DESCRIPTION
Floor Standing Split Air Conditioner
Citation preview
1
MFS
2
PAGE
1. CONTENTS 2
2. NOMENCLATURE 3
3. NAMES AND FUNCTION OF PART 4
4. TECHNICAL SPECIFICATION 5
5. OUTLINES AND DIMENSIONS 6
6. WIRING DIAGRAM 8
7. INSTALLATION (INDOOR) 9
CONTENTS
3
M F S 30
A
Generation
Capacity 30, 40, 50, 60
Standing Fan Coil
Floor
McQuay
Easy Maintenance The simple design concept has maintenance and servicing in mind. Access to the internal parts of the unit
can be from front or back of the unit by removing a few screws
Filter Rack The fan coil unit has a filter rack to hold the air filter. This ensure the air flow is clean and the filter is easily
accessible for maintenance and cleaning
Three Speed Motor The unit has 3-speed direct driven centrifugal fan and operate very silently to give whisper comfort condition. The speed of the fan can be adjusted through the electric controller. (See below).
Easy and Flexible Installation The easy is highly compact and therefore it is very easy to select a location to install the unit such that only small space is required.
Electric Controller
Electric Controller can display cool, dry and fan mode with auto, high, medium and low fan speed. The temperature settings range from 16 OC and 30 OC.
NOMENCLATURE
4
CONTROL PANEL
REMOTE CONTROL
AUTO mode
COOL mode
DRT mode
FAN mode
HEAT mode
SLEEP operation
SWING operation
NAMES AND FUNCTIONS OF PART
CLOCK Button Set desired Timed time
Fan Running Display Simulate the running
condition of ran
TIMER Button Select timed
starting or stopping
ON/OFF Button Start or stop
operation
SLEEP Button Set or cancel
sleep operation
TEMPERATURE SET Button
Set desired temperature
FAN SPEED Button
Set fan speed or indoor unit
SWING Button Set the flow in a fixed direction or
swing left
MODE Button Select the
operation mode
Clock button
Reset button
Batteries
ON/OFF button
Mode button
Swing button
Sleep button
Fan Speed button
Fan speed and sleep operation
display
Mode Display
Signal transmitting section
Set temperature display
Swing display
Time display
Temperature set button
On timer button
Off timer button
5
TECHNICAL SPECIFICATION
MODEL INDOOR UNIT MFS 30A MFS 40A MFS 50A MFS 60A
OUTDOOR UNIT MLC 30C MLC 40C MLC 50C MLC 61C
NOMINAL COOLING CAPACITY Btu/h 29,000 39,000 49,000 58,000
REFRIGERANT / CONTROL R22 / THERMAL EXPANSION VALVE
IND
OO
R
BLO
WER
& M
OTO
R
POWER SOURCE V/ph/Hz 240 / 1 / 50
TYPE CENTRIFUGAL / DIRECT DRIVEN
QUANTITY 1 1 1 1
NOMINAL AIR FLOW CFM 850 1,150 1,450 1,750
OUTLET VELOCITY m/s 3.1 4.2 5.3 6.4
MOTOR OUTPUT W 50 90 110 110
CAPACITOR SIZE f 3.5 6 5 5
RATED RUNNING CURRENT (EACH) Amps 0.85 1.3 1.6 1.6
FAN MOTOR POLES 4 Poles; IP55; Class B
EXTERNAL STATIC PRESSURE inWG 0.4 0.4 0.4 0.4
CO
IL
TUB
E MATERIAL COPPER
DIAMETER mm 9.52
THICKNESS mm 0.3
FIN
MATERIAL ALUMINIUM
THICKNESS mm/in 0.11
TUBE HEIGHT 29 36 36 36
ROWS
2 2 3 3
FIN PER INCH 14 14 14 16
FACE AREA m2 0.34 0.43 0.43 0.43
FIN LENGTH mm 480 480 480 480
AIR VELOCITY FPM 154 206 260 314
CASING MATERIAL PLASTIC FRONT PANEL
DIMENSION
HEIGHT mm 1900 1900 1900 1900
WIDTH mm 600 600 600 600
DEPTH mm 280 360 360 360
WEIGHT kg 42 65 65 65
CONTROL ROOM TEMPERATURE CAPILLARY TUBE
PIPING CONNECTION
GAS mm 15.88 19.05 19.05 19.05
LIQUID mm 9.52 9.52 9.52 12.7
CONDENSATE DRAIN SIZE FLEXIBLE HOSE
FILT
ER TYPE WASHABLE SARANET FILTER
SIZE WIDTH x HEIGHT mm 500 x 690
THICKNESS mm 5
QUANTITY 1
PACKING DIMENSION
HEIGHT mm 1970 1970
WIDTH mm 390 440
DEPTH mm 680 680
OU
TD
OO
R
CO
MP
TYPE SCROLL
POWER SOURCE V/Ph/Hz 220-240/1/50 415 / 3 /50
PROTECTION DEVICE OVERLOAD PROTECTION AND AUTO RESET HIGH/LOW PRESSURE SWITCH
FAN
FAN TYPE / DRIVE PROPELLER / DIRECT
BLADE MATERIAL ACRLY STYRENE RESIN
DIAMETER mm/in 609.6 / 24.0
POWER SOURCE V/Ph/Hz 240 / 1 / 50
CO
IL
TUB
E MATERIAL SEAMLESS COPPER
DIAMETER mm 9.52
THICKNESS mm 0.3
FIN
MATERIAL ALUMINIUM
THICKNESS mm 0.11
NUMBER x ROWS 1 x 1 1 x 2 1 x 2 1 x 3
FIN PER INCH 16 14 16 16
FACE AREA m2 0.89 0.85 0.87 1.23
DIMENSION
HEIGHT mm 850
WIDTH mm 1,030
DEPTH mm 400 460
WEIGHT kg 95 100 105 108
CASING MATERIAL ELECTRO-GALVANISED MILD STEEL
FINISH EPOXY POLYSTER POWDER COATING
