuclear Power Plant Work Orders as part of replacement steam generator activities.
Docket 50-305 NRC-02-015 February 22, 2002 Attachment 1, Page 4
14/15. Prior to severing the existing steam generators and following welding the replacement steam generators to the existing steam generators a manual ultrasonic examination was performed on the existing circumferential shell welds SG-W2 and SG-W10 to ensure that there was no growth in the previously recorded planar indications. These indications were recorded in 1991 for SGW2 and in 1991 and 1996 for SG-Wl0. All indications previously recorded as well as new indications recorded due to amplitude recording criteria change were acceptable either by ASME Boiler and Pressure Vessel Code Section XI 1989 acceptance standards or by fracture analysis as provided in Westinghouse Electric Corporation WCAP 11476 Rev.3 Handbook on Flaw Evaluation, Kewaunee Unit 1 Steam Generator Upper Shell to Cone Weld, May 1991, and evaluation by Kewaunee Nuclear Power Plant during 1996 and 2001 Refueling Outages.
16. Recordable indications on Loop A existing 16", 8" and 1" feedwater piping inner diameter surface for FW-W27BC were recorded during augmented magnetic particle examinations. These indications were repaired by Bechtel Corporation under Kewaunee Nuclear Power Plant Work Orders generated during steam generator replacement activities.
17. Recordable indications on Loop B existing 16", 8" and 1" feedwater piping inner diameter Surface for FW-W55BC were recorded during augmented examinations by magnetic particle and visual (VT-1) methods. These indications were repaired by Bechtel Corporation under Kewaunee Nuclear Power Plant Work Orders generated during steam generator replacement activities.
18. General visual indication consisting of a 4" x 8" surface defect was recorded on Plate 155. This surface defect was previously recorded and accepted in 1998 and showed no change in dimension or surface condition during the 2001 Refueling Outage.
19. General visual indication consisting of a slight inward bulge on Plates 74, 75, and 83 was recorded. The slight inward bulge was evaluated by Engineering and accepted under Kewaunee Nulcear Power Plant Specification TS-1052, Addendum No. 4, Item No. 19 Section 10.3 - Shell Tolerance.
20. General visual indication consisting of slight outward bulges on Plates 144, 145, 146, 147 and 148 were recorded. The slight outward bulges were evaluated and accepted by Engineering Analysis.
21. General visual indications consisting of weld deposits on Plate 62 and arc strikes on Plate 99 were recorded and are acceptable per ASME Boiler and Pressure Vessel Code Section XI 1992 Edition 1992 Addenda.
22. VT-3 indications consisting of lack of bonding and tears were recorded in the moisture barriers on Plates 62, 64, 65, 66 and 67 and were repaired under Work Order 0 1-018045.
23. A VT-I indication on an emergency airlock bolt was recorded and was repaired under Work Order 01-018283.
ATTACHMENT 2
Letter from T. Coutu (NMC)
To
Document Control Desk (NRC)
Dated
February 22, 2002
Summary of Class 1 and 2 Repairs and Replacement of Components 1 inch in Diameter or Smaller
Docket 50-305 NRC-02-015 February 22, 2002 Attachment 2, Page 1
The following summarizes the repairs and replacements performed following the 2000 Refueling Outage and during the 2001 Refueling Outage by grinding, buffing, filing, cutting or welding on the Class 1 and Class 2 pressure boundary. These repairs and replacements are in addition to those itemized on the attached Forms "NIS-2 Owner's Report for Repairs or Replacements."
Component Class Reference Repair/Replacement Method 3/4" Valve PS-2A 1 XK-100-10 Cutting and Welding of Replacement
Valve 3/4" Valve PS-30 1 XK-100-10 Cutting and Welding of Replacement
Valve 1" Valve RC-45A 1 XK-100-10 Cutting and Welding of Replacement
Valve and Piping 1" Valve RC-45B 1 XK-100-10 Cutting and Welding of Replacement
Valve and Piping Replacement Steam 1 XK-100-10 Repair by Welding Fillet Weld Generator 1B 1/2" Internal Nozzle Drain Line 3/4" Valve 1 XK-100-35 Cutting and Welding of Replacement CVC-21070-1 Valve Replacement Steam 2 M-203 Buffing and Grinding involving Metal Generators 1A and Removal for Arc Strikes, Gouges and 1B: 2", 1" and 3/4" Weld Spatter Piping Replacement Steam 2 M-205 Machining involving Metal Removal for Generators 1A and Pitting 1B Secondary Side Hand Holes
ATTACHMENT 3
Letter from T. Coutu (NMC)
To
Document Control Desk (NRC)
Dated
February 22, 2002
FORM NIS- 1 Owner's Report for Inservice Inspections of Class 1, Class 2, Class 3 Components
Page 1 of 9
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,
P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT OR APPURTENANCE
Reactor Vessel RV
Pressurizer PZR
Steam Generator SG1A
Steam Generator SGlB
Excess Letdown Heat Exchanger AHEL-1A
Excess Letdown Heat Exchanger AHEL-1B
Class 1 Piping
Reactor Coolant Pump RCP-1A
Reactor Coolant Pump RCP-1B
Residual Heat Exchanger AHRSI-IA
MANUFACTURER OR INSTALLER
Combustion Engineering
Westinghouse
Westinghouse/ Ansaldo Energia Milano
Westinghouse/ Ansaldo Energia Milano
Sentry
Sentry
Texas Pipe Bending
Westinghouse
Westinghouse
Joseph Oat and Sons
MANUFACTURER OR INSTALLER
SERIAL NO.
CE69202
1151
1141/0202
1142/0201
3996-5E
3996-6E
STATE OR PROVINCE NO.
U11480
U11402
U11400
U11401
U11407
U11408
NATIONAL BOARD NO.
21010
68-23
68-28/151
68-29/150
364
365
1A-1-618J871GO1
1B-2-618J871G02
1817-1E U11046 344
Page 2 of 9
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,
P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT OR APPURTENANCE
Residual Heat Exchanger AHRS2-1B
Charging Pump Pulsation Dampener APD-1A
Charging Pump Pulsation Dampener APD-1B
Charging Pump Pulsation Dampener APD-1C
Seal Water Heat Exchanger AHSW
Volume Control Tank VCT
Regenerative Heat Exchanger ARG
Letdown Heat Exchanger AHLD
MANUFACTURER OR INSTALLER
Joseph Oat and Sons
Greer Hydraulics
Greer Hydraulics
Greer Hydraulics
Atlas
Joseph Oat and Sons
Joseph Oat and Sons
Atlas
MANUFACTURER OR INSTALLER
SERIAL NO.
1817-1F
STATE OR PROVINCE NO.
U11424
NATIONAL BOARD NO.
345
GNI-1848
GNI-1846
GNI-1847
734
1787-1C
1831-13
1206
U11404
U11425
U11409 U11410 U11411
U11405
596
376
413 414 415
1031
Page 3 of 9
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS, P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT OR APPURTENANCE
Seal Water Injection Filter AFSI-1A
Seal Water Injection Filter AFSI-1B
Reactor Coolant Filter AFRC
Seal Water Filter AFSW
Class 2 Piping
Charging Pump APCH-1A
Charging Pump APCH-1B
Charging Pump APCH-1C
Charging Pump APCH-1A Suction Stabilizer
MANUFACTURER OR INSTALLER
Commercial Filters
Commercial Filters
AMF Cuno
AMF Cuno
Texas Pipe Bending
Ajax Iron Works
Ajax Iron Works
Ajax Iron Works
Greer Hydraulics
MANUFACTURER OR INSTALLER
SERIAL NO.STATE OR
PROVINCE NO.
101072
101073
121
123
NATIONAL BOARD NO.
1172
1173
2616
2618
6578
6576
6577
GH1-10234 568
Page 4 of 9
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,
P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT OR APPURTENANCE
Charging Pump APCH-1B Suction Stablizer
Charging Pump APCH-1C Suction Stablizer
Residual Heat Removal Pump APRHI-IA
Residual Heat Removal Pump APRH2-1B
Refueling Water Storage Tank
Diesel Generator AHDG-1A Cooling Water Exchangers (2)
Diesel Generator AHDG-1B Cooling Water Exchangers (2)
MANUFACTURER OR INSTALLER
Greer Hydraulics
Greer Hydraulics
Byron Jackson
Byron Jackson
General American Transportation Company
ITT Standard Corp.
ITT Standard Corp.
MANUFACTURER OR INSTALLER
SERIAL NO.STATE OR
PROVINCE NO.NATIONAL BOARD NO.
569GH1-10235
GH1-10236
681N0277
681N0276
C-8297/1969
750797-01-2 &
750797-01-3
750797-01-1 &
750797-01-4
570
Page 5 of 9
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,
P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT OR APPURTENANCE
Auxiliary Feedwater Pump APFM-1A Motor Driven
Auxiliary Feedwater Pump APFM-1B Motor Driven
Auxiliary Feedwater Pump APFT Turbine Driven
Class 3 Piping
Containment Fan Cooler AHCF-1A
Containment Fan Cooler AHCF-1B
MANUFACTURER OR INSTALLER
Pacific Pump
Pacific Pump
Pacific Pump
Texas Pipe Bending
Joy Manufacturing and American Air Filter
Joy Manufacturing and American Air Filter
MANUFACTURER OR INSTALLER
SERIAL NO.STATE OR
PROVINCE NO.NATIONAL BOARD NO.
46573
46574
46575
GF14402
GF14399
Page 6 of 9
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,
P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT OR APPURTENANCE
Containment Fan Cooler AHCF-1C
Containment Fan Cooler AHCF-1D
Safety Injection Pump APSI-1A
Safety Injection Pump APSI-1B
Safety Injection Pump Lube Oil Cooler AHSC-1A
Safety Injection Pump Lube Oil Cooler AHSC-1B
Safety Injection Pump Heat Exchangers (2) AHSC-1A
MANUFACTURER OR INSTALLER
Joy Manufacturing and American Air Filter
Joy Manufacturing and American Air Filter
Bingham Pump
Bingham Pump
Thermxchanger
Thermxchanger
Borg Warner
MANUFACTURER OR INSTALLER
SERIAL NO.STATE OR
PROVINCE NO.NATIONAL BOARD NO.
GF14401
GF14400
290696
290697
X10199A2
X10199A3
854030:854030
Page 7 of 9
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS, P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT OR APPURTENANCE
Safety Injection Pump Heat Exchangers (2) AHSC-1B
Residual Heat Removal Pump AHRLRP-1A Shaft Seal Heat Exchanger
Residual Heat Removal Pump AHRHRP-1B Shaft Seal Heat Exchanger
Accumulator Tank ACC-1A
Accumulator Tank ACC-1B
Containment Spray Pump APCS-1A
Containment Spray Pump APCS-1B
Containment Spray Pump AIPCS-1A Gland Seal Cooler
MANUFACTURER OR INSTALLER
Borg Warner
Borg Warner
Borg Warner
Wyatt
Wyatt
Ingersoll Rand
Ingersoll Rand
Helliflow
MANUFACTURER OR INSTALLER
SERIAL NO.
854030:854030
681N0276
681N0276
H-5645-69
H-5644-69
0670-74
0670-75
49486938
STATE OR PROVINCE NO.
NATIONAL BOARD NO.
U11397
U11398
Page 8 of 9
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,
P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT OR APPURTENANCE
Containment Spray Pump APCS-1B Gland Seal Cooler
Component Cooling Pump APCC-1A
Component Cooling Pump APCC-1B
Service Water Pump APSW-1A1
Service Water Pump APSW-1A2
Service Water Pump APSW-1B1
Service Water Pump APSW-1B2
Spent Fuel Pool Heat Exchanger AHSF
Main Steam Moisture Separator
Spent Fuel Pool Pump APSF-1A
MANUFACTURER OR INSTALLER
Helliflow
Ingersoll Dresser Pump Flow Serv.
Ingersoll Dresser Pump Flow Serv.
Worthington Pump
Worthington Pump
Worthington Pump
Worthington Pump
Struther Wells
Wright Austin
Gould Pumps
MANUFACTURER OR INSTALLER
SERIAL NO.
6080694
0600009
0600010
VTP27737
75 TU-1719-1
VTP27736
VTP27739
1-68-06-1519
6230
STATE OR NATIONAL PROVINCE NO. BOARD NO.
U11445
X.R. 6008
786A519.1
Page 9 of 9
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,
P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT OR APPURTENANCE
Spent Fuel Pool Pump APSF-1B
Service Water Pump Strainer ASSW-1A1
Service Water Pump Strainer ASSW-1A2
Service Water Pump Strainer ASSW-1B1
Service Water Pump Strainer ASSW-1B2
Component Cooling Heat Exchanger AHCC1-IA
Component Cooling Heat Exchanger AHCC2-1B
MANUFACTURER OR INSTALLER
Gould Pumps
S.P. Kinney Engineers
S.P. Kinney Engineers
S.P. Kinney Engineers
S.P. Kinney Engineers
Engineers and Fabricators
Engineers and Fabricators
MANUFACTURER OR INSTALLER
SERIAL NO.
786A519.2
2278
2279
2280
2281
S-15748-A
S-15748-B
STATE OR PROVINCE NO.
U11426
U11427
NATIONAL BOARD NO.
1139
1140
FORM NIS-1 (Back)
8. Examination Dates March 27,2001 to December 6, 2001
9. Inspection Period Identification 3rd
10. Inspection Interval Identification 3rd
1989 None 11. Applicable Edition of Section XI 1989 Addenda
12. Date/Revision of Inspection Plan November 27,2000/Revision 2
13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. Reference Tab C
14. Abstract of Results of Examinations and Tests. Reference Tab B and Tab F
15. Abstract of Corrective Measures. Reference Tab B and Tab F
Utilization of ASME Boiler and Pressure Vessel Code Section XI: Code Cases N-416-1, N-416-2, N-460, N-491, N-498 and N-498-1.
We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan
as required by the ASME Code, Section XI, and c) corrective measures taken conform to the rules of the ASMIE Code, Section X.
Certificate of Authorization No. (if applicable) '",/-' Expiration Date
Date .- K o Signed W Z -4A1e.. , cua-'u J 20 Owner
By~- A
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and
the State or Province of W1 I.OwNSiA and employed by NAxt-r-Fato SrmA, Lci', -r" of 4AA'rgoi•o C.-. have inspected the components described in this Owner's Report during the period
AfAR•,.4 ,'-7, ,avo/ to -e, , , and state that to the best of my knowledge and belief, the
Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance
with the Inspection Plan and as required by the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or
connected with this inspection.
4 ,-__ Commissions A"'72 / eo190s/ 11( -4 -•'T / s
6Signature National Board, State. Province, and Endorsements
Date A3 A
ATTACHMENT 4
Letter from T. Coutu (NMC)
To
Document Control Desk (NRC)
Dated
February 22, 2002
FORM NIS- 1 Owner's Report for Inservice Inspections for Class MC Compenents
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,
P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT OR APPURTENANCE
Reactor Building Containment Vessel
Personnel Airlock
MANUFACTURER OR INSTALLER
Chicago Bridge and Iron Company
Chicago Bridge and Iron Company
MANUFACTURER OR INSTALLER
SERIAL NO.
C4454
C4454
STATE OR NATIONAL PROVINCE NO. BOARD NO.
U11423
U11423
FORM NIS-1 (Back)
8, Examination Dates September 18, 2001 to December 4, 2001
9. Inspection Period Identification
10. Inspection Interval Identification
2nd
1st
1992 1992 11. Applicable Edition of Section XI ______________Addenda _____________
12. Date/Revision of Inspection Plan September 26, 2000/Revision 1
13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required
for the Inspection Plan. Reference Tab C
14. Abstract of Results of Examinations and Tests. Reference Tab B and Tab F
15. Abstract of Corrective Measures. Reference Tab B and Tab F
We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan
as required by the ASME Code, Section XI, and c) corrective measures taken conform to the rules of the ASME Code, Section
)a.
Certificate of Authorization No. (if applicable)
Date A a Q3 Signed J 2,1,WI
Expiration Date
p 5 6-j~c_ e-cOwner
By
National Board. State, Province. and Endorsements
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and
the State or Province of __ _ ___ ___ ___and employed by //A r10F*e ) ,7-6AbM13 It- r f
/4CAR7"FI C r have inspected the components described in this Owner's Report during the period Rdi001 t /e IOV, 200 ' , and state that to the best of my knowledge and belief, the
Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance
with the Inspection Plan and as required by the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or
con:a with t inspecion.
Commissions ,,.'4 " '/A./S / 2" , 'V, '4
ATTACHMENT 5
Letter from T. Coutu (NMC)
To
Document Control Desk (NRC)
Dated
February 22, 2002
FORM NIS-1 Owner's Report for Inservice Inspections of Replacement Steam Generators
Page 1 of 2
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,
P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT OR APPURTENANCE
Steam Generator SG1A
Steam Generator SG1B
Steam Generator SG1A
Steam Generator SGlB
Steam Generator IA Safe End Welds
Steam Generator 1B Safe End Welds
Class 1 Reactor Coolant Piping Installation Welds
Class 2 Main Steam Piping Installation Welds
MANUFACTURER OR INSTALLER
Ansaldo Energia Milano
Ansaldo Energia Milano
Westinghouse
Westinghouse
Ansaldo Energia Milano
Ansaldo Energia Milano
Bechtel Corporation
Bechtel Corporation
MANUFACTURER OR INSTALLER
SERIAL NO.
0202
0201
1141
1142
NA
NA
NA
NA
STATE OR PROVINCE NO.
U11400
U11401
U11400
U11401
NA
NA
NA
NA
NATIONAL BOARD NO.
151
150
68-28
68-29
NA
NA
NA
NA
Page 2 of 2
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,
P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT OR APPURTENANCE
Class 2 Feedwater Piping Installation Welds
Class 2 Feedwater Nozzle Adapter and Nozzle to Pipe Installation Welds
MANUFACTURER OR INSTALLER
Bechtel Corporation
Bechtel Corporation
MANUFACTURER OR INSTALLER
SERIAL NO.
NA
NA
STATE OR PROVINCE NO.
NA
NA
NATIONAL BOARD NO.
NA
NA
FORM NIS-1 (Back)
8. Examination Dates June 4, 2001 December 4, 2001
9. Inspection Period Identification 3rd
10. Inspection Interval Identification 3rd
1989 None
11. Applicable Edition of Section XI 1989 Addenda
12. Date/Revision of Inspection Plan November 27, 2000/Revision 2
13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required
for the Inspection Plan. Reference Tab C
14. Abstract of Results of Examinations and Tests. Reference Tab B and Tab F
15. Abstract of Corrective Measures. Reference Tab B and Tab F
Utilization of ASME Boiler and Pressure Vessel Code Section XI: Code Cases
N-416-2 and N-460.
We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan
as required by the ASME Code, Section XI, and c) corrective measures taken conform to the rules of the ASME Code, Section
XI.
Certificate of Authorization No. (if applicable) Expiration Date /
Date a\.JA4 CC, A.VQ3~ *QO Signed C-)J I I'~ L~. By J Owner
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and
the State or Province of 0A:i.o C-0 "T I,.- and employed by HA./,-rgao ST4Mi Boller CTr. of
4-e1-/o,'e-) r r" have inspected the components described in this Owner's Report during the period
,&,Tte, ,, ,0 O/ to A '9 "/, and state that to the best of my knowledge and belief, the
Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance
with the Inspection Plan and as required by the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations, tests, and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or
cone wit this inspection.
Commissions / 7 9" V/ Al/.S /OO"at XZ !ý 4., A J
c, .Actor's Signature National Board. State. Province. and Endorsements
V
ATTACHMENT 6
Letter from T. Coutu (NMC)
To
Document Control Desk (NRC)
Dated
February 22, 2002
FORM NIS-2 Owner's Report for Repair or Replacement (74 Total)
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson. Wisconsin 54016
4. Identification of System 33 Class 2 SAFETY INJECTION
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section X1 Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Manufacturer
ITT GRINNELL VALVE COMPANY
Manufacturer Serial No.
NA
National Board No.
NA
Other ID
NA
Date 11/1/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-016956
Type Code Sym. Stamp N..A
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1967
Repaired, ASMERepaired,
Replaced, or Replacement
REPAIRED
7. Description of Work REPAIR CLASS 2 SAFETY INJECTION SYSTEM 2" HANGER RSI-H70 DUE TO MISSING JAM NUT.
8. Tests conducted Hydrostatic
Other DJD Pneumatic
Pressure
F Nominal Operating Pressure
psi Test Temp.
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
RSI-H70
ASME Code
Stamped
N
D: deg. F
Exempt 17
N
NIS-2 (Back)
Sheet 2 of 2
Date: 11/1/2001
Name of Component: RSI-H70
Work Order Number: 01-016956
.20 _____
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XL. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed & Date 20 0A
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 7-;5'i0" to /-3/1 , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
• • • Commissions NB7741, I, N, IS, A WIS 100024
National Board, State, Province, and Endorsementspectors nature
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT
As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 33 Class 2 SAFETY INJECTION
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
RSI-H73
Name of Manufacturer
ITT GRINNELL VALVE COMPANY
Manufacturer Serial No.
NA
National Board No.
NA NA 1967 XtzHAIh(tU '4
Other ID
Date 11/1/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-016956
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date N.A
Code Case NAA
Year Built
Repaired, A�M �Repairedl, Replaced, or
Replacement
7. Description of Work REPAIR CLASS 2 SAFETY INJECTION SYSTEM 2" HANGER RSI-H73 DUE TO UNSPREAD COTTER PIN.
8. Tests conducted Hydrostatic
Other n
El Pneumatic
Pressure
Elpsi
Nominal Operating Pressure
Test Temp.
--] Exempt
deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code Stamped
REPAIREDNA 1967NA
NIS-2 (Back)
Sheet 2 of 2
Date: . 11/1/2001
Name of Component: RSI-H73
Work Order Number: 01-016956
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed ZSA4•V . •Jg? A o it. J OL, M Date ,20 L
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 7- ,T-" to /- -3/-02., and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XL.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
s uCommissions NB7741, I, N, IS, A WIS 100024
pectors Signature National Board, State, Province, and Endorsements
Date .-• 20 o'-
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT
As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation Date 11/1
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001 Sheet 1
2. Plant Kewaunee Nuclear Power Plant Unit No.
N490 HWY 42 Kewaunee. WI 54216-9511 Work Order
3. Work Performed By Nuclear Management Company, LLC Type Code
700 First Street, Hudson, Wisconsin 54016 Authorizatio
4. Identification of System 33 Class 2_ SAFETY INJECTION Expiration D
5. (a) Applicable Construction Code B31.1-1967 Code Case
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
RSI-H74
Name of
Manufacturer
ITT GRINNELL VALVE COMPANY
Manufacturer Serial No.
NA
National Board No.
NA
Other ID
NA 1967 REPAII�U
Year Built
/2001 of 2
1
01-016956
Sym. Stamp NA
nNo. NA
late NA
NA
Repa•ired, Replaced, or Replacement
7. Description of Work REPAIR CLASS 2 SAFETY INJECTION 2" HANGER RSI-H74 DUE TO LOOSE NUT.
8. Tests conducted Hydrostatic
Other D
Pneumatic F
Pressure
Nominal Operating Pressure
psi Test Temp.
El Exempt [-7 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
M�IYI�
Code Stamped
REPAIRED1967NA
NIS-2 (Back)
Sheet 2 of 2
Date: 11/1/2001
Name of Component: RSI-H74
Work Order Number: 01-016956
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed 44& L-"O Date 4Ak M ,20 0
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 7--V-1V to /-•i"-2,, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
4 12 .,0 Commissions NB7741, I, N, IS, A WIS 100024
Dae-20 ___
National Board, State, Province, and Endorsementst nspector's ,2nature
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT
As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson. Wisconsin 54016
4. Identification of System 05A Class 2 FEEDWATER
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section X1 Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
FDW-H170
Name of Manufacturer
ITT GRINNEL COMPANY
Manufacturer Serial No.
NF
National Board No.
NA
Other ID
NA 1967 REPAI RED N
Date 11/16/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-018043
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NNA
Code Case NA
Year Built
Nep�I[�u, MOIViE
Repaired, Replaced, or Replacement
7. Description of Work REPAIR CLASS 2 FEEDWATER SYSTEM 16" SUPPORT FDW-H170 DUE TO LOOSE NUTS.
8. Tests conducted Hydrostatic F
Other DPneumatic D-]Pressure
Nominal Operating Pressure
psi Test Temp.
1:1 Exempt E'
deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Code Stamped
REPAI RED IN1967NA
NIS-2 (Back)
Sheet 2 of 2
Date: 11/16/2001
Name of Component: FDW-H170
Work Order Number: 01-018043
Date / 20 -__ _
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed PC/W.t"J .VJ.,l.W.dI0, V2l"J Date • ,20 a
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 7-.2)VP to /-/-#1, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
""-" Commissions NB7741, I, N, IS, A WIS 100024
ýnspectors ý4nature National Board, State, Province, and Endorsements
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
FDW-H39
Name of Manufacturer
ITT GRINNEL COMPANY
Manufacturer Serial No.
NA
National Board No.
NA
Other ID
NA 1967 REPAIRED N
Date 11/16/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-018044
Type Code Sym. Stamp N.A
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
Repaired, ASMERepaired,
Replaced, or Replacement
7. Description of Work REPAIR CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" HANGER FDW-H39 DUE TO LOOSE NUT ON PIPE CLAMP.
8. Tests conducted Hydrostatic
Other F
El Pneumatic
Pressure
Nominal Operating Pressure
psi Test Temp.
D: deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code Stamped
Exempt []
REPAIRED N1967NA
NIS-2 (Back)
Sheet 2 of 2
Date: 11/16/2001
Name of Component: FDW-H39
Work Order Number: 01-018044
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed Y g%/e, /1kA/1A41WJ5KZ1 MAMA owrj Looj&ýDate _ 20 OX I Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 7- 2y-i" to /- 31-OZ , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspector's S;(nature National Board, State, Province, and Endorsements
Date-e / ,20 D
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT
As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of Component
FDW-H43
Name of Manufacturer
ITT GRINNEL COMPANY
Manufacturer Serial No.
NA
National Board No.
NA NA 1967 K�HAl�U I"
Other ID
Date 11/15/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-018044
Type Code Sym. Stamp NA.
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
Repaired, ASM ERepaired, Replaced, or
Replacement
7. Description of Work REPAIR CLASS 2 AUXILAIRY FEEDWATER SYSTEM 3" HANGER FDW-H43 DUE TO LOOSE NUT ON THE PIPE
CLAMP.
8. Tests conducted Hydrostatic ]
Other [Pneumatic Li Pressure
Nominal Operating Pressure
psi Test Temp.
n Exempt r•
deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code Stamped
REPAIRED INNA 1967NA
NIS-2 (Back)
Sheet 2 of 2
Date: 11/15/2001
Name of Component: FDW-H43
Work Order Number: 01-018044
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed Date__ ___ __ _2Dat 2 tQ
Owner or Owner's Designee, Title U
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period '7-o.rOe to 1-3t-OZ , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspector Signature National Board, State, Province, and Endorsements
Date / 20 0 L"
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section X1
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
FDW-H44
Name of
Manufacturer
ITT GRINNEL COMPANY
Manufacturer Serial No.
NA
National Board No.
NA
Other ID
NA
Date 11/16/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-018044
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1967
Repaired, ASMERepaired,
Replaced, or Replacement
REPAIRED
7. Description of Work REPAIR CLASS 2 AUXILAIRY FEEDWATER SYSTEM 3" HANGER FDW-H44 DUE TO LOOSE NUT ON THE PIPE
CLAMP.
8. Tests conducted Hydrostatic
Other D
Pneumatic
Pressure
Nominal Operating Pressure
psi Test Temp.
0l deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
N
Exempt El
N
NIS-2 (Back)
Sheet 2 of 2
Date: 11/16/2001
Name of Component: FDW-H44
Work Order Number: 01-018044
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed Iý ?,- Date••".i~at•-/--'4•P • (0.l~'l4/ Dh6t4 ,20 OcL
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period '7--F-7 to / -• ,and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
•4, Commissions NB7741, I, N, IS, A WIS 100024
nspector's Signa ure National Board, State, Province, and Endorsements
Date / 20 ___'-
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corooration
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 89A Class MC BUILDINGS - STRUCTURES
5. (a) Applicable Construction Code SEC. Il-CL.B-1965W
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1992 ADDENDA
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
RBCV
Name of
Manufacturer
CHICAGO BRIDGE AND IRON
Manufacturer Serial No.
C4454
National Board No.
NA
Other ID
1S-0002
Date 11/24/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-018045
Type Code Sym. Stamp N.•A
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1969
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work REPAIR CLASS MC (METAL CONTAINMENT) REACTOR BUILDING CONTAINMENT VESSEL MOISTURE BARRIER
BONDING BETWEEN ELEVATION 606' AND METAL CONTAINMENT.
8. Tests conducted Hydrostatic
Other 1
Dl Pneumatic
Pressure
D- Nominal Operating Pressure
psi Test Temp.
Exempt Li
deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
Y
NIS-2 (Back)
Sheet 2 of 2
Date: 11/24/2001
Name of Component: RBCV
Work Order Number: 01-018045
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed.20
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period T'7-Ar'- to /-31-03-, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
nspector's nature National Board, State, Province, and Endorsements
Date / ,20 D,..
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT
As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 33 Class 1 SAFETY INJECTION
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
S1-13B
Name of Manufacturer
VELAN VALVE CORPORATION
Manufacturer Serial No.
NF
National Board No.
NA
Other ID
S1116-002 1967 R�PLAC�M�N I N
Date 12/1/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-018277
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
I�p�ir�u, P.�IVIE
Repaired, Replaced, or Replacement
7. Description of Work REPAIR CLASS 1 6" SAFETY INJECTION SYSTEM VALVE SI-13B DUE TO 4 PIN HOLE LEAKS IN THE SEAL WELD
INCLUDING REPLACING 4 STUDS.
8. Tests conducted Hydrostatic El
Other D]Pneumatic "
Pressure 2240 psi
Nominal Operating Pressure
Test Temp. f55 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Code Stamped
Exempt F
REPLACEMENT N1967S1 116-002
NIS-2 (Back)
Sheet 2 of 2
Date: 12/1/2001
Name of Component: S1-13B
Work Order Number: 01-018277
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed &UN44 . •d w Date L 20 Q
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 7-15r-,90' to /- 3 /-, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I1 N, IS, A WIS 100024
Inspector's ignature National Board, State, Province, and Endorsements
Date / ,20 0,__
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 89A Class MC BUILDINGS - STRUCTURES
5. (a) Applicable Construction Code SEC. III-CL.B-1965W
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1992 ADDENDA
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
EMRG. AIRLOCK
Name of Manufacturer
CHICAGO BRIDGE AND IRON
Manufacturer Serial No.
C4454
National Board No.
NA 1S-0002 1969 t�.MAI �tU I
Other ID
Date 11/21/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-018283
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
Repaired, ASMERepaired, Replaced, or
Replacement
7. Description of Work REPAIR CLASS MC METAL CONATINMENT EMERGENCY AIRLOCK DUE TO BOLT NOT FLUSH WITH SURFACE.
8. Tests conducted Hydrostatic
Other F"
El Pneumatic
Pressure
R7psi
Nominal Operating Pressure
Test Temp.
Exempt Li
deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code Stamped
REPAIRED ,f1S-0002 1969NA
NIS-2 (Back)
Sheet 2 of 2
Date: 11/21/2001
Name of Component: EMRG. AIRLOCK
Work Order Number: 01-018283
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed • • ••1 Date - " ,20 Oý
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 7-23-'o to -3/-,2. , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
7ýý .-,Commissions NB7741, 1, N, IS, A WIS 100024
pector's Si" ature National Board, State, Province, and Endorsements
Date ; -.1"- .20 __ _._.
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 33 Class 1 SAFETY INJECTION
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
S1-13B
Name of
Manufacturer
VELAN VALVE CORPORATION
Manufacturer Serial No.
NF
National Board No.
NA
Other ID
S1116-002
Date 12/1/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-018402
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1967 REPAIRED N
Repaired, ASMERepaired,
Replaced, or Replacement
7. Description of Work REMOVE GOUGES AND PREPARE GASKET SURFACE OF CLASS 1 SAFETY INJECTION SYSTEM 6" VALVE SI
13B BONNET SURFACE.
8. Tests conducted Hydrostatic
Other j
Pneumatic El Pressure 2240 psi
Nominal Operating Pressure
Test Temp. 551 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
Exempt
REPAIRED N1967
NIS-2 (Back)
Sheet 2 of 2
Date: 12/1/2001
Name of Component: SI-13B
Work Order Number: 01-018402
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed Owwvf Date .20 "
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period "7-21o-ap to __3_-9__ , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, 1, N, IS, A WIS 100024
Inspectors ignature National Board, State, Province, and Endorsements
Da tee 20 99,A
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT
As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Manufacturer
ITT GRINNELL VALVE COMPANY
Manufacturer Serial No.
NA
National Board No.
NA
Other ID
NA
Date 11/26/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-018522
Type Code Sym. Stamp NA.