SOUND PRESSURE LEVEL dBA 58 58 58 61
PIPING CONNECTION
GAS mm 15.88 19.05 19.05 19.05
LIQUID mm 9.52 9.52 9.52 12.7
6
INDOOR UNIT MODEL: MFS 30A
MODEL: MFS 40A/50A/60A
OUTLINES AND DIMENSIONS
R
R
7
OUTDOOR UNIT MODEL: MLC 30C, 40C, 50C, 61C
Model A B C D E F G H J K L M N P
MLC 30C/40C/50C 1030 850 400 390 414 827 72 196 91 488 448 141.5 746.5 82
MLC 61C 1030 850 480 390 414 827 72 196 91 488 448 141.5 746.5 82
8
INDOOR - OUTDOOR UNIT MODEL: MFS 30A/40A/50A/60A MLC 30C/40C/50C/61C
WIRING DIAGRAM
PP
LP
HP
CRANKCASE
HEATER
L2
COMPRESSOR
WH
ITE
RE
D
L1
BLA
CK
BLU
E
L3
BLA
CK
3L2
4T2
1L1
2T1
5L3
RED
6T3
R S T N
GR
EE
N/Y
ELLO
W
OUTDOOR UNIT
FAN
MOTOR
L N
U
V W
R S T N
NO
RED
A1
A2
NC
NC
GREEN/YELLOW
RE
D
WH
ITE
BLU
E
DT
FU -
-
-
-
-
- DISCHARGE TERMOSTAT
AUTO RESET HP SWITCH
AUTO RESET LP PRESSURE
PHASE PROTECTOR
CONTACTOR
FUSE
BLUE
BLUE
RED
WHITE
BLUE
RELAY
PP
C
COM
WHITE
BLACK
BLACK
HP
BLUE BLUE BLUE
LP
BLACK BLACK
GREEN/YELLOW
FU
7ARED
OPERATING
BOARD
8 4
TC
BROW
BROW
RE
D
BLU
E
1L1
2T1
(NO)
(NO)
BLA
CK
RED
RE
D
BLU
E
WH
ITE
WH
ITE
DT
C
9
Preliminary Site Survey a) Electrical supply and installation is to confirm to local authoritys (e.g. National Electricity Board) codes
and regulations. b) Voltage supply fluctuation must not exceed +/- 10% of rated voltage. Electricity supply line must be
independent of welding transformers which can cause supply fluctuation. c) Ensure that the location is convenient for wiring and piping.
Piping Do not use contaminated or damaged copper tubing. If piping, evaporator or condenser are exposed or had been opened for 15 seconds or more, vacuum and purge with field supplied refrigerant. Generally, do not remove plastic/rubber plugs/caps from fittings, tubing and coils until ready to connect suction or liquid line into fittings.
Operational Check After all electrical wiring is completed and system is charged with refrigerant, make sure unit is operating properly. Check that: a) Condenser fans are running, with warm air blowing off the condenser coil. b) Evaporator blowers are running and discharging cool air. c) Suction line inside condensing unit feels cool. d) Liquid line inside condensing unit feels warm.
Electrical Connection As wiring regulations differ from country to country, please refer to your LOCAL ELECTRICAL CODES for field wiring regulations and ensure that these are complied with. Besides, observe the following general precautions: a) Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing
wiring work. b) Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit
breaker for over-current protection should be provided in the exclusive line. c) The unit must be GROUNDED to prevent possible hazard due to insulation failure. d) All wiring must be firmly connected. e) Electrical wiring must not touch the refrigerant piping, compressor and any moving parts of the fan
motors.
INSTALLATION (INDOOR)
10
Maximum Pipe Length And Maximum Number Of Bends When the pipe is too long, the required refrigerant quantity increases. Both the capacity and reliability drops as a result. As the number of bends increases, system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity and the compressor may become defective. If the height difference between the evaporator and the condenser is excessive, the cooling capacity drops, the lubricating oil return is retarded, affecting the compressor efficiency adversely. Always choose the shortest piping path and follow the recommendations as shown below:
Model Max. Elevation,
m (ft)
Max. Length,
m (ft)
Max. Total Length, m (ft)
Max. of
Bends
MLC 30C 25 (82.0) 20 (65.6) 45 (147.6) 8
MLC 40C 25 (82.0) 20 (65.6) 45 (147.6) 8
MLC 50C 25 (82.0) 20 (65.6) 45 (147.6) 8
MLC 61C 25 (82.0) 20 (65.6) 45 (147.6) 8
COUTION: 1) Our guarantee on the performance of our air-conditioners is strictly revoked if the height, length
and/or the number of bends of the refrigerant piping system installed is beyond the limit above. 2) Bending must be carefully made so as not to crush the pipe. Use a pipe bender to bend a pipe as far
as possible.
Maximum Allowable Piping Length & Elevation Difference
11
Recommended