Authorization No. NA
Expiration Date NA
Code Case NNA
Year Built
1967 REPAIRED N
Hepaired, A�MLRepaired, Replaced, or
Replacement
7. Description of Work REPAIR CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8" HANGER RHR-H18 DUE TO LOAD SETTING OF SCALE.
8. Tests conducted Hydrostatic "
Other n
Pneumatic -
Pressure
Nominal Operating Pressure
psi Test Temp.
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
RHR-H18
ASME Code Stamped
D: deg. F
Exempt El
REPAIRED IN1967
NIS-2 (Back)
Sheet 2 of 2
Date: 11/26/2001
Name of Component: RHR-H18
Work Order Number: 01-018522
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed P - -- eOU Date 20 0
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 7-0.S'- C.V to ________ , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
,1 -ý7ý Commissions NB7741, I, N, IS, A WIS 100024
National Board, State, Province, and Endorsements-- lnspector's S(nature
Date- ,'/ ,20 9 5La7
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT
As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
RHR-H24
Name of
Manufacturer
ITT GRINNELL VALVE COMPANY
Manufacturer Serial No.
NA
National Board No.
NA
Other ID
NA 1967 REPAIRED N
Date 11/26/2001
Sheet I of 2
Unit No. 1
Work Order 01-018522
Type Code Sym. Stamp N__A
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
Kepalreo, A�M �Repaired, Replaced, or
Replacement
7. Description of Work REPAIR CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8" HANGER RHR-H24 DUE TO MISALIGNMENT OF
SUPPORT.
8. Tests conducted Hydrostatic
Other F]
Pneumatic F1 Pressure
Nominal Operating Pressure
psi Test Temp.
D: deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Code Stamped
Exempt E
REPAIRED NNA 1967
NIS-2 (Back)
Sheet 2 of 2
Date: 11/26/2001
Name of Component: RHR-H24
Work Order Number: 01-018522
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed Date 20 0.1
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 7-,Sr-6' to /- .3/'-OZ , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
nsp C .Commissions NB7741, I, N, IS, A WIS 100024
nspector's Sig re National Board, State, Province, and Endorsements
Da ate7• •4 20 0
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 33 Class 1 SAFETY INJECTION
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
RSI-H7
Name of Manufacturer
ITT GRINNELL VALVE CO.
Manufacturer Serial No.
NA
National Board No.
NA
Other ID
NA 1967 REPAIRED N
Date 11/26/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-018525
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
Repaired, ASMERepaired,
Replaced, or Replacement
7. Description of Work REPAIR CLASS 1 SAFETY INJECTION SYSTEM 2" SUPPORT RSI-H7 DUE TO DAMAGED SPRING CAN.
8. Tests conducted Hydrostatic []
Other F
Pneumatic R
Pressure
Nominal Operating Pressure
psi Test Temp.
D3 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code Stamped
Exempt 17
REPAIRED N1967NA
NIS-2 (Back)
Sheet 2 of 2
Date: 11/26/2001
Name of Component: RSI-H7
Work Order Number: 01-018525
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed /4.,6 t I.TIVA•OffN ,O"m,. Date JA,20 _.L_
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period I.- 29.'-P to /- 3/-0 ZI., and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
9 sp tCommissions NB7741, I, N, IS, A WIS 100024
ospector's SiLgature National Board, State, Province, and Endorsements
Date 20 01:4-
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
RHR-3B
Name of
Manufacturer
CRANE COMPANY
Manufacturer Serial No.
NF
National Board No.
NA
Date 12/19/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-018670
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Other Year ID Built
AC034-002 1972 REPAIRED N
ICepaireu, M�IVI�
R~epaired, Replaced, or Replacement
7. Description of Work REPAIR BONNET TO BODY LEAK BY TORQUING BOLTING ON CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8"
VALVE RHR-3B.
8. Tests conducted Hydrostatic
Other D
R Pneumatic
Pressure
D Nominal Operating Pressure
psi Test Temp.
E] deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturers Data Reports to be Attached
Code Stamped
Exempt F•
REPAIRED NAC034-002 1972
NIS-2 (Back)
Sheet 2 of 2
Date: 12/19/2001
Name of Component: RHR-3B
Work Order Number: 01-018670
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed (O Date 20 Q2 Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 7-;r-00 to I/-3zNC , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspecors naNational Board, State, Province, and Endorsements
Date d, ,/ ,20 O,-P
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 33 Class 2 SAFETY INJECTION
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
SI-9B
Name of Manufacturer
VELAN VALVE CORPORATION
Manufacturer Serial No.
NA
National Board No.
NA
Other ID
S1012-002
Date 12/1/2001
Sheet 1 of 2
Unit No. 1
Work Order 97-212982
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1967
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work OPEN FOR REPACKING CLASS 2 SAFETY INJECTION SYSTEM 3" VALVE SI-9B.
8. Tests conducted Hydrostatic F] Other n
Pneumatic F Nominal Operating Pressure r
Pressure 2190 psi Test Temp. 551 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturers Data Reports to be Attached
ASME Code
Stamped
N
Exempt 1
N
NIS-2 (Back)
Sheet 2 of 2
Date:. 12/1/2001
Name of Component: SI-9B
Work Order Number: 97-212982
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed 7&ifL 4c A C L ft•• L4A, v, Date te kLM4AMJ 20 0_.
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period -I- 2r-,O9 to b }-.,,, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
X • .Commissions NB7741, I, N, IS, A WIS 100024
(--ýpectors Sign ure National Board, State, Province, and Endorsements
Date / ,20 0 "-
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 36 Class 1 REACTOR COOLANT
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
LD-3
Name of
Manufacturer
MASONEILAN INTERNATIONAL
Manufacturer Serial No.
H46695-1-2
National Board No.
NA
Date 12/3/2001
Sheet 1 of 2
Unit No. 1
Work Order 00-003219
Type Code Sym. Stamp NA
Authorization No. INA
Expiration Date NA
Code Case NA
Other Year ID Built
RC011-002 1970
Repaired, ASMERepaired,
Replaced, or Replacement
REPLACED N
7. Description of Work DISASSEMBLE AND INSPECT CLASS 1 REACTOR COOLANT SYSTEM 2" VALVE LD-3 AND REPLACE 8 STUDS
AND 8 NUTS.
8. Tests conducted Hydrostatic F]
Other F]Pneumatic n Nominal Operating Pressure E'
Pressure 2240 psi Test Temp. 551 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
Exempt El
REPLACED N
NIS-2 (Back)
Sheet 2 of 2
Date: 12/3/2001
Name of Component: LD-3
Work Order Number: 00-003219
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACED conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Date 20 0=1
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period ,1-5-O 0 to /-3-bZ, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
4/setors Sign6(ure National Board, State, Province, and Endorsements
Date 1' 20 T,
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corooration
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 05A Class 2 FEEDWATER
5. (a) Applicable Construction Code NA
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
SG-AH-1
Name of
Manufacturer
MCDOWELL WELLMAN
Manufacturer Serial No.
25.12620.004-1
National
Board No.
NA
Other
ID
1S-0066
Date 12/3/2001
Sheet 1 of 2
Unit No. 1
Work Order 00-004319
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1971
Repaired, Replaced, or Replacement
REPLACEMENT
7. Description of Work REBUILD 900 KIP HYDRAULIC SNUBBER ON CLASS 2 MAIN STEAM AND STEAM DUMP SYSTEM STEAM GENEARTOR IA.
8. Tests conducted Hydrostatic
Other L]-l Pneumatic
Pressure
-1DNominal Operating Pressure
psi Test Temp.
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
N
D: deg. F
Exempt FR
NIS-2 (Back)
Sheet 2 of 2
Date: 12/3/2001
Name of Component: SG-AH-1
Work Order Number: 00-004319
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed & "9LAdJ ZM5dAA, &ti-L" ' Owner or Owner's Designee, Title
Date 20 0,;0
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 745r-', to /--,/I-Z , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, 1, N, IS, A WIS 100024
Inspector's S~i ature National Board, State, Province, and Endorsements
Date 6A"• / 20 0,70
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 05A Class 2 FEEDWATER
5. (a) Applicable Construction Code NA
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
Name of Manufacturer
Manufacturer Serial No.
National Board No.
Other ID
Date 12/3/2001
Sheet 1 of 2
Unit No. 1
Work Order 00-004319
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
Repaired, ASMERepaired,
Replaced, or Replacement
25.12620.004-7 NA 1S-0066 1971 REPLACEMENT N
7. Description of Work REBUILD 900 KIP HYDRAULIC SNUBBER ON CLASS 2 MAIN STEAM AND STEAM DUMP SYSTEM STEAM
GENERATOR lB.
8. Tests conducted Hydrostatic El
Other r--
Pneumatic
Pressure
El Nominal Operating Pressure
psi Test Temp.
-- Exempt 17
deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
SG-AH-2 MCDOWELL WELLMAN
ASME Code
Stamped
REPLACEMENT N
NIS-2 (Back)
Sheet 2 of 2
Date: 12/3/2001
Name of Component: SG-AH-2
Work Order Number: 00-004319
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed , ewr-m- -, "* LO1 f, Date ,20 0
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 17-2- -0O to /- J/o-02, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, 1, N, IS, A WIS 100024
Unspector's Siglature National Board, State, Province, and Endorsements
Date .20 '
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL
5. (a) Applicable Construction Code NA
(b) Applicable Edition of Section X1 Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Manufacturer
AJAX IRON WORKS
Manufacturer Serial No.
6576
National
Board No.
NA
Other ID
00076
Date 2/26/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-001998
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1967
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work REPAIR CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM CHARGING PUMP 1B SUCTION VALVE.
8. Tests conducted Hydrostatic
Other DE- Pneumatic 1 Nominal Operating Pressure El
Pressure 26 psi Test Temp. 115 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
APCH-11B
ASME Code
Stamped
N
Exempt 1:]
NIS-2 (Back)
Sheet 2 of 2
Date: 2/26/2001
Name of Component: APCH-1 B
Work Order Number: 01-001998
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed k &*SaNdUft4U Date 200 ;6
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 1-7-r-00 to 1-3/1-2 , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspector's Si ature National Board, State, Province, and Endorsements
Date a20 0 ;t-
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 36 Class 1 REACTOR COOLANT
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Manufacturer
PCIENERGY SERVICES
Manufacturer Serial No.
110/1M
National
Board No.
NA
Other
ID
NA
Date 12/3/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-002115
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case N-416-2
Year Built
2001
Repaired, Replaced, or Replacement
REPLACED
7. Description of Work REPLACED WELD FOR CLASS 1 REACTOR COOLANT SYSTEM STEAM GENERATOR 1A NOZZLE TO SAFE END WELD
8. Tests conducted Hydrostatic
Other r-
Pneumatic r-
Pressure 2240 psi
Nominal Operating Pressure r7
Test Temp. 551 deg. F
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
RC-W76DM
ASME Code
Stamped
N
Exempt 11
9. Remarks UTILIZATION OF ASME BOILER AND PRESSURE VESSEL CODE SECTION XI: CODE CASE N-416-2 PER NRC APPROVAL OF RELIEF REQUEST RR-G-4.
NIS-2 (Back)
Sheet 2 of 2
Date: * 12/3/2001
Name of Component: RC-W76DM
Work Order Number: 01-002115
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed ; % &4,0~ 7eýP 04& -0M-
Owner or Owner's Designee, Title
Date 20 0
Certificate of INSERVICE INSPECTION
1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period *1,2f-l to /- 3/1#2.., and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
4 lns c7 &Commissions NB7741, I, N, IS, A WIS 100024
Inspector's Si National Board, State, Province, and Endorsements
Date f I ,20 0 Z
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 36 Class 1 REACTOR COOLANT
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Manufacturer
PCI ENERGY SERVICES
Manufacturer Serial No.
NA
National Board No.
NA
Other ID
NA
Date 12/3/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-002115
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case N-416-2
Year Built
2001
Repaired, Replaced, or Replacement
REPLACED
7. Description of Work REPLACED WELD FOR CLASS 1 REACTOR COOLANT SYSTEM STEAM GENERATOR 1A NOZZLE TO SAFE END.
8. Tests conductedHydrostatic El Other D
Pneumatic Nominal Operating Pressure
Pressure 2240 psi Test Temp. 551 deg. F
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
RC-W77DM
ASME Code
Stamped
N
Exempt 1
9. Remarks UTILIZATION OF ASME BOILER AND PRESSURE VESSEL CODE SECTION XI: CODE CASE N-416-2 PER NRC APPROVAL OF RELIEF REQUEST RR-G-2.
NIS-2 (Back)
Sheet 2 of 2
Date: 12/3/2001
Name of Component: RC-W77DM
Work Order Number: 01-002115
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed &14" Date 4 20 oA Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 7-4U'-00 to /°.3 I'V2, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
nspector's Sigrature National Board, State, Province, and Endorsements
Date .• • 20 "-0-
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson. Wisconsin 54016
4. Identification of System 36 Class 1 REACTOR COOLANT
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
RC-W78DM
Name of
Manufacturer
PCIENERGY SERVICES
Manufacturer Serial No.
110/2
National Board No.
NA
Other ID
NA
Date 12/3/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-002115
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case N-416-2
Year Built
2001
Repaired, ASM�Repaired,
Replaced, or Replacement
REPLACED N
7. Description of Work REPLACED WELD FOR CLASS 1 REACTOR COOLANT SYTEM STEAM GENERATOR 1B NOZZLE TO SAFE END
WELD.
8. Tests conducted Hydrostatic
Other D
Pneumatic F
Pressure 2240 psi
Nominal Operating Pressure L
Test Temp. 55_1 deg. F
9. Remarks UTILIZATION OF ASME BOILER AND PRESSURE VESSEL CODE SECTION XI: CODE CASE N-416-2 PER NRC APPROVAL
OF RELIEF REQUEST RR-G-4.
Applicable Manufacturer's Data Reports to be Attached
ASME Code Stamped
Exempt
REPLACED N
NIS-2 (Back)
Sheet 2 of 2
Date:. 12/3/2001
Name of Component: RC-W78DM
Work Order Number: 01-002115
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed , R lOr. Date ,n 4 20 0.
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period __-_______ to /- 31-07-, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, 1, N, IS, A WIS 100024
Inspectors ,nature National Board, State, Province, and Endorsements
Date . / ,20 •''-
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Manaqement Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 36 Class 1 REACTOR COOLANT
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
RC-W79DM
Name of Manufacturer
PCIENERGY SERVICES
Manufacturer Serial No.
110/1
National
Board No.
NA
Other ID
NA
Date 12/3/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-002115
Type Code Sym. Stamp N.AA
Authorization No. NA
Expiration Date NA
Code Case N-416-2
Year Built
2001
Repaired, Replaced, or Replacement
REPLACED
7. Description of Work REPLACED WELD FOR CLASS 1 REACTOR COOLANT SYSTEM STEAM GENERATOR 1B NOZZLE TO SAFE END.
8. Tests conducted Hydrostatic
Other D
rF Pneumatic F Nominal Operating Pressure E
Pressure 2240 psi Test Temp. 551 deg. F
Exempt 1
9. Remarks UTILIZATION OF ASME BOILER AND PRESSURE VESSEL CODE SECTION XI: CODE CASE N-416-2 PER NRC APPROVAL OF RELIEF REQUEST RR-G-4.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
N
NIS-2 (Back)
Sheet 2 of 2
Date:. 12/3/2001
Name of Component: RC-W79DM
Work Order Number: 01-002115
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed && I1IWA W &OnL~n dUM" Date 20 01
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 72 to ,/-3/-, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, 1, N, IS, A WIS 100024
rInspector's Si ature National Board, State, Province, and Endorsements
Date ." • 20 D ,
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL
5. (a) Applicable Construction Code SECTION III CLASS 2
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 12/11/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-003411
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Repaired, ASME
Name of Name of Manufacturer National Other Year Replaced, or Code
Component Manufacturer Serial No. Board No. ID Built Replacement Stamped
RHR-33-1 CROSBY VALVE AND GAGE N62651-00-0001 NA ACl 15-001 1978 REPAIRED N
COMPANY
7. Description of Work REMOVE FOR TESTING CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 4" VALVE RHR-33-1.
8. Tests conducted Hydrostatic
Other F
EI Pneumatic 1"1 Nominal Operating Pressure El
Pressure 150 psi Test Temp. 60 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Exempt 1
NIS-2 (Back)
Sheet 2 of 2
Date: 12/1/2001
Name of Component: RHR-33-1
Work Order Number: 01-003411
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed &V4ii CA194 Date 1-1 -20 Q Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 97I,.-v, to /-3/- 0 Z., and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
24 ,Commissions NB7741, 1, N, IS, A WIS 100024
lnspector'sSiaature National Board, State, Province, and Endorsements
Date ,C / 20 0
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section X1
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Manufacturer
CROSBY ASHTON GAGE COMPANY
Manufacturer Serial No.
NF
National
Board No.
NA
Date 12/1/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-003412
Type Code Sym. Stamp N..A
Authorization No. NA
Expiration Date NA
Code Case NA
Other Year
ID Built
AC107-001 1971
Repaired,
Replaced, or Replacement
REPAIRED
7. Description of Work REMOVE FOR TESTING CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 2" VALVE RHR-33.
8. Tests conducted Hydrostatic []
Other n
Pneumatic Nominal Operating Pressure
Pressure 150 psi Test Temp. 60 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
RHR-33
ASME Code
Stamped
N
Exempt 1
NIS-2 (Back)
Sheet 2 of 2
Date:. 12/1/2001
Name of Component: RHR-33
Work Order Number: 01-003412
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed . If-.A 4eI4A., L Date .q 1 ,20 O.1
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period ?7-2,r-a to/- 3/-# 2- , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
SCommissions NB7741, , N, IS, A WIS 100024
Inspector's Sigjture National Board, State, Province, and Endorsements
Date ,20 9'9;-
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 23 Class 2 CONTAINMENT SPRAY
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Manufacturer
WILLIAM POWELL CO.
Manufacturer Serial No.
NF
National Board No.
NA
Date 11/26/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-004985
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Other Year ID Built
ICS022-001 1968
Repaired, ASMERepaired,
Replaced, or Replacement
REPAIRED N
7. Description of Work OPEN FOR INSPECTION CLASS 2 CONTAINMENT SPRAY 2" VALVE Cl-1003.
8. Tests conducted Hydrostatic
Other F
Pneumatic F] Pressure 31 psi
Nominal Operating Pressure M
Test Temp. 69.6 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
Cl-1003
ASME Code
Stamped
Exempt 1
REPAIRED N
NIS-2 (Back)
Sheet 2 of 2
Date: .11/26/2001
Name of Component: C1-1003
Work Order Number: 01-004985
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed . a e &.a 4..'2%, AoLv ,.lý c 4 Date 6uomi 20
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period Y-Ar-a to -3d JJ-, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
&ýý "= -1,.,.•Commissions NB7741, I, N, IS, A WIS 100024
Inspector's jgnature National Board, State, Province, and Endorsements
Date / ,20
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 33 Class 1 SAFETY INJECTION
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Manufacturer
ANCHOR/DARLING ENTERPRISES
Manufacturer Serial No.
11542-13
National Board No.
NA
Other ID
SIl15-003
Date 12/3/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-005010
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1970
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work OPEN FOR INSPECTION CLASS 1 SAFETY INJECTION SYSTEM 12" VALVE SI-21A.
8. Tests conducted Hydrostatic
Other F
Pneumatic
Pressure 2240 psi
Nominal Operating Pressure
Test Temp. 551 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
SI-21A
ASME Code
Stamped
N
Exempt 1--
NIS-2 (Back)
Sheet 2 of 2
Date:. 12/3/2001
Name of Component: SI-21A
Work Order Number: 01-005010
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed ,, 'e• . -L'-•4 0 ,X A Date 20 Q, 1
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 1 ,-Knev to -,,31/'2, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
lnp ,Commissions NB7741, I, N, IS, A WIS 100024
Inspector'si ature National Board, State, Province, and Endorsements
Date -- :4 ,20 Z
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 33 Class 1 SAFETY INJECTION
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section X1 Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of Manufacturer
Manufacturer Serial No.
ANCHOR/DARLING VALVE NF COMPANY
National Board No.
NA
Other
ID
S1115-004
Date 12/3/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-005011
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1970
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work OPEN FOR INSPECTION CLASS 1 SAFETY INJECTION SYSTEM 12" VALVE SI-21B.
8. Tests conducted Hydrostatic
Other DlF Pneumatic r-1 Nominal Operating Pressure El
Pressure 2240 psi Test Temp. a55 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
SI-21 B
ASME Code
Stamped
N
Exempt 1]
NIS-2 (Back)
Sheet 2 of 2
Date: 12/3/2001
Name of Component: SI-21B
Work Order Number: 01-005011
Date / 20
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed I4.•, Date. ,4gADt 20 OZ Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period __-2___O' to 14/4O2-, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
ý_ -Commissions NB7741, 1, N, IS, A WIS 100024
National Board, State, Province, and Endorsements_.Inspector's Signature
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 33 Class 1 SAFETY INJECTION
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Manufacturer
ANCHOR/DARLING ENTERPRISES
Manufacturer Serial No.
NF
National Board No.
NA
Other ID
S1115-001
Date 11/26/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-005012
Type Code Sym. Stamp N._A
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1970
Repaired, Replaced, or
Replacement
REPAIRED
7. Description of Work OPEN FOR INSPECTION CLASS 1 SAFETY INJECTION SYSTEM 12" VALVE SI-22A.
8. Tests conducted Hydrostatic
Other F
Pneumatic F
Pressure 750 psi
Nominal Operating Pressure =.
Test Temp. 63 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
SI-22A
ASME Code
Stamped
N
Exempt 1"-
NIS-2 (Back)
Sheet 2 of 2
Date: .11/26/2001
Name of Component: SI-22A
Work Order Number: 01-005012
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed LJ6 •0 •..IW .A fPA"?1 l'1, Date 20 0-1
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the pedod _'__"__ to /-3/"6-a, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
SCommissions NB7741, I, N, IS, A WIS 100024
Inspector's nature National Board, State, Province, and Endorsements
Date 2 ,20 9
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI
1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001
2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee WI 54216-9511
Date: 12/12/01
Sheet: 1 of 3
Unit: No.1
Work Order#: SEE BELOW
WORK ORDER WP&IR DESCRIPTION 01-007152 M-FCU-385 REMOVE AND RECONNECT SW
PIPING TO CFCU'S
Work Performed by: Bechtel Construction
Identification of System: 02 Class: 3 Name: SERVICE WATER
(a) Applicable Construction Code: USAS B31.1, 1967 Ed. , No Add. C
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add. C
Identification of Components Repaired or Replaced and Replacement Components:
ode Case: N/A
ode Case: N/A
Name of Name of Manufacturer National Other Year Repaired, ASME Component Manufacturer Serial No. Board Identification Built Replaced, Code
No. or Stamped Replacement Yes/No
See continuation sheet, page 3
7. Description of Work: REMOVE AND REINSTALL SERVICE WATER SYSTEM CONTAINMENT COOLING
CONTAINMENT FAN COIL UNITS C AND D AND ASSOCIATED SERVICE WATER LINES
8. Tests Conducted: Hydrostatic E] Pneumatic [j Nominal Operating Pressure Z Exempt E]
Other: El Pressure: 92 psi Test Temp: 44.2 0 F
Page 1 of`3
3.
4.
5.
6.
Date: 12/12/01
Name of Component: SERVICE WATER
Work Order Number: 01-007152
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors
and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of
Hartford, CT have inspected the components described in this Owner's Report during the period 0 -Uf
to I , and state that to the best of my knowledge and belief, the Owner has performed
examinations and taken corrective measures described in this Owner's Report in accordance with the
requirements of the ASME Code, Section XI
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or
implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,
neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or
of loss of any kind arising from or connected with this inspection.
(Robert T. Ward)_ _ _ _ Commissions ' I(•A4 '
Inspector's Signature National Board, State, Province, and Endorsements
Date: /a-/•- 2001
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Page 2 of 3
CERTIFICATE OF COMPLIANCE
We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.
Type Code Symbol Stamp
Certificate of Authorization No. N/A Expiration Date N/A
Signed: Date/--Date Owner or Owner's Designee, Title
N/A
Continuation Sheet
Name of Component SERVICE WATER
Work Order Number: 01-007152
Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code
No. Or Stamped Replacement Yes/No
CFCU C INLET N/A N/A N/A N/A N/A REPAIRED NO PIPING CFCU C OUTLET N/A N/A N/A N/A N/A REPAIRED NO PIPING CFCU D INLET N/A N/A N/A N/A N/A REPAIRED NO PIPING CFCU D OUTLET N/A N/A N/A N/A N/A REPAIRED NO PIPING 5/8" BOLTS MACKSON N/A N/A HT USY87951 N/A REPLACEMENT NO
5/8" NUT MACKSON N/A N/A HT 7307732 N/A REPLACEMENT NO
5/8" STUD MACKSON N/A N/A HT M60635 N/A REPLACEMENT NO
t t -t 1 1
t �- I I t
I* ± I I
f + I 1
+ I I 1-
Page 3 of 3
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI
1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001
2. Plant: Kewaunee Nuclear Power PlantN490 HWY 42 Kt.w•Ni•e WI 54216-9511
Date: 12/12/01
Sheet: 1 of 5
Unit : No.1
Work Order#: SEE BELOW
WORK ORDER WP&IR DESCRIPTION 01-008137 M-ULR-311 Remove & Modify Upper
Lateral
Work Performed by: Bechtel Construction
Identification of System: 05A Class: 2 Name: "A" Upper Lateral inclu'
Snubber
(a) Applicable Construction Code: USAS B31.1, 1967 Ed. , No Add.
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements: 1989, No Add.
Identification of Components Repaired or Replaced and Replacement Components:
ding Spring Cans &
Code Case: N/A
Code Case: N/A
Name of Name of Manufacturer National Other Year Repaired, ASME
Component Manufacturer Serial No. Board Identification Built Replaced, Code
No. or Stamped Replacement Yes/No
See continuation sheet, page 3
8. Description of Work: Repaired Upper Lateral Restraint and replacement of bolting and shims for upper lateral
9. Tests Conducted: Hydrostatic [] Pneumatic [] Nominal Operating Pressure F1 Exempt 0
Other: r] Pressure: psi Test Temp -F
Page 1 of 5
3.
4.
5.
6.
7.
Date: 12/12/01
Name of Component: UPPER LATERAL RESTRAINT SYSTEM.
Work Order Number: 01-008137
CERTIFICATE OF COMPLIANCE
We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.
Type Code Symbol Stamp N/A
Certificate of Authorization No. N/A Expiration Date N/A
Signed: Yi, c -,:4-.e ,Sv,- Date -! Owner or Owner's Designee, Title
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors
and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of
Hartford, CT have inspected the components described in this Owner's Report during the period n9-/1?2•!
to [t- ,oci , and state that to the best of my knowledge and belief, the Owner has performed
examinations and taken corrective measures described in this Owner's Report in accordance with the
requirements of the ASME Code, Section XI
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or
implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,
neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or
of loss of any kind arising from or connected with this inspection.
(Robert T. Ward) Commissions t,• a3 SS•"-i)A-; PYft •,'
lnspeot6Fýs Signature/ National Board, State, Province, and Endorsements
Date: r -/% 20 cý .
Page 2 of 5
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code
No. Or Stamped Replacement Yes/No
"A" Hydraulic McDowell 25.12620.004-1 N/A IS-0066 1971 Repaired No Snubber Wellman "A" Upper Lateral N/A N/A N/A N/A N/A Repaired No Ring Girder Splice Plate, Ring Colonial Ht. No. 412H07 N/A N/A 2001 Replacement No Girder, ASTM A588, Gr. A Splice Plate Bolt, Colonial HT No. 10187- N/A N/A 2001 Replacement No ASTM A540, RYE Gr.B23, Cl. 2 Splice Plate Heavy Colonial Ht. No. 8994464 N/A N/A 2001 Replacement No Hex. Nuts, A194, Trace Code SBG Gr. 2H Splice Plate Colonial Ht. No. Y85307 N/A N/A 2001 Replacement No Washers, F436 Trace Code SBH Splice Plate Heavy Colonial Ht. No. S42483 N/A N/A 2001 Replacement No Hex Nuts, A 194, Trace Code I UV Gr. 2H Bumper Plate, A588 Colonial Ht. No. BI S6214 N/A N/A 2001 Replacement No GR A Side Bumper Colonial Ht. No. l B518 N/A N/A 2001 Replacement No Bearing Plate, A588 3" Threaded Rod, Colonial Ht. No. 8991820 N/A N/A 2001 Replacement No A540 Gr. B23, Cl. 2 V" Hex. Nut, A563 Colonial Ht. No. 34467PJ N/A N/A 2001 Replacement No Washer, F436 Colonial Ht. No. 107494 N/A N/A 2001 Replacement No Side Bumper Shim, Colonial Ht. No. EIF023- N/A N/A 2001 Replacement No A36 A12 Side Bumper Shim, Colonial Ht. No. E1GI 19- N/A N/A 2001 Replacement No A36 A16 Side Bumper Shim, Colonial Ht. No. EIG 119- N/A N/A 2001 Replacement No A36 A16 Side Bumper Shim, Colonial Ht. No. B1F669- N/A N/A 2001 Replacement No A36 C16 Side Bumper Shim, Colonial Ht. No. T2866 N/A N/A 2001 Replacement No A36 Side Bumper Shim, Colonial Ht. No. A1C202- N/A N/A 2001 Replacement No A36 B20 Side Bumper Shim, Colonial Ht. No. A1D370- N/A N/A 2001 Replacement No A36 B32 Side Bumper Shim, Colonial Ht. No. B1E825- N/A N/A 2001 Replacement No A36 B16
Side Bumper Shim, Colonial Ht. No. B11F555- N/A N/A 2001 Replacement No A36 C23 Side Bumper Shim, Colonial Ht. No. 64595 N/A N/A 2001 Replacement No A109 CI010 Side Bumper Shim, Colonial Ht. No. Y07405 N/A N/A 2001 Replacement No A109 CI010 Side Bumper Shim, Colonial Ht. No. 65747 N/A N/A 2001 Replacement No A109 CI010 Side Bumper Shim, Colonial Ht. No. M06708 N/A N/A 2001 Replacement No A109 CI010 Upper Lateral Ring Colonial Ht. No. N/A N/A 2001 Replacement No Plate, A36 A1T128'3 3/8" Threaded Rod, Colonial Ht. No. 813953 N/A N/A 2001 Replacement No A307, Gr. A
Page 3 of 5
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code
No. Or Stamped Replacement Yes/No
Heavy Hex Nuts, Colonial Ht. No. A61415 N/A N/A 2001 Replacement No A563, Gr. A Std. Washer, F436, Colonial Ht. No. B16294 N/A N/A 2001 Replacement No Type 1 Upper Lateral Ring Colonial Ht. No. A1U1599 N/A N/A 2001 Replacement No Plate Shim, A36 Upper Lateral Ring Colonial Ht. No. BIP5527 N/A N/A 2001 Replacement No Plate Shim, A36 Upper Lateral Ring Colonial Ht. No AOR0914 N/A N/A 2001 Replacement No Plate Shim, A36 Upper Lateral Ring Colonial Ht. No 7467439 N/A N/A 2001 Replacement No Plate Shim, A36 Upper Lateral Ring Colonial Ht. No 1A353 N/A N/A 2001 Replacement No Plate Shim, A36 3/8" Hex Hd. Bolt, Colonial Ht. No. 8878678 N/A N/A 2001 Replacement No A307-97 3/8" Std. Washer, Colonial Ht. No. B 16294 N/A N/A 2001 Replacement No F436 Type I Ring Girder Shim, Colonial Ht. No. 1E479 N/A N/A 2001 Replacement No A36 Ring Girder Shim, Colonial Ht. No. 1E744-A N/A N/A 2001 Replacement No A36 Ring Girder Shim, Colonial Ht. No. 2A6386- N/A N/A 2001 Replacement No A36 C Ring Girder Shim, Colonial Ht. No. 2A6593- N/A N/A 2001 Replacement No A36 C
Ring Girder Shim, Colonial Ht. No. 4151614 N/A N/A 2001 Replacement No A109-CR1010 Ring Girder Shim, Colonial Ht. No. A86743 N/A N/A 2001 Replacement No A109-CRIOIO Ring Girder Shim, Colonial Ht. No. 4151614 N/A N/A 2001 Replacement No A109-CRIOIO Ring Girder Shim, Colonial Ht. No. R4747 N/A N/A 2001 Replacement No A36 Flat Bar Backing KNPP JB8913 N/A QADC 0 1-349 2001 Replacement No Strip, A36 Ring Girder Shim, Colonial Ht. No. 4125164 N/A N/A 2001 Replacement No A109-CRIOO1 Back Bumper Colonial MRR-01030 N/A N/A 2001 Replacement No Bearing Plate and Pipes ¾" Threaded Rod, Colonial Ht. No. 8991820 N/A N/A 2001 Replacement No A540 Gr B23, C12 ¾/4" Nut, A563 Colonial 31167PJ N/A N/A 2001 Replacement No
3/4" Washer, F436 Colonial 107494 N/A N/A 2001 Replacement No
Back Bumper Shim, Colonial E1F023-A12 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial EIGI 19-A16 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial B1F669-C16 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial T2866 N/A N/A 2001 Replacement No A36 I
Page 4 of 5
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code
No. Or Stamped Replacement Yes/No
Back Bumper Shim, Colonial A1C202-B20 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial A 1D370-B23 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial B1E825-B16 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial B1F555-C23 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial 64595 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial Y07405 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial 65747 N/A N/A 2001 Replacement No A36 Ring Girder Shim, Colonial Ht. No. 2A6386- N/A N/A 2001 Replacement No A36 E Ring Girder Shim, Colonial Ht. No. 2A6593- N/A N/A 2001 Replacement No A36 E Snubber Bracket Colonial Ht No C0453 N/A N/A 2001 Replacement No Shim
Page 5 of 5
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI
1. Owner: Wisconsin Public Service Corporation700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001
Date: 12/12/01
Sheet: 1 of 2
2. Plant: Kewaunee Nuclear Power PlantN490 HWY 42 K4.waiine. Wl 54216-9511I
Unit: No. 1
Work Order#: SEE BELOW
WORK ORDER WP&IR DESCRIPTION 01-013145 M-SGA-362 REMOVE SHIPPING COVER 01-013376 M-SDS-322 SEVER STEAM DOME 01-008136 M-SDA-370 REFURBISH STEAM DOME 01-013376 M-SDA-372 RE-INSTALL STEAM DOME
3.
4.
5.
6.
Work Performed by: Bechtel Construction
Identification of System: 05/06 Class: 2 Name: "A" Steam Generator Secondary Side
(a) Applicable Construction Code: USAS B31.1, 1967 Ed. , No Add. Code Case:
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add. Code Case:
Identification of Components Repaired or Replaced and Replacement Components:
N/A
N-416-2
Name of Name of Manufacturer National Other Year Repaired, ASME
Component Manufacturer Serial No. Board Identification Built Replaced, Code No. or Stamped
Replacement Yes/No
Steam Dome Westinghouse 1141 68-28 N/A 1970 Repaired Yes
Replacement SG Ansaldo 202 151 N/A 2000 Replacement Yes Lower assembly Feedwater Nozzle PCI FW # 1 N/A MRR-01019 2001 Replacement No
Adaptor Main Steam Flow Ansaldo N/A N/A QADC-01-041 2000 Replacement No
Limiter
_________________ I _______________ ______________ _________ '. ________________ ..- _____ -
7. Description of Work: Prep New lower assembly for Steam Dome installation, Remove Steam Dome from
the Old Lower Assembly, Refurbish the Feedwater Nozzle, Install the Main Steam Flow Limiter, Install the
Steam Dome on the New Lower Assembly
8. Tests Conducted: Hydrostatic El Pneumatic El Nominal Operating Pressure *
Other: E] Pressure: 1040 psi Test Temp: 549.35°F
* NOTE: The Secondary Side Hydrotest was conducted at NOP per Code Case N-416- 2
Exempt E]
Page 1 of2
Kewaunee WI 54216-9511
Date: 12/12/01
Name of Component: SG # A
Work Order Number: 01-013145, 01-008136, 01-013376.
CERTIFICATE OF COMPLIANCE
We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.
Type Code Symbol Stamp N/A
Certificate of Authorization No. N/A
Signed: -- ' 1(uf% /
Expiration Date N/A
Date (.
uwner or uwner s uesigjnee, I We
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors
and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of
Hartford, CT have inspected the components described in this Owner's Report during the periodn'-/7Z-
to I- t'p , and state that to the best of my knowledge and belief, the Owner has performed
examinations and taken corrective measures described in this Owner's Report in accordance with the
requirements of the ASME Code, Section XI
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or
implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,
neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or
of loss of any kind arising from or connected with this inspection.
(Robert T. Ward) Commissions f t n ý • </ 'I I/a.(
Inspector s Signature/ National Board, State, Province, and Endorsements
Date: 200\
Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI
1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001
2. Plant: Kewaunee Nuclear Power PlantN490 HWY 42 Kp~w•inp.• WI 54216-9511I
Date: 12/12/01
Sheet: 1 of 4
Unit: No.1
Work Order# : SEE BELOW
WORK ORDER WP&IR DESCRIPTION 01-013376 M-LLR-314 Replace Upper Col.
Adapters and Reshim Lower Lateral Restraint
3.
4.
5.
6.
Work Performed by: Bechtel Construction
Identification of System: 36 Class: 1 Name: "B" Col. Adapter Plates and Lower Lateral Shims
(a) Applicable Construction Code: USAS B31.1, 1967 Ed., No Add. Code Case: N/A
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add. Code Case: N/A
Identification of Components Repaired or Replaced and Replacement Components:
Name of Name of Manufacturer National Other Year Repaired, ASME Component Manufacturer Serial No. Board Identification Built Replaced, Code
No. or Stamped Replacement Yes/No
See continuation sheet, page 3
7. Description of Work: Replaced steam generator support upper column adapters and removed and restored
lower lateral support bumper guides to the steam generator and shimmed the adjacent support bumper steel.
Exempt 0
Page 1 of 4
8. Tests Conducted: Hydrostatic E] Pneumatic E Nominal Operating Pressure El
Other: [] Pressure: psi Test Temp
Kewaunee WI 54216-9511
Date: 12/12/01
Name of Component: "B" Upper Col. Adapter Plates and Reshim Lower Lateral Restraint.
Work Order Number: 01-013376
CERTIFICATE OF COMPLIANCE
We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.
Type Code Symbol Stamp N/A
Certificate of Authorization No. N/A
Signed: KA%• , . -5,,Owner or Owner's Desianec
Expiration Date N/A
Dateý.2.//,Mw
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors
and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of
Hartford, CT have inspected the components described in this Owner's Report during the period 05 -,/ti1
to . - , and state that to the best of my knowledge and belief, the Owner has performed
examinations and taken corrective measures described in this Owner's Report in accordance with the
requirements of the ASME Code, Section XI
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or
implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,
neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or
of loss of any kind arising from or connected with this inspection.
(Robert T. Ward)__ Commissions ^'-Z3 ii c c•V('i9V'
Inspector's Signature/ National Board, State, Province, and Endorsements
Date [1 1 2001
Page 2 of 4
•. I Itl•
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
Name of Name of Manufacturer National Other Year Repaired ASME
Component Manufacturer Serial No. Board Identification: Built Replaced Code No. Or Stamped
Replacement Yes/No
Shims Colonial Ht. No. 4125164 N/A N/A 2001 Replacement No
Shims Colonial Ht. No. A86743 N/A N/A 2001 Replacement No
Shims Colonial Ht. No. 4151614 N/A N/A 2001 Replacement No
Shims Colonial Ht. No. 2A6593- N/A N/A 2001 Replacement No
A
Shims Colonial Ht. No. T 1273-A N/A N/A 2001 Replacement No
Shims Colonial Ht. No. 1 E802 N/A N/A 2001 Replacement No
Shims Colonial Ht. No. R6759 N/A N/A 2001 Replacement No
Shims Colonial Ht. No. 2A6387- N/A N/A 2001 Replacement No A
Shims Colonial Ht. No. R6791 N/A N/A 2001 Replacement No
Shims Colonial Ht. No. 2A6593- N/A N/A 2001 Replacement No
E
Shims Colonial Ht. No. 2A6386- N/A N/A 2001 Replacement No D
Shims Colonial Ht. No. 2A6384- N/A N/A 2001 Replacement No A
Shims Colonial Ht. No. TI273-B N/A N/A 2001 Replacement No
Shims Colonial Ht. No. R4747 N/A N/A 2001 Replacement No
Shims Colonial Ht. No. 1E803 N/A N/A 2001 Replacement No
Shims Colonial Ht. No. R6791 N/A N/A 2001 Replacement No
Shims Colonial Ht. No. 1E542 N/A N/A 2001 Replacement No
1" Bolts A325 Colonial Ht. No. 706907 N/A N/A 2001 Replacement No
1" Bolts A325 Colonial Ht. No. 213265 N/A N/A 2001 Replacement No
1" Flat Washers Colonial Ht. No. B28393 N/A N/A 2001 Replacement No
F436-93
I" Hex. Hd. Nuts Colonial Ht. No. S41165 N/A N/A 2001 Replacement No
A194 Gr. 2H ¾" Bolt, A-490 Colonial Ht. No. 8996654 N/A N/A 2001 Replacement No
¾" Lockwashers Colonial Ht. No. 43739D N/A N/A 2001 Replacement No
B 18.21 S.G. Col. Adapter Colonial Fabricated N/A MRR 01042 2001 Replacement No
A588 Assembly
Page 3 of 4
Name of Name of Manufacturer National Other Year Repaired ASME
Component Manufacturer Serial No. Board Identification: Built Replaced Code
No. Or Stamped Replacement Yes/No
S.G. Col. Adapter Colonial Ht. No. N/A N/A 2001 Replacement No
Pin AISI 4340 8996496C0477 2 0 R p a e n N
S.G. Col. Adapter Colonial Ht. No. N/A N/A 2001 Replacement No
Pin Washer A-588, 803M62250 Gr. A S.G. Col. Adapter Colonial Ht. No. 255029 N/A N/A 2001 Replacement No
Pin Washer Bolts Trace Code I UX A-325 S.G. Adapter Col. Colonial Ht. No. 10618 N/A N/A 2001 Replacement No
Adapter Bolts A- Trace No. IUU 54 0, G r. B 23 , C l. 2 2001_R place entN
S.G. Adapter Col. Colonial Ht. No. S42483, N/A N/A 2001 Replacement No
Jam Nuts, SA307 Trace No. IUY Gr. B S.G. Adapter Col. Colonial Ht. No. 8994464 N/A N/A 2001 Replacement No
Heavy Hex. Nut, Ht Code SBG SA 194 Gr. 2H
S.G. Col. Adapter Colonial Ht. No. 8997945 N/A N/A 2001 Replacement No
Washers AISI 4150 Trace Code I UW I-- I
I. I* -I- I 1
_______ I + I I 1
_______ I F + I I 1
_________ F F I I I 1
_______ I F I I I t
_ _ _ _ _ I I
I I I -1I
Page 4 of 4
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI
1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001
2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee, WI 54216-9511
Date: 12/13/01
Sheet: 1 of 2
Unit: No. 1
Work Order#: SEE BELOW
WORK ORDER WP&IR DESCRIPTION 01-008135 M-BDA-382 S.G. "A" BLOWDOWN CUT / REWELD 01-008135 M-BDB-383 S.G. "B" BLOWDOWN CUT / REWELD 01-013145 M-SGA-364 S.G. "A" SMALL BORENOZZLE PREPS 01-013145 M-SGB-365 S.G. "B" SMALL BORE NOZZLE PREPS
3. Work Performed by: Bechtel Construction
4. Identification of System: 07 Class: 2 Name: BLOWDOWN
5. (a) Applicable Construction Code: USAS B31.1, 1967 Ed. , No Add.
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add.
Code Case: N/A
Code Case: N-416-2
6. Identification of Components Repaired or Replaced and Replacement Components:
Name of Name of Manufacturer National Other Year Repaired, ASME Component Manufacturer Serial No. Board Identification Built Replaced, Code
No. or Stamped Replacement Yes/No
SG LOOP-A N/A N/A N/A N/A N/A Repaired No BLOWDOWN PIPING SG LOOP-A ANSALDO 202 151 N/A 2000 Replacement Yes LOWER ASSY BLOWDOWN NOZZLE SG LOOP-B N/A N/A N/A N/A N/A Repaired No BLOWDOWN PIPING SG LOOP-B ANSALDO 201 150 N/A 2000 Replacement Yes LOWER ASSY BLOWDOWN NOZZLE
7. Description of Work: TEMPORARY REMOVAL OF EXISTING BLOWDOWN PIPING AT EACH STEAM
GENERATOR OUTLET NOZZLE AND PREPERATION OF BLOWDOWN NOZZLES ON NEW STEAM
GENERATOR LOWER ASSEMBLIES. ALL PIPING WAS PREPARED AND REINSTALLED BY WELDING.
8. Tests Conducted: Hydrostatic F] Pneumatic E] Nominal Operating Pressure [* Exempt rl
Other: [] Pressure: A-1040 psi / B-1030 psi Test Temp: A-549.35°F / B-548.17°F
* NOTE: The Secondary Side Hydrotest was conducted at NOP per Code Case N-416- 2
Page 1 of2
Date: 12/13/01
Name of Component: BLOWDOWN
Work Order Number: 01-008135
CERTIFICATE OF COMPLIANCE
We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.
N/AType Code Symbol Stamp
Certificate of Authorization No. N/A Expiration Date N/A
Signed: • 4• Ak•qJftR SA-,cz5'"-Owner or Owner's Designee, Title
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors
and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of
Hartford, CT have inspected the components described in this Owner's Report during the period 65 -I>"-•
to 1 tI ' \ , and state that to the best of my knowledge and belief, the Owner has performed
examinations and taken corrective measures described in this Owner's Report in accordance with the
requirements of the ASME Code, Section XI
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or
implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,
neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or
of loss of any kind arising from or connected with this inspection.
(Robert T. Ward) Commissions r,3 ii S-) A,.Qi L-'- /( Y 9
Inspect& 'SIgf' ture National Board, State, Province, and Endorsements
Date: ___ _ .2001
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
Page 2 of 2
Date I/j*a/K L
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI
1. Owner: Wisconsin Public Service Corporation700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001
Date: 12/13/01
Sheet: 1 of 5
2. Plant: Kewaunee Nuclear Power PlantN490 HWY 42 IKowai~n•. WI 54216-9511
Unit: No. 1
Work Order#: SEE BELOW
WORK ORDER WP&IR DESCRIPTION 01-008137 M-ULR-312 Remove & Modify Upper
Lateral
3. Work Performed by: Bechtel Construction
4. Identification of System: 5A Class: 2 Name: "B" Upper Lateral inclu
Snubber
5. (a) Applicable Construction Code: USAS B31.1, 1967 Ed., No Add.
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add.
6. Identification of Components Repaired or Replaced and Replacement Components:
ding Spring Cans &
Code Case: N/A
Code Case: N/A
Name of Name of Manufacturer National Other Year Repaired, ASM: Component Manufacturer Serial No. Board Identification Built Replaced, Code
No. or Stamped Replacement Yes/No
See continuation sheet, page 3 1
4- -k I F I
4- 4- 4 1 F I
4- I I F I
__________ .1. _________ L ________ A ______ i __________ L ___ J
7. Description of Work: Repaired Upper Lateral Restraint and replacement of bolting and shims for upper lateral
8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure n Exempt Z
Other: n Pressure: psi Test Temp oF.
Page 1 of 5
Kewaunee WI 54216-9511
Date: 12/13/01
Name of Component: UPPER LATERAL RESTRAINT SYSTEM.
Work Order Number: 01-008137
CERTIFICATE OF COMPLIANCE
We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.
Type Code Symbol Stamp N/A
Certificate of Authorization No. N/A
Signed: 2L4 ý KL-pPpmq;ýSý
Expiration Date N/A
Date / i/ol"Owner or Owner's Designee, Title
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors
and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of
Hartford, CT have inspected the components described in this Owner's Report during the period C9-/'f2"rl
to - K-'0"• , and state that to the best of my knowledge and belief, the Owner has performed
examinations and taken corrective measures described in this Owner's Report in accordance with the
requirements of the ASME Code, Section XI
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or
implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,
neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or
of loss of any kind arising from or connected wi this inspection.
(Robert T. Ward) Commissions p / i-•?ApJ/? L-j •"/i('$'
Inspec sSignature/ National Board, State, Province, and Endorsements
Date: 2001
Page 2 of 5
Name of Component
"B" Hydraulic Snubber "B" Upper Lateral Ring Girder Splice Plate, Ring Girder, ASTM A588, Gr. A Splice Plate Bolt, ASTM A540, Gr.B23, Cl. 2 Splice Plate Heavy Hex. Nuts, A194, Gr. 2H Splice Plate Washers, F436 Splice Plate Heavy Hex Nuts, A 194, Gr. 2H Bumper Plate, A588 Side Bumper Bearing Plate, A588 ¾" Threaded Rod, A540 Gr. B23, Cl. 2 ¾" Hex. Nut, A563 Washer, F436 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A36 Side Bumper Shim, A109 CIO10 Side Bumper Shim, A109 C1010 Side Bumper Shim, A109 CI010 Side Bumper Shim, A109 CI010 Washer Plate, A36
Upper Lateral Ring Plate, A36
Nai Ma
N/A
N/A
Col
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
me of Manufacturer National Other Year Re
nufacturer Serial No. Board Identification: Built Re No. Or
Re
N/A N/A N/A N/A Re
k N/A N/A N/A N/A Re
onial Ht. No. 412H07 N/A N/A 2001 Re
Colonial
Colonial
Colonial
Colonial
Colonial Colonial
Colonial
Colonial Colonial Colonial
Colonial
Colonial
Colonial
Colonial
Colonial
Colonial
Colonial
Colonial
Colonial
Colonial
Colonial
Colonial
Colonial
Colonial
HT No. 10187RYE
Ht. No. 8994464 Trace Code SBG
Ht. No. Y85307 Trace Code SBH Ht. No. S42483 Trace Code I UV
Ht. No. BIS6214 Ht. No. 1B518
Ht. No. 8991820
Ht. No. 34467PJ Ht. No. 107494 Ht. No. EIF023A12 Ht. No. E1GI19A16 Ht. No. EIG119A16 Ht. No. B1F669C16 Ht. No. T2866
Ht. No. Al C202B20 Ht. No. A1D370B32 Ht. No. BIE825B16 Ht. No. BIF555C23 Ht. No. 64595
Ht. No. Y07405
Ht. No. 65747
Ht. No. M06708
Ht. No. 404875
Ht. No. A1T1203
N/A N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A N/A N/A N/A
N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
Re
paired placed
placement
paired
paired
placement
placement F
ASME Code Stamped Yes/No No
No
No
No
No
No
No
No No
No
No No No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Page 3 of 5
Re2001
2001
2001
2001
2001 2001
2001
2001 2001 2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
Replacement
Replacement
Replacement
Replacement Replacement
Replacement
Replacement Replacement Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code
No. Or Stamped Replacement Yes/No
3/8" Threaded Rod, Colonial Ht. No. 813953 N/A N/A 2001 Replacement No A307, Gr. A
Heavy Hex Nuts, Colonial Ht. No. A61415 N/A N/A 2001 Replacement No A563, Gr. A
Std. Washer, F436, Colonial Ht. No. B 16294 N/A N/A 2001 Replacement No Type I Upper Lateral Ring Colonial Ht. No. AIU1599 N/A N/A 2001 Replacement No Plate Shim, A36
Upper Lateral Ring Colonial Ht. No. BIP5527 N/A N/A 2001 Replacement No Plate Shim, A36
3/8" Hex Hd. Bolt, Colonial Ht. No. 8878678 N/A N/A 2001 Replacement No A307-97 3/8" Std. Washer, Colonial Ht. No. B16294 N/A N/A 2001 Replacement No F436 Type I Ring Girder Shim, Colonial Ht. No. 1E479 N/A N/A 2001 Replacement No A36 Ring Girder Shim, Colonial Ht. No. 1 E744 N/A N/A 2001 Replacement No A36 Ring Girder Shim, Colonial Ht. No. 2A6386- N/A N/A 2001 Replacement No A36 C Ring Girder Shim, Colonial Ht. No. 2A6593- N/A N/A 2001 Replacement No A36 C Ring Girder Shim, Colonial Ht. No. 4151614 N/A N/A 2001 Replacement No A109-CRI010 Ring Girder Shim, Colonial Ht. No. A86743 N/A N/A 2001 Replacement No
A109-CRIOIO Ring Girder Shim, Colonial Ht. No. R4747 N/A N/A 2001 Replacement No A36 Flat Bar Backing KNPP JB8913 N/A QADC 01-349 2001 Replacement No Strip, A36 Ring Girder Shim, Colonial Ht. No. 4125164 N/A N/A 2001 Replacement No A109-CRIOIO Back Bumper Colonial MRR-01030 N/A N/A 2001 Replacement No Bearing Plate and Pipes ¾" Threaded Rod, Colonial Ht. No. 8991820 N/A N/A 2001 Replacement No A540 Gr B23, C12 ¾" Nut, A563 Colonial 31167PJ N/A N/A 2001 Replacement No
¾" Washer, F436 Colonial 107494 N/A N/A 2001 Replacement No
Back Bumper Shim, Colonial E1F023-A12 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial EIGI 19-A16 N/A N/A 2001 Replacement No
A36 Back Bumper Shim, Colonial BIF669-C16 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial T2866 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial A1C202-B20 N/A N/A 2001 Replacement No A36
Back Bumper Shim, Colonial A1D370-B23 N/A N/A 2001 Replacement No A36 Back Bumper Shim, Colonial B1E825-B16 N/A N/A 2001 Replacement No A36
Page 4 of 5
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
Name of Name of Manufacturer National Other Year Repaired ASME
Component Manufacturer Serial No. Board Identification: Built Replaced Code No. Or Stamped
Replacement Yes/No
Back Bumper Shim, Colonial BIF555-C23 N/A N/A 2001 Replacement No
A36 Back Bumper Shim, Colonial 64595 N/A N/A 2001 Replacement No
A36 Back Bumper Shim, Colonial Y07405 N/A N/A 2001 Replacement No
A36 Back Bumper Shim, Colonial 65747 N/A N/A 2001 Replacement No
A36 Ring Girder Shim, Colonial Ht. No. 2A6386- N/A N/A 2001 Replacement No
A36 E
Ring Girder Shim, Colonial Ht. No. 2A6593- N/A N/A 2001 Replacement No
A36 E
¾" Nut, A563-93 Colonial 107494 N/A N/A 2001 Replacement No
TYPE 1 1 1
Page 5 of 5
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
As Required by the Provisions for the ASME Code Section XI
1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001
2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee WI 54216-9511
Date: 12/12/01
Sheet: 1 of 2
Unit: No.1
Work Order#: SEE BELOW
WORK ORDER WP&IR DESCRIPTION 01-013145 M-SGB-363 REMOVE SHIPPING COVER 01-013376 M-SDS-323 SEVER STEAM DOME 01-008136 M-SDB-371 REFURBISH STEAM DOME
01-013376 M-SDB-373 RE-INSTALL STEAM DOME
3. Work Performed by: Bechtel Construction
4. Identification of System: 05/06 Class: 2 Name: "B" Steam Generator Secondary Side
5. (a) Applicable Construction Code: USAS B31.1, 1967 Ed. , No Add. Code Case: N/A
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add.
6. Identification of Components Repaired or Replaced and Replacement Components:
Name of Name of Manufacturer National Other Year
Component Manufacturer Serial No. Board Identification Built No.
Steam Dome Westinghouse 1142 68-29 N/A 1970
Code Case: N-416-2
Repaired, Replaced, or Replacement Repaired
Replacement SG Ansaldo 201 150 N/A 2000 Replacemen Lower assembly Feedwater Nozzle PCI FW# 2 N/A MRR-01019 2001 Replacemen
Adaptor I.. ,,,, l. .
Main Steam Flow Ansaldo N/A N/A Limiter
It
t
ASME Code Stamped Yes/No Yes
Yes
No
No
7. Description of Work: Prep New lower assembly for Steam Dome installation, Remove Steam Dome from the
Old Lower Assembly, Refurbish the Feedwater Nozzle, Install the Main Steam Flow Limiter, Install the Steam
Dome on the Niew Lower seby
8. Tests Conducted: Hydrostatic E] Pneumatic El Nominal Operating Pressure Z* Exempt [1
Pressure: 1030 psi Test Temp 548.17 OF
* NOTE: The Secondary Side Hydrotest was conducted at NOP per Code Case N-416- 2
Page 1 of 2
Other: M]
Rep ace,./ ,L!31 t nIQAUL;-U - -04-1 /-UUU
uome
on me New LOWS[ /•55•lllUly.
Date: 12/12/01
Name of Component: SG # B
Work Order Number: 01-013145, 01-013376, 01-008136.
CERTIFICATE OF COMPLIANCE
We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.
Type Code Symbol Stamp N/A
Certificate of Authorization No. N/A Expiration Date
Signed: 4--Jp- Q -. D Owner or Owner's Designee, Title
N/A
ate___________
Page 2 of 2
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors
and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of
Hartford, CT have inspected the components described in this Owner's Report during the period (tc-)L/"-0
to "I -' - I , and state that to the best of my knowledge and belief, the Owner has performed
examinations and taken corrective measures described in this Owner's Report in accordance with the
requirements of the ASME Code, Section XA
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or
implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,
neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or
of loss of any kind arising from or connected with this inspection.
(Robert T. Ward) Commissions &;& (/S5"5) tJ5F Q q iLc 4' Inspector ifgnature/ National Board, State, Province, and Endorsements
Date: I~-I•200\
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI
1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001
2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee, WI 54216-9511
Date: 12/13/01
Sheet: 1 of 3
Unit: No.1
Work Order#: SEE BELOW
WORK ORDER WP&IR DESCRIPTION 01-008139 M-FWA-380 S.G. "A" FW /AFW CUT OUT AND WELD 01-008139 M-FWB-381 S.G. "B" FW /AFW CUT OUT AND WELD
3. Work Performed by: Bechtel Construction
4. Identification of System: 05A/05B Class: 2 Name: FEEDWATER / AFW
5. (a) Applicable Construction Code: USAS B31.1, 1967 Ed. , No Add. Code Case: N/A
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add.
6. Identification of Components Repaired or Replaced and Replacement Components:
Code Case: N-416-2
Name of Name of Manufacturer National Other Year Repaired, ASME
Component Manufacturer Serial No. Board Identification Built Replaced, Code No. or Stamped
Replacement Yes/No
SEE CONTINUATION, SHEET 3
7. Description of Work: TEMPORARY REMOVAL OF EXISTING FEEDWATER PIPING AT EACH STEAM
GENERATOR OUTLET NOZZLE. TEMPORARY REMOVAL OF EXISTING AUXILLARY FEEDWATER
PIPING AT THE MAIN FEEDWATER BRANCH AT EACH STEAM GENERATOR. WELD REPAIRS ON BOTH
REMOVED FEEDWATER SPOOLS AND REPLACEMENT OF FEEDWATER VENT VALVE ASSEMBLY
(FW-80 A / B) CONNECTIONS USING NEW SOCKOLET AND INSERT REDUCER FITTINGS. ALL PIPING
WAS PREPARED AND REINSTALLED BY WELDING
8. Tests Conducted: Hydrostatic Fl Pneumatic El Nominal Operating Pressure [* Exempt E]
Other: F] Pressure: [A-FW 1040 psi / AFW 1040 psi] [ B-FW 1030 psi / AFW 1030 psi]
Test Temp: [A-FW 549.351F / AFW 57 0F] [B-FW 548.17'F / AFW 57°F]
* NOTE: The Secondary Side Hydrotest was conducted at NOP per Code Case N-416- 2
Page 1 of 3
Date: 12/13/01
Name of Component: FEEDWATER / AUXILLARY FEEDWATER
Work Order Number: 01-008139
CERTIFICATE OF COMPLIANCE
We certify that the statements made in the report are correct and this repair and replacement
conforms to the rules of the ASME Code, Section XI repair or replacement.
Type Code Symbol Stamp N/A
Certificate of Authorization No. N/A Expiration Date
Signed: o4L',- AP4UP-•P DS'or flun,�r'� n�inn�A Title
N/A
ate/ 41sl(
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors
and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of
Hartford, CT have inspected the components described in this Owner's Report during the period 09-f!)-f I
to I (- ?P-C, , and state that to the best of my knowledge and belief, the Owner has performed
examinations and taken corrective measures described in this Owner's Report in accordance with the
requirements of the ASME Code, Section XI
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or
implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,
neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or
of loss of any kind arising from or connected with this inspection.
(Robert T. Ward) Commissions • A tV ) A1- .-A.' ? c/-1/'
Inspector's Signature National Board, State, Province, and Endorsements
Date: t 0) -r 20O0
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
Page 2 of 3
/
Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code
No. Or Stamped Replacement Yes/No
SG LOOP-A N/A N/A N/A N/A N/A REPAIRED YES FEEDWATER SG LOOP-A N/A N/A N/A N/A N/A REPAIRED YES AUXILLARY FEEDWATER SG LOOP-B N/A N/A N/A N/A N/A REPAIRED YES FEEDWATER
SG LOOP-B N/A N/A N/A N/A N/A REPAIRED YES AUXILLARY FEEDWATER
SOCKOLET N/A N/A N/A HT# 2016 ANB REPLACEMENT NO
16"X 2" QADC 01-408
REDUCING N/A N/A N/A HT# 1566 ANB REPLACEMENT NO INSERT 2" X 1"
QADC 01-408
Page 3 of 3
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI
1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001
2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee WI 54216-9511
3.
4.
5.
6.
Date: 12/12/01
Sheet: 1 of 2
Unit: No.1
Work Order#: SEE BELOW
WORK ORDER WP&IR DESCRIPTION 01-005474 M-IWR-394 S.G. "A" INSTALL
LEVEL INSTR. WIDE RANGE
01-005474 M-IWR-395 S.G. "B" INSTALL LEVEL INSTR. WIDE RANGE
Work Performed by: Bechtel Construction
Identification of System: 06 Class: 2 Name: MAIN STEAM AND STEAM DUMP
(a) Applicable Construction Code: USAS B31.1. 1967 Ed. , No Add. Code Case: N/A
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add. Code Case: N-416-2
Identification of Components Repaired or Replaced and Replacement Components:
Name of Name of Manufacturer National Other Year Repaired, ASME
Component Manufacturer Serial No. Board Identification Built Replaced, Code
No. or Stamped Replacement Yes/No
CONDENSATE KNPP N/A N/A QADC 01-393 2001 REPLACEMENT NO
POT HT 85188
7. Description of Work: INSTALL NEW UPPER WIDE RANGE TAP, CONDENSATE POT AND TUBING.
8. Tests Conducted: Hydrostatic Dl Pneumatic [I Nominal Operating Pressure Z* Exempt E]
Other: E] Pressure: A-1 040 psi / B-1 030 psi Test Temp: A-549.35°F / B-548.17°F
* NOTE: The Secondary Side Hydrotest was conducted at NOP per Code Case N-416- 2
Page 1 of 2
Date: 12/12/01
Name of Component: MAIN STEAM AND STEAM DUMP
Work Order Number: 01-005474
CERTIFICATE OF COMPLIANCE
We certify that the statements made in the report are correct and this repair and replacement
conforms to the rules of the ASME Code, Section XI repair or replacement.
Type Code Symbol Stamp N/A
Certificate of Authorization No. N/A Expiration Date N/A
Signed: • • -/%•,"' 1F•,L k-, TIA Date Owner or Owner's Designee, Title
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors
and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of
Hartford, CT have inspected the components described in this Owner's Report during the period OC -0--31
to I I 3- 1•• ý , and state that to the best of my knowledge and belief, the Owner has performed
examinations and taken corrective measures described in this Owner's Report in accordance with the
requirements of the ASME Code, Section XI
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or
implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,
neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or
of loss of any kind arising from or connected with this inspection.
(Robert T. Ward) Commissions 0J1% 1 55") A4 UL-37- o) 4/..y
Inspector's Signature National Board, State, Province, and Endorsements
Date: t• 20-X).
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI
1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001
2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee Wl 54216-9511
Date: 12/12/01
Sheet: 1 of 2
Unit: No.1
Work Order#: SEE BELOW
WORK ORDER WP&IR DESCRIPTION 01-008141 M-MSA-350 S.G. "A" MS CUT OUT AND WELD 01-008141 M-MSB-351 S.G. "B" MS CUT OUT AND WELD
3. Work Performed by: Bechtel Construction
4. Identification of System: 06 Class: 2 Name: MAIN STEAM
5. (a) Applicable Construction Code: USAS B31.1, 1967 Ed. ,No Add.
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add.
6. Identification of Components Repaired or Replaced and Replacement Components:
Code Case: N/A
Code Case: N-416-2
Name of Name of Manufacturer National Other Year Repaired, ASME Component Manufacturer Serial No. Board Identification Built Replaced, Code
No. or Stamped Replacement Yes/No
SG LOOP-A N/A N/A N/A N/A N/A REPAIRED YES MAIN STEAM SG LOOP-B N/A N/A N/A N/A N/A REPAIRED YES MAIN STEAM 1 "GAMMA PORT COLONIAL HT # 87261 N/A N/A 2000 REPLACEMENT NO PLUG X 1" LG MACHINE HT CODE A696 GR C COMPANY, INC. AEM 1 "GAMMA PORT WFI HT # 8998228 N/A N/A 2001 REPLACEMENT NO PLUG X 2" LG INTERNATIONAL HT CODE A696 GR C 297YNB
7. Description of Work: TEMPORARY REMOVAL OF EXISTING MAIN STEAM PIPING AT EACH STEAM
GENERATOR OUTLET NOZZLE. EXISTING PIPING WAS PREPARED AND REINSTALLED BY WELDING.
REINSTALLATION INCLUDES ADDITION OF TWO NEW RADIOGRAPHY GAMMA PORTS AND PLUGS
PER LOOP.
8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure * Exempt E]
Other: 0 Pressure: A-1 040 psi/ B-1 030 psi Test Temp: A-549.35°F / B-548.17°F
* NOTE: The Secondary Side Hydrotest was conducted at NOP per Code Case N-416- 2
Page 1 of`2
Date: 12/12/01
Name of Component: MAIN STEAM
Work Order Number: 01-008141
CERTIFICATE OF COMPLIANCE
We certify that the statements made in the report are correct and this repair and replacement
conforms to the rules of the ASME Code, Section X1 repair or replacement.
Type Code Symbol Stamp N/A
Certificate of Authorization No. N/A Expiration Date N/A
Signed: 7,, "• -- , " .Date " Owner or Owner's Designee, Title
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors
and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of
Hartford, CT have inspected the components described in this Owner's Report during the period p9-/?-oj
to /I- ?-,- , and state that to the best of my knowledge and belief, the Owner has performed
examinations and taken corrective measures described in this Owner's Report in accordance with the
requirements of the ASME Code, Section XI
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or
implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,
neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or
of loss of any kind arising from or connected with this inspection.
(Robert T. Ward) CommissionstX3_ii&ý) A,,.; cT Y6/,
Inspec s Signature National Board, State, Province, and Endorsements
Date: h. "1 '• 20kO _
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
As Required by the Provisions for the ASME Code Section XI
1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001
2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee WI 54216-9511
Date: 12/12/01
Sheet: 1 of 2
Unit: No.1
Work Order#: SEE BELOW
WORK ORDER WP&IR DESCRIPTION 01-008137 M-RCS-366 S.G. "A" RCS CUT OUT
AND WELD
01-008133 M-RCS-360 S.G. "A" RCS NOZZLE PREP
3. Work Performed by: Bechtel Construction
4. Identification of System: 36 Class: 1 Name: REACTOR COOLANT
5. (a) Applicable Construction Code: USAS B31.1, 1967 Ed. ,No Add. Code Case: N/A
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add. Code Case: N-416-2
6. Identification of Components Repaired or Replaced and Replacement Components:
Name of Name of Manufacturer National Other Year Repaired, ASME
Component Manufacturer Serial No. Board Identification Built Replaced, Code
No. or Stamped Replacement Yes/No
STEAM WESTINGHOUSE 1141 68-28 NONE 1970 REPAIRED YES
GENERATOR STEAM ANSALDO 202 151 QADC-00-376 2000 REPLACEMENT YES
GENERATOR 11/2" CAP WESTINGHOUSE N/A N/A HT# 8000913, N/A REPLACEMENT NO
SCREW HT CODE RVP
1 1/2" CAP WESTINGHOUSE N/A N/A HT 204394, N/A REPLACEMENT NO
SCREW HT CODE SAZ
7. Description of Work: THE EXISTING WESTINGHOUSE LOWER ASSEMBLY WAS SEVERED FROM
REACTOR COOLANT PIPING. A NEW LOWER ASSEMBLY WAS PREPARED. INSTALLED. AND
CONNECTED TO THE REACTOR COOLANT PIPING BY WELDING.
8. Tests Conducted: Hydrostatic E] Pneumatic El Nominal Operating Pressure * Exempt El
Other: El Pressure: 2240 psi Test Temp: 551 .1OF
* NOTE: The Primary Side Hydrotest was conducted at NOP per Code Case N-416- 2
Page 1 of 2
Date: 12/12/01
Name of Component: REACTOR COOLANT
Work Order Number: 01-008137, 01-008133
CERTIFICATE OF COMPLIANCE
We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section XI repair or replacement.
Type Code Symbol Stamp N/A
Certificate of Authorization No. N/A
Signed: .4--- 1 .. "£ K 4fA ac- -I*>v
Expiration Date N/A
Date /I/'cfOwner or Owner's DesiQnee, Title
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors
and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of
Hartford, CT have inspected the components described in this Owner's Report during the period 09-//9
to ___- ____, and state that to the best of my knowledge and belief, the Owner has performed
examinations and taken corrective measures described in this Owner's Report in accordance with the
requirements of the ASME Code, Section Xl
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or
implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,
neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or
of loss of any kind arising from or connected with this inspection.
(Robert T. Ward) Commissions S.)3115S'7,JJ. U•.- 3 2(&'1
InspecteA -Signature National Board, State, Province, and Endorsements
Date: to-r% 2001
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
Page 2 of 2
f
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
As Required by the Provisions for the ASME Code Section XI
1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001
2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee WI 54216-9511
3. Work Performed by: Bechtel Construction
4. Identification of System: 36 Class:
5. (a) Applicable Construction Code: USAS B31.1, 1967 E
(b) Applicable Edition of Section X1 Utilized for Repairs or
6. Identification of Components Repaired or Replaced
Name of Name of Manufacturer P
Component Manufacturer Serial No. E
STEAM WESTINGHOUSE 1142 6 GENERATOR STEAM ANSALDO 201 1
GENERATOR 11/2" CAP WESTINGHOUSE N/A h SCREW 11/2' CAP WESTINGHOUSE N/A SCREW
Date: 12/12/01
Sheet: 1 of 2
Unit: No.1
Work Order#: SEE BELOW
WORK ORDER WP&IR DESCRIPTION 01-008137 M-RCS-367 S.G. "B" RCS CUT OUT
AND WELD
01-008133 M-RCS-361 S.G. "B" RCS NOZZLE PREP
1 Name: REACTOR COOLANT
-d. ,No Add. Code Case: N/A
Replacements: 1989, No Add. Code Case: N-416-2
and Replacement Components:
Jational Other Year Repaired, ASMIE Board Identification Built Replaced, Code 0o. or Stamped
Replacement Yes/No
8-29 NONE 1970 REPAIRED YES
50 QADC 00376 2000 REPLACEMENT YES
N/A HT# 8000913, N/A REPLACEMENT NO HT CODE RVP
VA HT 204394, N/A REPLACEMENT NO HT CODE SAZ
7. Description of Work: THE EXISTING WESTINGHOUSE LOWER ASSEMBLY WAS SEVERED FROM
REACTOR COOLANT PIPING. A NEW LOWER ASSEMBLY WAS PREPARED, INSTALLED, AND
CONNECTED TO THE REACTOR COOLANT PIPING BY WELDING.
8. Tests Conducted: Hydrostatic E] Pneumatic E] Nominal Operating Pressure [ Exempt El
Other: E] Pressure: 2240 psi Test Temp: 551 .1F
* NOTE: The Primary Side Hydrotest was conducted at NOP per Code Case N-416- 2
Page 1 of 2
Date: 12/12/01
Name of Component: REACTOR COOLANT
Work Order Number: 01-008137, 01-008133
CERTIFICATE OF COMPLIANCE
We certify that the statements made in the report are correct and this repair and replacement
conforms to the rules of the ASME Code, Section Xl repair or replacement.
Type Code Symbol Stamp N/A
Certificate of Authorization No. N/A
Signed: A /4t-/ P4.r &- '_
Expiration Date N/A
Date 1!ý/ 7 /
Owner or Owner's Designee, I tle
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors
and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of
Hartford, CT have inspected the components described in this Owner's Report during the period 05/-0- I
to P , and state that to the best of my knowledge and belief, the Owner has performed
examinations and taken corrective measures described in this Owner's Report in accordance with the
requirements of the ASME Code, Section XI
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or
implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,
neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or
of loss of any kind arising from or connected with this inspection.
(Robert T. Ward) Commissions AA Ill'S'2dIJ; G"-s P'V(- Y..iA
Ins p(ýsSig nature National Board, State, Province, and Endorsements
Date: 200(
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions for the ASME Code Section XI
1. Owner: Wisconsin Public Service Corporation 700 North Adams P.O. Box 19001 Green Bay, WI 54307-9001
2. Plant: Kewaunee Nuclear Power Plant N490 HWY 42 Kewaunee WI 54216-9511
3.
4.
5.
6.
Date: 12/12/01
Sheet: 1of 4
Unit: No.1
Work Order# : SEE BELOW
WORK ORDER WP&IR DESCRIPTION 01-013376 M-LLR-313 Replace Upper Col.
Adapters and Reshim Lower Lateral Restraint
Work Performed by: Bechtel Construction
Identification of System: 36 Class: 1 Name: "A" Col. Adapter Plates and Lower Lateral Shims
(a) Applicable Construction Code: USAS B31.1, 1967 Ed. ,No Add. Code Case: N/A
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1989, No Add. Code Case: N/A
Identification of Components Repaired or Replaced and Replacement Components:
Name of Name of Manufacturer National Other Year Repaired, ASME Component Manufacturer Serial No. Board Identification Built Replaced, Code
No. or Stamped Replacement Yes/No
See continuation sheet, page 3
7. Description of Work: Replaced steam generator support upper column adapters and removed and restored
lower lateral suDport bumper guides to the steam generator and shimmed the adiacent support bumper steel.
Exempt Z
OF
Page 1 of 4
8. Tests Conducted: Hydrostatic [] Pneumatic E] Nominal Operating Pressure El
Other: [] Pressure: psi Test Temp
Date: 12/12/01
Name of Component: "A" Upper Col. Adapter Plates and Reshim Lower Lateral Restraint.
Work Order Number: 01-0133760
CERTIFICATE OF COMPLIANCE
We certify that the statements made in the report are correct and this repair and replacement conforms to the rules of the ASME Code, Section Xl repair or replacement.
Type Code Symbol Stamp N/A
Certificate of Authorization No. N/A Expiration Date N/A
Signed: . - ,, eH $--V Date 4 I , Owner or Owner's Designee, Title
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler Pressure Vessel Inspectors
and the State or Providence of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of
Hartford, CT have inspected the components described in this Owner's Report during the period C')C -/ ) -0i1
to I and state that to the best of my knowledge and belief, the Owner has performed
examinations and taken corrective measures described in this Owner's Report in accordance with the
requirements of the ASME Code, Section XI
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or
implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore,
neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or
of loss of any kind arising from or connected with this inspection.
(Robert T. Ward) Commissions 6 ii -),,4
Inspecti_'s-gfiature National Board, State, Province, and Endorsements
Date: - Is 2001
Page 2 of 4
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS
Continuation Sheet
Name of Component
Shims
Shims
Shims
Shims
Shims
Shims
Shims
Shims
Shims
Shims
Shims
Shims
Shims
Shims
V" Bolts A325
I" Bolts A325
1" Flat Washers F436-93 I" Hex. Hd. Nuts A194 Gr. 2H ¾" Lockwashers B18.21 S.G. Col. Adapter A588 S.G. Col. Adapter Pin AISI 4340 S.G. Col. Adapter Pin Washer A-588, Gr. A S.G. Col. Adapter Pin Washer Bolts A-325
Name of Manufacturer Manufacturer Serial No.
Colonial Ht. No. 264344
Colonial Ht. No. 812J3592
Colonial Ht. No. 4126617
Colonial Ht. No. 4122060
Colonial Ht. No. 4155918
Colonial Ht. No. 4125164
Colonial Ht. No. A86743
Colonial Ht. No. 4151614
Colonial Ht. No. 2A6593A
Colonial Ht. No. T1273-A
Colonial Ht. No. I E802
Colonial Ht. No. R6759
Colonial Ht. No. R6791
Colonial Ht. No. I E542
Colonial Ht. No. 706907
Colonial Ht. No. 213265
Colonial Ht. No. B28393
Colonial Ht. No. S41165
Colonial Ht. No. 43739D
Colonial Fabricated Assembly
Colonial Ht. No. 8996496C0477
Colonial Ht. No. 803M62250
Colonial Ht. No. 255029 Trace Code I UX
National Other Board Identification. No.
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A MRR 1042
N/A N/A
N/A N/A
N/A N/A
Year Built
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001
2001 I Replacement
Page 3 of 4
Repaired Replaced Or Replacement Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
Replacement
ASME Code Stamped Yes/No No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Name of Name of Manufacturer National Other Year Repaired ASME Component Manufacturer Serial No. Board Identification: Built Replaced Code
No. Or Stamped Replacement Yes/No
S.G. Adapter Col. Colonial Ht. No. 10618 N/A N/A 2001 Replacement No Adapter Bolts A- Trace No. IUU 540, Gr. B23, Cl. 2 S.G. Adapter Col. Colonial Ht. No. S42483, N/A N/A 2001 Replacement No Jam Nuts, SA307 Trace No. 1UY Gr. B
S.G. Adapter Col. Colonial Ht. No. 8994464 N/A N/A 2001 Replacement No Heavy Hex. Nut, Ht Code SBG SA 194 Gr. 2H
S.G. Col. Adapter Colonial Ht. No. 8997945 N/A N/A 2001 Replacement No Washers AISI 4150 Trace Code 1UW
%" Hex Head Bolt, Colonial 8996654 N/A N/A 2001 Replacement No
A-490
___________ I 4 4 + +
4 4 ± t t
4 4 ± ± t
4 4 + I t
+ *1� 1 T
I I [ 1 1 F
Page 4 of 4
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 33 Class 1 SAFETY INJECTION
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of Manufacturer
Manufacturer Serial No.
ANCHOR/DARLING VALVE NF COMPANY
National Board No.
NA
Other ID
S1115-002
Date 11/26/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-005013
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1970
Repaired, Replaced, or Replacement
REPLACEMENT
7. Description of Work OPEN FOR INSPECTION CLASS 1 SAFETY INJECTION SYSTEM 12" VALVE SI-22B AND REPLACEMENT OF 1
VALVE BONNET STUD.
8. Tests conducted Hydrostatic
Other DR Pneumatic r] Nominal Operating Pressure E
Pressure 750 psi Test Temp. 63 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
SI-22B
ASME Code
Stamped
N
Exempt 1
NIS-2 (Back)
Sheet 2 of 2
Date: 11/26/2001
Name of Component: SI-22B
Work Order Number: 01-005013
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed £/ffiM geJ~g9U A &OW14 Date
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period -74 S-D 0 to / - 31-0 2-, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
7 i 4-1, Commissions NB7741, 1, N, IS, A WIS 100024
Inspector' Signature National Board, State, Province, and Endorsements
Date a, t- A , / - ,20 01.
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL
5. (a) Applicable Construction Code NA
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
APRH1-IA
Name of
Manufacturer
BRYON JACKSON
Manufacturer Serial No.
681N0277
National Board No.
NA
Other ID
00127
Date 11/27/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-005020
Type Code Sym. Stamp N._A
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1970
Repaired, Replaced, or
Replacement
REPAIRED
7. Description of Work INSPECT AND REBUILD CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM RESIDUAL HEAT REMOVAL PUMP 1A.
8. Tests conducted Hydrostatic
Other F
7] Pneumatic El Pressure 375 psi
Nominal Operating Pressure =l
Test Temp. 341 deg. F
9. Remarks NOT APPLICABLE
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
N
Exempt 1
NIS-2 (Back)
Sheet 2 of 2
Date: 11/27/2001
Name of Component: APRH1-IA
Work Order Number: 01-005020
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed e, C.4 V .. m&Aot. ae6.ý D4ateL 20 Z
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period -1-A,-0o to /- 3 /-0Z , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, conceming
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspector's ignature National Board, State, Province, and Endorsements
Date / 20 e .
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
LD-13
Name of
Manufacturer
CROSBY VALVE & GAGE CO.
Manufacturer Serial No.
NF
National
Board No.
NA
Other ID
CS014-001
Date 11/2912001
Sheet 1 of 2
Unit No. 1
Work Order 01-005030
Type Code Sym. Stamp N.A
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1971
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work REMOVE FOR TESTING CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE LD-13.
8. Tests conducted Hydrostatic L] Other D
Pneumatic F Nominal Operating Pressure El Pressure 84 psi Test Temp. 87 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturers Data Reports to be Attached
ASME Code
Stamped
N
Exempt [:
NIS-2 (Back)
Sheet 2 of 2
Date: 11/29/2001
Name of Component: LD-13
Work Order Number: 01-005030
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed 6k ý__.• ( y-,4- Date 4_ ! ,20 O.L OV - O DeXi Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 1-2S-- 0 to /- 3/- 01, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
7 4 1 Commissions NB7741, I, N, IS, A WIS 100024
nspector'Sqnature National Board, State, Province, and Endorsements
Date / ,20 02
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 11/29/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-005031
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Repaired, ASME Name of Name of Manufacturer National Other Year Replaced, or Code
Component Manufacturer Serial No. Board No. ID Built Replacement Stamped
LD-5 CROSBY ASHTON GAGE NF NA CS109-001 1970 REPAIRED N CO.
7. Description of Work REMOVE FOR TESTING CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE LD-5.
8. Tests conducted Hydrostatic
Other F
--1 Pneumatic E Pressure 500 psi
Nominal Operating Pressure 17
Test Temp. 250 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Exempt 1:1
NIS-2 (Back)
Sheet 2 of 2
Date: 11/29/2001
Name of Component: LD-5
Work Order Number: 01-005031
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed l.e/,aI £. .T-,44Q/LA Date L- 20 OQ
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 7-,aS-0 O to /-/'-O3.- , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspector' Signature National Board, State, Province, and Endorsements
Date 2 • .•,• / ,20 1,,-
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT
As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 36 Class 1 REACTOR COOLANT
5. (a) Applicable Construction Code ASME 111-1968
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 12/4/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-005033
Type Code Sym. Stamp N._A
Authorization No. NA
Expiration Date NA
Code Case NA
Name of Manufacturer
Manufacturer Serial No.
CROSBY, ASHTON GAGE NF COMPANY
National Board No.
NA
Other Year ID Built
RCOO8-001 1972 REPLAL�M�N N
��p�I1-�u,Repaired, Replaced, or
Replacement
7. Description of Work REMOVE CLASS 1 REACTOR COOLANT SYSTEM 6" VALVE PR-3A FOR TESTING AND REPLACING DICS INSERT.
8. Tests conducted Hydrostatic
Other ElEl Pneumatic F
Pressure 2240 psi
Nominal Operating Pressure E
Test Temp. 5_1 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
PR-3A
Code Stamped
Exempt [-1
REPLACEME=NT NRC008-001 1972
NIS-2 (Back)
Sheet 2 of 2
Date: . 12/4/2001
Name of Component: PR-3A
Work Order Number: 01-005033
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed _____, ______________ Date • g 20 0-1
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period -7-"2S-oO to /- ,/-0,Z , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
4 = "Commissions NB7741, I, N, IS, A WIS 100024
Inspector's Signature National Board, State, Province, and Endorsements
Date ,20 O
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
AFW-4B
Name of
Manufacturer
WILLIAM POWELL CO.
Manufacturer Serial No.
61208
National Board No.
NA
Other ID
F015-002
Date 12/20/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-005272
Type Code Sym. Stamp N.A
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1972
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work REPAIR CLASS 2 AUXILARY FEEDWATER SYSTEM 3" VALVE AFW-4B DUE TO IMPROPER SEATING.
8. Tests conducted Hydrostatic
Other D]LI Pneumatic F Nominal Operating Pressure F]
Pressure 1030 psi Test Temp. 57 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
N
Exempt 1
N
NIS-2 (Back)
Sheet 2 of 2
Date: .12/20/2001
Name of Component: AFW-4B
Work Order Number: 01-005272
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed Date •'o ,20 _._20 _
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period I-•,• 00 to ,/-,/9•2 , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
ln "Commissions NB7741, I, N, IS, A WIS 100024
Inspector's ignature National Board, State, Province, and Endorsements
Date t ,20 6-.
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 05B Class 2 AUXILIARY FEEDWATER
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of Manufacturer
WILLIAM POWELL CO.
Manufacturer Serial No.
NF
National
Board No.
NA
Other
ID
FO15-001
Date 12/20/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-005273
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1972
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work REPAIR CLASS 2 AUXILIARY FEEDWATER SYSTEM 3" VALVE AFW-4A DUE TO IMPROPER SEATING.
8. Tests conducted Hydrostatic [
Other D
Pneumatic Nominal Operating Pressure =V
Pressure 1040 psi Test Temp. 57 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
AFW-4A
ASME Code
Stamped
N
Exempt 1
NIS-2 (Back)
Sheet 2 of 2
Date: •12/20/2001
Name of Component: AFW-4A
Work Order Number: 01-005273
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed PXfluO-A.l 1Z n Ou -v Date 2 0,20
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 9÷S'• 00 to / -3/OV , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, 1, N, IS, A WIS 100024
Inspector'signature National Board, State, Province, and Endorsements
Date f -/ ,20 1PZ
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 23 Class 2 CONTAINMENT SPRAY
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
ICS-2B
Name of
Manufacturer
CRANE VALVE CO.
Manufacturer Serial No.
NF
National Board No.
NA
Date 12/3/2001
Sheet I of 2
Unit No. 1
Work Order 01-007182
Type Code Sym. Stamp N__A
Authorization No. NA
Expiration Date NA
Code Case NA
Other Year ID Built
ICS002-002 1970
Repaired, ASMERepaired,
Replaced, or Replacement
REPAIRED N
7. Description of Work OPEN FOR MAINTAENANCE CLASS 2 INTERNAL CONTAINMENT SPRAY 8" VALVE ICS-2B.
8. Tests conducted Hydrostatic E
Other RI
Pneumatic r- Nominal Operating Pressure FX
Pressure 30 psi Test Temp. 70.4 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
Exempt 1"1
REPAIRED N
NIS-2 (Back)
Sheet 2 of 2
Date: 12/3/2001
Name of Component: ICS-2B
Work Order Number: 01-007182
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XL. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed / / 4 'f,0Jfl- Date ,20 02
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period '7--2S-9 to /-3/ -02, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspectors Signature National Board, State, Province, and Endorsements
Date / 20 _.___,20_
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 23 Class 2 CONTAINMENT SPRAY
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
ICS-2A
Name of
Manufacturer
CRANE VALVE CO.
Manufacturer Serial No.
NF
National Board No.
NA
Date 12/3/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-007183
Type Code Sym. Stamp N__AA
Authorization No. NA
Expiration Date NA
Code Case NA
Other Year
ID Built
ICS002-001 1970
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work OPEN FOR MAINTENANCE CLASS 2 INTERNAL CONTAINMENT SPRAY 8" VALVE ICS-2B.
8. Tests conducted Hydrostatic
Other D--1-1 Pneumatic 1:1 Nominal Operating Pressure IE
Pressure 30 psi Test Temp. 70.4 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
N
Exempt 1
NIS-2 (Back) Sheet 2 of 2
Date: 12/3/2001
Name of Component: ICS-2A
Work Order Number: 01-007183
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed _.D ••e•J L.'i 20 0 _
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period '7-;,'5-' 0 to I-3 / -V2 , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
ie, -7 .Commissions NB7741, I, N, IS, A WIS 100024
U p oiorsSignature National Board, State, Province, and Endorsements
Da te- .20 01
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 23 Class 2 CONTAINMENT SPRAY
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of Component
RHR-400B
Name of Manufacturer
CRANE COMPANY
Manufacturer Serial No.
NA
National Board No.
NA
Date 1/14/2002
Sheet 1 of 2
Unit No. I
Work Order 01-007184
Type Code Sym. Stamp NA..
Authorization No. NA
Expiration Date NA
Code Case NA
Other Year ID Built
ICS006-006 1970
Repaired, ASMERepaired,
Replaced, or Replacement
REPAIRED
7. Description of Work OPEN FOR MAINTENANCE CLASS 2 INTERNAL CONTAINMENT SPRAY 6" VALVE RHR-400B DUE TO POSSIBLE
DISC TO SEAT GALLING.
8. Tests conducted Hydrostatic
Other
Pneumatic Nominal Operating Pressure rl
Pressure 144 psi Test Temp. 87 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
N
Exempt r-1
NIS-2 (Back)
Sheet 2 of 2
Date: 1/14/2002
Name of Component: RHR-400B
Work Order Number: 01-007184
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xi. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed f, Date6MAAAM,20 •
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period I-2S'CD 0 to /J/,OZ , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
;,2 s 7 a44 • Commissions NB7741, I, N, IS, A WIS 100024
(5 p 5iature National Board, State, Province, and Endorsements
Date ,20 #-1-_
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT
As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 23 Class 2 CONTAINMENT SPRAY
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of Component
RHR-400A
Name of Manufacturer
CRANE COMPANY
Manufacturer Serial No.
NF
National Board No.
NA
Date 12/20/2001
Sheet I of 2
Unit No. 1
Work Order 01-007185
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NNA
Code Case NA
Other Year ID Built
1C5006-005 1970 REPAIRED N
Kepalrea,Repaired, Replaced, or
Replacement
7. Description of Work OPEN FOR MAINTENENCE CLASS 2 INTERNAL CONTAINMENT SPRAY SYSTEM 6" VALVE RHR-400A DUE TO
POSSIBLE DISC TO SEAT GALLING.
8. Tests conducted Hydrostatic Dl Other F
Pneumatic Nominal Operating Pressure r7
Pressure 375 psi Test Temp. 341 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Code Stamped
Exempt F
REPAIRED NICS006-005 1970
NIS-2 (Back)
Sheet 2 of 2
Date: 12/20/2001
Name of Component: RHR-400A
Work Order Number: 01-007185
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed Date < 20 0A
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period '7-1S"-00 to /-$1-t2,, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XL.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
pectors Signature National Board, State, Province, and Endorsements
Date / 20 J0
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 23 Class 2 CONTAINMENT SPRAY
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of Component
ICS-5B
Name of Manufacturer
CRANE VALVE CO.
Manufacturer Serial No.
NF
National Board No.
NA
Date 11/9/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-007186
Type Code Sym. Stamp NAA
Authorization No. NA
Expiration Date NA
Code Case NA
Other Year
ID Built
ICS006-003 1970
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work OPEN FOR REPAIR CLASS 2 CONTAINMENT SPRAY SYSTEM 6" VALVE ICS-5B DUE TO DISC TO SEAT GALLING.
8. Tests conducted Hydrostatic
Other DD- Pneumatic
Pressure
D Nominal Operating Pressure n
280 psi Test Temp. 75 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
N
Exempt F
NIS-2 (Back)
Sheet 2 of 2
Date:. 11/9/2001
Name of Component: ICS-5B
Work Order Number: 01-007186
,20 6
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed A &Q lT'/c,2*. A•A•h acW•U t Date 4 ,20 0.1
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owners Report during the period 7_-_'_o to I/-'S-, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
w o--: Commissions NB7741, I, N, IS, A WIS 100024
National Board, State, Province, and Endorsements
SInspector's iignature
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson. Wisconsin 54016
4. Identification of System 23 Class 2 CONTAINMENT SPRAY
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
ICS-6B
Name of
Manufacturer
CRANE VALVE CO.
Manufacturer Serial No.
NF
National
Board No.
NA
Date 11/9/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-007187
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Other Year ID Built
ICS006-004 1970
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work OPEN FOR MAINTENANCE CLASS 2 CONTAINMENT SPRAY SYSTEM 6" VALVE ICS-6B DUE TO DISC TO SEAT GALLING.
8. Tests conducted Hydrostatic
Other ElEl Pneumatic Nominal Operating Pressure I•
Pressure 280 psi Test Temp. Z5 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
N
Exempt 1
NIS-2 (Back)
Sheet 2 of 2
Date: 11/9/2001
Name of Component: ICS-6B
Work Order Number: 01-007187
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed eI "a, &JV.AnJ AAJ Date l i ,20 0O.1 Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period '7- 2Y-,0 to /-JI/-0 X, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
S44 ,Commissions NB7741, I, N, IS, A WIS 100024
Date ,20 60.1
National Board, State, Province, and EndorsementsV Inspector's 11gnature
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 33 Class 1 SAFETY INJECTION
5. (a) Applicable Construction Code B16.5-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
SI-304A
Name of
Manufacturer
VELAN VALVE CORPORATION
Manufacturer Serial No.
NF
National Board No.
NA
Other ID
SI116-005
Date 9/7/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-013239
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Year Built
1967
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work TORQUE BOLTING ON CLASS 1 SAFETY INJECTION SYSTEM 6" VALVE SI-304A DUE TO EVIDENCE OF LEAKAGE.
8. Tests conducted Hydrostatic
Other --
F Pneumatic
Pressure
D Nominal Operating Pressure
0 psi Test Temp.
1:1 Exempt El
0 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
N
NIS-2 (Back)
Sheet 2 of 2
Date: 9/7/2001
Name of Component: SI-304A
Work Order Number: 01-013239
Da tetej 20 ~
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed Date 20 C.
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 7t.4"O to /-3/-#;L , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
A ?-3" 7~t",Commissions NB7741, 1, N, IS, A WIS 100024
National Board, State, Province, and EndorsementsI" Inspecr's Signature
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section X1 Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Manufacturer
GRINNELL FIRE PROTECTION SYSTEMS
Manufacturer Serial No.
NF
National
Board No.
NA
Date 8/20/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-013438
Type Code Sym. Stamp N.A
Authorization No. NA
Expiration Date NA
Code Case NA
Other Year ID Built
CS033-005 1973
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work TORQUE BOLTING ON CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 3" VALVE CVC-4C DUE TO BODY TO BONNET LEAK.
8. Tests conducted Hydrostatic
Other F
1I- Pneumatic
Pressure
L] Nominal Operating Pressure El
23 psi Test Temp. 11_5 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
CVC-4C
ASME Code
Stamped
N
Exempt El
NIS-2 (Back)
Sheet 2 of 2
Date: 8/20/2001
Name of Component: CVC-4C
Work Order Number: 01-013438
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed 1CA AAX.L.A ,7T- t CJ* Date 20 6,20
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 74--'O0 to /-3/-D2- , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, 1, N, IS, A WIS 100024
Inspectors Signature National Board, State, Province, and Endorsements
Date 20 O;
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
RHR-100B
Name of Manufacturer
CRANE VALVE CO.
Manufacturer Serial No.
NF
National
Board No.
NA
Date 11/21/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-014566
Type Code Sym. Stamp N A
Authorization No. NA
Expiration Date NA
Code Case NA
Other Year
ID Built
AC010-008 1972
Repaired,
Replaced, or Replacement
REPAIRED
7. Description of Work OPEN FOR REPAIR CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8" VALVE RHR-100B.
8. Tests conducted Hydrostatic
Other DPneumatic 1 Nominal Operating Pressure El
Pressure 114 psi Test Temp. 87 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
N
Exempt LI
NIS-2 (Back)
Sheet 2 of 2
Date: .11/21/2001
Name of Component: RHR-100B
Work Order Number: 01-014566
Date / 20 2
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed __.JA CA)Jt Date .20 0 ca,
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 74So-' to 3/ 1'- 2-, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
National Board, State, Province, and Endorsementsa.nspector's'gnature
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson, Wisconsin 54016
4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Component
RHR-100A
Name of
Manufacturer
CRANE VALVE COMPANY
Manufacturer Serial No.
NF
National Board No.
NA
Date 11/27/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-014567
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Other Year
ID Built
AC010-007 1972
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work REPAIR CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8" VALVE RHR-100A.
8. Tests conducted Hydrostatic
Other 1:
LII Pneumatic
Pressure 340 psi
Nominal Operating Pressure L
Test Temp. 189 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
ASME Code
Stamped
N
Exempt 1
NIS-2 (Back)
Sheet 2 of 2
Date: .11/27/2001
Name of Component: RHR-100A
Work Order Number: 01-014567
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed 1k: •W A 0LN 111. flh1, Date 20 0.__
Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period '7-;S'00 to I 3/'-0Z, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
A ý nCommissions NB7741, I, N, IS, A WIS 100024
Inspe or's Signature National Board, State, Province, and Endorsements
Date - ••. 20 -0
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENT As Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street, Hudson. Wisconsin 54016
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL
5. (a) Applicable Construction Code NA
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Name of
Manufacturer
AJAX IRON WORKS
Manufacturer Serial No.
6577
National Board No.
NA
Other ID
00077
Date 9/5/2001
Sheet 1 of 2
Unit No. 1
Work Order 01-014609
Type Code Sym. Stamp N.A
Authorization No. NA
Expiration Date NA
Code Case NNA
Year Built
1967
Repaired, Replaced, or Replacement
REPAIRED
7. Description of Work REPAIR CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM CHARGING PUMP 1C (SUCTION VALVE REPAIR).
8. Tests conducted Hydrostatic
Other R
Pneumatic 1: Nominal Operating Pressure El
Pressure 20 psi Test Temp. 112 deg. F
9. Remarks NOT APPLICABLE
Applicable Manufacturer's Data Reports to be Attached
Name of
Component
APCH-1C
ASME Code
Stamped
N
Exempt El
NIS-2 (Back)
Sheet 2 of 2
Date: 9/5/2001
Name of Component: APCH-1C
Work Order Number: 01-014609
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed " e•. 640-•pao• Date • ,20 0 Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period 1- 2r-0 0 to /__3_-_ 2_, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
lns Jtr Commissions NB7741, I, N, IS, A WIS 100024
Inspector's Signature National Board, State, Province, and Endorsements
Date / 20 0 ,
Recommended